2 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3 Issued: 2014-12-03
Revision: B
2. Application
REG630 provides main protection for generator and
generator-transformer units in, for example, small– and
ABB 3
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
RET630
Preconf. n
3U ANSI IEC
87T 3ΔI>T
3I
HV 27 3U<
Io side 46 I2>
49T 3I >T REF630
50P/51P 3I>>> Preconf. n
51BF/51NBF 3I>/Io>BF ANSI IEC
51N-1/51N-2 Io>/Io>> 25 SYNC
51P-1/51P-2 3I>/3I>> 27 3U<
59 3U> 50P/51P 3I>>>
Io 87NL dIoLo> 51BF/51NBF 3I>/Io>BF
LV 46 I2> 51N-1/51N-2 Io>/Io>>
side 50P/51P 3I>>> 51P-1/51P-2 3I>/3I>> U12
3U 51P-1/51P-2 3I>/3I>> 59 3U>
3I
3I
3I 3I
3U 3U
3U Uo
Io Io
3I 3I
Io Io
REG630 REG630
Preconf. A Preconf. A
REU615
ANSI IEC ANSI IEC
Std. conf. A
27 3U< 27 3U<
ANSI IEC
32R/32O P>→ 32R/32O P> →
47O-/59 U2>/3U>
32U P<→ 32U P< →
47U+/27 U1</3U<
40 X< 40 X<
59G Uo>
46G/46M I2>G/M 46G/46M I2>G/M
81 f</f>,df/dt
49T/G 3Ith>T/G 49T/G 3Ith>T/G
81LSH UFLS/R
51BF/51NBF 3I>/Io>BF 51BF/51NBF 3I>/Io>BF
51P-1/51P-2 3I>/3I>> 51P-1/51P-2 3I>/3I>>
51V I(U)> 51V I(U)>
59 3U> 59 3U>
59G Uo> 59G Uo>
60 FUSEF 60 FUSEF
67N-1/67N-2 Io>→/Io>>→ 67N-1/67N-2 Io>→/Io>>→
81U/81O/81R f</f>/Δf/Δt 81U/81O/81R f</f>/Δf/Δt
87G/87M 3dl>G/M 87G/87M 3dl>G/M
GUID-95FFD0DD-9A1E-422D-A6F2-0603158D0DBA V1 EN
4 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
3I
3U RET630
Preconf. n
ANSI IEC
46 I2>
Io
51BF/51NBF 3I>/Io>BF
51P-1/51P-2 3I>/3I>>
59 3U>
59G Uo>
67N-1 Io>→
87T 3ΔI>T
3U
REG630
Preconf. n
ANSI IEC
GUID-C93D2D3A-8C8E-40CB-9242-FA76FA0E3C3D V1 EN
ABB 5
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
REF630
U12 Preconf. n
ANSI IEC
25 SYNC
3I 27/47U+ 3U</U1<
3I 46 I2>
50N/51N Io>>>
3U 50P/51P 3I>>>
51BF/51NBF 3I>/Io>BF
51P-1/51P-2 3I>/3I>>
59/47O- 3U>/U2>
Io 59G Uo>
60 FUSEF
67N-1/67N-2 Io>→/Io>>→
68 3I2f>
Uo
REG630
Preconf. n
ANSI IEC
32R/32O P>→
40 X<
46G/46M I2>G/M
3U 51BF/51NBF 3I>/Io>BF
51N-1/51N-2 Io>/Io>>
51P-1/51P-2 3I>/3I>>
59 3U>
59G Uo>
EXC. 81U/81R f</df/dt
AVR 87T 3ΔI>T
3I
REK510 3I
Ufn
REG630
Io Preconf. n
Io ANSI IEC
Uo
21GT Z<GT
24 U/f>
27 3U<
27/59THD ΔU03f>/Uo>
32R/32O P>→
49T/G 3Ith>T/G
51BF/51NBF 3I>/Io>BF
51P-1/51P-2 3I>/3I>>
59 3U>
59G Uo>
60 FUSEF
64R Io>R
GUID-42A3A43D-4F62-4541-AB39-D662B21769AB V1 EN
The protection is implemented with two REG630 generator available transformer differential protection function and
protection relays and one REF630 feeder terminal. One REF630 is protecting and controlling the feeder part of this
REG630 is taking care of protecting the generator itself, the application.
second REG630 is protecting the power transformer with
6 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
ABB 7
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
1× 1× U<>
3I> 3I>> U<>
51P-1 51P-2
∆Io 1× 1×
Io>→ Io>→ Object Ctrl 2) - I, U, Io, Uo, P, Q, E, pf, f
67N-1 67N-2 - Sequence current/voltage measurement
3I CB 2 - Limit value supervision
Uo DC - RTD/mA measurement (optional)
8
ES Analog interface types B
1)
Check availability of binary inputs/outputs Current transformer 7
2× 2× 2× 1× 2× 2×
from technical documentation
3U< 3U> Uo> f> 2)
Control and indication function for Voltage transformer 3
27 59 59G 81O primary object
Io 2× 2× 2× 2×
df/dt> f< SYNC
81R 81U 25
2× 2×
Z<GT U/f> dUo(3H)>/Uo(3H)<
21GT 24 27/59THD
3× 2× 2×
U<RT Q>→, 3U< U2>
27RT 32Q, 27 47O-
2× 2×
U1> U1< Io>>> 3I>>>
47O+ 47U+ 50N/51N 50P/51P
2×
Io> Io>> Io>R 3I>→
51N-1 51N-2 64R 67-1
3I>>→ 3I2f> VS
67-2 68 78V
REMARKS
GUID-73E671D3-F46A-4778-8A7E-03AAED8AAACA V1 EN
8 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
3× 2× 3× 3× AND
3I
U<RT Q>→, 3U< P> P< OR
27RT 32Q, 27 32R/32O 32U *) Fixed or detached LHMI is available.
2× 2× 2× 2×
X< I2>G/M U2> U1>
CONDITION MONITORING COMMUNICATION
40 46G/46M 47O- 47O+
3U AND SUPERVISION
Protocols: 1 0 1 0 0 0 1 1 0 0 1 1 0 0
2× 2× IEC 61850-8-1 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
Uo U1< 3Ith>T/G Io>>> 3I>>> FUSEF CBCM E IEC 60870-5-103 1 1 0 0 1 1 1 0 1 1 0 1 0
1 0 1 1 0 1 1 0 1 1 0 1 0 0
47U+ 49T/G 50N/51N 50P/51P 60 CBCM E DNP3 1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0
1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
Interfaces: 1 1 0 0 1 1 1 0 1 1 0 1 0
2× 2× 3×
Ethernet: TX (RJ45),1 0 1(LC)
FX 1 0 1 1 0 1 1 0 1 0 0
3I>/Io>BF Io> Io>> 3I> MCS 3I OPTS TCS
Io Serial: Serial glass fiber (ST),
51BF/51NBF 51N-1 51N-2 51P-1 MCS 3I OPTM TCM
Serial plastic fiber
(snap-in connector)
2× 2× 2× 3×
3I>> I(U)> 3U> Uo> Io>R U<>
51P-2 51V 59 59G 64R U<>
2× 2×
3I>→ 3I>>→ Io>→ Io>→ 3I2f>
67-1 67-2 67N-1 67N-2 68 CONTROL AND INDICATION 1) MEASUREMENT
∆Io 4× 4× 4×
Object Ctrl 2) - I, U, Io, Uo, P, Q, E, pf, f
VS f> df/dt> f< - Sequence current/voltage measurement
3I 78V 81O 81R 81U CB 2 - Limit value supervision
DC - RTD/mA measurement (optional)
8
ES Analog interface types A B C
3dl>G/M 3dlHi>G/M dIoHi>
87G/87M 87GH/87MH 87NH 1)
Check availability of binary inputs/outputs Current transformer 51) 7 8
from technical documentation
2)
Control and indication function for Voltage transformer 4 3 2
16× primary object 1)
One of available current transformer
3dI>T MAP inputs is sensitive (0.1 / 0.5 A)
Io 87T MAP
SYNC
25
REMARKS
Optional 3× Total nr. of
function instances
GUID-21213F0B-B9FF-4310-9561-24A39E51157B V1 EN
Description Preconfiguration
ABB 9
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Description A n
Protection
Underpower protection 2 3
Overfrequency protection 2 4
Underfrequency protection 2 4
Overexcitation protection - 2
10 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Tripping logic 1 2
Control
Bay control 1 1
Interlocking interface 3 10
Circuit breaker 1 2
Disconnector 2 8
Synchrocheck - 1
Event counter - 1
Trip-circuit supervision 2 3
Energy monitoring 1 1
Measurement
ABB 11
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Binary receive - 10
Interlock receive - 59
Integer receive - 32
4. Protection functions stability and reliability, and thus avoid grid collapse. The low-
REG630 offers wide protection functionality for synchronous voltage ride-through protection allows monitoring of
generators against internal faults and abnormal conditions of distributed generation during low-voltage or fault ride-
external systems. The generator management IED features through, in order to determine whether and when to
non-directional and directional overcurrent and earth-fault disconnect from the grid. A reactive power undervoltage
protection functions, over- and undervoltage protection protection (QU) can be used at grid connection point of
functions and specific functions for the protection of distributed power generation units. The voltage vector shift
generators, for example, voltage-controlled overcurrent protection detects islanding from the grid. It measures
protection, reverse/directional overpower protection, continuously the duration of voltage cycle. At the instance of
differential protection, underexcitation protection, islanding, the duration of measured voltage cycle becomes
overexcitation protection, high-impedance-based restricted shorter or longer than the previous one, i.e. the measured
earth-fault protection, underimpedance protection (line back- voltage cycle shifts with time.
up protection), thermal overload protection, negative-phase
sequence protection, frequency protection and underpower
protection. Rotor earth-fault protection function to be used
with a separate fundamental frequency voltage injection
device is also included.
ABB 13
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
The monitoring functions provide operational circuit breaker User Administrator. The user group association for each
history data, which can be used for scheduling preventive individual user enables the use of the IED according to the
circuit-breaker maintenance. profile of the user group.
14 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
AA 4 1 4 - -
AB 7 - 3 - -
AC 8 - 2 - -
BA 4 1 4 8 4
BB 7 - 3 8 4
BC 8 - 2 8 4
Default AA 14 9
Default AA 14 9
The IED supports the following time synchronization methods With special time synchronization wiring
with a timestamping resolution of 1 ms. • IRIG-B (Inter-Range Instrumentation Group - Time Code
Format B)
Ethernet communication based
• SNTP (simple network time protocol)
• DNP3 IEC 60870-5-103 serial communication has a time-stamping
resolution of 10 ms.
IEC 61850 ● ●
DNP3 ● ●
IEC 60870-5-103 ● ●
● = Supported
1) Please refer to the Selection and ordering data chapter for more information
16 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Table 7. Dimensions
Description Value
Width 220 mm
Depth 249.5 mm
1) Without LHMI
Uauxnominal 100, 110, 120, 220, 240 V AC, 50 and 60 Hz 48, 60, 110, 125 V DC
Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)
Power supply input must be protected by an For example, type S282 UC-K.
external miniature circuit breaker The rated maximum load of aux voltage which is given as 35 watts. Depending on the voltage
used, select a suitable MCB based on the respective current. Type S282 UC-K has a rated
current of 0.75 A at 400 V AC.
ABB 17
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Description Value
• Continuously 4A 20 A
• For 10 s 25 A 100 A
Voltage inputs Rated voltage, Un 100 V AC/ 110 V AC/ 115 V AC/ 120 V AC
Voltage withstand:
• Continuous 425 V AC
• For 10 s 450 V AC
1) Residual current
2) Phase currents or residual current
Description Value
18 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Description Value
RTD inputs Supported RTD sensor 100 Ω platinum TCR 0.00385 (DIN 43760)
Operation accuracy ±0.1% ±20 ppm per °C of full-scale Ambient temperature -40°C...
70°C
Operation accuracy ±0.1% ±40 ppm per °C of full-scale Ambient temperature -40°C...
70°C
ABB 19
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Description Value
Breaking capacity when the control-circuit time constant L/R<40 ms, at ≤0.5 A/≤0.1 A/≤0.04 A
U < 48/110/220 V DC
Description Value
Breaking capacity when the control-circuit time constant L/R<40 ms, at ≤1 A/≤0.3 A/≤0.1 A
U< 48/110/220 V DC
Description Value
Breaking capacity when the control-circuit time constant L/R<40 ms, at ≤1 A/≤0.3 A/≤0.1 A
U < 48/110/220 V DC
Description Value
Isolation level 4 kV
20 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Screw terminal, pin row header IRIG-B Shielded twisted pair cable
Recommended: CAT 5, Belden RS-485 (9841- 9844) or Alpha Wire
(Alpha 6222-6230)
660 mm 1 mm Snap-in 10 m
Description Value
Front side IP 40
Description Value
Description Value
Altitude up to 2000 m
ABB 21
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
22 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
100 kHz and 1 MHz burst disturbance test IEC 61000-4-18, level 3
IEC 60255-22-1
• Contact discharge 8 kV
• Air discharge 15 kV
• Conducted, common mode 10 V (rms), f=150 kHz...80 MHz IEC 61000-4-6 , level 3
IEC 60255-22-6
• All ports 4 kV
• Communication 1 kV line-to-earth
• 2s 100 A/m
Power frequency immunity test Binary inputs only IEC 60255-22-7, class A
IEC 61000-4-16
ABB 23
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
• Radiated RF-emission
• Resistance <0.1Ω, 4 A, 60 s
24 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Description Reference
LV directive 2006/95/EC
Description Reference
Description
ABB 25
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Protection functions
Characteristic Value
PHHPTOC:
IFault = 2 × set Start value Typically 19 ms (±5 ms)
PHLPTOC:
IFault = 2 × set Start value Typically 23 ms (±15 ms)
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
1) Set Operate delay time = 0.02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 × I n , f n = 50 Hz, fault current in one
phase with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Includes the delay of the heavy-duty output contact
26 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value of ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the set value of ±20 ms
1) Measurement mode = default, current before fault = 0.0 × I n, f n = 50 Hz, fault current in one phase with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements.
2) Includes the delay of the signal output contact.
ABB 27
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Characteristic Value
DPHLPDOC Current:
±1.5% of the set value or ±0.002 × In
Voltage:
±1.5% of the set value or ±0.002 × Un
Phase angle:
±2°
DPHHPDOC Current:
±1.5% of the set value or ±0.002 × In (at currents in the range of 0.1…
10 × In)
±5.0% of the set value (at currents in the range of 10…40 × In)
Voltage:
±1.5% of the set value or ±0.002 × Un
Phase angle:
±2°
Start time1)2) IFault = 2.0 × set Start value Typically 24 ms (±15 ms)
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)
1) Measurement mode = default (depends of stage), current before fault = 0.0 × I n, f n = 50 Hz, fault current in one phase with nominal frequency injected from random phase angle, results
based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × I n , Start value multiples in range of 1.5...20
28 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
1) Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 × I n, f n = 50 Hz, earth-fault current with nominal frequency injected
from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × I n, Start value multiples in range of 1.5...20
ABB 29
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Characteristic Value
DEFLPDEF Current:
±1.5% of the set value or ±0.002 × In
Voltage
±1.5% of the set value or ±0.002 × Un
Phase angle: ±2°
DEFHPDEF Current:
±1.5% of the set value or ±0.002 × In
(at currents in the range of 0.1…10 × In)
±5.0% of the set value
(at currents in the range of 10…40 × In)
Voltage:
±1.5% of the set value or ±0.002 × Un
Phase angle: ±2°
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
1) Set Operate delay time = 0.06 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 × I n , f n = 50 Hz, earth-fault current
with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × I n , Start value multiples in range of 1.5 to 20
30 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value of ±20 ms
Table 41. Third harmonic based stator earth-fault protection (H3EFPSEF) main settings
ABB 31
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Characteristic Value
Start time1)2) IFault = 2.0 × set Operate value Typically 22 ms (±5 ms)
IFault = 10.0 × set Operate value Typically 15 ms (±5 ms)
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Table 43. High-impedance based restricted earth-fault protection (HREFPDIF) main settings
Characteristic Value
1) Current before fault = 0.0 × I n , f n = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
32 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Characteristic Value
Start time1)2) IFault = 5.0 × set Start value Typically 43 ms (±15 ms)
Operate time accuracy in definite time mode ±1.0% of the set value or ±35 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±30 ms 3)
Table 47. Negative-sequence overcurrent protection for machines (MNSPTOC) main settings
Table 48. Three-phase thermal overload protection, two time constants (T2PTTR)
Characteristic Value
1) Overload current > 1.2 × Operate level temperature, Current reference > 0.50 pu
Table 49. Three-phase thermal overload protection, two time constants (T2PTTR) main settings
ABB 33
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Characteristic Value
Current measurement:
±1.5% of the set value or ±0.002 × In
Ratio I2f/I1f measurement:
±5.0% of the set value
Characteristic Value
1) Differential current before fault = 0.0 × I n , f n = 50 Hz. Injected differential current = 2.0 × set operate value
2) Includes the delay of the output contact value and f n = 50 Hz
34 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Table 53. Transformer differential protection for two-winding transformers (TR2PTDF) main settings
Table 54. High-impedance or flux-balance based differential protection for machines (MHZPDIF)
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value of ±20 ms
ABB 35
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Table 55. High-impedance or flux-balance based differential protection for machines (MHZPDIF) main settings
Characteristic Value
Table 57. Stabilized differential protection for machines (MPDIF) main settings
Characteristic Value
Start time1)2) UFault = 2.0 × set Start value Typically 17 ms (±15 ms)
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)
1) Start value = 1.0 × Un, Voltage before fault = 0.9 × U n, f n = 50 Hz, overvoltage in one phase-to-phase with nominal frequency injected from random phase angle
2) Includes the delay of the signal output contact
3) Maximum Start value = 1.20 × U n, Start value multiples in range of 1.10...2.00
36 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Characteristic Value
Start time1)2) UFault = 0.9 × set Start value Typically 24 ms (±15 ms)
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)
1) Start value = 1.0 × Un, Voltage before fault = 1.1 × U n, f n = 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random phase angle
2) Includes the delay of the signal output contact
3) Minimum Start value = 0.50 × U n, Start value multiples in range of 0.90...0.20
ABB 37
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Positive-sequence voltage before fault = 0.0 × U n, f n = 50 Hz, positive-sequence overvoltage of nominal frequency injected from random phase angle
2) Includes the delay of the signal output contact
Characteristic Value
Start time1)2) UFault = 0.9 × set Start value Typically 28 ms (±15 ms)
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Positive-sequence voltage before fault = 1.1 × U n, f n = 50 Hz, positive-sequence undervoltage of nominal frequency injected from random phase angle
2) Includes the delay of the signal output contact
38 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Negative-sequence voltage before fault = 0.0 × U n, f n = 50 Hz, negative-sequence overvoltage of nominal frequency injected from random phase angle
2) Includes the delay of the signal output contact
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Residual voltage before fault = 0.0 × U n, f n = 50 Hz, residual voltage with nominal frequency injected from random phase angle
2) Includes the delay of the signal output contact
ABB 39
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
1) Start value = 0.05 × Sn, Reactive power before fault = 0.8 × Start value . Reactive power overshoot 2 times. Results based on statistical distribution of 1000 measurement.
Table 71. Directional reactive power undervoltage protection (DQPTUV) main settings
Characteristic Value
40 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Characteristic Value
Characteristic Value
Start time1)2) Start value = 0.05 Hz/s Typically 110 ms (±15 ms)
df/dtFAULT = ±1.0 Hz/s
Operate time accuracy in definite time mode ±1.0% of the set value or ±30 ms
ABB 41
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Characteristic Value
±0.003 Hz
Operate time accuracy in definite time mode ±1.0% of the set value or ±30 ms
Characteristic Value
±0.003 Hz
Operate time accuracy in definite time mode ±1.0% of the set value or ±30 ms
Characteristic Value
Operate time accuracy in definite time mode ±1.0% of the set value or ±40 ms
42 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Table 83. Low voltage ride through protection function (LVRTPTUV) main settings
ABB 43
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Characteristic Value
Operate time accuracy in definite-time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse-time mode ±5.0% of the theoretical value or ±50 ms
Characteristic Value
44 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Characteristic Value
Retardation time Total retardation time when the impedance returns from the operating
circle <40 ms
Operate time accuracy in definite-time mode ±1.0% of the set value of ±20 ms
Characteristic Value
Operate time accuracy in definite-time mode 1)2) ±1.0% of the set value or ±20 ms
ABB 45
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Characteristic Value
Characteristic Value
46 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
ABB 47
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Control functions
Characteristic Value
48 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Characteristic Value
Table 99. Runtime counter for machines and devices (MDSOPT) main settings
Characteristic Value
Characteristic Value
Operate time1) • NPS function UFault = 1.1 × set Neg Seq voltage Typically 35 ms (±15 ms)
Lev Typically 25 ms (±15 ms)
UFault = 5.0 × set Neg Seq voltage
Lev
• Delta function ΔU = 1.1 × set Voltage change rate Typically 35 ms (±15 ms)
ΔU = 2.0 × set Voltage change rate Typically 28 ms (±15 ms)
1) Includes the delay of the signal output contact, f n = 50 Hz, fault voltage with nominal frequency injected from random phase angle
Characteristic Value
ABB 49
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Characteristic Value
Characteristic Value
Characteristic Value
50 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Measurement functions
Characteristic Value
±0.5% or ±0.002 × In
(at currents in the range of 0.01...4.00 × In)
Characteristic Value
±0.5% or ±0.002 × Un
(at voltages in the range of 0.01...1.15 × Un)
Characteristic Value
±0.5% or ±0.002 × Un
(at voltages in the range of 0.01...1.15 × Un)
Characteristic Value
±0.5% or ±0.002 × In
(at currents in the range of 0.01...4.00 × In)
Characteristic Value
±0.5% or ±0.002 × Un
ABB 51
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Characteristic Value
Characteristic Value
±1.0% or ±0.002 × In
at currents in the range of 0.01...4.00 × In
Characteristic Value
±1.0% or ±0.002 × Un
At voltages in range of 0.01…1.15 × Un
52 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Control functions
Characteristic Value
Characteristic Value
Operation value:
±1.0% of the Ud or ±0.004 × Un for Us = 1.0 × Un
Operate time accuracy in definite time mode 1) ±1.0% of the set value or 0.11 s
Operate time accuracy in inverse time mode 1) ±15.0% of the set value or 0.15 s
(at theoretical B in range of 1.1…5.0) Also note fixed minimum operate
time (IDMT) 1 s
Reset ratio for analog based blockings (except run back raise voltage Typically 0.96 (1.04)
blocking)
ABB 53
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Table 117. Tap changer control with voltage regulator (OLATCC) main settings
54 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
19. Front panel user interface with LED indicators. The 15 programmable alarm LEDs can
The 630 series IEDs can be ordered with a detached front- indicate a total of 45 alarms. The local HMI offers full front-
panel user interface (HMI). An integrated HMI is available for panel user-interface functionality with menu navigation, menu
4U high housing. The local HMI includes a large graphical views and operational data. In addition, the local HMI can,
monochrome LCD with a resolution of 320 x 240 pixels (width using PCM600, be configured to show a single-line diagram
x height). The amount of characters and rows fitting the view (SLD). The SLD view displays the status of the primary
depends on the character size as the characters' width and apparatus such as circuit breakers and disconnectors,
height may vary. selected measurement values and busbar arrangements.
GUID-5CFD3446-A92F-4A5F-B60D-90025DCFDC61 V2 EN
Mounting methods:
• Flush mounting
• Semi-flush mounting
• Overhead/ceiling mounting
ABB 55
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
270
252,5
366
13
101,6
180
ø6,8
GUID-945D3C86-A432-4C1F-927A-A208E0C1F5F6 V2 EN
GUID-AF1BEC0B-A9DC-4E9B-9C89-98F28B1C81DB V1 EN
Figure 7. Flush mounting
Figure 8. Semi-flush mounting
,5 22 0
25
25 8,
177
13
265,9
4
22
GUID-A368C5C3-D4A9-40B7-BD0E-181A6BB7ECA6 V1 EN
Figure 10. 6U half 19" unit wall mounted with two mounting
brackets and detached LHMI
56 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
21. Selection and ordering data The order code consists of a string of letters and digits
generated from the hardware and software modules of the
The IED type and serial number label identifies the protection IED. Use the ordering key information in tables to generate
and control IED. The label placed is on the side of the IED the order code when ordering protection and control IEDs.
case. The IED labels include a set of smaller size labels, one
label for each module in the IED. The module labels state the
type and serial number of each module.
SBGAABACBBAZAANBXD
# Description
1 IED
630 series, 4U half 19” housing S
630 series, 6U half 19” housing T
630 series, 4U half 19” housing & connector set U
630 series, 6U half 19” housing & connector set V
2 Standard
IEC B
3 Main application
Generator protection and control G
GUID-6D418C83-076D-494E-B0DC-8379B03E2EBA V3 EN
The preconfiguration determines the analog input and binary I/O options. SBGAABACBBAZAANBXD
The example below shows standard configuration “A” with chosen options.
# Description
4-8 Functional application, preconfigurations:
A = Preconfiguration A for directly connected generator set
N = None
Pre- Available analog input options Available binary input/
conf. output
options
AA = 14 BI + 9 BO
AB = 7I (I0 1/5 A) + 3U AB = 23 BI + 18 BO
A BB = 7I (I0 1/5 A) + 3U + AC1,3) = 32 BI + 27 BO
8mA/RTD in + 4mA out AD2) = 41 BI + 36 BO
AE2,3) = 50 BI + 45 BO
AA = 4I (I0 1/5 A) + 1I (I0 0.1/0.5 A) + 4U
AB = 7I (I0 1/5 A) + 3U
AA = 14 BI + 9 BO
AC = 8I (I0 1/5 A) + 2U
AB = 23 BI + 18 BO
BA = 4I (I0 1/5 A) + 1I (I0 0.1/0.5 A) + 4U
N 8mA/RTD in + 4mA out AC1) = 32 BI + 27 BO
1) Binary input/output option AC is not available for 4U high variant (digit #1 = S or U) with RTD card option
(digit #5-6 = BA, BB or BC)
2) Binary input/output options AD and AE require 6U half 19” IED housing (digit #1 = T or V)
3) Binary input/output option AE is not available for 6U high variant (digit #1 = T or V) with RTD card option
(digit #5-6 = BA, BB or BC)
GUID-4642B41A-FAA5-4178-B117-5CB69DC75A70 V3 EN
ABB 57
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
SBGAABACBBAZAANBXD
# Description
9 Communication modules (Serial)
Serial glass fibre (ST connector) A
Serial plastic fibre (Snap-in connector) B
10 Communication modules (Ethernet)
Ethernet 100Base-FX (LC connector) A
Ethernet 100Base-TX (RJ-45 connector) B
11 Communication (Protocol)
IEC 61850 protocol A
IEC 61850 and DNP3 TCP/IP protocols B
IEC 61850 and IEC 60870-103 protocols C
GUID-A0EFE2B7-D63B-4BBB-9F53-A49D3125D585 V3 EN
SBGAABACBBAZAANBXD
# Description
12 Language
Language package Z
13 Front panel
Integrated LHM1) A
Detached LHMI + 1 m cable B
Detached LHMI + 2 m cable C
Detached LHMI + 3 m cable D
Detached LHMI + 4 m cable E
Detached LHMI + 5 m cable F
No LHMII 2)
N
14 Option 1
Transformer differential protection for two-winding transformers3) A
Third harmonic based stator earth-fault protection 4)
B
All options3,4) Z
None N
15 Option 2
None N
16 Power supply
Power supply 48-125 VDC A
Power supply 110-250 VDC, 100-240 VAC B
17 Reserved
Undefined X
18 Version
Version 1.3 D
58 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Example code: S B G A A B A C B B A Z A A N B X D
Digit (#) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Code
GUID-E3F56E28-FDF2-4963-A1FE-D79599D4FE3A V3 EN
22. Accessories
Flush mounting kit for one 4U half 19” housing IED 1KHL400040R0001
Semi-flush mounting kit for one 4U half 19” housing IED 1KHL400444R0001
Wall-mounting kit (cabling towards the mounting wall) for one 4U half 19” housing IED 1KHL400067R0001
Wall-mounting kit (cabling to the front) for one 4U half 19” housing IED 1KHL400449R0001
19" rack mounting kit for one 4U half 19” housing IED 1KHL400236R0001
19" rack mounting kit for two 4U half 19” housing IEDs 1KHL400237R0001
Overhead/ceiling mounting kit (with cable space) for one 4U half 19” housing IED 1KHL400450R0001
Wall-mounting kit for direct rear wall mounting (with cabling to the front) of one 6U half 19" housing IED 1KHL400452R0001
Wall-mounting kit (with cabling towards the mounting wall) for one 6U half 19" housing IED 1KHL400200R0001
Overhead/ceiling mounting kit (with cable space) for one 6U half 19" housing IED 1KHL400464R0001
19" rack mounting kit for one RTXP8 test switch (the test switch is not included in the delivery) 1KHL400465R0001
19" rack mounting kit for one RTXP18 test switch (the test switch is not included in the delivery) 1KHL400467R0001
19" rack mounting kit for one RTXP24 test switch (the test switch is not included in the delivery) 1KHL400469R0001
Connector set for one 4U housing IED including analog input variant 4I + 5U or 5I + 4U 2RCA021735
Connector set for one 6U housing IED including analog input variant 4I + 5U or 5I + 4U 2RCA021736
Connector set for one 4U housing IED including analog input variant 7I + 3U 2RCA023041
Connector set for one 6U housing IED including analog input variant 7I + 3U 2RCA023042
Connector set for one 4U housing IED including analog input variant 8I + 2U 2RCA023039
Connector set for one 6U housing IED including analog input variant 8I + 2U 2RCA023040
ABB 59
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
24. Tools browser (IE 7.0 or later). For security reasons, the web-
The IED is delivered either with or without an optional factory browser based user interface is disabled by default. The
made preconfiguration. The default parameter setting values interface can be enabled with the PCM600 tool or from the
can be changed from the front-panel user interface, the web- front panel user interface. The functionality of the interface is
browser based user interface (WebHMI) or the PCM600 tool by default limited to read-only, but can be configured to
in combination with the IED specific connectivity package. enable read and write access by means of PCM600 or the
local HMI.
PCM600 offers extensive IED configuration functions such as
IED application configuration, signal configuration, DNP3 The IED connectivity package is a collection of software and
communication configuration and IEC 61850 communication specific IED information, which enable system products and
configuration including horizontal communication, GOOSE. tools to connect and interact with the IED. The connectivity
packages reduce the risk of errors in system integration,
When the web-browser based user interface is used, the IED minimizing device configuration and set-up times.
can be accessed either locally or remotely using a web
60 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Parameter setting ● ●
Disturbance handling ● ●
Signal monitoring ● ●
Event viewer ● ●
Hardware configuration - ●
Signal matrix - ●
Communication management - ●
User management - ●
Creating/handling projects - ●
IED Compare - ●
25. Supported ABB solutions among the distinctive features of the protection system
ABB’s 630 series protection and control IEDs together with approach enabled by the implementation of the IEC 61850
the Grid Automation controller COM600 constitute a genuine substation automation standard.
IEC 61850 solution for reliable power distribution in utility and
industrial power systems. To facilitate and streamline the At the substation level COM600 utilizes the logic processor
system engineering ABB’s IEDs are supplied with and data content of the bay level IEDs to offer enhanced
Connectivity Packages containing a compilation of software substation level functionality. COM600 features a Web-
and IED-specific information including single-line diagram browser based HMI providing a customizable graphical
templates, manuals, a full IED data model including event and display for visualizing single line mimic diagrams for
parameter lists. By utilizing the Connectivity Packages the switchgear bay solutions. To enhance personnel safety, the
IEDs can be readily configured via the PCM600 Protection WebHMI also enables remote access to substation devices
and Control IED Manager and integrated with the Grid and processes. Furthermore, COM600 can be used as a local
Automation controller COM600 or the MicroSCADA Pro data warehouse for technical documentation of the substation
network control and management system. and for network data collected by the IEDs. The collected
network data facilitates extensive reporting and analyzing of
The 630 series IEDs offer support for the IEC 61850 standard network fault situations using the data historian and event
also including horizontal GOOSE messaging. Compared with handling features of COM600.
traditional hard-wired inter-device signaling, peer-to-peer
communication over a switched Ethernet LAN offers an COM600 also features gateway functionality providing
advanced and versatile platform for power system protection. seamless connectivity between the substation IEDs and
Fast software-based communication, continuous supervision network-level control and management systems such as
of the integrity of the protection and communication system, MicroSCADA Pro and System 800xA.
and inherent flexibility for reconfiguration and upgrades are
ABB 61
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Product Version
62 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
3 BO3_PO_TCS 3 BO3_PO_TCS
VT 5 CT 5
4 TCS 4 TCS
6 6
5 5
VT VT, CT
6 BO4_PO 6 BO4_PO
7 7
7 7
VT 8 VT 8
8 8
BO5_PO BO5_PO
9 9
VT 9 VT 9
10 10 10 10
BI4 17 BI4 17
5 BO9_SO 5 BO9_SO
6 18 6 18
BI5 BI5
7 7
BI6 BI6
8 8
BI7 BI7
9 9
BI8 BI8
10 10
11 11
BI9 BI9
12 12
BI10 BI10
13 13
BI11 BI11
14 14
15 15
BI12 BI12
16 16
BI13 BI13
17 17
BI14 BI14
18 18
X9 X9
(glass) transmitter (glass) transmitter
1) 1)
TX Fiber optic (plastic) transmitter TX Fiber optic (plastic) transmitter
RX Fiber optic (glass) receiver 1)
RX Fiber optic (glass) receiver 1)
(plastic) receiver (plastic) receiver
X4 X4
1 GNDC 1 GNDC
2 NC 2 NC
3 IRIG-B- 3 IRIG-B-
4 IRIG-B+ 4 IRIG-B+
X1 X1
LAN 1 2) LAN 1 2)
X0 X0
LAN / HMI 3) LAN / HMI 3)
1) Optional 1) Optional
GUID-78CCF517-A2D8-49C3-9E61-15A6879DA9AE V1 EN
ABB 63
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
GUID-5E27DD50-FD15-4824-BDFB-DD52E29730EA V2 EN
Unit BI/BO
4U X319 + X3161)
X324 + X321
6U X324 + X3211)
X329 + X326
X334 + X331
X339 + X336
64 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
GUID-CB7B1CF8-A0E4-42F5-998C-701641515127 V1 EN
27. References
The www.abb.com/substationautomation portal offers you
information about the distribution automation product and
service range.
ABB 65
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Protection
Three-phase directional overcurrent protection, low stage DPHLPDOC 3I> -> 67-1
Three-phase directional overcurrent protection, high stage DPHHPDOC 3I>> -> 67-2
Three-phase thermal overload protection, two time constants T2PTTR 3Ith>T/G 49T/G
66 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
Control
Measurement
ABB 67
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
68 ABB
Generator Protection and Control 1MRS757583 B
REG630
Product version: 1.3
ABB 69
70