Vous êtes sur la page 1sur 20

8/7/2015

Introduction

Chapter 3 Electrical transmission systems operate in their


steady-state mode under normal conditions.
Three major problems encountered in steady-
state mode of operations are listed below :
Load Flow Studies 1. Load flow problem
2. Optimal load dispatch problem
3. Systems control problem

The computational procedure required to determine The magnitude of generation voltage is


the steady-state operating characteristics of a maintained at the specified level by an automatic
power system network is termed load flow (or voltage regulator acting on the machine excitation.
power flow). Loads are specified by their constant active and
The aim of power flow calculations is to determine reactive power requirements.
the steady-state operating characteristics of a The loads are assumed to be unaffected by the
power generation/transmission system for a given small variations of voltage and frequency expected
set of bus bar loads. during normal steady-state operation.
Active power generations are specified according to The main information obtained from the load flow
economic dispatching. study consists of:

- Magnitudes and phase angles of load bus voltages . The single-line diagram of a power system
- Reactive powers and voltage phase angles at generator having four buses is shown in Figure 2. 1
buses . In the power system, the variables defined
- Real and reactive power flow on transmission lines. on each bus are:
- Power at the reference bus.
- Complex powers supplied by generators Sg1
This information is essential for the continuous
and Sg2
monitoring of the current state of the system.
The information is also important for analyzing the - Complex powers drawn by loads, Sd1 , Sd3,
effectiveness of the alternative plans for the future, and Sd4
such as adding new generator sites, meeting increased
load demand and locating new transmission sites. - Complex voltages, V1 ,V2 ,V3 and V4.

1
8/7/2015

• The transmission system may be a primary transmission


system or sub-transmission system.
• The primary transmission system transmits bulk power
from the generators to the bulk power substations.
• The sub-transmission system transmits power from the
substations or some old generators to the distribution
substations.
• The transmission system has to be designed in such a
manner that the power system operation is, reliable and
economic and no difficulties are encountered in its
operation.

In system operation and planning, the voltages


The difficulties involved are:
and powers are kept within certain limits.
- One or more transmission lines becoming
overloaded . The power system networks of today are highly
- Generators becoming overloaded . complicated consisting of hundreds of buses and
transmission links.
- The stability margins for a transmission link
being too small Thus, the load flow study involves extensive
There may be emergencies, such as: calculations.
- The loss of one or more transmission links . With the advent of fast digital computers with
- Shutdown of some generators which gives rise to huge memory, all kinds of power system studies
overloading of other generators and transmission including the load flow study can now be carried
links.
out conveniently.

NETWORK MODEL FORMULATION The surplus power at some of the buses is


A real-life power system comprises a large transported via transmission lines to buses
number of buses for a load flow study. deficit in power.
These buses are interconnected by means of
The single-line diagram of a three-bus
transmission lines.
system is shown in Figure 2.2. Normally a
Power is injected into a bus from generators,
transmission line is modeled by a nominal-л.
while the loads are tapped from it.
There may be some buses with no generation- while the line resistance is always
facilities and some buses may have VAR neglected in load flow analysis.
generators attached to them.

2
8/7/2015

The power at the ith bus injected into the


transmission system is called the bus power and
is defined as

 The equivalent power source at the ith bus injects


current Ii into the bus.
 All the sources are always connected to a common
ground node.
The transmission lines are replaced by their nominal-л
equivalent (Figure 2.3).
The line admittance between the nodes i and k is
depicted by Yik and Yik = Yki
 The mutual admittances between the lines is assumed
to be zero.
Applying the Kirchhoff’s current law (KCL) at nodes 1,
2, and 3, respectively (Figure 2.4):

3
8/7/2015

LOAD FLOW PROBLEM

The complex power injected by the source into


the ith bus of a power system is
*
S i  Pi  jQi  Vi I i (i  1,2,.........., NB )
NB
Substituting the value of Ii   Yik Vk in the above power equation
k 1

V Z I (2.10)
Bus Bus Bus

Separating the real and imaginary parts of above


equation to get real and reactive powers.

4
8/7/2015

The above equation can also be written as Separating the real and imaginary parts of the
above equation to get real and reactive powers

or

Slack Bus/Swing Bus/Reference Bus PQ Bus/Load Bus


 Voltage magnitude and voltage phase angle are A pure load bus is a PQ bus. A load bus has no generating
specified. facility (i.e. Pgi = Qgi = 0).
At this type of bus, the net real power Pi and the reactive
 Normally, voltage magnitude is set to 1 pu and power Qi are known as
voltage angle is set to zero.
 The real and reactive powers are not specified. Where
Pgi , Qgi are the real and reactive power generations at the
- The known parameters are voltage bus respectively.
magnitude |V |, and voltage angle δi . Pdi, Qdi are the real and reactive power demands at the bus
respectively.
- The unknown parameters are real power Pi Pdi and Qdi are known from load forecasting and Pgi and Pgi
and reactive power Qi are specified.

PV Bus/Generator Bus
The known variables on bus are real
power Pi and the reactive power Qi the A generator is always connected to a PV bus.
the net power Pi known as Pdi load forecasting.
unknowns are voltage magnitude |Vi |
and voltage angle δi. - The known are real power Pi and the voltage
magnitude |Vi | .
The PQ buses are the most common
- The unknowns are reactive power Qi and the
comprising almost 85% of all the buses in
voltage angle δi.
a given power system.
- PV buses comprise about 15% of all the buses
in a power system.

5
8/7/2015

Voltage-Controlled Buses
Limits
Generally the PV buses and the voltage-controlled buses
are grouped together but these buses have physical  For static load flow equations (SLFE) solution to
difference.
have practical significance all the state and control
The voltage-controlled bus has also voltage control variables must be within the specified practical
capabilities, and uses a tap-adjustable transformer
limits.
and/or a static VAR compensator instead of a generator.
Hence, P gi= Qgi =0 at these buses.  These limits are represented by specifications of
Thus Pi = - Pdi and Qi =- Qdi at these buses.. power system hardware and operating
The known are real power Pi , reactive power Qi and
constraints, and are described as follows:
voltage magnitude |Vi|.
The voltage angle δi is an unknown parameter.

COMPUTATION OF LINE FLOWS

Consider the line connecting the buses i and k figure below


Where:
Yik is the series admittance
Yik0 , Yki0 are the shunt admittances

Figure Transmission line connecting i and k buses

The current fed by the bus i into the line can be expressed as Substituting the conjugate of above equation

Similarly, the power injected into the line from bus k to bus i is

The power loss in the (i- k)th line is the sum of the power
flows in the (i- k)th line from the ith bus and the kth bus,
respectively, i.e.

6
8/7/2015

MODELLING OF REGULATING
Total transmission losses can be computed by summing all TRANSFORMERS
the line flows of the power system.
Transformers provide real power and reactive
power flow along a transmission line.
Real power can be controlled by means of
shifting the phase of voltage and reactive power
The slack bus power can also be obtained by summing the
line flows on the lines terminating at the slack bus. by changing its magnitude.
Voltage magnitude can be changed by
transformers provided with tap changing under
load (TCUL) .

Transformers specially designed to adjust voltage


magnitude or phase angle through small values
are called regulating transformers.
The presence of regulating transformers in lines
modifies the YBus matrix thereby modifying the
load flow solution.
Transmission line with regulating transformer
Consider a line, connecting two buses, having a
regulating transformer with off-nominal turns
(tap) ratio a included at one end as shown in
Figure below.

Since the transformer is assumed ideal, complex Similarly,


power output from it equals complex power input, i.e.

For transmission line,

Equations above can be written in matrix form

7
8/7/2015

Alternative method

where

π-network representation of an off-nominal


transformer Can be write as
and
For an off-nominal turns ratio transformer, a is
real, i.e. a' = a.

can be rewritten as

π-representation of a transmission line

Off-nominal transformers at both line ends


where
With off-nominal tap-setting transformers at each
end as shown in Figure below we have

or

Off-nominal transformers at both transmission line ends.

8
8/7/2015

POWER FLOW SOLUTION


SOLUTION STRATEGY FOR THE POWER FLOW EQUATIONS

Two methods are applied for power flow analysis.


These are the Gauss-Seidel method and the
Newton-Raphson method.
Application to the power flow problem.

- Newton-Raphson method
u k  J k x k
 x k  ( J 1 ) k  u k

POWER FLOW ANALYSIS: TWO BUS CASE

- The two-bus system selected to illustrate the solution


procedure described in the preceding section is a simple one.
- The specific two-bus system to be analyzed here for power
flow along the transmission line is depicted in Fig. 5-5.
- Because ,there is a single generator bus, it is made the
The vector x is frequently called the state vector of the slack bus, which means in turn that the bus 1 voltage and
electric power system. The updated values of the system phase angle are respectively 1 pu and 0°.
state vector can be expressed as
- The second bus is a load bus at which the demanded
real and reactive powers are specified.
- These quantities are identified as P2 =- 1.0 and Q2 = - 1.0
p.u.

9
8/7/2015

Example 1

Solution
The corresponding base quantities are then

and

The impedance of transmission line between buses 1 and 2

The reference base for this power system is assumed to


be 100MVA and 230 kV at the transmission level. Using
Newton-Raphson method in finding a solution for V2 and
δ2 so that these variables will satisfy for the value
specified.

Similarly, the transfer impedance between these buses is


The corresponding line admittance is then given as

The per unit value of each shunt capacitive susceptance


associated with the π equivalent circuit of the transmission
line is
the equation for real power at bus 2 as well as the
equation for reactive power at this bus we get

the self-admittance of the transmission line at either bus 1


or bus 2 can be represented by Note that we choose to use the lower-case letter for P
wherever we are preparing to perform an iteration procedure
in search of the quantities required on the right side that in
fact make the real power equal to the specified value.

Inserting the known values of V1 and δ1 then yields

we have two equations and two unknowns, the


resulting jacobian in this case will be a 2 x 2 square
matrix.
Because the jacobian is to be evaluated at each
iteration, it is useful to have the general expressions for By inserting the elements of Ybus we get the final forms of
these partial derivatives available. the power flow equations as they are used in the iteration
Accordingly, the appropriate partial differentiation of the procedure to obtain a solution
expressions for P2 and q2 yields the following,

10
8/7/2015

The process is begun by assuming all magnitudes of the


unknown bus voltages equal to unity and all the phase
angles equal to 0°.
Examination of the Assumed Solution, V2 = 1 and δ2 = 0°.To
check whether or not this solution works, we insert these
values into Eqs. power flow equations. Thus, we find

1st Iteration: the first corrected values of the unknown


variables are by

2nd Iteration: The second corrected values of the unknown


variables are now given by

Upon inserting these updated values into the power flow


equations, we find 3rd Iteration: The corrected values of the third iteration of
the unknown variables are now expressed as

11
8/7/2015

In summary, then, the solution to the power flow problem


as formulated is given by the bus 2 voltage vector.

4th Iteration: The updated estimates of the solutions now


take on the values
This conclusion is premised on the assumption that the
error of 0.5% present in the solution for the reactive power
is acceptable.

With the solutions of V2 and δ2 now at the real power PR1


the
reactive power to be generated at bus 1 is identified as The current injected into the transmission line is given by

in this case the per-unit line resistance is

the copper loss by the alternative procedure of taking the


product of the transmission line current squared and the line
resistance.

GAUSS-SEIDEL METHOD

Gauss-Seidel method of solving the power flow equations.


The inherent nonlinearity of these equations, however,
demands that the solution again be achieved by a process
of iteration on an appropriately modified form of the
Figure show the Solution to a two-bus power flow problem equations.
The analysis begins by the second form which can be
written as

12
Slide 69

PR1 PHAN RAVY, 3/8/2010


8/7/2015

A straightforward application of the instructions contained


on the right side of this last equation is called the Gauss
iteration method.
In the case of an n-bus transmission network yields the
following (n - 1) nonlinear algebraic equations with bus 1
taken as the slack bus.

use the Gauss-Seidel method to solve the problem in


example 1 to obtain the solution for the voltage and
angle at bus 2.
which on insertion of the parameter values becomes,

Solution
Solution The bus admittance matrix for this two-bus
Begin the iteration by assuming an initial value for bus 2
transmission network is given by voltage of unity ( V 2 )0  10 o
The result of the first iteration is as follows.

1st iteration:
Moreover, the injected complex power at bus 2 is specified
as S2 = -1 - j. Hence,

POWER FLOW ANALYSIS: THREE-BUS CASE


2nd iteration:
Example2: The three-bus transmission network analyzed
in this section is depicted in Fig.5-7. Generating units are
tied to buses 1 and 3. Generator G1 is assumed to have a
V
2
 0.780513   7.974 o
rating of 300 MVA at 15kV. The rating of generator G3 is
2
250MVA at 15 kV.
3nd iteration:
The transmission line voltage is 230kV, and appropriate
transformers are assumed to be in place to provide the
transition from the generating level to the transmission
4nd iteration:
level. As is customary, the power flow analysis takes place
at the transmission level.
5nd iteration:
The base reference quantities are chosen to be: 100 MVA
and 230 kV.

13
8/7/2015

Solution
Solution by the Newton-Raphson method
Accordingly, the base quantities for impedance and
admittance are respectively

On this basis the p.u values of the admittances of the


transmission lines between the three buses are determined
to be per phase

Accordingly, the net complex power injected into the


transmission network at bus 2 is

Writing the power flow equations. The three specified,


values of real and reactive power to be used in the solution
of the power flow equations are P2, P3, and Q2. these are
At bus 2:
net quantities considered to be injected into the
transmission network at the buses.
Consider first bus 2. The complex power associated with the
RL circuit is 2.5 + j1.2 pu. Because the capacitor takes an
amount of reactive power given by - j2 pu

At bus 3: the solution by the Newton-Raphson method, it is necessary


next to obtain the jacobian matrix of partial derivatives.
The expressions for evaluating the elements of the first row
of this matrix are obtained by taking the partial derivative of
inserting V1 = 1.0, V3 = 1.1, and δ1 = 0° as well as the
transmission line parameters as they appear in Ybus, these P2 with respect to each independent variable. Thus,
equations can be expressed more explicitly as

14
8/7/2015

Solution by the Newton-Raphson method.


We begin the solution process, as we did the two-bus case,
by assuming an initial solution where the unknown
independent voltage magnitudes are set equal to unity and
the unknown phase angles are set equal to 0°. Thus, the
initial unknown state vector is

1st Iteration

The new values of the elements of the state vector are

Inserting these values of the independent variables into the


power flow equations yields
Applying these corrections to the independent variables
yields the modified values which are to be used in the first
iteration.

The new value of the corrective vector that serves to move


the next iterative solution still closer to the actual values now
becomes

2nd Iteration

The corresponding element values of the jacobian are:


A check on the results follows upon substituting these
values into the power flow equations. We get

3rd iteration.

15
8/7/2015

Agreement with the specified values of P2, P3, and Q3 is so


close that we can now declare the values of the
independent variables displayed in the solutions to the
nonlinear power flow equations.

Evaluation of Dependent Quantities at Generator Buses.


A bus is considered to be a generator bus when ever
dependent quantities are to be determined. In
this three-bus case these dependent quantities are P1. Q1.
and Q3.
Entry of these independent variables into the power
flow equations yields the power flow equations.

Evaluation of bus-to-bus complex power flow.


As the last step of the power flow analysis, we compute the
level of complex power that appears at each bus on each
transmission line along the electric power system.

Bus. 1
By Kirchhoff’s current law the current that flows from bus
All the quantities on the right side of this equation are
1 into the transmission link between bus 1 and bus 2 is
known, the solution of the power flow equations are
given by
widely.
In this instance the results are found to be

Hence, the net injected complex power at bus 1 is


The current in the transmission link between buses 1
and 3 is found in the same way.
Bus 2
The current that flows from bus 2 to bus 1 is

16
8/7/2015

Similar the current flow from bus 2 to bus 3 is described by

Bus 3

The value of the net injected current at bus 2 readily


follows as the sum of I21 and I23, which is

GAUSS-SEIDEL METHOD

Power system is comprised of three types


of buses, namely slack bus, PQ buses and
PV buses. The net injected complex conjugate current at bus 3 is

The slack bus is numbered one, and the


remaining (NB - 1) buses may be PQ
buses or PV buses.

EXAMPLE 3
Figure below, the generators are connected at all the four
buses, while loads are at buses 2, 3, and 4.
The values of real and reactive powers are listed in Table All
buses other than slack are of PQ-type.
Find the voltages and the bus angles at the three buses
using the GS (Gauss Seidel) iteration.
Solution
Y-bus is calculated

Y11 =5.724138 - j12.310340

Y12 =Y21 =- 1.724138 + j4.310345

Y13 =Y31=0.0 + j 0.0

Y14 =Y41=- 4.0 + j8.0

17
8/7/2015

Set iteration counter, r =0


Y22 = 4.224138 – j11.810340

Y23 =Y32 =-2.5 + j7.5


Using Eq. (4),
Y24 =Y42= 0.0 + j 0.0

Y33 = 4.386792 – j14.103770

Y34 =Y43=- 1.88679+j6.603774

Y44 = 5.886792 – j14.603770


Assuming flat start (means set the voltage to -1 p.u. value)

V3 is

18
8/7/2015

If the convergence criterion is not satisfied, go for the next


iteration by incrementing the counter r, i.e. r =r + 1.
To start the new iteration, the following voltage values are
used in which the value of voltage V4 is the updated value.

The slack bus real and reactive powers are


computed using the following equation

The line flows result are in Table below

19

Vous aimerez peut-être aussi