PROl ECTIVE R E L A Y S , CONTI�OLS D E V I C E S AND

I N S T R U M E N T S - SPECIFICATION
T A B L E Of' CONTENTS

0.1 Circulation Lisi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . • . . . . . . . . . . . . . . . . . . . . . . . . . • . . . . . . . . . . . . . . . . . 4

0.2 A m e n d m e n t Recore! , 5

FOREWORD 6

l . SCOPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . • . . . . . . . . . . . . . . . . . . . . . • . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

2. N O R M A T I V E R E F F. R E N C E S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . • . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

3. D E T' l N I T I O N S A N D A B B R E V I A T I O N S 8

J. I . /\ 13 f3 R E V I A T I O N S ..................................................................•...........•......................... 8

4. R E Q U I R E M l3 N T S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . • . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

4.1. SERVI E C O N D I TI O N S 8

4.2.
G E N E R /\ L R E Q l J I R E M E N l S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . • . . . . . . . . . . . . . . . . . . . . 8

4.3. S l ' E C l f' I C R E Q U I R l : M E N T S ,. 9

4.3.1. Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . • . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

4.3.2. Instruments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . • . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I O

4.3.3. Protective Relays IO

4.4.DETAll .rm S P E C ll' I C A T I O N S - R E L /\ V S . I N S T R U M E N T S /\ N D CONTROL D E V I C E S 1 1

4.4.1. Ratings for Protection Relays and Control Devices: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . • 1 1

4.4.2. Distance Protection Relay Type 1 : 1 1

4.4.3. Distance Protection Relay Type I I : I 7

4.4.4. Biased Differential Protection Relay for a Two or Three W i n d i n g Power lransformer:22

4.4.5. Restricted Earth Faull Relay: 24

4.4.6. Feeder Protection Relay: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . • • . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

4.4.7. Electrical R e s e t - T r i p Relay 29

4.4.8. Sci f-Reset Trip Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . • . . . . . . . . . . . . . . . . . . , 30

4.4.9. Trip C i rc u i t Supervision Relay Type I : . . . . 31

4.4.10. A u x i l i a r y relays For Transformer M e c h a n i c a l Protection Trip Function Type I : 32

4.4.11. A n n u n c i a t o r Relay Type I 32

4.4.12. A n n u n c i a t o r Relay Type 1 1 : , 34

4.4.13. Discrepancy S w i t c h for C i r c u i t Breaker C o n t ro l : 35

4.4.14. Semaphores lor I s o l a t o r and Earth Switch P o s i t i o n I n d i c a t i o n 16

4.4.15. LED I n d i c a t i n g Lamps:- 37


TITLE: Du,. Nu. KP 1 /JC!J/TSP/02/004

\:_ PROTECTIVE RELAYS, CONTROL Issue Nu. I

-
-
DEVICES A N D I N S T R U M E N T S ­

S l ' F: C I F I C A T I O N
Rcvlsiun Nu. 3

Kenya Power Dale of Issue 2019-06-07

Page 3 ul'72

4.4.16. M u l u- F u n c r i o n u l Power Meler 38

4.4.17. A d d i t i o n a l S p e c i f i c a t i o n s for Relays 40

'
4.4.18. Relay Programming Software and Connection Cables .4()

A P P E N D I X /\ : TESTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . • . . . . . . . . . . . . . . . . . . . . . . 4 1

A l ' P E N IJ I X 13: WARRANTY 41

APPl:NDIX Q U A L I T Y M A N A G E M E N T SYSTl'M ( N O R M A T I V E ) 4 1

/\ l ' l ' E N IJ I X IJ: TECI I N I C A I . D O C U M l i N T /\ T I O N ( N O R M A T I V E ) 42

A P P E N D I X F· T E C H N I C A L M A N U A L S / G U I D E & O P E R A T I O N A N Ll M A I N T L ' N A N C ! , M A N U A L S

,13

A P P E N D I X F: FACTOl{Y ACCEPTANCE TESTS, I N S P E C T I O N A N D T l { A I N I N G 44

APl'ENDIX G: LO 'AL T R A I N I N G I N N A I R O l:1 1 .44

APPENDIX H: R E Q U I R E M E N T FOR T E N D E R ' E V A L U A T I O N .45

A l ' l ' E N IJ I X I: SOFTWARE 46

A P P E N D I X J: re TO IJ E V I C E C O N N E C T I O N C A l1 1 . E 46

/\ l ' l ' !o N IJ I X K: P A C K I N G A N D D E I . I V F R Y . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . • . . . . . . . . . . . . . . . . . . . . . . . . . .46

APPENDIX I.: D E i . I V E I Z Y . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . • . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

/\ l ' l ' E N D I X M : T E N D E R A W A R D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . • . . . . . . . . . . . . . . • . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

APl'l'NDIX N: T E C H N I C A L S C H E D U L E S FOR R E L A Y S : . . . . . . . . . . . . . . . . . . . . . . • . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .119

Issued by: Head of Section, Standards Development A u t h o r i z e d by: Head or Department, Standards

Signed: Signed:

Date: 2019-06-07 Date: 20 I 9-06-07


Doc, No.
TITLE: KP I /3CB/'J'S P/02/004

l
Issue No.
PROTECTIVF, RV.LA VS, C O N T R O L I

- -
DEVICES A N D I N S T R U M E N T S -

S P E C I Fl CATION
Revialnn No.
3

Kenya Power Dr11<: of IS.f;,111.l


2019-06-07

Pugc '1 of" 72

0 . 1 C i r c u l a t i o n Lisi

COPY NO. COPY I I O L D EI {

I Manager. Standards

E loctronic copy (pell') on Kenya Power server ( hllp://\ 7 2 . 1 6 . i .40/drns/browsc.php?ffolderlcl=23)

R F. V I S I O N OF K P L C S T A N D A R D S

To keep abreast of progress 111 the industry. KPLC Standards shall be regularly reviewed.

Suggestions for i Ill provemen ts to approved standards, addressed to the Manager. Standards

department, arc welcome.

ID Kenya Power & L i g h t i n g Co. Ltd.

Users arc re m i n d e d that by S e c t i o n 25 of the Copyright Act, 200 I (Revised 2009) Cap 1 3 0 o f the

Laws of Kenya copyright subsists in a l l K P I . C Standards and except as provided under Section 26

of t h i s act. no KPl"C Standard produced by K P L lllllY be reproduced. stored i n retrieval system by

any means without prior permission from the M a n a g i n g Director & CEO, K P L C .

Issued hy: I-lead of Section, Standards Development A u t h o ri z e d hy: I-lead of Department, S t a n d a r d s

Signed: Signed:
a , , v' )\ ) ) _..C O L,
". '
-y �
Date: 2019-06-07 D n t c : 2019-06-07
TITLE: Due. No.
KP I /3 C il/' f 'SI' /02/004

l P R O T E C T I V E R E L !\ YS, C O N T R O L tssuv Nu.


I

-
-
DEVICES AND INSTRUMENTS-

SPECIFICATION
Rcvisiun Nu.
"
j

Kenya Power D1111: or l.ssuc


2019-06-07

Pugc 5 of 72

0.2 A m e n d m e n t Record

Rev Date Description of Prepared by Approved by

No. (YYYY-MM-DD) Change ( N a m e & Signature) ( N a m e & Signature)

lssue I 2018-06-28 Replaces Issue l S. N g u l i


rev O
LJr. Eng. P. Kimernia

Rev l ol 2013-08-29

I SSllC I 2019-06-07 Replaces Issue I rev l Nancy W a i ri r n u Dr. Eng. l'. K imerniu

Rev 2 or 20 I 8-0G-28

Issued by: l leud of Section, S t u n d u rd s Devclupmeut A u t h o ri z e d by: Heud of D e p a r t m e nt, Standards

Signed: Sii;11cd: '


r M-·0-, • '
'
v v
:,

Date: 2019-06-07 D a t e : 2019-06-07


TITUC:: Doc. No.
KP I /3Cl3/TSP/02/004

l
Tss11�· No.
PROTECTIVI<: R E L A VS, C O N T R O L I

- -
DEVICES AND INSTRUMENTS-

SPECIFICATION
Revision Nn,
'

Kenya Power DiHl' uf Issue


2019-06-07

Pngc (
1 of 72

FOREWORD

This specification has been prepared by Network M a i n t e n a n c e (Protection section) of the Network

Management D i v i s i o n i n c o l l a b o ra t i o n with Standards Department both ofborh oi'The Kenya l 'o w e r

and L i g h t i n g Company L i m i t e d ( K P L ) and lays down specification for Design, Manufacture and

Tosti ng of Protective Relays. Control devices and Accessories, Measuring and Indicating

I nst ru 111 en ts.

This s p ecific a tion is intended for procurement of materials and docs not i n c l u d e provision o f contract.

This specification s t i p u l a t e s the m i n i m u m requirements for protective relays. control devices mid

measuring and indicating instruments acceptable for USC 111 the company and it shal I he the

r e s p o n s i b i l i t y of the s u p p l i e r s and manufacturer to ensure that the o ff e re d design is or the h i g h e s t

q u a l i t y and guarantees excellent service to KPLC, and good w o r k m a n s h i p and good engineering

practice in the manufacture.

There are no other spcci fl cations in t h i s series.

Users or these Kenya Power s p e c i fi c a t i o n s arc responsible for their correct i ntcrprctation and

application.

The following arc members of the team that developed t h i s specification.

Name Depa rt men t

Eng. Paul Mwangi Network Maintenance

Eng. Stephen N g u l i Standards

Mr Bernard Rouch Standards

Mrs. Nancy W a i ri m u Standards

Issued hy: I-lead of Section, Standards Development /\ 1 1 t h o l ' i z c d hy: 1-lcfld of' D c p n rt m c n t , Standards

Signed: Signed: - t
r

:
. �� ill )J- ) f J

Date: 2019-06-07 '


f Date: 2019-06-07
TITLE: Due. No. Kl'I/JCB/TSP/02/004

l
PROTECT! V E R E L A YS, CONTROL Issue No. I

- OE V I C E S A N D I N S T R U M E N T S -

Sl'ECIFICATION
llcvisiuu No. 3

Kenya Power Date of Issue 2019-06-07

I. SCOPli:

This specification is for Protective Relays, Controls devices and I n s t r u m e n t s .

2. N O R M A T I V E R F. F E R E N C E S

The f o l l o w i n g standards c o n t a i n provision which, through reference in this text, constitute provisions

0 1· t h i s s p ec i f i c a t i o n , For elated e d i t i o n s the cited e d i t i o n w i l l apply; for undated e d i t i o n s the latest

e d i t i o n of the re f e re n c e d document s h a l l a p p l y : -

IEC 60255: Measuring relays and protection e q u i p m e n t . Part I : Common re qu i re m e n t s

(All relevant parts)

l lc'. C 6 0 6 8 8 : Electrical measuring transducers for converting a.c. and D . C . e l e c t r i c a l quantities to

analogue or d i g i t a l s i g n a l .

IEC 6 1 0 0 0 - 4 - 1 3 : Purl 4 - 1 3 : Electromagnetic c o m p a t i b i l i t y (EMC) - Testing and measurement

techniques. H arm on i c s and i n t e r h arm o n i c s i n c l u d i n g mains s i g n a l l i n g .

I l�C 6 1 8 5 0 - 8 - 1 : 2 0 1 1 : C o m m u n i c a t i o n networks and systems for power u t i l i t y automation

ICC 60932 A d d i t i o n a l requirements I o r enclosed switchgear and comrolgear trorn I kV to 72.5 k V

to be used i 1 1 severe c l i m a t i c c o n d i t i o n s

IEC 6 0 0 5 1 Direct acting indicating analogue electrical measuring instruments and their

accessories. (Relevant purls)

I FC 60870-5- I 03 Tc l c c o mro l equipment uud systems - Pan 5-103: Tra n s m i s s i o n protocols -

C o m p a n io n standard t o r the i n f o rm a t i v e i n t e rf a c e c fp ro t e c t i o n e q u i p m e n t

ICC 61010-1 Safely requirements lvr electrical e q u i p m e n t Ior measurement, control, and laboratory

use - Part I : General re qu i re m e n t s

BS 1 4 2 E l e c t r i c a l protection relays. R equirem ent s lor single i n p u t energizing qu a r n i r y relays.

Specification for s ing!<! i n p u t energizing q u a n t i t y m e a s u r i n g relays w i t h dependent

specified t i m e

I S O / I C C 1 7 0 2 5 General re qu i re m e n t s lor the competence o tt e s t i n g and ca libr atio n iaborutorics

I SO 900 I : 2 0 1 5 Qua! ity management systems -- Req uircmcnts

Issued by: Head of S cc t i o u , S t u n d u rd s D c v e l u p u u- u t A u r h u ri z e d by: Head uf D c p u rt m e n t , S t a n d a rd s

Si�ncd: � Si!(ucd: ,...:::::::.i......,-;.£.--

'-------:::_��L::a:.'.--_---+-------� - // D
Dute: 2019-06-07 Date: 2019-06-07
TITLE: Doc. No. K P I /3CB/TSP/02/004

l
Issue No.
PROTECT! VE IUtLA VS, C O N T R O i . I

- -
D l � V I C F. S A N D I N S T R U M F. N T S ­
Revision No. 3

SPECIFICATION
Kenya Power Dure of Issue 20 J 9-06-07

Pngu R rir12

3. D F. F I N I T I O N S A N D A B B R E V I A T I O N S

For the purpose of t h i s specification the d e fi n i t i o n s and a b b r e v i a t i o n s given in t h e reference standards

shall a p p l y together w i t h the following:

3.1. ABBREVIATIONS

KPLC- Kenya Power and L i g h t i n g Company L i m i t e d

I EC - I n t e r n a t i o n a l Electro Technical C o m m i s s i o n

ISO - I n t e rn a t i o n a l Organi zation for Standardization

4. REQUIREMENTS

4.1. SERVICE CONDITIONS

The e q u i pm e n t s h a l l be t ro p i c a l i ze d , designed and constructed for c o n t i n u o u s i n d o o r operation

in areas w i t h the following atmospheric c o n d i t i o n s : -

(i) Altitude: Fro111 sea level up In 2200111 above mean sea level.

(ii) Humidity: High a, the Coast, up 10 95% a n d lower i n l a n d . up 10 50%.

(iii) Temperatures: Average a m b i e n t t e m p e ra t u r e o f + 35"C w i t h a m i n i m u m or - I °C and a

m a x i m u m of +40'C.

(iv) Maximum Indoor temperature i n s i d e t h e Relay Panels is +50 • C.

(v) Pollution: Design p o l l u t i o n level to be taken as "Heavy" ( P o l l u t i o n l e v e l Ill) for i n l a n d

and "Very Heavy" ( P o l l u t i o n level IV) for coastal a p p l i c a t i o n s in accordance w i t h IEC

60815.

Heavy saline with severe corrosive effects in coastal lands and g e n e ra l l y clean air

in lancl.

4.2. GENERAL REQUIREMENTS

4.2. I . /\ I I Relays shall be designed for operations in the severe t ro p i c climate c o n d i ti o n s and fully

c o m p l y w i t h c l i m a t i c a g i n g tests as per I EC 6 0 9 3 2 - C l a s s 2.

4.2.2. In choosing materials and their finishes, due regard sh,111 be given to the humid t ro p i c a l

c o n d i t i o n s u n d e r which the R e l a y w i l l work.

4.2.3. Iron and Steel are g e n e ra l l y lo be painted or galvanized as a p p ro p r ia t e . I nd o o r p ar t s m ay

a l t e rn a t i v e l y have c h ro m i u m or c o pper - nic k el pl a ted or other app roved p ro t e c t iv e fi nish.

Issued hy: Head of Section, S t a n d a rd s Development A u t h o ri z e d by: Head of D c p n r n n c n r , S t a n d a rd s

Signed: Signed:

Date: 2019-06-07 I D a t e : 2019-06-07


T IT L E : Do,·. No. Kl' I /3C U/'J'S P/02/0()4

l
-
P R O T E C T I V F. R E L A Y S , CONTROL

UI,VICES ANU INSTRUMENTS-


Issue No. I

3
-
R,visiu11 No.

Sl'ECI F I C A T I O N
Kenya Power U,11, or Issue 20 J 9-06-07

Page 9 ul'72

4.2.4. S111all i ro n and steel purls (other thun s t a i n l e s s steel) ot' a l l Relays and instruments, the cores 01·

electromagnets and the 111e1�J puns o f relays und m e c h a n i s m s shall be treated in an appropriate

manner to prevent rusting.

4.2.5. The use oJ' Iron and steels shall be avoided 111 i n s t ru m e n t s and c lec t ri cu l relays wherever

possible. Steel screws s h a l l be zinc, cadmium or c h ro m i u m plated or where plating is not

possible owing to tolerance l i m i t at i o n s ; it shall be o lc o rro s i o n r e s i s t i n g steel.

4.2.6. I n s t r u m e n t screws (except tho se fo r m i n g pun o fa magnetic c i r c u i t ) s h a l l be olbrass or b ro nze.

4.2.7. S p rin gs sha!l be of n u n - r u s t i n g m a t e ri a l , c.g., p h ospho r -bronze or nickel silver, as for us

possi bl e.

4.2.8. N e o p re n e an d s i m i l a r synthetic c o mp ou n ds . not subjec t to deter i ora t io n du e to the climatic

c o n d i t i o n s , s h a l l be used lor gaskets.

4.2.9. Power s up p l y m o du l e s t o r Relay s and M e a s u ri n g ins t rumen t s:

(i) All e q ui pmen t and a ppara tu s including p rotectiv e relays and con tr ol and measuring

dev i ce s shal I be c apa b le of s a t i s f a c t o ry o p e ra t i o n at 80% to 1 2 5 % or t h e rated supply

v o ltag e .

(ii) The Ra ted DC su pp l y v o lt age s h a l ] be i n s c rib e d on the device.

4.J. S l ' E C I F I C l{EQUll{EMENTS

4.3. I . M a t e ri a l s

4.J.1.1. A l l m a t e ri a l s s h a l l be new and of the best q u a l i t y and of the d<1ss m o st s u i t a b l e for worki n g

under the c o n d i t i o n s specified.

4 . 3 . I .2. The de vi ces s h a l l w i t h s t a n d the v ar i ations o lt c r n p e ra t u rc and atmospheric c o n d i t i o n s a r i s i n g

under working c o n d i t i o n s w i t h o u t d i s t o rt i o n , deteriora t ion or un d ue stresses i n any p ans or

heating,

4.3.1.3. A l l the devices s h a l t be s u i t a b l e tor i n s t u l l a t i o » i n re l ay p anels i n s i d e c o n t ro l rooms w i t h o u t

air conditioning.

4.3. I .4. The heat generated by the relays and other measurin g de v i c e s shall t h erefor e be m i n i m a l to

ensure that the temperature i n s i d e the p anels does 1101 rise beyond t he ra t i n g otthc relays and

other devi c es .

Issued by: I lead uf S e c t i o n , S t u n d u r d s D e v c l u p m c n t Authorized by: Mead of Dcparuucut, S t a n d a r d s

Signed:

Ihle: 2019-06-07
T I T l , F. : no,·. No. KP 1/3CB/TSP/02/004

l P R O T E C T I V E RELA VS, CONTROL Issue. No. I

- -
D E V I C E S A N D I N S T R l J M F: N T S ­
Rcvlslnn No. 3

SPF.: I FI CATION
Kenya Power Dote of Issue 20 J 9-06-07

l'agc I O nt' 72

4.3.2. Instruments

4.3.2.1. /\ I I measuring instruments, including the energy meters. shall be 01· f l us h - m o u n t e d, buck­

connected. dust-proof' and heavy-duty switchboard type and 111 accordance with th

r e q u i r e m e n t or !EC 6 0 0 5 1 .

4.3.2.2. For analogue type instruments. scale plates shall be of' a permanent white circular or

r e c t a n g u l a r f i n i s h with black pointer and m a r k i n g s . The scale range s h a l l be provided as given

in t h e dcrai led speci fications.

4.3.2.3. /\ I I measuring i n s t r u m e n t s o fa n a l o g type s h a l l be a p p ro x i m a t e l y 96 X 96 111111 enclosures and

s h a l l be provided with clearly readable long scale. a p p ro x i m a t e l y 240 degrees. The m a x i m u m

error s h a l l not be more than one and a h a l f ( I .5%) percent of full-scale range.

4.3.3. P r o t e c t i v e Relays

4.3.3.1. A l l Measurement relays s h a l l be flush mounted and of N u m e r i c Design, with event recording.

disturbance recording, power measurement, and s h a l l be i n accordance to ! E C 6 0 2 5 5 .

4.3.3.2. Besides the communication port, the relays shall have a h u m a n - m a c h i n e interface facility

(I ! M l ) comprising a keypad and an LCD screen, where one can easily access relay

information and m a n u a l l y program the parameter s e t t i n g s .

4.3.J.J. Relay contacts s h a l l be s u i t a b l e for m a k i n g and breaking t h e m a x i m u m currents. w h i c h they

arc required In control in normal service.

4.3.3.4. In p a rt i c u l a r, the Relay Trip contacts shall be capable of i n t e rr u p t i n g w i t h o u t damage the

Circuit Breaker Trip C o i l Current s h o u l d the i rc u i t Breaker A u x i l i a r y Contacts fail to open.

Relay trip contacts s h a l l be rated for 130V DC and s w i t c h i n g capacity or I O O O W / V /\ make.

and JOW/V A break. P e r m i s s i b l e current s h a l l be 5/\ c o n t i n u o u s and I Si\ t o r 3 seconds.

4.3.3.5. Where contacts of the protective relays are not sufficient for C i r c u i t Breaker T r i p p i n g and

i n te rru p t i n g the Trip Current, t h i s s h a l l be clearly stated by the manufacturer.

4.3.3.6. Relay contacts shall make fi r m l y without bounce and the relay mechanism shall not be

affected by Panel v i b ra t i o n or external m a g n e t i c fi e l ds ,

4.3.3.7. Relays shall be suitable for o p e ra t i o n on the rated D.C. auxiliary supply without use of

d r o p p i n g resistors or d i des.

4.3.3.8. The relay Thermal rating shall be such that the fault clearance t i m e s on any c o m b i n a t i o n o f

current and t i m e m u l t i p l i e r settings s h a l l not exceed the thermal w i t h s t a n d c a p a b i l i t y of the

relay. ( M a x . fault c u r r e n t = 3 1 . S k A ) .

Issued hy: Head of Section, S t a n d a rd s Development Authorized by: Head of Department, S t a n d a r d s

Signed: Signed:

Dale: 2019-06-07 Date: 2019-06-07


TITLE: lluc. Nu. KP I /3CB/TSP/02/004

l
P R O T E C T I V E RELAYS, CONTROL Issue Nu. I

-
-
DEVICES AND INSTRUMENTS­

SPECIFICATION
Kenya Power IM, or Issue 20 J 9-06-07

PHgt..'. 1 ! ul"72

4 . 3 . 3 . 9 . The relays. control devices and instruments shall be s u p p l i e d complete w i t h a l l screws, bolts,

b ru c k e t s und all other uccessories necessary for m o uru i n g / i n s t a l l a t i o n 111 panels and

r e r m i n au n g a l l external w i r i n g connections.

4 . 3 . 3 . 1 0 . Plug i n a u x i l i a r y relays for D I N ra i l m o u n t i n g s h ul ] be s u p p l i e d complete w i t h the bases.

4.4. D E T A I L E D S P E C I F I C A T I O N S - R E L /\ VS, I N S T R U M E N T S A N D C O N T R O L D E V I C E S

4.4.1. Ratings for l'rotcction Relays and C o n tro l Devices:

U n l e s s otherwise stated, a l l protection relays and control devices s h a l l have the f o l l o w i n g rated values:

(i) The power system where the relays are to be i n s t a l l e d has nominal frequency of 501-IZ

(ii) The rared CT secondary cw-rent is I A

(iii) The rated VT secondary voltage is 1 1 OV A C , phase to phase ( 6 3 . S V /\C phase 10 ground)

(iv) DC a u x i l i a r y rat i n g is 1 1 OV DC.

(v) Relay trip operation shall be indicated by a red LED. for measurement relays, Red

mechanical llags are acceptable t o r t ra n s f o rm e r mechanical protection - a u x i l i a r y

4.4.2. Distance Prutccrion Relay Type I :

4.4.2.1. The Distance relay is Ior use 011 Tra n sm i s s i o n Lines, to provide Ii.1st and h i g h l y dependable

selective f a u l t clearance on both overhead mid underground feeders.

4.4.2.2. The R e l a y sh,111 be lor application i n a substation with I Y, c i r c u i t breaker c o n t l g ura i i o n ,

hence s h a l l be s u i t a b l e for t r i p p i n g or two c i r c u i t breakers. m on i t or i n g the status or two

c i r c u i t breakers and a ut o ma t i c recloser or two c i r c u i t breakers. The relay s h a l l be used tor

re t ro f i t 10 replace e x i s t i n g old static & electn mechanical relays.

M a n u fa c t u r e r ' s E x p e r i e n c e a n d P r o d u c t Q u a l i fi c a t i o n

4.4.2.3. The Distance Protection Relay Type I manufacturer shall have a m i n i m u m experience or

25 years i n the m a n u t a c t u rc or Distance p ro t e c t i o n relays, I 5ycars or w h i c h s h a l l be in the

m a n u f a c t ure or N u m e r i c a l D i s t a n c e Protection relays.

4.4.2.4. The Relay type o t t e re d m u s t have been in Service and given re l i ab l e ervice tor a m i n i m u m

period o r 8 years, in at least two u t i l i t i e s , in at least three or the Joi l o w i n g regions/continents:

,1. Europe

b. North America

c. A trica and

d. /\sin

I ssued hy: Head of S c c t i o u , Suuulurds Development A u t h o ri z e d by: Hem! uf D e p a rt m e n t , S t a u d n r d s

Sigm•d: � �. -. '
Sigucd:
....,.. .., . '-•� ,",. j· ) �

Dute: 2019-06-07 v D a t e : 2019-06-07


TITLE: nor. No. K l' 1 /3CB/TSP/02/004

\'_ PROTECTIVE R E L A VS, C O N T l < O L Issue No. J

- OEVICES A N D I N S T R U M E N T S ­

SPECI f1 1 C A T I O N
Revisiun No. 3

Kenya Power llnlc of ls,uc 20 J 9-06-07

Pngc 12 nf 72

Note: The monufa .turer shall provide references to support this req11ire111e111. including

Export records with copy '!f contract fellers. relay de/ails and date of export. I.etters of'

satisfactionfrrn» the utiluies should also be provided 111i1h the hid 1'111ail address co ntactsfor

Senior Technical personnel in the utilities where the relay is already in service shall he

provided with the hid.

4.4.2.5. Relays that have failed i n service or mal-opcratcd 011 the Kenyan Power System s h a l l not

be accepted.

4.4.2.6. The Warranty for the offered relay s h a l l be F i v e (5) years from the date ofrelay d e l i v e r y to

K P L C Store.

F u n c t i o n s and Features:

4.4.2.7. The Distance Protection Relay s h a l l have Four (4) analogue current input channels and Five

(5) voltage input c h a n n e l s for connection o f CTs & VTs secondary a n a l o g u e s i g n a l s as a

111ini111u111.

4.4.2.8. The relay s h a l l be c fN u m e ri c / D i g i t a l Design and employ complete d i g i t a l signal processing

of measured values.

4.4.2.9. The relay s h a l l be s u i t a b l e for Flush m o u n t i n g on the protection panel.

4.4.2.10. The relay shall have Full Scheme distance protection. with p a ra l l e l calculation and

m o n i t o r i n g o fa l l the fault loops.

4.4.2.11. The relay s h a l l have selective s i n g l e phase and/or three phase t r i p p i n g Logic

4.4.2.12. Under Impedance Starting criteria. Other s t a rt i n g criteria in a d d i t i o n to the under impedance

starting are acceptable.

4.4.2.13. Five zones or phase distance protection (Ior Phase-phase faults) w i t h selectable M h o and

quadrilateral characteristics. Pararnctcrs ( r e s i s t iv e reach. reactive reach and t i m e delay) for

each zone t() be i n d e p e n d e n t l y set.

4.4.2.14. As a 111inim L1111 live zones o f ground dista n ce p ro tecti o n . (for Phase- G ro u n d/ P h a s e - E a rt h

Faults) with selec ta ble Mho and Q uadril a te ra l c h a ra c t e ri st i c s with r e s id u a l c urr e nt

co m p e n sation. Pa ram eters (r es istive reach. r ea ctive reach and t i m e del a y ) for each Zone to

be ind e pendently set.

4.4.2.15. The Distance Pro tection Zones d i re c t i o n s h a l l be independently set as forward or reverse or

non-di rc c t i o n .

4.4.2.16. O p e ra tin g t i m e for Dist a nce Zone I set at O s eco n ds del a y s h a l l not exceed 30111s

4.4.2.17. The Distance protection relay s h a l l have C o mm u n i c a t i o n Channel A ided S che m e l og ic for

p hase and g ro u n d dist a nce p ro tec t ion w i t h at least t he fo l l o w i n g sche m e s: -

(a) Per m is s ive U n d c rc a c h Transfer T r i p s c h em e (PU TT)

(b) Pe rm i ss ive Ov e rreach Transfer Trip s che m e (POTT) and

Issued hy: Head of Section, S t a n d a r d s Development Authorized hy: Hearl of D e p a rt m e n t , S t a n d a rd s

Signed: Signed: � l s•

- -- u
Ihle: 20 I '>-06-07 O n i e : 2019-06-07
TITLE: Dul'. Nu. KP 1/3CB/TSP/02/004

1 P R O T E C T I V E RELA VS, CONTROL Issue No. l

- -
DEVICES A N U INSTRUMENTS­
ltcvlsivn Nu. 3

SPECIFICATION
Kenya Power Dute uf Issue 2019-06-07

l'a!!,� I J of 72

(c) B l o c k i n g Schemes.

(d) Direct Tra n s f e r Tripping Scheme

Note: The Tele-protection scheme shall be suitablefor hardwiring connection between the relay

c111d the teleconnnuniccnion tnultiplexer cabinet,

4.4.2.18. Load e n c ro a c h m e n t Discriruiruuion Feature, to guarantee reliable d i s c ri m i r u u l o n between

loud o per a ti o n and short circuits fr,ult, lbr l o n g h e a v i l y loaded l i n e s , to prevent i n a dv e rt e n t

trips.

4 . 4 . 2 . 1 '). P a r n l k l l i n e compensation f e at ure lO cancel the effect of mutual i n du c t a n c e .

4.4.2.20. M e a s u r i n g voltage monitoring/ Fust! f a i l ur e supervision Logic.

4.4.2.21. The distance rcluy s h a l l be blocked lrorn operating in the event or f a i l ure o f the measuring

voltage or when the a u x i l i a r y switch of' the Voltage t ra n s f o rm e r secondary MCIJ trips.

4.4.2.22. Weak encl in-Iced P ru t c c t i o n : Echo and/or Trip, to a l l o w effective o p e rat i o n of p e rm i s s i v e

schemes when there is l i t t l e or no in-reed on one encl or the l i n e .

4.4.2.23. CL11Tcnl Reversal Guard Feature - f"or use on p ara l l e l lines, to prevent m a l - o p c ra t i o n or

relays on the healthy line, due 10 current reversal d u r i n g s e q ue n t i a l fault c l e a ra n c e .

4.4.2.24. Power S w i n g detection f e a t u re for blocking D i s t a n c e o p e ra t i o n for moderate power swings.

The Power swing shall be selected lo block or 1101 block each d i s t a n c e protection zone.

4.4.2.25. Out or step protection to a l l o w t r i p p i n g and network separation tor generator out or step

condition.

4.4.2.26. Voltage Memory Feature f"or use by the distance comparators

4.4.2.27. Aut ornu iic S w i t c h on to F a u l l Feuturct Sfr'lF). enabled when the l i n e is de-energised and

only active tor a set t i m e delay alter the line c i rc u i t breaker is closed

4.4.2.28. Directional lc'.anh Fault Prutcction. w i t h c o m m u n i c a t i o n channel aided scheme w i t h al least

the fo l l o w i n g schemes: -

(a) D i r e c t i o n a l C o m p a ri s o n Schcmcrl'O'I'T)

(b) B l o c k i n g Scheme

(c) Selectable Iinal 1i111e t ripping lor use w hen t he communication c h an n e l is 11 01 i n

use, or for use on ra di a l feeder. 11 s hall be p o s sibl e e n a b l e / d i s ab l e t he final time

t rip feature,

4.4.2.29. Bac k up t hr e e p h ase o v e rc urrc n t & E a rt h fault p rot e c t i o n , with the follow ing pr otection

luncuons:

a. I ligh set clement fo r P hase and E a rt h l au l t o v c rc u rre n t wi t h sel e c t a b l e de f i n i t e t ime

delay

Issued by: I-lead of Section, S t u u d u rd s Dcvcluprucut A u t h u r i :, c d by: Head of Ilc p u rt m e u t , S u u u l u rd s

Signed: Si!(ncd: 1
0
1
��������-
� -��-- ������-11

Dair: 2019-06-07 v D a l e : 2019-06-07


TITLE: noc. No.
K P I /3C13/TSP/02/004

l
Issue No.
PROTECT! VE RELA VS, CONTROL

- -
D E V I C F: S A N D I N S T R U M E N T S ­
Revision No. .
",

SPECIFICATION
Kenya Power Dnte of Issue
2019-06-07

b. Low set element for Phase and Earth fault overcurrcnt with inverse current-time

characteristics as per ! E C 6 0 2 5 5 .

4.4.2.30. S t u b \3us overcurrent p ro te c t i o n enabled v i a b i n a r y i n p u t when t h e bay d i sc o n n e c t e r is open

4.4.2.31. Under frequency and rate of' change of f re q u e n c y P ro t e ct io n

4.4.2.32. Overvoltage protection

4.4.2.33. Circuit Breaker F a i l u re Protection

4.4.2.34. Circuit Breaker Contact wear feature

4.4.2.35. Broken Conductor detection for A l a rm purposes.

4.4.2.36. A u t o - re c l o s e function for One Phase and/or three phases. suitable for use with the

f o l l o w i n g selections made v i a external switch:

(i) i\uto rcclose Block: No Auto-rcclose: Trip to Lockout for all faults

(ii) Single Pole Autorcclosc: (Single p ole Tri p a nd Auio-reclose for I istance Zon e I- p h a se

to g rou nd faults o n l y ) . Othe r fau l t typ es shall lcacl lo three p has e t r i p and lo c k out.

(iii) Single P o l e + Thr e e Phase Auto-rcclosc ( S P /\ R + D A R ) : Single pole t r i p and auto­

rcclosc for D i s t a nc e Z one I p ha s e to g round faults only, f ol low ed by t hree pole trip a n cl

a u t o - re c l o s e for the ne x t p hase to g ro u n d fault or p h a se to p h a s e lault within the reclaim

time). l lthe fi rst fau lt is p h a se to phase, t he n the s che m e will p erfor m one s ho t of three

p h a se tri p an d auto-rcclose only and lock o u t i fa second fault of any type occurs during

th e re c lai m t i m e . Three ph as e faults shall lead 10 three ph a se t rip and Lockout.

( i v j 'T h rc e Phase Auro-reclose ( D A R ) : th r ee p h as e Trip a nd auio-rcclose onl y for p h ase to

g ro und f au lts or Phase to Phase fa ults. Three p h a se tri p an d Lock out for three ph ase

faults.

(v) It shall be p o s s ible to initiate a u t o - re c l o s e in th e d is t a n c e r elay from t he line c u r rent

di lfercntial rel a y in the n e i g h b o u r i n g p a nel p ro t e c t i n g t h e sam e t ra n s m i s s i o n line.

4.4.2.37. S y n c h ro - c h c c k Function fo r use w i t h t hree p h a se a u t o - re c l o s e

4.4.2.38. Fault Locator; with a uto m a tic di s p l ay on th e Relay L D Screen of' the distance to fault in

terms of Lin c percentage or di s t ance in km . Thi s i n f o rm a t i o n is for use by the

m a i n ten a nce / r ep a ir tea m s . The l a st d istanc e to fa ul t w i l l always be displayed on the sc re e n .

for ease on access by the m a in t en a nce per s onnel.

Issued by: Hearl or Section. S ta n d a r d s Development A u t h o r i z e d hy: Head of Department, S11111clnrrls

Signed: Signed:
- <=&:..-,<-L.,,.-
•,
Date: 2019-06-07 '1/ D n t c : 2019-06-07
TITLE: Doc. No. KJ> l/JCO/TSP/02/004

issue No.
PROTECT I VI� R E L A VS, CONTROL J


nevi
-
-
ES A N D I N S T R U M E N T S ­
Revislun Nu. 3

Sl'ECIFICA'J'ION
Kenya Power Dale of Issue 2019-06-07

1'11g..: I 5 uJ' 72

Note I : In the bid subrnisslon the bidder shall demonstrate 1ha11/1e requirement oj'thi.,· clause

isjully 111e1. Requirement to use the keypad or PC us the unly way to access this informution

is not acceptable

Nole 2: Distance Reluys which do 1101 111ee1 this 1·eq11ire111e/71 shall not bl! accepted

4.4.2.39. The accuracy 01· Distance tu l a u l t l o c a t i o n slut I I be ±2% as a 111ini111u111.

4.4.2.40. The f o l l o w i n g i n f o rm ar i o n s h a l l be provided w i t h fault location:

(i) The s h o rt - c i r c u i t loop w h i c h was used to determine the fa u l t reactancc

(ii) The reaciance X per phase i n Oh111s P ri m a ry and secondary

( i i i ) The reactance R per phase in Ohms Primary and secondary

(iv) The distance 10 l a u l t i n percentage and kilometers u l ' l i n e l e n g t h

4.4.2.41. The relay s h a l l be able 10 d i s p l a y Fault d e t a i l s on the L D such as F a u l t - Loop or F a u l t y

phases, the Zone that has operated and the Relay operate t i m e .

4.4.2.42. The Distance re l a y s h a l l have a Disturbance recorder with capacity to record ten analogues

,111d twelve digital signals. The relay shall have capacity lo s t o re the latest, twenty (20),

d i s t u r b a n c e records. The p re - fa u l t . f a u l t and post luult d ura t i o n or the l u ul t record s h a l ] be

f re e l y set.

4.4.2.43. Storage o fa t least one h u n d r e d ( J O O ) event records

4.4.2.44. Storage or at least Twenty (20) Trip records. The f o l l o w i n g l a ul t data w i l l be uv u i l a b l e :

(i) M a g n i t u d e and phase angle of' phase currents und voltages be lore the f au l t

(ii) M a g n i t u d e und phase angle of phase currents and vo ltage s duri ng the fa u lt

( iii ) T h e sequence o f eve n ts or d i g i ta l s i g n a l s, s t rt


a a n d operate ( Tri p ) si g n a l s i n volved in

laul t detection a n d c l e a ra n c e . T h e e v e nts sh al l b e ti m e -tagge d 10 l Urns level.

4.4.2.4 5. Eve nt s und fault r ecor ds shall n ot b e erased ev e n when th e aux ili a ry D C supply is switched

o i l'.

4.4.2.4 6 . M e t eri n g and d i pl


s ay on the LC D scre n e of t he fo ll o wing Power sys te m instantuneous

p a ra m e r e rs i n c l u d i n g ;

(i) Voltage

( ii) l . ou d current

( iii ) Act iv e Power ( i m p o rt ( 1 ) o


r Ex po rt ( -))

( i v ) Re acti ve P o we r ( irnport (+) or Export t-j)

Issued by: I-lead uf Se ction, Suiudurds Dcvdup111c111 Au t h o l' i1, c d by: Head of Dcpuruneut, S t a n d a r d s

S ig11cd: Sigurd:
� r
-..\ .,..

Date: 21119-06-07 v Date : 2019-06-117


TITl,E: noc. Nu. KI' I /3 CR /rs P/02/004

l
Issue No. J
PROTECTIVE R E L A Y S , C O N T R O i ,

- D E V I C E S AND I N S T R U M E N T S ­

SPECIFICA TION
Revision No. 3

Kenya Power Dntc of Issue 20 J 9-06-07

Page. 16 or 72

(v) Apparent rower

(vi) Power Factor and

( v i i ) Frequency

Nore: Si11111/1aneo1.1s Moxi11111111 demand values ofActtve Power. Reactive Power one/ Appwent

Power shall he available in the relay.

4.4.2.47. Al least Twenty-Four (24) B i n a ry i n p u t s .

4.4.2.48. Al least Thirty-two (32) 13inary o u t p u t s

Nole: Two pairs a/the binary 011tp111 relays s/10// he rated In dire ·1/y energise the circuit

breaker trip coil. These 01.11p11! relays shall provide phase servegated ontputsfor each phase.

This is to al/0111 single phase tripping and auto-reclose. This trip output relays shall havefast

operating times ofless than Sins. Adequate output contacts shut/ he providedfor trippi11g 11(

two circuit breakers.

4.4.2.49. S t a b i l i t y against s w i t c h i n g inrush currents and reverse f a u l t s .

4.4.2.50. Clear faulted phase i n d i c a t i o n .

4.4.2.51. Clear fault i d e n t i fi c a t i o n even for boundary conditions.

4.4.2.52. At Least twelve ( 1 2 ) LEOs for i n d i c a t i o n of the following: - Relay trip. Phase L I , P has e L 2.

P h a se L3. Z one I , Z one 2, Zo n e 3. DEF, C h a nnel a id e d t rip . SOTf', Back up 0/C. Re lay

h e a lth y L ED ( R e l a y s el f - s u pe r vision . wi t h L CD for h e a l t h y sta t us i n d i c a r i o n t g re e n ) i111d

12 rror i n d i c a t i o n (reel) a nd watchdog c on t a c t )

4.4.2.53. P ro to c ol a p p licabl e : Full !EC 618 50-8-1 c ompliant & IE C 608 70-5- 103. Ap pr o pri a t e

communication p orts to be p ro vided lor local a nd rem ot e communication.

4.4.2.54. Re ay l T erminals-shall b e s crew t ype t er m in a l s l a r g e e nough o


l accommodate at least 2 x

2 .5 1111112 cable and s hall b e loc a ted at t he back o r the re l ay

4.4.2.55. F ro nt S erial RS2 12 . o r U SB or Optical or Et hernet P ort shall be provided tor relay

configuration and parameter s e l l i n g and download o r Data u s i n g a Lapt o p Computer,

4.4.2.56. S oftware for P ro g ra m m i n g the c o n fi g u ra t i o n and Relay Settings and also d o w n l o a d i n g an d

analysing t he Re lay D ata sh a l l be p ro vided.

4.4.2.57. Relay lo Laptop connec t ion cable s h a l l be provided.

4.4.2.58. Relay c o n fi g ura t i o n : T he M a n u fa c t u r e r shall carry out relay c o n f i g ura t i o n at the F ac tory to

s u i t i n s t a l l a t i o n in exis t ing t ra n s m i s s i o n substations in KrLC Netwo r k. E x i s r i n g Prot e c tion

and control draw i ngs for the substations s h a l l be handed over to the manufacturer/supplier

for relay configuration. The F /\T s sha l l be carried out once the relays have bee n configur e d .

Issued hy: I-lend of Section, S ta n d a rd s Development A 1 1 t h o r i 1, c d hy: I-lend of D e p a rt m e n t , S t a n d a r d s

,
Signc,1: Signed:

Date: 2019-06-07 Date: 21119-116-07


TITLE:
Due. No. KP 1 / 3 C 13/TSP/02/004

l
-
P R O T li: C T I V I!'. Rl�LA YS, CONTROL

DEVICES AND INSTRUMENTS­


Issue No. I

- SPECIFICATION
Rcvisiun No. J

Kenya Power Dute ul' Issue 2019-06-07

Correct fu n c t i o n a l i t y or a l l relay Protection and Control F u n c t i o n s s h a l l checked d u r i n g the

FATs, i n c l u d i n g correct opcnuiun ofthe s i n g l e pole auto recluse scheme where applicable.

4.4.3. D i s t a n c e Protection Relay Type I I :

D i s ta n c e P r o t e c t i o n Relay Type 11 M a n u fa c t u r e r ' s E x p e r i e n c e and P r o d u c t Q u a l i fi c a t i o n : -

4.4.3.1. The Relay 111<111ul�1c1urcr shall haw a m i n i m u m experience o f 2 5 years in the m u n u l a c t urc

or D i s t a n c e P ro t e c t i o n relays, 1 5 years or which shall be in the m a n u fa c t u re o f N u m e ri c a l

Distance Protection relays.

4.4.J.2. The Relay Type Offered must have been in Service and given re l i a b l e service for a 111ini111L1m

period o 1· 8 years, in al leas I l wo uti I itics, i n each of the l'ol lo w i n g regions: -

a. Europe

b. North America

L A lricu uud

cl. Asia

Note: The 111w11.1/c1c111rer shul] provide references lo snpport this l'eq11il'e111e111. including

Export records with copy o]' contract fellers. relay details. inciuding 1111111bers um/ dote u/
export, Letters o] sutisfactionfrom utilities should be provided with the bid Emal] contacts

for senior Technicat personnel i11 the utilities shall be provided with the bid

4.4.3.3. Relays t h a t haw f a i l e d i n service or rnal-operated on the Kenyan Power system s h a l l not be

accepted.

4.4.3.4. Warranty for the offered relay s h a l l be five ( 5 ) years from the date or relay d eliver y to

K P L C store.

The D i s t a n c e P ro t e c t i o n Relay Type I I s h a l l h a v e the f o l l o w i n g F u n c t i o n s a n d Features:

4.4.3.5. The Distance relay s h a l l be used for p ro t e c t i o n of Sub transmission and D i s t r i b u t i o n Lines.

both overhead lines and underground cables or d i ff e re n t c h a rac t e ris t i c impedances and

lengths. The relay s h a l l be used for l a u l t location on the protected feeders.

4.4.3.6. To achieve t h i s , the relay s h a l l a ut o m at i c a l l y display the dist ance lo fa u l t i n km on the LCD

screen upon limit i n t e r r u p t i o n . This r e q u i r e m e n t is c r i t i c a l and the offered relays that are not

able tu 111ee1 t h i s r e q u i r e m e n t w i l l not be considered.

4.4.J.7. 'lhe ability to Access the distance to luult details using the Keypad or u laptop is or

secondary value and s h a l l not be considered as a s o l u t i o n for the above requirement.

4.4.3.8. The relay shall have lour analogue current i n p u t channels and lour voltage i n p u t c h a n n e l s

for connection or CT & VT secondary analogue signals

Issued by: I lead uf S e c t i o n , S t a u d u rd s O c v c l o p 111 c 1 1 1 A u l h o l'i '. c d by: Head ul' Deparuucut, S t a n d u rd s

Sigucu:
G

Dute: 21119-0<,-07
Oak: 2019-06-07
TITLE: noc. Nu. KP I /3CR/TSP/02/004

l l ' R O T E C T I V F: R F: L A VS, C O N T R O L
Issue No. J

-
-
DEVICES ANO

SPECIFICATION
INSTRUMENTS­
Rcvisinn No. J

Kenya Power Dnte of Is<uo 20 J 9-06-07

Pug.c I � of 72

4.4.3.9. S h a l l be suitable for F l u s h m o u n t i n g on the protection panel

4.4.3.10. The relay s h a l l be or· Numeric/Digital Design and employ complete d i g i t a l processing o r

measured values

4.4.3.11. F u l l distance Protection Scheme, i . e .. non-switched

4.4.3.12. Under lmpcdance S t a r l i n g c r i t e r i a . Other s t a r t i n g criteria in a d d i t i o n to the under impedance

starting are acceptable,

4.4.3.13. The relay shall emp oy l t ree


h p a h se t ri p p i n g C ri te ria , si nce i t sh a l l be us e d 011 sub­

t ra n s m i s s i o n a n d di tributio
s n line s

4.4.3. 1 4 . Four zon es o f Phase distance protec ion t (to r P ha e- s p h as e fa ult s) w ith s elect a ble M h o and

Q u a dril a t e ra l c h a ra cteris ics. P ra t a me ter s ( re i s s t i v e re ac h. r eact i ve reach a n d t i m e d e lay) t o r

e ach Z one i ndcpcndcntly set.

4.4.3.1 5 . F o ur z o es o
n r G rou n d di ta
s n ce pr ot e c i
t o n . (for p h ase- G ro u n d / P h a s e - E a rt h F a u l t s ) with

selec ta ble M ho a d
n Q u a dril a t er a l c h a ra c t e ri s t i c s w ith re i s dua l c ur r e nt co m p e n s a t i o n .

Pa ra me te s r (r esisti v e re ch a , r ea cti e v re ac h and t i m e de lay) for e ach z o e


n s h a l l b e

ind e pe d n en t y set.
I

4.4.3.1 6 . T he Dis ta nce P rote cti on Zones di re cti o n s h ,1 1 1 be independently se t as forw a rd or reverse or

non di - rec tio n .

4.4 3.1 . 7 . M ini m u m o p eratin g ti me s hall n ot ex ceed 4 0m, .

4.4. 3 .1 8 . Th e distance R el ay s h a l l ha e v C o mm unic a tion c h nnel


a A i d e d S c e
h m e log c i For the dista nc e

p ro t e ctio n w i th a l leas t the fo l l ow in g s che mes:

( i ) Per m is is v e U nd r r e - eac h T ra n s f e r s c e h m e

( ii ) Per m issi v e O ve r each


r T ra ns fer sc he me a n d

( iii Di ecl
) r Transfer Tr ip p in g Scheme

Nore: The tele-protect ion shall be achieved by hard wiring between I he relay and Ihe 1e/econ-11111.111ia11 ion

eq11ip111e111

4.4.3.1 9 . Load e nc ro ach m ent D i sc ri m in at i o n F e a t u re , t o incre se a th e possi b ilit y to d ete ct h i gh

r esis t iv e f au l t s o n he a v i l y l o ad e d lin es.

4.4.3.2 0 . F u e s fa ilure su pe rv i sio n L o gic

4.4.3.21. V olta ge M e mo ry Fe atu re fo r u se by th e dist a nce co mp a ra tors

4.4.3.2 2 . A u o t ma tic S w itch on to F a u lt Fc at urc( SO TF), en abled w h n t e line


e h is de - ner
e gis e d and

on l y ac ti v e o
f r a set t i m e delay a ft er the l i n e circuit breaker is closed

4.4.3. 2 3. D re i c tional Earth Fault Pr o tection, w ith c o m m u n i c a t i o n channel aided s c eme a


h s f ollo ws: -

(i) Directional C omparison Scheme

( i i ) Bl o cking Scheme

Issued by: Head of Section, Standarrls Dcvclopmeut A u t h o ri z e d hy: Hem! of D e p a r t m e n t , S t a n d a rd s

Sign eel: Signed:

Date: 2019-06-07 Dale: 2019-06-07


TITLE: Doc. No. KI' I /3 C BITS P/02/004

t
-
P R O T E C T I V E RELAYS, C O N T R O L

OE V I C E S A N O I N S T R U M E N T S ­
Issue Nu.

3
I

-
Revision No.

S P E C J Fl C A T I O N
Kenya Power D:11, of Issue 2019-06-07

Page 1 9 uJ'72

Nute: Setectahtefinat 1i111e 1rippingjor use when the cm11111111'1icu1i,m channel is 1w1 in use.

orfor use on radialfeeder.

4.4.3.24. Back up three phase ovcrcurreru & Earth luult protection, with the following protection

functions:

(i) H i g h set e l e m e n t t o r Phase and �arth fault ovcrcurreru w i t h selectable d e fi n i t e

lime delay

( i i ) Low set e l e m e n t for Phase and Earth [ a u l t o v e rc u rre n t with inverse c urre n t - t i m e

c h a ra c t e ri s t i c s as per IEC 6 0 2 5 5 .

Other F1111crio11s, include:

4.4.3.25. S e n s i t i v e Earth Fault Protection

4.4.3.26. S t u b Bus o v e rc u rre n t p ro t e c t i o n

4.4.3.27. C i r c u i t Breaker F a i l u r e Protection

4.4.3.28. Under-frequency and rate of change 0 1 · frequency protection

4.4.3.29. Overvoltage protection

4.4.3.30. Broken conductor detection lor Alarm purposes.

4.4.3.31. Auto-reclose function t o r three phases, s u i t a b l e t o r high speed and de l ay e d uuio-reclosc.

Faull types a n d Zones that i n i t i a t e auto-reclose lo be selectively e nabled.

4.4.3.32. T he A ut o - re c l o s e sc heme w i l l be s e l e c t ab l e a s enabled or d isabled p re f e ra b l y on the r elay

LCD sc r e e n:

4.4.3.33. On l y the selected l u n c r i o n s i n t he dista n c e relay shall initiate auto-rcclose

4.4.3.34. T he auto-reclose function shall be capable of two auto-rcclosc s h o t s , wi th se p a ra t e l y set

dea d ti mes.

Nore: Ir shull be possible lo initiate auto-reclose in the distance relayfrom un external

/Jock1111 011e1"C11rre111 011d ear1/1Jc11.J!1 relay on the same Panel.

4.4.3.35. Fault Locator; with a u t o m at i c display o n t he Re ay l LCD S cre e n or th e d i s t a n c e lo fault i11

te r ms of Line p e rc e n t a g e or distance in k m . T his i n f o rm a t i o n is fo r use by ot her o p e ra t i o n a l

s t a l fr o g uide t he m a i n te n a n c e t ea m s. T he l a s t d is t a n c e o fault
t s hall a lw a y s be display ed on

the screen.

Note: In the bid submission the bidder shull demonstrate that the requireinent ofihis cluuse

isji,lly 1111'/. lle1111ire111e111 to use the keypad or laplujl to access this ir!fim11wio11 is UK. as a

secondary option, hut will not he considered 011 its own 10Ji1/jil 1/1e requirements ab o ve ,

Issued by: Head of Section, S t a u d a rd s Development Aut h o rized by: Head uf D e p a r t m en t , S t u m l u rd s

S i gned: Sigu�d:
(;

f
Datt•: 2U l 9-U6-U7 Date: 2019-06-07
TITLE: Doc. No. KP 1 1 3 C 13/TS I' 102/004

\:.
Issue No. J
PROTECTIVE RELA VS, C O N T R O L

-
-
D E V I C F: S A N D I N S T R U M E N T S ­

SPECIFICATION
Revision No. J

Kenya Power Dote or Issue 20 19-06-07

Distance Relays Offered which do 110/ meet the above requirement sl,a/1110/ be accepted

4.4.3.36. The accuracy of D i s t a n c e to fault location s h a l l be ±2% as a m i n i m u m .

4.4.3.37. The following a d d i t i o n a l i n fo r m a t i o n s h a l l be provided with fault location:

(i) The s h o rt- c i rc u i t loop w h i c h was used to d e t e r m i n e the fault rcactancc

(ii) Th reactance X per phase in O h m s Primary and secondary

(iii) The reactance R per phase in O h m s Primary and secondary

iv) The distance to fault in percentage and k m o f l i n e l e n g t h :

4.4.3.38. The relay s h a l l be able to d i s p l a y F a u l t d e t a i l s on t h e I .CD Screen such as F a u l t - Loop or

la u l t y phases, the Zone, and the Relay Operate t i m e .

4.4.3.39. I n t e rn a l Disturbance recorder with capacity to record eight analogue and twelve digital

s i g n a l s . The relay s h a l l have capacity In store t h e latest. twenty (20). d i s t ur b a n c e records.

4.4.3.40. Storage of at least Fifty (50) event records

4.4.J.4 J . Storage ofat least twenty (20) trip records. The following fault data w i l l be a v a i l a b l e :

(i) M a g n i t u d e and phase a n g l e of phase currents and voltages b e fo re the la ult

(ii) M a g n i t ud e and phase a n g l e of phase currents and voltages d u r i n g the fa u l t

(iii) The sequence or events or d i g i t a l s i g n a l s , star! and operate (Trip) signals i n v o l v e d in f a u l t

detection and clearance. The events s h a l l me t i m e tagged to I Oms level.

4.4.3.42. Events and fault records s h a l l not be erased even when the a u x i l i ar y DC su ppl y is switched

of!".

4.4.3.43. Metering and display on the LCD screen or the following Power system instantaneous

parameters i n c l u d i n g ;

(i) Voltage

(ii) Load current

(iii) Active Power ( Import(+) or E x p o r t ( - )

(iv) Reactive Power( I m p o rt (+) or Export (-)

(v) Apparent Power

(vi) Power Factor and

(vii) Frequency

Nole: Si1111.1/raneo1.1s Maxl111u111 demand values o.f Active Power, Reactive l'ower and

Apparent Power shall be available in the relay.

Issued hy: I-lead of Section, S t a n d a r d s Development A u t h n ri z c d hy: Head of D e p a rt m e n t , S t a n d a r d s

- .
Signed: Signed:

Date: 21119-06-07 Date: 21119-116-07


TITIY: Doc. Nu.
KP I /3C 13/TSP/02/004
�.��-+-���������-11

1
-
l'ROTECTIVE RELA VS, CONTROL l.ssuc No. I

-
D E V I C E: S AND INSTRUMENTS­
Revislun Nu.
3
Sl'ECIFICATION

Kenya Power U,lll' of Issue


2019-06-07

Pa!;!-C 2 1 ol'72

4.4.3.44. /Is u 111i11imu111 the relay s h a l l have ten ( I 0) Binary inputs.

4.4.3.45. As a m i n i m u m the relay s h a l l have twelve ( 1 2 ) B i n ary outputs,

Note: Two pairs ofthe binary outpu! retays shall be rated tr, directly e11agise the circuit

hreaker trip mil. These contacts shall be able to sq/ely interrupt the Circuir Breaker trip

Coil current,

4.4.3.46. S t a b i l i t y against switching inrush currents and reverse faults.

4.4.3.47. Clear faulted phase i n d i c a t i o n .

4.4.3.48. Clear faulr i d e n t i f i c at i o n even tor boundary c o n d i t i o n s .

4.4.3.49. flt least twelve ( 1 2 ) L E D s for i n d i c a t i o n of' the lo I lowing; - Relay t r i p . Phase L I , Phase L2,

Phase LJ, !'.one I , Zone 2. Zone 3 , D E F , C h a n n e l a id e d t r i p , SOTI', etc.

4.4.3.50. Relay healthy I.ED

4.4.3.51. Relay s e l l- s u p e rv i s i o n , with LED for healthy status i u d i c a t i o n t g rc e n ) and Error i n d i c a t i o n

(red) and watchdog contact

4.4.3.52. Protocol a p p l i c ab l e : ! E C 6 1 8 5 0 - 8 - 1 . Appropriate c o r n m u n i c a r i o n pons lo be provided 011

the relay.

4.4.3.53. Relay T e rm i n a l s - s h a l l be screw type terminals large enough to accommodate al least 2

x2.51111112 cable and shall be located at the back or the relay.

4.4.3.54. Front S e ri a l RS232 or USB or Optical or Ethernet Pon shall be provided for re l a y

c o n l i g u ra t i o n and parameter s e l l i n g and download or Data using a Laptop 0111pu1er.

4.4.3.55. S o ft w a re for P ro g rer n m i n g the c o n f i g uru u o n and Relay Settings and also d o w n l o a d i n g and

a n a l y s i n g the Rcluy Data s h a l l be provided.

4.4.3.56. Relay 10 Laptop connection cable

4.4.3.57. Relay c o n fi g u ra t i o n : The M a n u f a c t u re r shall carry out relay configuration al the Factory

10 suit installation 111 existing t ra n s m i s s i o n stlbstations 111 KPL Network. Existing

P ro t e c t i o n and c on trol d ra w i n g s tor the substations shall be handed over to the

m a n uf a c t ure r/ s u p p l i e r for relay c o n f i g ura t i o n . '!'he FA Ts shall be carried ou t once the r e la ys

h ave been c o n f i g u re d. C o rr ec t fu n c t i o n a l i t y or a l l r e l a y i ' ro t c c t i on and C o n t ro l Functions

shall c h ecked during th e F A TS .

Issued by: Heall of S c c t i u u , S t a n d a rd s Development A u t h o ri z e d hy: Hcnd of U c p : 1 1 · 1 111 c n l , Sta111lanls

Signed: Signed:

Date: 2019-06-07 D a l e : 2019-06-07


TIT! Ooc. No.
, F. :
KP I /3CR/TSP/02/004

l P R O T E C T I V E RELAYS, C O N T R O L Issue No.


I

--
D E V I C E S A N D I N S T R I J M F: N T S - Revtslnn No. '
J

S P F: C I F I C /\ T I O N
Kenya Power l > n t f' or I s s u e
2019-06-07

PaJ.!1.: 22 of 72

4.4.4. Biased Differential Protection Relay for a Two or Three W i n d i n g Power

T r a n s fo r m e r :

Biased D i ffe re n t i a l Protection Rclnr M a u u f n c t u re rs F.xpcricnce and Product Qualification:-

4.4.4.1. The Relay m a n u fa c t u re r s h a l l have a m i n i m u m experience ol' 2 5 years i n the manufacture

or Biased D i ffe re n t i a l Protection relays. I 5 years or which s h a l l be i n the m a n u f a c r u re of

Numerical Distance Protection relays.

4.4.4.2. The R e l a y type offered must have been in Service and given r e l i a b l e service for a m i n i m u m

period o f 8 years. i n at least two u t i l i t i e s . in each of the following regions:-

a. 12uropc

b. North America

c. A fri c a and

cl. Asia

Nore: The manufacturer shed! provide references to support this req uircnt nt,

including Export records with copy o.f con/me/ fellers. relay details. including

1111111/,ers and dare r!f' export. l.etters o


f satisfoction f
rrnn ntilities should he

provided with the hid. Email contacts for senior Technical personnel in the

utilities shall he provided 111i1h the hid.

4.4.4.3. Relays that have failed in service or mal-operated on the Kenyan Power System s h a l l not

he accepted.

4.4.4.4. Warranty for Offered relay s h a l l be Five (5) years [rom the date of relay delivery 10 the

KPLC store.

The Biased Differential Protection Reial' s h a l l have the followine Functions and Features: -

4.4.4.5. S u i t a b l e for protection or a two or three w i n d i n g power transformer, w i t h a power ra t i n g

of up to 90 MV /\. with I-IV w i n d i n g rated up lo 2 4 5 k V . S p e c i fi c re q u i re m e n t s w i l l be stated

in the Scope or supply or Price schedules.

4.4.4.6. Relay 111us1 be olNumerical design

4.4.4.7. F l u s h m o u n t i n g design

4.4.4.8. P i c k up s e t t i n g range. for I D I F F > 0 . 1 lo 1 . 0 x rated current, as a m i n i m u m

4.4.4. 9. P i c k u p on sw it ch- on (factor of I D ! f'f'>) 1 . 0 to 2.0

4.4.4.10. High-set Element ( I D I F F > > ) w i t h a s e l l i n g range or 1 . 0 to 20.0 x rated current

4.4.4.1 I . Independent d e fi n i t e t i m e delay setting for I D I FF> and lor ! D I FF>> o f 0.00 to 30.00

seconds as a 111i11i111u111

Issued by: I-lead of Section, S t a n d a r d s Development Authotizer! hy: I-lend of Department, S t n n d a rd s

Signed: Signed: c
' � '» c a
Oak: 2019-06-07 v na tc: 2019-06-07
TITLE: Uuc. No. KP J /JC 13/'l'S I' /02/004

l P R O T E C T I V E R E L A Y S , CONTROL Issue Nu. J

- -
O E V I C E S AND I N S T R U M l!'. N T S ­
R i: v i s l o u No. 3

SPECIFICATION
Kenya Power Dute or lss11,• 2019-06-07

P.ig� 23 ur'72

4.4.4. 1 2 . M a g n e 1 i ;,: i 1 1 g current inrush re s t ra i n t I e u t urc , using 2nd harmonic rcsuuiru ,111d /or zero

cros,ing 011 the sine wave

4 .4.4. I J, S c t r i n g range o r 121i1/lfn of 1 0 10 50% as a m i n i m u m

4.4.4. 1 4 . Compensation tor zero sequence currents that nwy a pp e a r on o n l y one w i n d i n g or the

power transformer

4.4.4.15. Measurement and i n d i c a t i o n on the LClJ screen. of phase - I-IV & L V currents and re l a y

di t f e re n t i a l and bias currents

4.4.4. 1 6 . S to ra g e o fa t least Five (5) F au l : records and Ten ( I 0) Event records

4 .4.4. 1 7 . Events and fa u l t records s h a l l not be erased even when the a u x i l i a r y D ' s u p p l y is switched

orr

4.4.4.18. The F a u l t flags should be v i s i b l e on the L 'D screen, c111d provide d e t a i l s or the phases that

have pcratcd and the fau l t c urre n t values,

4.4 .4. 1 9 . O v e r - f l u x i n g p ro t e c t i o n f u n c t i o n w i t h al least two stages o fa l a rm and t r i p lu n c t i o n s

4.4.4.20. 5th harmonic re s t ra i n t f e a t ure on the d i f f e re n t i a l Element to p re v e n t u n n e c e s s a ry tripping

clue to CT s a t ura t i o n or t ra n s fo rm e r o v c r- c x c i i at i o n .

4.4.4.21. Over-excitation P ro t e c t i o n w i t h both alarm am! t r i p clements

4.4.4.22. Stabilized against t ra n s i e n t and steady-state fault c urre n t s caused c.g. by o v e r- e x c i t a t i o n of

t r a n s f o rm e rs . using f i ft h harmonic.

4.4.4.23. i n s e n s i t i v e against DC offset currents and current uunsformer saturation.

�.4.4.24. I l i g h s t a b i l i t y a l s o I o r d i ff e re n t current t ra n s f o rm e r saturation

4.4.4.25. High-speed i n s t a n t a n e o u s t r i p on high-current transformer fa u l t s .

4.4.4.26. I n d e p e n d e n t o lt h e c o n d i t i o n i n g or the star point(s) of the power uu n s l o rm c r.

4.4.4.27. H i g h earth-fault s e n s i t i v i t y by detection o f the star p o i n t current or an earthed transformer

winding

4.4.4.28. lnicgratcd m a t c h i n g o r the trans l o rr n c r connection group

4.4.4.29. I ntegrated matc hing of th e t ra nsformation ratio i n c l u d i n g d i ff e re n t rated currents or th e

t ra ns fo r m e r w i n d i n g s

4.4.4.30. D L Ja l Bias c h a ra ct e r i s ti c s w t i h t wo slopes lo ens ure r e lay s tability lor heavy through tuults.

T he st u n a nd e ncl o ft h e two l
s opes sha ll be scuablc, in t e rms ulthc rated cu rr e n t .

4.4.4.31. Unbalanced Load Prot e c t i on

4.4.4.32. T hermal O v e rl oad P ro t e c t i o n

4.4.4.33. Back up O v e rc urre n t a nd Ea rth Fau ll p rotection for I IV a nd/or LV w in d i n g

4.4.4.34. The following meas ure m e nt s s hall be av u i l u b l e i n the relay:

1. Magnitudes a nd phase a ngles of th e phase c u rre n t s lor t he thr e e phases on the I-IV

side o fTra n s f o rm e r

11. M a g n i t u d e s and p hase angles or the phase currents for the three phases on the L V

side or Tran s f o rm e r

I ssued by: Head of Section, S t a n d a rd s D e v e l o p m e n t A u t h o ri z e d by: Head of D e p a r t m e n t , S t a n d a rd s

Siuned: Signed: r
'5 ,.
_::_b������-jc� ��1�
- ,,�"l).�)_' ����____j
L ' J '

Date: 2(119-06-07 I Ila le: 2019-06-07


TITLE: Doc. No. KPl/3CB/TSP/02/004

\'_ P R O T E C T I V E R E L /\ VS, CONTROL Issue No. I

-
-
D E V I C E S AND INSTRUMF.NTS­

S P E C I fl C A T I O N
Revision No. 3

Kenya Power Dw· or Issue 2019-06-07

111. M a g n i t u d e o f differential current and r e s t ra i n i n g current for t h e three phases

4.4.4.35. The disturbance recorder function s h a l l have a capacity for eight (8) a n a l o g u e and twelve

( 1 2 ) digital s i g n a l s . The last four d i s t u r b a n c e records w i l l be a v a i l a b l e in the r e l a y .

4.4.4.36. Red L . E . D to i n d i c a t e t h a t the relay has operated/issued trip co1111m111d

4.4.4.37. Relay Sell" diagnostic. with LED to indicate Relay la i l u re and a contact for remote

indication or relay f ailure status

4.4.4.38. The relay s h a l l have al least e i g h t (8) L E D s for t r i p and alarms and al least four (4) binary

i n p uts .

4.4.4.39. The relay s h a l l have al least our (4) outputs relays w i t h n o r m a l l y open co ntac ts for c i r c u i t

breaker tripping and alarm annunciation. Two pa ir s o r contacts shall be ra ted to directly

ene r gi s e the c i r c u i t bre a ker t r i p p i n g c o i l .

4.4.4.40. The relay s hall have the a b ility to select o u t p u t co n t a c t s to l a t c he d or n o n - l a t c h e d sta tus

a nd the LCD screen where th e sc n ings and m e a s u ra n d s can be read.

4.4.4.41. T he r e l a y s h a l l have keypad for m anual p ro g ra m m i n g o fs e u i n g s and data a cce ss.

4.4.4.42. The r elay s h a l l have front se r i a l RS232 o r U S 8 or Ethe rn e t run for Relay c o m m u n i c a t i o n

w ith a la p t o p co m put e r fo r rel ay c o n f i g ura r i o » a nd p a ra m e t e r settings a nd do w nload or

faul t records. e vents records a nd di s t u rb a n c e record.

4.4.4.43. R el a y terminals-shall h e s crew type terminals la r ge eno u gh t o accommodate at le a s t

2x2rnrn2 cable a nd s h a l l be loc a ted at t h e back o f th e r el a y .

4.4.4.44. Fou r (4) s e t s o f i n s t a l l a t i o n . c o m m i s s i o n i n g . o p e ra t i o n and ma intenance ma nuals sh,111 be

p rovided.

4.4.4.45. R e l a y lo Laptop c onne c tion cab l e s h a l l be p ro v i c lc c l .

4.4.4.46. Software fo r r elay c o n f i g u r a t i o n a nd s ettings p ro gra m m in g us ing La p t o p co m p u t e r s hall

be p ro vided .

4.4.5. R e s t ricted Earth F a u l t Relay:

Rcstriclc<I Earth F a u l t l'mteclion Relay M n n u f a c l u r e r ' s l':xpcric11cc a11<1 Prod11ct 0 1 1 a l i fi c a l i o 1 1 : -

4.4.5.1. The relay manufacturer s h a l l have a m i n i m u m o f " 2 5 years in t h e m a n uf a c t ure of Rest r icted

Earth F a u l t Relays, I O years of which s h a l l be in the manufa c ture of n u m e r i c a l Restricted

Earth F a u l t relays.

4.4.5.2. The relay type offered must ha v e been in service and given r e l i a b l e servi e lor a n1ini111u111

p e r i od 0 1 " 8 years. i n al Least two u t i l i t i e s . in each of the f o l l o w i n g re g ions: -

a. Europe

b. North A m e ri c a

c. J\ frica and

c l. Asia

Note: The manufacturer shall provide references lo support this requirement, inc/11ding

Export records with copy of con/met letters, relay details, including numbers and

Issued by: Head of Seel i o n , S t a n d a rd s Development Authorized hy: Head of D e p a rt m e n t , S t a u d a rd s

Signed: Signed:
CG£�;·
Date: 2019-06-07 II Date: 2019-06-07
T I T L l2 : Due. Nv. KP 1/JCD/TSP/02/004

l P R O T E C T I V E l{l,'.LA YS, CONTROL Issue Nl,, I

- -
DEVICES A N D INSTRUMENTS­
Revisiun Nu. 3

Sl'ECIFICATION
Kenya Power Dute or Issue 2019-06-07

Page 25 cf 72

elute ofexport. Letters <if s,rfi4itc·1ivnji'o111 utilities shouh! be provided with the bid

E111uil contactsfor Senior Technical personnel in the utilities shul] be provide« with

1/Je hid

4.4.5.3. Relays that have failed i n service or mal-operated on the Kenyan Power System s h a l l not

be accepted.

4.4.5.4. Wa.,.,1111y for offered relay shall be live (5) years Crom the date of relay d e l i v e ry to KPLC

store.

�rht llcslrictctl Earth Faull Prolcction l{ch,v shall ha v� thl' follu,\li11g Fu11ctions aud Features: -

4.4.5.5. This relay s h a l l be used lc,r protection o fo n e w i n d i n g ofa power t ra n s f o r m e r .

4.4.5.6. This relay s h a l l have the fo l l o w i n g fu n c t i on s and features:

1. Relay shall be of N u m e ri c al , static type or E lec tro -Me ch an ica l type.

ii. The Relay shall operate on h i g h impedance p ri n c i p l e .

111. The relay s h a l l be o f numeric design.

i v . The relay s h a l l be suitable t o r Ilusl: 1110L11Hing on panel front.

4.4.5.7. The relay s h a l l be or an i n d e p e n d e n t relay and 1101 a f u n c t i o n i n the d i tl e re n t i a l relay.

4.4.5.8. Relay s h a l l reject h a rm o n i c s produced by the system p a rt i c u l a rl y t h i r d h a rm o n i c s ,

4 . 4 . 5 . <J . S t a b i l i s i n g resistor and voltage dependent resistor ( r n c t ro s i l ) or suitable ra t i n g s h a l l be

offered w i t h the Relay based on mnxi111u111 through Fault o f 3 I kA.

4.4.5.10. The relay current setting range s h a l l be 0 . 0 5 - 0.8 x rated current (in) as a m i n i m u m and an

operating t i m e « 2 5 m s al 5 times the s e t t i n g .

4.4.5.11. The relay s h a l l have four (4) LEDs l'or relay status indication and for trip and a l arm s

an n u n c i a t i o n as a m i n i m u m and two (2) binary inputs as a m i n i m u m

4.4.5.12. The relay s h a l l have lour (4) Binary Outputs as a m i n i m u m w i t h LCD screen where the

s e t t i n g s ,111d rncasurauds can be read

4.4.5.13. The re l u y s R C I ' operate current shall be displayed 011 the I.CD screen and keypad lor

m a n u a l p ro g ra m m i n g or settings and data access

4.4.5.14. The relay shal] have serial RS232, USB or l�themct Port fur relay c o n f i g ura u u n and

p ro g ram m i n g o r parameter settings and data download us i n g a luptop computer.

4.4.5.15. The relay s h a l l have an e v e n t recorder w i t h capacity tu store the last lifiy (50) events

4.4.5.16. The relay s h a l l haw la u l t recorder w i t h capacity to store the last ten ( I 0) l a u l t records

4.4.5.17. The relay s h a l l have a disturbance record with c ap u c i i y tu store the last four (4) disturbance

records

4.4.5.18. The relay t e rm i n a l s s h a l l be screw type t e rm i n a ls l a rg e e nou g h t o accommodate at least 4

111111 2 c a bl e a n d s h a l I b
e lucatcd a t the b c
a k or the re l a y

Issued by: Head of' S c c t i o u , Srnndanls D e v e l o p m e n t Authorized by: Head or D e p u rt m e n t , Stamlanls

Signed: S i g n e t! :
' . .
, s N:,

Dute: 20 I 9-06-07 v D a l e : 20 I 9-06-07


Doc. Ni1.
TITLl3: KP I /JCB/TSP/021004

't PROTECTIVE R ELA VS, CONTROL I s s ue No.

--
DEVICES A N D I N S T R U M E N T S ­

SPECIFICATION
Revtslon No. .
",

Kenya Power Dute of Issue 2019-06-07

4.4.5.19. S t a b i l i z i n g Resistor

Each REF relay shall be s u p p l i e d with an adjustable s t a b i l i z i n g resistor. For

d i m e n s i o n i n g of the s t a b i l i z i n g resistor consider m a x i m u m through fault p h a s c =- c a n h

current of 3 1 . S k A .

4.4.5.20. Voltage Dependent Resistor (Mctrosit)

Each R E F relay s h a l l be supplied with a voltage dependent resistor ( V D R ) or m c t ro s i l to

l i m i t voltage across the Rl.oF h i g h impedance c i rc u i t . The basis for the rated voltage of the

V D R is the 111aximu111 phase-earth through fa u l t of 3 1 . S k A .

Note: The Stahilising resistor and the Voltage dependent resistor shall preferably he housed

in a box with terminals that allow conn iction ofthe REP relay to the resistor and VDR in

the box. Several terminals will he provided lo allow selection of required stahilizinr

resistor. The single box will he suitoblefor panel mounting.

4.4.6. Feeder Protection Relay:

Feeder Pro1cclion Relay M n n u fo c l u , · c r ' s F:xpcricucc nml P ro d u c t O u a l i l i c a t i o n : -

4.4.6.1. The relay m a n u f a c t ure r s h a l l have a 111ini111u111 or 25 years in the m a n u fa c t u re o f Feeders

Prot e c tion relay. 15 years of which shall he in the m a n u f a c t ure o r nu m e ri cal Distanc

Protection relays,

4.4.6.2. The relay type offered must have been i n service and given re l i ab l e service for a 111ini111u111

period ni'8 years. in at Least two u t i l i t i e s , in each or the following rcgions:-

,1. Europe

b. North America

c. A [rica and

cl. Asia

Note: The manufacturer shall provide references to support this requirement, including

export records with C0/1)1 of contract letters, relay details. including ntnnbcrs and dole r!f'

export. Letters ofsatisfactionfrom the utillties should he provided with the hid. Email

contactsfor senior Technical personnel in the utillties shall be provided with the hid.

4.4.6.J. Relays that have f a i l e d i n service or mat-operated on the Kenyan Power System s h a l l not

be accepted.

4.4.6.4. Warranty for offered relays shall be five (5) years Irorn the elate of relay d e l i v e r y to the

KPL store.

Issued hy: I-lend of Section, S t a n d a rd s Development Authorized by: I-lead of D e p a rt m e n t , S t u n du rd s

Signed: r . / �-' Signed: r •


u
�·,l .x , _/
/

O.itc: 2019-06-07 ' r Date: 2019-06-07


TITLE: l Iur, Nu. K P l /3 C 13/lS I' /02/004

'i
Issue No.
PROTECTIVE RELAYS, C O N T R O L I

-
-
DEVICES AND INSTRUMENTS­
Rcvlsiun No. J

SPECI Fl C A T I O N
Kenya Power Dure uf' Issue 2019-06-07

Page 27 ut'72

The Feeder l ' m t c r t i o u Relay s h a l l have the following F u n c ri o u s and Feutures.-

4.4.6.5. The Relay shall have the f o l l o w i n g protection fun .tions and features in a s i n g l e casing as

a 1111n11nun1: -

I. Three phase o v e rc urre n t

11. Ear11i li,ult

1 1 1 . S e n s i t i v e Earth F a u l t

iv. Broken C o n d u c t o r detection

v. A u r o - re c l o s e fu n c t i o n fur three phase auio-rcclosc.

VI. Under and Over Frequency Protection, i n c l u d i n g rate ofchange frequency protection

Note I : Earth Vault and Sensitive Earth Fault Protection ele111e111s shall be separate tu allow

independent settings lo be applied. Thesefunctions 111i// have separate CT inputs

N o t e 2 : Earth Fault <11111 Se11:1i11i·e eanhfauh ele111e111s sl1C1/I have separote 'T /11µ1.11.,·.

Not c 3: Detai led specif icut ions Jui· I hree phase u vercurrent, eart it Ji111l 1 and sensi Ii ve eart hfaut t

[unctions (11'1! included elsewhere in this specification. All requireinenis 111/1.,·1 be met.

4.4.6.6. There shall be independent CT input tor Earth Fault and tor Se ns it iv e Earth Fault

P ro t e c t i o n to allow independent connection of lite Sensitive Earth Fault Protection

F u n c t i o n to a separate Core type CT

4.4.6.7. Relay must be o fN u m e ri c a l design.

4.4.6.8. Relays that have foiled in service or nm I-operated s h a l l 1101 be acceptable

4.4.6.9. The relays s h a l l bl' s u i t a b l e for l l u s h m o u n t i n g on the J'ro111 of the panel

4.4.6.10. Current setting range for o v e rc urre n t fu n c t i o n s h a l l be 0 . 5 1 1 1 - 2 . 0 l n as ,1 minimum

4.4.6.11. u1Tc111 s e l l i n g range for canh fa u l ! fu n c t i o n s h a l l be 0 . 0 S l n - 0 . 8 1 n us a m i n i m u m

4.4.6.12. Two stages of H i g h Set Element lor botb o v e rc urrc ru and earth I a u l t protection function,

w i t h a s e t t i n g range or 1 - 2 0 1 1 1 as a 111i11i111u111 and a d e f i n i t e t i m e delay sel l in g or O - 60

s e co n ds as a minimum.

4.4.6.13. I.D.M.'J' ch a ra c t e r i s t i c s lor o v e rc u rre r u and E a rt h f au l t pr otecti on function acc o rdi n g to

BS 142 or I E C 6 0 2 5 5 i . c . St a nd ar d I nv e r s e (SI), Ve ry I nv e r se (VI), E x t re m e l y In v ers e ( E l ) ,

Long T i me Inv e r s e (LTI), including d e fi n i t e time for the high-set Elements.

4.4.6.14. T i me sellin g multiplier 0.0 5 - 1. 0 as a minimum

4.4.6.15. Cu r ren t s e llin g ra n ge for s e ns i t i ve e a rt h fa u l t l u n c t i o n 0.0 I In - 0.8111 as a minimum

4.4.6.16. Definite time delay characteristic for Sensitive earth fau l t f un c t i o n ; s e t t in g range, 0- 30

seconds <IS !1 minimum.

Issued I.Jy: I-lead uf Sectiuu, Standards D e v e l o p m e n t A u t h o rl z c d by: I-lead of D c p u ru n e u t , S t a n d a rd s

S igned: Sigucd:
c·�··)­
r --- -------11
Dute: 2 019- 06-0 7 D a l e : 2019-06-07
TITLE: 11o,·. Nu. KP I /3CB/TSP/02/004

t
-
l ' R O T F: C T I V E R r<: L A VS,

O F. V I C E S A N O INSTRUMENTS-
CONTROL Issue

Rcvlston
No.

No. 3
I

- S P E C I Fl C A T I O N
Kenya Power Dole of Issue 2019-06-07

4.4.6.17. R e q u i re m e n t s for the a u t o rcclose f u n c t i o n :

1. Three phases auto reclosc

11. Selectable I - 3 auio-reclose shots

111. I n d e p e n d e n t l y set dead t i m e l o r each shot

,v. Auto-reclosc i n h i b i t after m a n u a l close

v. Each auio-reclose shot shall be initiated by the selected Protection Funorion/s).

Operation 01· Protection Function not selected to initiate a p a rt i c u l a r shot or Auto­

reclose s h a l l lead to Lock-out.

vr. Auro-rcclose i n h i b i t i o n for over current h i g h set. element

4.4.6.18. Data Storage:

1. Storage o f at least rive ( 5 ) fault/trip records

11. Ten ( I 0) event records

111. Five (5) d i s t u r b a n c e records

Note: livcnts 011c/_/c11i/1 records shall not he erased even when the auxiliary DC s11p1,ly is

switched ofT

4.4.6.19. C o n f i g u ra b l e o u t p u t relays for protection e l e m e n t pick up (start) and Trip outputs w h i c h

can be used to back-trip upstream circuit break rs and t o r i m p l e m e n t i n g b l o c k i n g schemes

f o r busbar protect ion.

4.4.6.20. Reel L . 12 . D to i n d i c a t e that the protection functions have operated and issued a t r i p o u t p u t

to Trip the c i r c u i t breaker.

4.4.6.21. Relay sclf-diagnosti , with I . E D to indicate relay h e a l t h y status (green colour) and relay

failed status (red colour) and a watch dog contact for remote a l a r m

4.4.6.22. L E D s : The relay s h a l l have a m i n i m u m e i g h t (8) LEDs for a l a r m s a n n u n c i a t i o n .

4.4.6.23. Binary Outputs: The relay s h <1 I I have as a m i n i m u m twelve ( 1 2 ) B i n a ry i n p u t s .

4.4.6.24. B i n a r y Ou tp uts: The relay s h a l l have a m i n i m u m four (4) outputs R e l a y s . One ( I ) of the

output relays s h a l l be adequately rared 1.0 d i r e c t l y operate the c i r c u i t breaker t r i p c o i l .

4.4.6.25. LCD screen where the setting s and m c a s u ra n d s can be read

4.4.6.26. Keypad for manual p ro g ra m m i n g or settings and data access

4.4.6.27. Relay T e r m i n a l s - s h a l l be screw type t e r m i n a l s large enough to a cornrnodate at least

41111112 cable and s h a l l be located at the back of' the relay

4.4.6.28. The relay a p p l i c a b l e protocol s h a l l be l [ C 6 1 8 5 0 - 8 - 1

Issued hy: I-lead of Section, Standards Development A u t h n ri z ed hy: Head of D e p n rr m e n t , S t a n d a rd s

Signed: Signed: .....--::::,


_ �(_,,
,--

- --v
Date: 2 0 1 9 - 0 6 - 07 ' u Date: 2019-06-07
TITLE: Doc. No.
KP I /3C B/TSP/02/004

l PROTECTIVE R E L A Y S , ONTROL Issue No.

- -
DF.VI.CES A N D I N S T R U M E N T S ­
ltcvisio11 No.

Sl'ECI F I C A T I O N
Kenya Power D111c uf lssuc
20 I 9-0G-07

P11g1.: 29 or72

4.4.6.-9. Front Serial RS232 or U S H or Ethernet Port Ior relay c o r u m un i c a i i o n with a l a p t o p

computer for relay c o n l i g u ra t i o n and parameter settings and download of fa u l t records,

events records and d i s t u rb a n c e records for a n a lys is .

4.4.6.30. Son ware f o r c o n fi g u ra t i o n and relay parameter s e t t i n g s and also d o w n l o a d i n g a11J

a n a l y s i n g the relay fa ul t data s h a l ) be provided.

4.4.6.J 1 . Relay to Laptop c o n n e c t i o n cable shall be p ro v i d e d

4.4.6.32. A 1 1 1 0 reclosc relay lu n e t i o n in the feeder p ro t e c t i o n relay. T h i s auto reclosc fu n c t i o n shall

be housed w i t h i n the feeder protection relay: -

1. Selectable I - J auto rcclosc shots

1 1 . Independently set dead t i m e for each shot

111. A u i o - re c l o s c i n h i b i t alter manual close

rv. Eacl: auto-rcclose shot s h a l l bi: i n i t i a t e d by the selected protection i u n c u o n t s ) . Operation

of protection lu n c t i o n not selected to i n i t i a t e a p a rt i c u l ar shot of auto-reclose shall lead

to lock-out o f the relay.

v. A u i o - re c l o s c i n h i b i t i o n l o r over c u rre n t high set e l e m e n t .

4 . 4 . 7. Electricul Reset - Trip Relay

E l e c t r i c a l Rcscl - T r i p Relay M l l n u fa c t u r c r ' s E , u c r i c u c c auil Product Q u a l i l k a l i o u : -

4.4.7.1. The m a n u l u c t u re r s h a l l have experience or <1111ini111u111 or 1 5 years in the m a n u l u c t urc of

Trip relays

4.4.7.1. The o t t e re d relays must have been sold t o u t least two u t i l i t i e s o u t s i d e the country o f

m a n u f a c t ure , and operated r e l i a b l y f o r at least 8 years. Copy o r Export sales contract

s h a l l be p ro v i d e d w i t h the bid to support t h i s re qu i re m e n t .

4 .4. 7 . 3 . Relays that luiled in Service or Mal-opcnucd on the Kenyan Power System shall not be

accepted.

4.4.7.4. Warranty l o ro fl e r e d relays shall be Five (5) years frum the date ofrclu y d e l i v e r y to the

K P I . C store.

"l'hc E l c <.: l r i c a l l{l�Sl't 'l'rip l{�lav shall have the


1
follo\\ ing F1111cliuns a11d Jfr;.1111rcs: -

4.4.7.5. H i g h burden t r i p p i n g relay, i m m u n e to capacitance discharge currents and leakage

c urre n t s

4.4.7.6. A l least Four (4) pairs or n o r m a l l y open (NO) and two (2) pairs or n orma lly closed (NC)

or 4NO/NC o u t p u t contacts.

4.4.7.7. lnstuntancous operation; t i m e < l Sms

Iss ued by: I-lead of S e c t i o n , S t u u d u rt l s D e v e l u p u r e u r


A u l h u r i z c d by: Head of D c p u rn u c n r , S t a u u u rd s

f-S-ig_1_c
1_i
·_
1, '1(%�)_)='--_'------I Signed:
6
Date: 2019-06-07 "=r D u r e: 2019-06-07
TITL[: Doc. No.
KP l/3CB/TSP/02/004

\:_ PROTECTIVE RELA VS, CONTROL Issue No.


I

-
-
D E V I C E S AND INSTRlJMF:NTS-

S P F: C I F I C A T I O N
Rcvlslun No.
3

Kenya Power Date or Issue 2019-06-07

l'agc J(J ot'72

4.4. 7 . 8 . The Relay shal] be s u i t a b l e for flush m o u n t i n g

4.4. 7 . 9 . Flag or target shall be a red; L . 12 . D , or durable b u l b or Reel Mechanical flag

4.4. 7 . 1 0 . The Relay s h a l l be electrically reset, and the reset button s h a l l be i n b u i l t on the relay and

accessible w i t h o u t opening the relay cover or s h a l l be s u p p l i e d separately for panel flush

m o u n t i n g , in which case the reset button s h a l l be i l l u m i n a t e d with red c o l o u r .

4.4.7.11. Contact ra t i n g - capable or carrying 3 0 /\ m p s for J seconds and I OA. c o n t i n u o u s l y

4.4.7.12. Relay t e r m i n a l s - s h a l l be screw type large enough lo accommodate HI least 4 m m 2 cable

and shall be located at the back or the relay

4.4. 7 . 1 3 . Relay t erm in als s h a l l be clearly marked

4.4.7 14. Relay contacts c o n fi g u ra t i o n s h a l l preferably be drawn on the relay casing.

4.4.7.15. A l t e rn a t i v e l y , a connection drawing s h a l l be supplied w i t h the relay.

4.4.7.16. Size not greater than 24x I 9x6 cm

4.4.8. Self-Reset T r i p Relay

Sell� Reset - T l'i p Rclav M a 1 1 1 1 f o c t u r c r ' s Experience and Product O n n l i f i c n t i o n : -

4.4.8.1. The m a n u fa c t u r e r s h a l l have experience of' a m i n i m u m or 1 5 years i n the manufacture of

t r i p relays

4.4.8.2. The offered relays must have been sold to at least two u t i l i t i e s outside the country or

manufacture. and operated r e l i a b l y for al least 8 years. Copy of Export sales contract

s h a l l be provided w i t h the bid lo support this requirement.

4.4.8.3. Relays that have foiled i n service or mal-operaicd on the Kenyan Power System shall not

be accepted.

4.4.8.4. Warranty for offered relays s h a l l be live (5) years from the date or relay d e l i v e r y to

KPLC store.

The Self-Reset T,·ip Relay shnll have the followini;: Functions and Fcnturcs:-

4.4.8.5. H i g h burden tripping relay, immune to capacitance discharge currents and leakage

currents

4.4.8.6. At least Four (4) pairs of normally open (NO) and two (2) pairs or n o r m a l l y closed (N )

or 4NOfNC o u t p u t contacts.

4.4.8.7. Instantaneous operation; t i m e < I Srns

4.4.8.8. The Relay s h a l l be s u i t a b l e lor flush m o u n t i n g or for m o u n t i n g on 35m111 D I N ra i l . i n

w h i c h case the relay s h a l l be supplied complete w i t h the base

4.4.8.9. Flag or target s h a l l be a red; L . E. . D . or d u r a b l e b u l b or Red Mechanical flag

4.4.8.10 The R e l a y s h a l l be self-reset. once the relay i n i t i a t i n g the t r i p resets.

4.4.8.11. Contact r a t i n g - capable otcarrying 3 0 /\ m p s for 3 seconds and l OA. c o n t i n u o u s l y mid

the Relay te rm ina ls s h a l l be clearly marked

4.4.8.12. Relay T e r m i n a l s - s h a l l be screw type t e r m i n a l s large enough to accommodate at least

4.4.8.13. 2 x 2.5 1111112 cable �nd shall be localed at the back or the relay

Issued hy: Head or Section, Standards Development Author'izcd hy: Head or Dcpar1111c111, S t a n d a rd s

-
,.
Signed: Signed: ,

:I, �-,:
�·- u
Du te: 20 t 9-06-07 Date: 2019-06-07
' r rn . r; Dul', Nu.
KP I /3 C BITS P/02/004

\'_ l ' R O T £ C T I V E RELA VS, CONTROL Issue Nu.


I

-
-
D E Y I C !c S A N D I N S T R U M £ N T S -
Revlslun No.
3
S P F. IFICATION
Kenya Power 0:11t..• uf Issue
2019-06-07

l'ugi.: 3 1 vf'72

4.4.8.14. Drawing Ior relay connection shall be provided w i t h the relay

4.4.8.15. Relay contacts c o n f i g u ra t i o n shall preferably be drawn on the relay casing.

4.4.8.16. A l t e rn a t i v e l y , a connection drawing shall be s u p p l i e d with the relay.

4.4.8.17. Size 1101 greater than 24x i 9x6 cm

4.4.9. Trip C i r c u i t S u p e rv i s i o n Relay Type I:

·rrip Circuit Supcrvisiu11 Relnv ·r)'.(H! I- Mauufac1urcr's Expl�ricucc and Pruducl <2ualifiratiou:-

4.4.9.1. '!' he m a n u f a c t ure r shal l ha ve ex p e r i e n c e ofa mi nimum or 1 5 years in the m a n u f a c t ure or

Tri p C r i cui t S u p e r v i s i o n relays

4.4.9.2. The o ffe re d relays m ust ha v e been so ld LO at leas t two utilities o utside t he countr y of

manufacture, and o perated r e l i a b l y fo r at least 8 years. C opy or Exp o rt sa esl c o n t ra c t

sh all be p ro vide d with the bid 10 s u pport t his re qui re m e n t .

4.4.9.3. Relays that have l


fa i e d in s e rv i c e or m a l - o p e ra t c d on t he K e n y a n Power Sy s tem shall no t

be acc e p t e d .

4.4.9.4. W arranty tor Offered re l ay s s h a l l be five (5) years from t h e date o fd e l i v e ry Lo Kl'LC

store.

The Trip C i r c u i t S u p e r v i s o r }'. l{chtl' s h a l l have the f'ollu"viu� Functions and F e a t u rc s . -

The relay s h a l l have t h e f o l l o w i n g featurest-

4.4.9.5. C o n t i n u o u s supervi s i on of trip circuit t o r c i rc u i t breaker in both O P E N & CLOSED

positions

4.4.9.6. Trip C i r c u i t l - l e a l t h y - Red/ recn 1 .. E . D ON

4 . 4 . 9 . 7. T r i p c i r c u i t I a i l =- G re e n / R e d 1 .. E . D O F F

4.4.9.8. Two (2) n o r m a l l y c l osed (N C ) and two (2) normally o p e n ( N O ) o r 2 C/0 (change-over)

output contacts

4.4. 9.9. The relay s h a l l have a t i m e dela y ofat l east I 5 0 m S to avoid tran s i ent operations

4.4.9.10. Contact ratings - 30 Am p s l u r J seco n ds mid 5 Amps c o n t i n u o u s l y .

4.4.9.11. S u i t a b l e for F l u s h m o u n t i n g o n t h e relay p a n el

4.4.9.12. Relay Te rrn i n u l s - s h a! l be screw type terminals large enough Io accommodate al least

41111112 cables and sh,111 be located at t h e buck o r the relay und relay t e rm i n a l s shall be

clear I y marked,

4.4.9.13. Relay s h a l l be s u p p l i e d c o m p l e t e w i t h the base.

4.4.9.14. R c l uy c o n t a c t s c o n fi g u ra t i o n s h a l l p re f e ra b l y be drawn on the relay c a s i n g .

4.4.9.15. A l t e rn a t i v e l y . a c o n n e c t i o n d ra w i n g s h a l l be su p p lie d with the relay.

4.4.9.16. Size not greater than 1 6 x 9 x 9 cm

Issu e d by: H ea d of S ect i on, Stan d a r ds Development Authoriz e d by: I-lead uf Ocp,1rt111 e 11t, Standa r ds

Signed: Sign e d:
( "' r:
iN _c9 6=

Date: 2019-06-07 y D u t e : 2019-06-07


Doc. No.
TITLE: KP I /3CB/TSP/02/004

1 P R O T E C T I V E RitLAYS, lssuc No.


ONTROL I

- -
D E V I C F. S AND I N S T R U M E N T S - Rcvlslnn No.
,
J

SPECIFICATION
Kenya Power D111e of Issue
20 I 9-06-07

Pugc 32 or 72

4 . 4 . I 0. A u x i l i a r y relays For Transformer M e c h a n i c a l Protection Trip F u n c t i o n Type I :

Au xilia r y ,·clays for T ra n s fo r m e r M e c h a n i c a l Protection Irin F u n c t i o n I - Ma n u fn c u , rcr's

Ex(lcricncc and Product Q u a l i f i c a t i o n : -

4 . 4 . I 0. I . The manufacturer s h a l l have experience or a 111ini111u111 or 1 5 years in the m a n u f a c t ure of

a u x i l i a r y relays for Power Transformer Mechanical Protection.

4.4. I 0 . 2 . The offered relays must have been sold to al least two u t i l i t i e s outside the country o f

manufacture, and operated r e l i a b l y li1r al least 8 years, Copy o r Cxpol'l sales contract s h a l l

be provided with the bid It) support t h i s requirement.

4.4. I 0.3. Relays that have foiled i n service or mal-opcraicd on the Kenyan Power System s h a l l not be

accepted.

4.4. I 0.4. Warranty for Offered relays s h a l l be five (5) years lrorn th e date or de livery t o KPLC s t ore .

A n 1 1 1 1 1 1 c i a 1 0 . - T ype I l
Re ay, Functions a nd Featurcs.-

4.4. I 0.5. The relays s h a l l be used as repeat r ela ys for power t ra n s fo rm e r m echa n ical p ro t ect i o n

fun ctions .

4.4. I 0.6. T he Re lay s h a l l have th e fo l l owin g features: -

I. Hig h sp eed o p e ra u o n . c 20 m s for t r i p p i n g

I I . One ( I ) clement i n on e casin g /relay

1 1 1 . Ha nd reset contacts

IV. M a n u a l l y reset Ope ra tio n indication/mechanical Hag (Red in c o l o u r)

V, Shall be suitable for 3 5111111 D I N ra il mounting in s i d e t he pa nel

V I . A t L east Three (3) p airs or normally o pen (NO) o utput c on t a c t s

4 . 4 . 10.7. R elay T e rm i n a l s - s h a l l be s crew t ype t e r m i n a l s large enough to accommodate at least 2 . 5

1111112 cables and located at the back of the relay.

4.4. I 0.8. Contact ra t i n g s - JO Amps for 3 seconds and I O Am p s c o n t i n u o u s l y .

4.4. I 0.9. Relay t e r m i n a l s s h a l l be c l e a r l y marked. with i n d e l i b l e numbers

4.4. I 0. I 0. Relay s h a l l be supplied complete with base.

4.4. I 0 . 1 1 . Relay contacts configuration s h a l l preferably be d rawn on t he relay c a sing.

4.4. I 0. 1 2 . A l t e rn a t i v e l y , a con n ection d ra w i n g s h a l l be s u p p l i e d w i t h the relay.

4.4.10.13. Size not greater than 24x I Sx I O cm

4 . 4 . 1 1 . A n n u n c i a t o r Relay Type I

A n n u u c i n t o r Relay Type I - Mnnufncnu-cr» F.xncricucc and Q u n l i f i c a l i o n : -

4.4.11.1. The m a n u fa c t u r er s hall have a m i n i m u m experience of 1 5 y ears in the m a n u f a c t u re or the

annunciator relay.

4.4. 1 1 . 2 . The offered relays must have been sold to nt least two u t i l i t i e s o u t s i d e the countr y 01·

manufacture, and operated r e l i a b l y for at least 8 years. opy or Export sa l es contract s h a l l

be provided with the bid to sup p ort this requirement.

Issued hy: Head of Section, S t a n d a rd s Development Authorized by: Hem) of D e p a rt m e n t , S ta nd ards

Signed: Signed: .
r fLtr( ,21. ")
.....
.I / '-"

Date: 2019- 0 6- 0 7 11 Dale: 20 1 9- 0 6- 0 7


TITLE: Dor. No. KP I /Jl'B/TSP/02/004

l P R O T E C T I V E RELA VS, CONTROL Issue- Nn. J

- -
DEVICES AND INSTRUMENTS­
Rcvisiun No. 3

S P E C I F' I C /\ T I O N
Kenya Power D:tl< ul' Issue 2019-06-07

4.4.1 1.3. Relays tlun have f o i l e d in service or mal-operatcd on the Kenyan Power System s h a l l not

be accepted.

4.4.11.4. Warranty for Ol'krecl relays s h a l l be live ( 5 ) years l'i-0111 the date o fd e l i v e ry 10 K l ' I . store.

A u n 1 1 1 u � i a l o r llclay t v p c I - F u n c l i o n s nud Features:�

The A n n u n c i a t o r relays s h a l l have compact d e s i g n . The Relay s h a l l have the Iotlowing leatures:

4.4.11.5. The A 1 1 1 1 u 1 1 c i a 1 o r s h a l l be designed to receive s t a t i o n e q u i p m e n t suuus i n f o rm a t i o n t h ro u g h

hardwired contacts. hence provide a rn111111011 point through which alarms can be

m o n i t o re d .

4.4.1 1.6. The relay s h a l l be compact and integrated into one co111111on device. Relays with i n d i v i d u a l

alarm covers arc 1101 acceptable.

4.4.1 1.7. The relay s h a l l be s u i t a b l e lo read and acknowledge alarms l o c a l l y or remotely

4.4.1 1 . 8 . The relay shall be l u l l y p ro g ra m m ab l e via keypad und/or I .aptop.

4.4.11.9. The status of the alarms s h a l l be retained even with loss of a u x i l i a r y tic power supply. On

power, Lip the last alarm status w i l l be displayed.

4.4.1 1 . 1 0 . S h a l l have Sile nce, Accept, Reset and Test push buttons, to control the Alarms

4. 4 .11 .11. The s i n g l e reluy s h a l l be equipped w i t h al least t h i rt y - s i x (36) separate a l a rm c l e m e n t s i n a

s i n g l e casing. Each alarm to be i n de p e n d e n t l y progrumruablc

4.4.1 1 . 1 2 . The relay s h a l l be of d i g i t a l design

4.4.11.13. The relay s h a l l be s u i t ab l e f o r I-lush panel m o u n t i n g

4.4.1 1 . 1 4 . Each of the e l e m e n t s s h a l l be freely assigned to one of two common o u t p u t a l a rm s : Urgent.

and Non-urgent alarm.

4.4.1 1 . 1 . 5 . Each A l a r m E l c m c r u s h a l l have a red L . E . D . 10 i n d i c a t e ,do1r111 ON status, I i shall also have

provision tor f i x i n g o f l d e n t i f i c a r i o n Label changeable at s i t e . A f l u s h i n g alurrn e l e m e n t

s h a l l be clearly v i s i b l e .

4.4.11.16. The Urgent and Non-Urgeru common a l a r m s shall be freely c o n f i g urab l e lo the o u t p ut

relays.

4.4.11.17. I i s h a l l have h i g h i m m u n i t y against electrical i n t e rf e re n c e .

Issued by: Head or Section, Standards Development i\ u t h o r i i c d by: Head of Dcpa1·1111cu1, Standunls

Date: 2019-06-07 D u t e : 2019-06-07


TITLE: Doc. No.
KPl/3 13/TSP/02/004

\'_ PROTF:CTIVE RELA VS, CONTROL lssuc No.

-
-
OF,VICES A N D INSTRUMENTS­ llevis-ion No.

S P E C I F I C A TI ON
Kenya Power 2019-06-07

Page }4 or 72

4.4.11.18. R e l a y T e rm i n a l s - s h a f be or screw type, large enough 10 accommodate at least

4.4.11.19. 2 x 2 . 5 rn rn 2 cable and s h a l l be localed at the back of' the relay

4.4.11.20. R e l a y t e rm i n a l s s h a l l be clearly marked w i t h indelible writing

4.4.11.21. R e l a y contacts c o n fi g u ra t i o n s h a l l p re f e ra b l y be drawn 011 the relay c a s i n g

4.4.11.22. Al least two output relays one for urgent and the other for non-urgent alarm

4.4.11.23. The relay s h a l l be supplied with fi e l d c o n fi g u ra b l e labels.

4.4.11.24. Al least two (2) pairs o fN o rm a l l y Open (NO) o u t - p ut contacts for each out-put relay

4.4.12. A n n u n c i a t o r Relay Type I I :

A n n u n c l n t o r Relay Type II - M a n u fa c t u r e r ' s Expcl'icncc a n d P r o d uc t O n a l i t i c n t i o n : -

4.4.12.1. The manufacturer s h a l l have a m i n i m u m experience o f 1 5 years in the m a n u fa c t u r e of t h e

a nn u n c i a t o r re l a y .

4.4.12.2. The offered relays must have been sold to at least two utilities outside the country or

m a n u f a c t u re , and operated r e l i a b l y for at least 8 years. 'opy or Export sales c o n t ra c t shall

be provided with the b i d to support t h i s r e q u i r e m e n t .

4.4.12.3. R e l a y s that have failed i n service or mal-operatcd on the Kenyan Power System shall not

be accepted.

4.4.12.4. Warranty for Offered relays s h a l l be live (5) years from the elate of delivery to K P L store.

A n n u n c i a t o r Relay l'ypc II - Functions und F e a t u re s :

The relay s h a l l have the fo l l o w i n g functions and features: -

4.4.12.5. The Annunciator shall be designed to receive s t a t i o n e qu i p m e n t status i n f o rm a t i o n through

hardwired c o n ta c t s . hence p ro v i d e a co111111on point t h ro u g h which alarms c1111 be

m o n i t o re d .

4.4.12.6. The relay s h a l l be compact and integrated into one co111111011 device. Relays with i n d i v i d u a l

alarm covers are not acceptable.

4.4.12. 7. The relay s h a l l be s u i t a b l e to read and acknowledge a l a rm s l o c a l l y or remotely

4.4.12.8. The relay s h a l l be f u l l y p ro g ra m m a b l e via keypad and/or Laptop.

4.4.12.9. The status of the a l a r m s s h a l l be retained even with loss of a u x i l i a r y de power s u p p l y , 011

power up the last alarm s t a t u s w i l l be d i s p l a y e d .

4.4.12.10. The relay s h a l l be o fd i g i t a l d e s i g n

4.4.12.11. The relay shall be s u i t a b l e for fl u sh panel mounting. The Relay shall have the following

leatures: -

4.4.12.12. Shall have S i l e n c e . Accept, Reset and Test push b u t t o n s . to c o n t ro l t h e A l a r m s

Issued hy: II cad of Section, S t a n r l a r d s Development A u t h n rj z cd hy: I-lead of D e p a r t m e n t , S t a n d a rd s

Signed: Signed:
L. ,

Date: 2 0 1 9 - 0 6 - 07 Dntc: 2019-06-07


TITLE: Doc. No.
KP I /JCU/'1 SP/02/004

- No.
'1 P R O T E C T I V E R E L A Y S , CONTROL ls.sui:

-
-
DEVICES A N D INSTRUMENTS­

SPECIFICATION
Rcvlslun Nv.
3

Kenya Power l>Htt• of Issue


2019-06-07

Page 35 oC72

4.4.12.13. The s i n g l e relay sh,111 be equipped with sixteen ( 1 6 ) separate alarm Elements in a single

cas: ng.

4.4.12.14. The Relay O ff e re d must have been 111 Service 111 Kenya Power System and operated

s uc c e s s f ul l y f o r the, last 4 years. Improved designs of previous relays arc acceptable.

4.4.12.15. Relays o ff e rs from M a n u fa c t u re rs who haw not s u p p l i e d relays before arc 1101 acceptable

Ior t h i s tender.

4.4.12.16. Relays that have lhiled in service or mal-operated s h a l l not be acceptable

4.4.12.17. Each o tt h e elements s h a l l be f re e l y assigned to one oftwo co111111011 output Alarms; Urgent

and NON-urgent Abr111.

4.4.12.18. Each Alarm Elc111e111 shall have a Red L.E.D. to i n d i c a t e ON status. It s h a l l also haw

p r o v i s i o n tor l i x i n g of l d c n t i f i c a t i o n Label changeable on s i t e . /\ flushing A l a rm ek111e111

s h a l l be clearly v i s i b l e .

4.4.12.19. The Urgent and Non-Urgent co111111on alarms shall be freely configurable to the output

R e la ys ,

4.4.12.20. I t s h a l l have h i g h i m m u n i t y against clcctrica) i n t e rf e re n c e

4.4. 1 2 . 2 1 . Relay Terminals-shall be or screw type, large enough to accommodate at least 2x2.5 1111112

cable and s h a l l be located at the back ofthe relay

4.4.12.22. Relay t e rm i n a l s s h a l l be c l e a rl y marked, with i n d e l i b l e w r i t i n g

4.4.12.23. Relay contacts c o n f i g u ra t i o n s h a l l p re f e ra b l y be drawn on the relay casing

4.4.12.24. A t least two o u t - p u t relays one for urgent and the other lor non-urgent alarm

4.4.12.25. Drawings for w i r i n g or the relay shall be supplied with the relay.

4 . 4 . 1 3 . Discrepancy S w i t c h fur C i r c u i t Breaker C u n t ru l :

1
1
l)iscrcpancy S,, itch fur Circ..·tlit Breaker Coutrol- M a 1 1 u f a c t u r c r s E x p e r i e n c e anll P r o d u c t Q u a l i f i c a t i o n : -

4.4.13.1. The m a n u f ac t ure r s h a l l have m i n i m u m experience or 1 5 years in the r n n n ul a c t u re of the

switch.

4.4.13.2. The offered Discrepancy switch must have been sold to al least two u t i l i t i e s outside the

country of m a n u f a c t ure , and operated reliably Iur at least 8 years. Copy or Export sales

contract shall be provided w i t h the bid lo support t h i s requirement.

4.4.13.3. Discrepancy switches that haw foiled 111 service or mal-operated on the Kenyan Power

System shall not be accepted.

4.4.13.4. Warranty for offered Discrepancy S w i t c h e s s h a l l be live (5) years from the elate or delivery

to K P I . C store.

Issued by: I lead of S e c t i o n , S t a n d a rd s Developrucut Aulhul'i,.cd by: I-lead of D c p u ru u e u t , S t a n d a r d s

Signed: S i g u c t.l :

Date: 2019-06-07 Date: 20 l 9-06-07


TITl,E: Doc. No.
KP I /3CB/TSP/02/004

\'_ P R O T E C T I V E RELA VS, C O N T R O i , lssur No.


I

-
-
DF:VICF:S A N D I N S T R U M E N T S -

S P U: C I F I C A T I O N
Revtstou No.

f---
3

Kenya Power Dntc of Issue


2019-06-07

Pugi.: 36 nr72

The Discrcpnnci' Switch for Circuit Breaker Control switch - Functions and Features: -

4.4.13.5. S u i t a b l e flush m o u n t i n g

4.4.13.6. Press and Turn o p e ra t i o n ror C i r c u i t Breaker close and open o p e ra t i o n .

4.4.13.7. As a minimum three (3) pairs of N or m a l l y Open(NO) contacts for circuit breaker close

opera l i o n and two (2) pairs of Normally Opcn(NO) contacts for c i rc u i t breaker open

o p e ra t i o n .

4.4.13.8. White colour ontinuous i I I um i n a t i o n for d iscrcpancy 111 circuit breaker status. The

i l l u m i n a t i o n shall be by while LFD b u l b .

4.4.13.9. The d i s c r e p a n c y switch s h a l l be sturdy ancl d u r a b l e .

4.4.13.10. The position for c i r c u i t breaker close and the position for c i r c u i t breaker open O p e ra t i o n s

shall be clearly marked on the escutcheon plate s u p p l i e d w i t h the switch.

4.4.13.11. The lop of the switch h a v i n g the escutcheon p l a t e s h a l l have a rectangular outer shape.

4.4.13.12. The s w i t c h s h a l l have screw type t e r m i n a l s large enough to accommodate 2 x 2 . 5 1 1 1 1 1 1 2 cable

4.4.13.13. Switch terminals s h a l l be i n d e l i b l y marked, w h i t e numbers on black background

4.4.13.14. The s w i t c h contacts c o n fi g u ra t i o n s h a l l p re f e ra b l y be drawn on the switch

4.4.13.15. S w i t c h lo be s u p p l i e d w i t h w h i t e i l l u m i n a t i o n I .FD bulb

4.4.13.16. The l a m p s h a l l be rated at below 4 W power c o n s u m p t i o n

4.4.13.17. The switch shall be s u p p l i e d with a d ra w i n g s h o w i n g how the switch operates and contact

con Ii gu ration.

4.4.13.18. Swit h Offered s h a l l be type DK I O or e q u i v a l e n t in terms or size. q u a l i t y and d u ra b i l i t y .

4 . 4 . 1 4 . Semaphores for l s o l a t o r :111d Earth Switch P o s i t i o n Indication

Semaphores for Isolator and Earth switch P o s i t i n n I u d i c a t i o n - M au u f a c t u rc rs experience :11111

P ro d u c t Oualiticatio11:-

4.4.14.1. The manufacturer shall have at least 15 years' experience 111 the 1r1a11 u fact ure or the

semaphores.

4.4.14.2. This d e v i c e s h a l l be used to remotely m i m i c on the control panel, the p o s i t i o n (open or closed)

ofdisconnectors/lsolarors, which arc located in the switchyard,

Issued hy: Head of Section, S t a n d a r d s Development ,\11thori1.cd hy: Head of' D e p a rt m e n t , S t a n d a rd s

Signed : Signed:
:'N )· <
_..,... A ,
-,."l"'!l'..:c1w. "1.. I f - 6'.C o'
Date: 2019-06-07 v Date: 2019-06-07
TITLE: Dor. Nu.
KP I /3 C 13/TS P/02/004

--
l l ' R O T E C T I V E RELAYS, C O N T R O L Issue Nu.
I

-
-
DEVICES ANO INSTRUMENTS-

Sl'ECIFICATION
Revlsiou No.
'
j

Kenya Power Dall' of Issue


2019-06-07

Pugc J7 uf72

"

4.4.14.3. The offered Semaphores 111us1 have been sold to al leas! two ut i l i t i e s outside the country of

manufacture. and operated r e l i a b l y tor al least 8 years. Copy o f Export sales coruract s h a l l be

provided w i t h the bid 10 support t h i s requirement.

4.4.14.4. Semaphores iha: have f a i l e d i n service or mal-opcruted on the Kenyan Power System s h a l l

not be accepted.

4.4.14.5. Warraruy for O ff e re d semaphores s h a l l be Five (5) years l ro m the date of d e l i v e r y to Kl'LC

store.

Scrnaphorc� for I s o l a t o r uml E H r l h s w i t c h l'usi1io11 l u d i c u t i o n - F u u c t i o u s and Features:-

4.4.14.6. S h u l l be s u i t a b l e Ior flush m o u n t i n g

4.4. 14.7. With Red L . E . lJ Jar closed (ON) status i n d i c a t i o n and Green L . E . D tor open (01'1·') status

l ndi carion .

4.4. 1 4 . 8 . S h a l l be of c i r c u l a r or rectangular front appearance

4 . 4 . I 4.'J. The U n i t s h a l l have screw type terminals large enough to accommodate 2x2.51111112 cable

4.4.14.10. The T e r m i n a l s s h a l l be i n d e l i b l y marked

4.4. I 5. LED Iudicuting Lumps»

Ll�I) I n d i c a t i n g La111ps - M a 1 1 u f a c t u r c r ' s F.xpcric1u.:c and P ro d u c t Q u a l i t i c a t i u u : -

4 . 4 . I 5. I . The m a n u f a c t u re r shall haw at leust 15 years, experience in the manu foe t urc of LED

in d i c a t i n g lumps. The lamps me p r i m ar i l y tor indicating the status o f switchgear in ihe

substation.

4.4. I 5.2. The offered Ll�D l n d i c a t i n g l .arnps must have been sold to ar least two u t i l i t i e s outside the

country of m a n uf a c t ure , and operated reliably for at least 8 years. Copy or Export sales

coruract s h a l l be p ro v i d e d w i t h the bid to support this re q u i re m e n t .

4.4. I 5.3. LED lndicating Lamps that have failed in service or mal-operated on the Kenyan Power

System s h a l l 1101 be accepted.

4.4. I 5.4. Warr,1111y for o ff e re d LED I n d i c a t i n g Lamps s h a l l be live (5) years from the date \Jr d e l i v e r y

to KP LC store.

LE[> lndicHtin� Lu111ps- F u n c t i u n s und F cu t u rc s : -

They s h a l l have the fo l l o w i n g features: -

4.4.15.5. The Ll.:D i n d i c a t i n g lamps s h a l l be c o m p l e t e w i t h l a m p and m o u n t i n g base

4 . 4 . I 5.6. These s h a l l be s u i t ab l e lc.1r m o u n u n g on the front of the control panel ( F l u s h m o u n t i n g ) .

4.4. I 5.7. The I n d i c a t o rs Lamps s h a l l be or L E I) type

Issued by: Head of Section, S t u u d u rd s Ocvclupmcnl Authol'izctl by: I-lead uf Dcp11rl111c111, S t a n d a r d s

Signed: Signed:
r: n. ., .r �
G � ls
. ' . )•

lhtc: 2019-06-07 v Ontc: 2019-06-07


TITLC: Doc. No. K P I /3CB/TSP/02/004

\:_ PROTl�CTIVI� RELA VS, CONTROL lssuc No. J

-
-
DEVICES A N D INSTRUMENTS­

S P E C I FICA TION
Kenya Power D111c or Issue 2019-06-07

Page 38 of 72

4.4.15.8. The Lamp Indicators should be rated for 4 W power consumption or less.

4.4.15.9. The lamp i n d i c a t o r s should be designed for c o n t i n u o u s operation and to g i v e n l o n g o p e ra t i n g

l i f e o ta : least 1 0 years.

4.4.15.10. Red I . E D indicators s h a l l be of the high brightness type

Note I : The colour and quantities of the /YD Indicating lamps 111il/ he specified in the

Bill of materials and price schedules

Note 2: The manufacturer ofMiniature Circuit Breakers (MCB.1) shall experience of at

least 15 years in the ma1111fac111,-e of the M 'Bs

4.4.16. M u l ti - F u n c t i o n a l Power Meter

M u l l i - F 1 1 n c 1 i o n n l Po,,·cr M e t e r - M a n u f a c t u r e r ' s Expcl'icncc aud Product Q u a l i fi c n t i o n : -

4.4.16.1. The manufacturer s h a l l have al leas! 1 5 yearn' experience in the manufacture o f the M u l t i ­

functional Power Meter.

4.4.16.2. The offered power meters 111l1st have been sold to al least two u t i l i t i e s outside the country or

manufacture, and operated reliably for at least 8 years. Copy of Export sales contract shall be

provided w i t h the bid to support t h i s requirement.

4.4.16.3. Power meters that have failed in service or r n a l - o p c ra t c d 011 the Kenyan Power System s h a l l

not be accepted.

4.4.16.4. Warranty for Offered M u l t i - f u n c t i o n a l Power Meters s h a l l be live (5) years from the date of

delivery 1.0 KPLC store.

M u l t i - F u n c t i o n a l Power M e t e r - F u n c t i o n s and Fcnturcs:-

4.4.16.5. This is a power measurement meter for panel m o u n t i n g

4.4.16.6. The u n i t shall be of numerical design

4.4.16.7. The u n i t s h a l l have a large LCD d i s p l a y for d i s p l a y i n g f o ur (4) or more l i n e s or mcasurands

si rnul iancously.

4.4.16.8. The keypad s h a l l be simple to a l l o w s c r o l l i n g between the various mcasurands

4.4.16.9. The u n i t s h a l l measure instantaneous values of; rms voltage, both phase - phase and phase 10

ground, phase currents, active power, reactive power, apparent power, energy, Frequency,

power factor and phase angle per phase

Issued by: I-lend of Section, S t a n d a r d s Development Author'ized hy: I lead or D e p a rt m e n t , Standards

Signed: Signed: I �
..5

Date: 2019-06-07 Date: 2019-06-07


TITLE: noe. Nu. KP I /lCB/TSP/02/004

1
Issue Nu.
PROTECT ! V E R E L A YS, C O N T R O L I

- -
D E V I C l!: S A N O I N S T R U M E N T S ­
Rcvlsluu Nu. 3

SPECI FICATION
Kenya Power Dntc uf Issue 20 J 9-06-07

4 . 4 . 1 6 . 1 O. The U n i t s h a l l measure t i m e stumped m a x i m u m and m i n i m u m demand lor current and rower

(MW & M V /\ )

4.4. I 6 .11 . The u n i t shall also measure unb alan c e voltage and current

4.4. 1 6 . 1 2 . The u n i I shal I measure To t a l harmonic distortionf'lH DJ and Tomi Demand lJ i s t or t i o n ( T D D )

Ior current and voltage

4.4.16.13. The u n i t s h a l l haw the lei l o w i n g i n p u t rulings,


I I A m p s and 1 1 OVA ' p h a s e to phase.

4.4.16.14. The u n i t should be able to c o n t i n u o u s l y w i t h s t a n d 2Amps and 260 V /\C

4.4.16.15. The u n i t shall be for flush mounting on the front o ft h e panel

4.4.16.16. The u n i t s h a l l be lor 3 phases, 4 -wirc connection on the secondary 01· c u rre n t and voltage

trans formers

4.4.16.17. The u n i t s h a l l be equipped w i t h an RS232 port lor p ro g ra m m i n g the u n i , to ensure correct

measurement and d i s p l uy Di' the p a ram e t e rs . The CT and VT ra t i o s shal l be programmable.

A l t e rn a t i v e l y , programming can be achieved through the keypad.

Nute: Progn11m11ing will be conducted 111 site during installation.

4.4.16.18. RS 485 port s h a l l be provided for remote c o n u n u n i c a t i o n .

4.4.16.19. C o m m u n i c at i o n protocol s h a l l bi: I E C 6 1 8 5 0 and l li C 6 0 8 7 0 - 5 - 1 0 4

4.4.16.20. The accuracy ofmeasurement s h a l l be at least class 1 . 0

4.4.16.21. Sh a l l have i n b u i l t r e a l - t i m e c l o c k and calendar

4.4.16.22. It shall be posxiblc to d i s p l a y a l l the measured parameters 011 the screen through the pre­

programmed display screen. The screen to be d i s p l a y e d shall be selectable u s i n g the keys on

the l ro n t of' the u n i t

4.4.16.23. The s o f t w are and the PC to power meter u n i t connection cable s h a l l be supplied w i t h the

units. /\t least eight c o m m u n i c a t i o n cables devices shall be required

4.4.16.24. /\ I I the terminals s h a l l be dearly marked

4 . 4 . 1 G.25. The measurement range tor power s h a l l at least be lip to 90 M V A .

4.4.16.26. Th-, meter shal I be powered w i t h I I OV DC; ur I I OV D ' / I I OV AC

Issued by: Head of Section, Stuudurds D e v e l u p r u e n t A u t h o r i z e d by: Head of Ucp,11·1111cnt, Standards

Signed: Signed:

----- u
lJatc: 2019-06-07 Dale: 20 t 9-06-07
TITLE.: nor. No. KPl/3CB/TSP/02/004

\'_ PROTECTIVE RELA VS, CONTROL Issue No. 1

-
-
OEVICES AND INSTRUMENTS­
Revislnu Nn. J

S P E C I Fl CATION
Kenya Power llMu or Issue 2019-06-07

Page dO o f 7 2

4 . 4 . 1 7 . A d d i t i o n a l Specifications for Relays

4.4.17.1. A l l measurement relays must be of Numeric design.

4.4.17.2. Relays or Electromechanical design arc acceptable only for use as auxiliary relays and

contacrors. 1101 for measuring relays.

4 . 4 . 1 8 . Relay P r o g r a m m i n g Software a n d C o n n e c t i o n Cables

4.4.18.1. Software must be provided tor p ro g ra m m i n g and downloading claw for a l l n u m e r i c a l relays

supplied and also for any numerical i n s t ru m e r u s SL1ch as transducers provided.

4.4.18.2. It shall be possible to install the Software to twenty different computers without any

a d d i t i o n al License Cost. Two (2) CDs s h a l l be s u p p l i e d for each different type o r Software.

4.4.18.3. Four (4) copies the software Users G u i d e s h a l l also be s u p p l i e d . The numerical relays w i l l

be equipped with an RS232 communication port or other s ui t a b l e port to facilitate

connection to a Laptop.

4.4.18.4. The relevant c o m m u n i c a t i o n cable, between the relay and the laptop s h a l l also be p ro v i d e d .

Four (4) cables s h a l l be provided for each set or Relays using the same cable. Four (4)

c o m m u n i c a t i o n cables shall be provided for each set or transducers and also for the power

measurement u n i t .

4.4.18.5. ornmunication fa c i l i t i e s shall be provided on each numerical relay for remote

inte rro ga tion and programming of the nu me rical relays.

4.4.18.6. The relays w i l l a l s o have an M M ! c o n s i s t i n g o r a keypad and an I .CD screen to facilitate

m a n u a l relay p ro g ra m m i n g and data access.

4.4. 1 8 . 7. Relay operation clue to system rmil I. sha 1 1 be i nclicatcd by a reel I , . E. D. and the fau I t cletai Is

(flags) s h a l l be displayed on the LCD screen. Both the relay fault nags and red L . E . D w i l l

be reset without opening the relay cover. except where the relay contacts are latched.

Tl I I S S P A C [ I S LliFT A LANK I N T E N T / O N A l , L Y

Issued hy: I-lead of S e c t i o n , Standards Development /\ u t h o r i i c < I by: H ea d of D e p a r t m e n t , S t a n d a rd s

Signed: Signed:
la: - •
- <03
l),, te: 20 t 9-06-07 f Date: 211 t '>-06-117
TITLE: Due Nu. KP I /3(13/TSP/02/004

1
-
PROTECT! VE IU�LA YS, C O N T R O L

D��VICES A N D I N S T R U M E N T S ­
rssuc N1J. J

- Sl'ECIFICATION
Kenya Power IJ,,,, or lssu< 2019-06-07

A P P E N D I X A: TESTING

A. I . The m a n u f a c t urers s h a l l carry o u t a l l the ro u t i n e Jests o ft h e protective relays, c orurol

devices and accessories and measuring i n s t ru m e n t s at the f a c t o ry .

A.2 Copies oftest reports s h a l l be packaged together with the respective relays and measuring

i n s t ru m e n t s before d e l i v e ry 10 KPLC.

/\ . 3 . The tests sh a l l be i n accordance with the re q u i re m e n t s o f I E C 60255 & l � C 6 0 0 5 1 .

A P l ' lc N D I X B: WARRANTY

B. I . The s u p p l i e r/ m a n uf ac t ure r warrants the purchaser that n i l goods s u p p l i e d under t h i s tender s h a l l

have no defect u ri s i n g lrorn design, materials or w o r k m a n s h i p .

tl . 2 . f
\ warranty o l ' 6 0 m o n t h s [rorn the dale c ld e l i v e ry ofihe measuring protection re lays 10 KPLC

store s h a l l be ullcred by t h e m a n u f a c t u re r for the protection measurement re l ay s , i n c l u d i n g

a n n u n c i at o r relays.

B.4. The Warranty for other a u x i l i a r y relays and control devices shall be 60 months from the date of

d e l i v e ry or the devices to Kenya 1,ower store. /\ny protection relays and control and

m e a s ure m e n t devices found 10 have failed at c o m m i s s i o n i n g or while the device is in service or

store d u r i n g the Slated warranty periods s h a l l be replaced free ofchurgc by the

mun u l u c t u re r(S u ppl ier,

A P P E N D I X C: Q U A L I T Y M A N A G E M E N T SYSTEM ( N O R M A TI V E )

C. I . The s u p p l i e r shall s ub mit H q u a l i t y assurance plan (Q/\P) that w i l l be used Lo ensure that the

PQA properties, tests and documenuuion, w i l l fu l fi l the requirements stated in the contract

documents, standards, s p e c i f i c a t i o n s and regulations. The Q/\P shall be based on and i n c l ud e

relevant parts to Iul Ii I the re qu i re m e n t s or I S O 900 I : _ ( ) 1 5

C.2. The M a n u la c r ure r ' s Declaration o tCo n f o rr n i t y to a p p l i c a b l e siandurds and copies o fqu a l i t y

management c e rti f i c a t i o n s . i n c l u d i n g copy o f v a l i d mid relevant ISO 9 0 0 I : 2 0 1 5 certificate,

s h a l l be s ub m i u e d w i t h the tender for e v a l u a t i o n .

Issued by: Heinl uf Section, Standanls Develupurcut A u t h u ri z ed by: I-lead of D e p u ru u e u t , S t a n d n rtl s

'"--c::::" \'.::'
l
=S�g
i�1
:
t c�d:=::
: � �=::
=::
� �<
" {
� ·
� ,,
� ).,�
j)�
' - ) =::
=:: =::
=::
=::
� l
� S-gr-:
i_ n _c_d_�
: ���-------=:::,
� � � �- C, � --
- �����--1t

Date: 2019-06-07 · t Date: 2019-06-07


TITl,F: no,. No. l<PI/JCB/TSP/02/004

1 P R O T E C T I V E RELA VS, CONTROL tssuc No. J

-
-
D E V I C E S A N D I N S T R l J M F: N T S ­
Revision No. J

S P F: C I F I C A T I O N
Kenya Power Date of lssuc 20 I 9-06-07

l'agc 42 of 72

.3. The m a n u f a c t ure r s h a l l i n d i c a t e the d e l i v e r y l i m e ofthe e q u i p m e n t : manufacturcrs m o n t h l y

and annual production capacity and experience in the production of the type and size o fi t e m s

being offered. /\ detailed l i s t and contact addresses ( i n c l u d i n g e - m a i l ) of' the m a n u Iacturers

previous customers for s i m i l a r type of PQ/\ sold i n the last five years as well as reference

letters Irorn at least four of the customers s h a l l be submitted w i t h the tender for eva l u a t i o n ,

A P P E N D I X D: T F: C H N I C A L D O C U M E N T A T I O N ( N O R M A T I V F: )

D. I . The bidder s h a l l submit its lender complete with technical documents required Ior tender

evaluation. The technical documents to be submitted (all in English language) fo r l e n de r

e valuation shall include t he follo w i n g :

a) F u l l y - fi l l e d cl a u s e by c l au s e G ua ra nt e ed T e c h n i c a l P a rt ic u l a r s (GTPs) - A ppendix

D - stamped and si g ned by the m a n u f a c ture r.

b) C opi e s o f th e M a n u f a ct u rer ' s ca t alo g u es , brochure s . d ra w in g s a nd te chn i c a l data

lor the e q u i p m e n t :

c) D etails of the m an u f a ct u rer ' s e x perience ; S ales records fo r the las t live ye a r s and

at least four c u s t o m er r ference let t er s .

cl) C o p i e s of p r e v ious test c e rt i f i c at e s a nd t es t report s (As g iv e n i n Cla u se /\ . 2 ) by t he

rel eva n t I n t e rn a t i o n a l or Na tional T e s t in g / S t a nd a rds Au thori t y o f the cou ntry of'

m a n u facturc ( or ISO/I LC 17 025 acc r e d it e d in d ep e nd e n t l a b o ra t o ry ) sh a l I be

s ubmitted w ith the offer for evaluation.A copy or accredita t i o n cer t i f i c a t e for t he

l a bor a t o r y s hall a l s o be s ub m i t t e d (a ll i n l�nglish L anguage):

e) M a r k i n g & Packa g in g d e t a i l s ( i n c l u d i n g packa g ing m a te ri a l s ).

D.2. The successful bidder ( supplier ) s h a l l s u b m i t the l o l l o w i n g d o c u m e n t s / d e t a i l s to The Ke n y a

Po wer & L i g h t i n g Company for appro v al before manufacture:

a) F u l l y f i l l e d clause by clause Guaranteed T e c h n i c a l Partic u lars ( GTPs ) stamp ed and

signed by the manufacturer (these arc not t h e ones s u b m i t t e d w i t h the t e n d e r ) ;

Issued hy: Head of Section, Stnnrlarrls Development A u t h n ri z e d hy: Hem! of D e p a r t m e n t , S rnndards

Signed: Signed:

Date: 2019-06-07 71 Date: 2019-06-07


TITLE: Uol·. No.
Kl' I /3CB/TSl'/02/004

\'_ l ' R O T F: C T I V E REL AYS, C O N T R O L


Issue No.

-
-
DEVICES AND INSTl{UMENTS­
Rcvixiun Nu.
3
Sl'ECI Fl CATION
Kenya Power L>atc of Issue
2() 19-06-07

P11ti.: 43 ot'72

b) Te c h n i c a l details mid drawings with details or portable single phase secondary

in j e c t io n set to be m a n u f a c t ure d tor KPLC.

c) Q u a l i t y assurance p l a n (QAP) that w i l l be used 10 ensure that the design, material;

workmanship, tests, service c a p a b i l i t y , maintenance and documentation w i l l fulfil

the requirements stated in the contract documents, standards, s p e c i f i c a t i o n s and

re g u l a t i o n s ,

D.J. R o u t i n e 1111cl sa mple lest reports tor the e q u i p m e n t to be s u p p l i e d shall be subrniued to Kenya

Power for approval be l o re s h : prneru/dcl i very o I' the goods.

D.4. Each e q u i p m e n t package shall be s u p p l i e d with detailed user's manual printed in English

language that i n c l u d e s the l u l l o w i n g among other i n f o r m a t i o n w r i t t e n i n English language to

Kenya Power stores. A l l i n lo nn au c n s h a! l be unambiguous. A l l d o c u m e n t a t i o n necessary l o r

salcry o f the e q u i p m e n t as specified in Ji:,C 6 1 0 1 0 - 1 clause 5.4 shall be provided with the

cqu1p111e111.

APPl�NDIX E: TECHNICAL M A N U A L S / G U I D F: & OP[RATION AND MAJNTENANCE

MANUALS

Technical m a n u a l s and operation and maintenunce manuals shall be supplied w i t h the goods as

follows: -

E. l . Eleven ( I I ) copies of' hard copy i c c h n l c a l manual/guides shall be furnished to K P L C for each

type or relay, transducer, and i n s r ru m e n r and c o r u ro l device. Son copy or the m a n u a l s s h a l l

also be s u p p l i e d w i t h the goods.

The technical m a n u a l s h a l l describe in d et ail the h a n d l i n g , i n s t a l l at i o n , a p p l i c a t i o n , technical

data and o p e ra t i n g curves, test and commissioning, s c rv i c i n g / r n u i n t c n a u c c and c a l i b ra t i o n or

the protection relays, measuring devices. transducers mid control accessories,

E-- These s h a l l also i n c l u d e uscr/opcrutor g u i d e lor protection relays, transducers, instruments and

measuring devices for programming or the settings and configuration, and accessing the

settings and data. A p p l i c ar i o n drawings for the relay/device s h a l l be i n c l u d e d

The t e c h n ic a l manuals shall be d e l i v e re d lo the office of the General Manager. Network

Mana ge me nt, Kl-'l_C_ 111 S t i rn a Plaza, N a i ro b i .

Issued by: He ad of Section, Stuudurds Dcvclopmcut A u t h or i z e d by: Head of D e p a rt m e n t , S t u u d a rd s

Signed: Signed:

.
D:lll': 20 I ?-116-07 /I D a t e : 2019-06-07
TITLE: noe. No. K P I / J C B/ T S r / 0 2 / 0 0 4

l
Issue No.
P R O T E C T I V E Rl�LA VS, C O N T R O L I

- OEVICES A N O INSTRUMENTS­

S l ' E C I Fl CATION
Revision ND. 3

Kenya Power Onie of lss111• 2019-06-07

Page 44 of 72

A l ' l ' E N D I X F: FACTORY A C C E P T A N C I � Tl�STS, I N S l ' F: C T I O N A N O T R A I N I N G

F. I . The protective relays s h a l l be subjected lo factory acceptance testing and i n s p e c t i o n by al least

two K P L C engineers ,11. place o f manufacture where a l l routine tests as per I E 60255 s h a l l be

carried out on a m i n i m u m of two relays of each type for each speci tic ( u n i q u e ) c o n fi g u ra t i o n .

F.2. A l l the Relays, Instruments and Control devices s h a l l be inspected 10 ensure they fully c o m p l y

with the s p e c i fi c a t i o n s .

F.3. In addition. training shal] be conducted in the factory for the two K l ' I . C engineers a t t e n d i n g

FATs, for the durations indicated below. A p p ro v a l for shipment of goods by KPLC shall

dependent 011 a s a t i s f a c t o ry F/\T report by t h e En gineers.

l'.4. The full cost o ft h e v i s i t , i n c l u d i n g air tickets and accommodation s h a l l be borne by KPLC.

F.5. Factory T ra i n i n g s h a l l be carried out l'or the following relays: -

(i) Distance Protection Relay - 3 days

(ii) Biased Differential Protection Relay - 2 days

(iii) Feeder Protection & Control Relay - 2 days

(iv) Power Measurement U n i I - I day

F.6. The purpose ofthe t ra i n i n g is to ensure that the K P L C engineers have a d e q ua t e knowledge so

that the relays are correctly installed, con figu re d and parameters correctly set and fi n a l l y the

relays are successfully tested and put into service on the Kenyan rower system. The

manufacturer/supplier s h a l l conduct an assessment to ensure that the KPLC Engineers have

acquired the necessary knowledge and s k i l l s to be able 10 successfully apply the relays on the

power system.

F.7. Where the number o f days required Ior t r a i n i n g on any o r the above relays is more 1hi111 what

is indicat ed above. the m a n u f a c t u re r/ b i d d e r s h a l l i n d i c a t e the required number or days i n t h e i r

b i d . The number or days indicated above is however the 111ini111u111 re q u i re m e n t .

F.8. Each supplier/manufacturer shall conduct training for the protection relays they shall be

offered 10 s u p p l y .

APPENDIX G: LOCAL T R A I N I N G IN N A I R O R I

G. I . Local T ra i n i n g s h a l l be conducted for K P I .C Engineers and T e c h n i c i a n s 111 N a i ro b i . This

t r a i n i n g s h a l l cover the f o l l o w i n g relays: -

(a) Distance Protection Relay - 2 days

Issued by: I-lead of Section, S t a n d a rds Development A u t h n ri ze r ! hy: I-lend of D e p a rt m e n t , S t a n d a r d s

..
Signed: Signed:
T/

Date: 2019-06-07 ' v Date: 2 0 1 9 - 0 6 - 0 7


T I T L F. : Dor. No. KP I/JC 13/TSP/02/004

\'_ l'l{OTECTIVE RELAYS, CONTROL lssut· Nu. 1

-
-
O U: V I C E S A N D

Sl'ECIFICATION
INSTRUMENTS­
Revisluu Nu. J

Kenya Power Dute of Issue 2019-06-07

Pug.1.: '-15 ol'T1

(b) Tru n s f o rm c r D i l fe rc n u a ! P ro t e c t i o n Relay - 3 <lays

(c) Feeder Proicctiun & C o n t ro l Relay - 2 days

(d) Power Measurement U n i t - I clay

G.2. The l'ra i n i n g s h a l l be for a maximum or I O working days and w i l l i n v o l v e t ra i n i n g of nut less

than 1 5 l.onginecrs/ T e c h n i ci a n s .

G.3. The m a n u f a c t ure r shall med the total cost or the fuct ory trnining as we ll as Local T ra i n i n g in

N a i r o b i Kenya.

G.4. The s u p p l i e r s h a l l also meet u l l the other costs for c o n d u c t i n g the local t ra i n i n g , i n c l ucling local

a c c o m m o d a t i o n and transport for the t ra i n i n g s t a l f The s u p p l i e r shall p ro v i d e u l ] the t ra i n i n g

materials in c l u d i n g notes. However the costs d11 1101 i n c l u d e the uu ns p o rt and accommodation

l'ur K P L C engineers

G.5. The purpose of the t ra i n i n g is to ensure that the KPLC Engineers/Technicians have adequate

knowledge so that the relays are correctly i n s t a l l e d , configured and parameters correctly set

and f i n a l l y the relays are s u c c e s s f ul l y tested and put i1110 service on the Kenyan power system.

The m a n u f a c t ure r/ s u p p l i e r shal) conduct an assessment to ensure that the Kl'LC E n g i n e e rs

have acquired the necessary knowledge mid s k i l l s to be able to successfully apply the relays

011 the power system.

APPENDIX 1-1: REQUIREMENT FOR T E N D E R EVALUATION

I- I . I . Two copies each or product cutulogue and technical p u b l i c a t i o n s for the s p e c i f i c p ro t e c t i o n

relays, transducers, instruments and control devices o ff e re d shall accompany the b i d .

The product c at a l o g ue and technical publications provided shall provide all the technical

details o ft h e o ff e re d relays/devices, i n c l u d i n g a l l the technical data and protection and control

lu n c t i o n s i n c l u d e d in the device.

The product catalogue and t e c h n i c a l p u b l i c a t i o n s h a l l be used to verity i n lu rr n a t i o n entered in

the t e c hn ica l s c h e du l e s co m p l e t e d by the bidder.

1-1.2. Application d ra w i n g s for the relay/device s h a l l also be s u b m i t t e d with the b i d .

1-1.3 F a i l ur e tu s u b m i t the product c a talo g ue and the technical publication for each re l a y / d e v i c e

included i n the bid may lead to rej e c t i o n of the b i d .

Issued by: I-lead of Section, S t a n d a r d s Development Authorized by: I-lead of D e p a r t m e n t , S t a n d a rd s

Signed: Signed:
t' '
A\], ) '
� - -- y
Date: 2019-06-07 Date: 20 l '>-06-07
TITLE: noc. Nn.
K P I /3CB/TSP/02/004

1 P R O T E C T I V I� HULA VS, CONTROL lssnc Nu.

- -
D E V I C E S A N D I N S T R I J M F. N T S ­

SPECIFICATION
Revlslnn No.
'
J

Kenya Power nnrc of lssuc


2019-06-07

l'agc46nf72

APPENDIX I: SOFTWARE

I . I . The software for each relay. t ra n s du c e r and measurement device s h a l l be s u p p l i e d tor: -

(i) C o n f i g u r a t i o n o r the protection, measurement and transducer device.

(ii) Setting and p ro g r a m m i n g of a l l parameters for the relay. measurement and t ra n s d u c e r device/

(iii Download and a n a l y s i s o fr e l a y disturbance and fault record data.

1.2. Four CDs and lour memory sticks for each type of software shall be s u p p l i e d .

J.J . It s h a l l be possible to i n s t a l l each software in twenty (20) desktop/laptop computers w i t h o u t

requirement for a d d i t i o n a l li cen e s s. W her e a d d it on


i a l licenses arc re q uired , t e co
h st s h a ll be

c o ns deri e d to have been incl u de d in the b i d .

1 4
. T e h la te t s v er i
s o n o fe a c h s o ft w a re al t he 1 i 111 e o f s h i p m en t o f th c go ods s h a l l be s u pp l i ed .

APPENDIX .J: PC TO D E V I C E C O N N l!: C T I O N C A B L E

T we lv e ( 12) s et s or ea ch d i f f e re n t t ype o f PC to r ela y / m e sure


a m ent tr n du
/ a s cer de v ice

conn e ction cabl e an d a ll o th er inte g ra l a cc e ssories/tools t o ensure successful c o m m u n i c a t i o n

b tween
e th e La pt o p and t h e r e lay/d evi c e s hal l be s u p p l i e d .

A P P F. N l) ( X K : P A C K I N G A N D DELIVERY

K. l . P A C K I N C.

(i) Each i te m s hall b e p acked p ro perly o r p ro t e c t e d for ship m ent fr o


m t he pl c a e of m a n u f a c t u re to

th e K P L C st o re.

( ii) ( ii) Eac h c rat e o f p ac k g a e s h a l l contain a packin g li s t in a w at erpr o o f' e n ve lop e an d a c o py in

trip i l c a e
t s hall be fo rw rded a Lo KPL C prio r to d i s p a t c h . A l l ite m s or m a t e r i a l s h a ll b e c le a rl y

m ar k ed fo r e as y id e nt i Ji c at i o n a gai 11s1 the p a c k i n g I isl.

(ii ) i A l l ca e . packages, etc .. s h a l l he


s s c learly marked on the o u t s i d e to indicate the tota l we gh . ti t o

show where the we ght i is bearing an d the corre c t position or the s i n g s l a nd shall bear an

i d e n t i fi c a t i o n mark r e a t n g l i t hem to the appropriate s h i p p i n g documents.

(iv) A l l Acces ories necessary for m o u n t i n g the Relays. Instruments an


s d Contro l De v i c es on t o th e

panels, tor t e r m i n a t i o n s o f c ables or for l a b e l l i n g of LED i n d i c a t i o n s s h a l l be provided w i t h th e

R e lays. I n s t r u m e n t s and C o n t ro l Dev ces i .

Issued by: Head or Section, S t a n d a rd s Development A111huri1.c<I hy: Mead of D e p a rt m e n t , S t n n d n rt l s

Signed: Signed:

Onie: 2019-06-07 Ihle: 2019-06-07


TITLE: uoc. No. KP I /JCB/TSl'/021004

No.

'i
lsiHll' I
l ' R O T F. C T I V F. R E L /\ YS, CONTROL

-
-
DILVICES A N D INSTRUMENTS­
Revisinn Nu. J

Sl'ECIFICATION
Kenya Power Uaie or Issue 2019-06-07

l'ugc 47 ot'72

K.2. MARKING

The packaging s h a l l be marked as d e t a i l e d below.

(a) Consignee: T H E K E N Y A P O W E R & L I G J ! T I N G CO. LTD.

(b) Name of P roj e c t : P R O T E C T I V E REL/\ YS /\ N D CONTROL DC V I C E S A N D

I N S T R U M c N T S 1 : o R l'ROJl.:CTS

(c) C o n t ra c t N o . :

(cl) Port or destination:

e) I t e m Number, Package number and q u a n t i t y per p a c k a g e : - - - - - - - - - - - - - - -

1) Description olComc m s: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . • . . .

Net and gro�s weight, cubic 11icasL1re: . . . . . . . . . . . . . . • . . . . , .

A l ' l ' E N l > I X L: DELIVERY

L. I . The S u p p l i e r s h a l l d e l i v e r a l l th e Protect i o n and C o n t ru l items Lu K P L C b u l k Stores at lsiolo

Road, N a i r o b i .

L.2. Before acce pta nc e or t he de vi ce s, a l l th e re l ays, In s trum e n ts and Co n t rol acce ss o r i es s h a l l be

checked for any ph ys ic a l damage, for c om pl ete n ess mid correctness.

L.3. The S u p p l i e r shal I no Li ry K P LC at l east on e week in a d vance on his/her dare o 1· d e l i very or the

g o ods to the st o re .

L .4 . "I ogciher w i t h K P L C ' s rcprcscnuuivc the s u p p l i e r w i l l remove t he seals on t h e packages and

to ge ther insp ect t h e g ood s t o r a dhe r e nce lo specifications. 1<>1· com pl ete n ess and to en su re that

the goods ha v e 110 p h y s i c a l damage.

L.5. Incorrect, damaged or incomplete Relays, Instruments and Control Acce ss orie s as per t h e

Technical S p e c i f i c a u o n s and the accepted offer and the del iv e ry s hall not be accepted and t h e

supplier w i l l take away such goods .

L.6 A l l goods must be s u p p l i e d w i t h i n the s t i p u l a t e d t i m e as per the c o n t ra c t .

Al'l'ENUIX M: T E N D E R AWARD

The tender s h a l l be a w a r ded on the ba s is of the lowest e v aluated bidder for each item; i . e . , t h e Rela ys ,

Cont ro l de v ices. Tran s ducers and Me as urement I n s t ru m e n t s ,111d Measurement Uni t .

I s sued by: I-lead of Section, S r u r u l a r d s De v elopment Au t horized by: I-lead uf D e p a rt m e n t , Stunrlurds

Signed: Signed:

Dute: 2019-06-07 I o •• 1c: 2019-06-07


TITLE: Doc. No. KP 1 /3Cl3/TSP/02/004

1 PROTECTIVE REL/\ VS, C O N T R O L Issue No. J

- -
O E V ! C E S /\ N D I N S T R lJ M F: N T . -

SPECIFICATION
llc·vi:,inn Nn. 3

Kenya Power fht,· of lssuc 2019-06-07

Pngc t!R of 72

Protection relays and control devices offered and which has shown poor performance service i n the

system s h a l l be rejected.

For purposes of r e l i a b i l i t y M t h e Power System Protection Systems. Distil nee Relays Type I and I . i n e

Current Differential Relay Type I may be awarded to two d i f f e re n t m a n u f a c t u re rs each. The same case

a p p l i e s lo Distance Protection type II and Line u rre n t D i ff e re n ti a l Type II. This is however subject to

the relays meeting a l l the requirements o ft h e s p e c i f i c a t i o n s .

Warranty for a l l protection relay devices s h a l l be 5 years [rom th e l a t e of d eliv e r y o


t the stores.

Note I: The costfor hard cover Technical Ma1111als. Guide and Operation and Maintenance manual

shall he deemed IO be included in the 1111it cos, r?f' the respective Protection relay. Transducer.

Measurement device and control device. T111e/ve ( 12) hard copy original manualsfor each relay/device

type shall he supplied together with the relay/device.

Note 2: Each snpptier/monufacturer shall supply Twelve (12) l.aptop» [ar the lot that the

snpplicr/manufocntrer is offered 10 supply. The cost ofthe serial communication rahles shall he deemed

to he included in the hid price.

Note 3: Sn.fiware.for the Protection relays. Transducers and ['ower measurement units shall he supplied

as indicated elsewhere in these specifications. This software shall he supplied by the

supplier/manufacturerfor the items they are ,!ffered to supply. The cost of the sq/I ware shall he deemed

lo he included in the bid price.

T H I S S P A C E IS LEl' T 11 L A N K I N T E N T I O N A L L Y

Issued by: Head of Seel i o n , S t u n d a rt l s Development Authorized hy: I-lend of D ep a rt m e n t , S t a n d a rd s

Signed: Signed: ......-:-i_ I

,,

Onie: 2019-06-07 v Date: 2019-06-07


T IT I . E : l>ui.:. Nu.
KP I /3C U/TSl'/02/004

\'_ P R O T E C T I V I � IUi:LA YS, C O N T R O L Issuv No.


I

-
-
DEVICES ANO INSTRUMENTS-

Sl'ECI Fl C A T I O N
Rcvisiun Nu.
3

Kenya Power Dntc of Issue


2019-06-07

Pngc 49 of'72

A l ' l ' E N O I X N: T E C H N I C A L S C I- I E DU LES FOi{ RELA VS:

'!(, he [illed um/ signed by the Man11(i1':lill'e/' wit! submitted together wlth relevant copies of the

Mu1111/i1c1 urer 's cutulogues. brochures. ,/1·a111i 11:,:;.,·, technical d<111.1. sales records fo: previous five
Jleors . . four c1.1.,·1011u!r reference letters, details ofsuppliers · cupacity and experience; and copies of

complete type test certificates 0111/ test reportsfor lender evuluatton. all in English Language)

Tender No . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

CLAUSE Kl'LC R E Q U I R E M E N T S U I D D E R ' S OFFER

I Scope State

3 A p p l i c n b l c standard State

Rcu u i r c m e n t s

. I Service c o n d i t i o n s Stale

4.2 General re q u i re m e n t s

.2.1 Cornnliance tu c l i m a t i c aging c o n d i t i o n s as per IEC 60932 class 2 State

4.2.2 Withstand o fm at c ri a l x and f i n i s h e s lo h u m i d tropical c o n d i t i o n s Stale c o m n l i u n c e

4.2.3 Protective f i n i s h used for i n d o o r Darts State

4.2.4 P ro t e c t i o n 01· i ro n and steel against rus t i n g State


r-r

.2 5 Material steel screws State

.2.6 M a t e r i a l used tor i n s t ru m e n t screws Stale

.2.7 M a t e r i a l used fur springs State

.2.8 Material used fur gashts State

4.2.9 Operation voltage ranue State

The Rated DC supply voltage s h a l l be inscribed on the device State c o m n l i an c c

.3. I Materials

4.3.1. I Shall be new and o : ' the best qua I iiy and or· the class most s u i t a b l e !'or

working under the conditions specified State compliance

4 . 3 . I .2 Ability to withstand the v a ri a t i o n s or temperature and atmospheric

conditions Stale

4 . 3 . I .3. Shall be SU i table tor i n s t a l l a t i o n Ill relay panels inside control rooms State

w i t h o ut a i r c o n d i t i o n i n g .

�J.1.4 M i n im a l heat ucneraiion by the relays and o t h e r mcasurinu d e v i c e s Stme

4.3.2 I n s r ru m c n r s

4.J.2.1 lnsuurncnts to be fl u s h mounted, back connected and dust roof as per l � C

60051 Sta te

.J.2.2 S c a l e olarcs prov i de d S uite

4.3.1.3 D i m e ns i o n or Analogue rvoe e n cl o su r es S tate

lvnc of sca l e n ro v i d e d !Stal�

!VI ax j 111 LI Ill e r ror Stale

Iss u e d IJy: Head of Se c t i o n , S t u u d u rd s D c v cl opmcn l


-
A u t h u r i -. c d by: Head uf D e p a rt m e n t , S t a u d u ru s

Signed: Signed: .

'
��· · X J , u

Dute: 2019-06-07 I
D" le: 2U 19-06-07
f>oc. No.
TITLC: KP I /3Cl3/TSP/02/004

i
Issue No.
PROTF,CTIVE R E L /\ VS, CONTROL I

- D E V I C E S AND I N S T R U M E N T S -

SPECIFICATION
Rcvlxlnn Nn.
3

Kenya Power Onie of Issue 2019-06-07

Pngc .50 of72

C L A U S F, KPLC R E Q U I R E M E N T S 131 ODER'S OFFER

,],J, Protective Rclavs

.J.3. I Reluvs lo be flush mounted and Numeric desian as ner I FC 60255 State

.3.3.2 "': 0 1 1 1 1 n u n i c a t i o n nort tvne, H M ! l a c i l i t v State

.3.3.3 Rclav m a k i n u and break in!.( contacts ra t i n g State

4.3.3.4 Relay T r i p contacts shal I be capable o f i n t e rr u p t i n g wi thou I damage I he

Circuit Breaker Trip C o i l Current should the Circuit Breaker A u x i l i a r y

Cont ct a s fai I to oncn St te a comnliance

.3.3.5 R el ay D C voltaue ra tin g


St ate

.3.3.6 S w i t c h i n a canacitv State

4.3.J,5 A r e co n tacts of the p ro t ectiv e rela y s su ffi cien t for Circuit B re ak er T r i pp in g

·111d i n t e r l'l 1 1 1 ti ng the T i r p C urrent ? S t t a e

4.3.3.6 R el ay con ta c s sh
t a ll m ak e fi r m l y withou t. b ou n e c and t he re l ay m e c h an is m

sh a ll no t be a ffe c ed t bv P an e l v ib ra tion or e xt e rn a l m a c n e ti c fi elds St at e co mp li ance

4.3.3.7 Suita b l e for op e ra t i o n on the rate d D. C . Au x iliar y s upply w ithout use o f

d ro r m i n a re i tor
s s s or diodes S atet comnl lance

.4.3.8 Relav th er ma l r at in gs and m u l t i n l i c r Scuinas St a t e

4.4.3. 9 Supplied wi t h a l l acce ss orie s nec e ss ar y fo r mounting/installation i n panels

land r e rr n i n a t i n a a l l e x t e rn a l w i r i n g c o n n ec tio n s. State eo11111I iancc

4.4.3. I O P l u g - i n a u x i l i a r y rela y s for DrN ra i l m o u n t i n g s h a l l be supplied com p l e te

with the bases St,1te

.4. I Ratinns f r Protection Relays and Control Devices:


o

(i) Secondar y ra ing o f relay CTs


t
State

(ii) Secondary Volrauc R a t i n g orVF S a e


t t

(iii) D C a u x i l i a rv ra t i n a State

iv) Relay t ri n i n d i c a t i o n State

.4.2 D i s ta n c e Prot ec tion Rclav Tv11c I

4.4.2. I Shall p rovide last and h i g h l y dependable s e lective lauh clearance on bo h t State c o m p i a n c e l

o v erhead and undcruround feeders

4.4.2.2 S h a l l be s u i t a b l e for appli c ation in a s u b s t a t i o n w i th I & 1/2 circui t b reaker S l a t e cornpl iance

co n fi c, u ra t ion

Manufacturer's Name State

Tvoe or Desiunation name of Rela y State

Cornplcre order number for offered R e l a y State

4.4.2.3 Experience i n m a n u f a c t u re or D istan c e P r o tection R e l a y State

Experience i n Manufacture o r Diuital D i st ance R c a v l Stale

.4.2.4 fl' t l i l i e s and Reuions/contincnts where the rclav is alreadv in


i servi e c State

4.4.2.5 Has relav failed in s ervi c e or mal-oneraled on the Kenyan Po w er System? State

4.4.2.6 Rclav Warrantv Period i n vears S tat e

4.4.2.7 Numb e r o fa n a l o u u e current i n p u t c h a n n e l s S tale

Issue d hy: Henri of Section, Standards Development Authorized hy: Head of Departm e n , Standards
t

I
Signed: Sig n ed :
.---r.:--
� ..l\ J ' /
�-

Dill e: 2019-06-07 r Dat e: 211 J 9-0C.-07


TITLE: Doi.:. Nu.
KP I /3CB/TSP/02/004

1
Issue No.
l'ROTECTI V E R E L A YS, CONTROL I

- -
D E V I C E S AND INSTRUMENTS-

SPl,CIFICATION
Revisiun Nu.
3

Kenya Power D:1h.• of Issue


2019-06-07

P11gi: 51 uf72

CLAUSE Kl'LC R E Q U I R E M E N T S l.l l D D E R ' S OFFER

N u m b e r or voltage i u n u t c h a n n e l s State

.4.2.8 N u m e r i c a l D c s i u r : and ernplov comolete d i u i t a l siunal processina State comoliancc

4.4.2.9 S h a l l be suitable 1()1' F l u s h 111m111tinu 011 the protection panel. State comolinnce

4.4.2.10 I-l <1 ve Fu! I Scheme distance protection. with parallel calculation and State compliance

m o n i t o r i n g o fa l l the l au l t loons

4.4.2.11 I-hive selective s i n u l c chase and/or three chase t ri u u i n u Louie State c o m p l i a n c e

1.4.2.12 Starting criteria State

.4.2.13 Number of phase distance nrotection zones Stale

4.4.2.14 Number or around d i s t a n c e protection zones State

.4.2.15 Distance protection zone protection State

.4.2.16 O o e ra r i n u t i m e for Distance Zone I State

.4.2.17 C o m m u n i c a t i o n Aided Schemes lor Distance Protection State

.4.2.18 P ro v i s i o n of l .oad Encroachrneru D i s c ri m i n a t i o n Feature State

.4.2.19 P ro v i s i o n o f P ara l l e l l i n e comoensation f e a t ure State

.4.2.20 M c a s uri n u vohuue 111oni1ori110 FL1si: f a i l u re suncrvision Louie Stale

4.4.2.21 S h a l l be blocked from operating in the event of fa i l u r e or the measuring State compliance

voltage or when the a u x i l i a r y switch of the Voltage uu n s f o rr n c r secondary

M C IJ trios

.4.2.22 Weak em! in-Iced Protection/ Echo and/or t r i o feature State

4.4.2.23 Current Reversal Guard Feature State

,!:1 . 2 24 Power S w i n u detection l c u t u re State

4.4.2.25 0111 of step protection State

.4.2.26 Voltauc Memory Feature· State

.4.2.27 Au tom at ic S w i t c h on to F a u l t Featurc(SOTF) State

4.4.2.28 COi 11111 u nicat ion Aided schemes lor D i re c t i o n a l Emth F a u l t ( D l2 F ) State

Protection

4.4.2.29 Back-,11J Ovcrcurreru mid Earth f a u l t protection function Stme

.4.2.JO S t u b Bus ovcrcurrcnt protection function State

.4.2.31 Under lreuucncv anti rate of chunue or frequency Protection function State

4.4.2.32 Overvoltaae nrctection St a t e

.4.2.33 Circuit Breaker F a i l ure P rot e c t ion State

.4.2.34 Circuit B reaker Co n t a ct wear feature Stat e

.4.2.35 Br ok e n Con d u c t o r detec tion for Alarm ouruoscs St at e

.4. 2.36 A ui o -rc c l o s c function St a tc

.4.2.37 S v n c h ro - c h e c k Function St a l e

�.4._ 38 Fa u It I .ocator with �1u1un1,1Li1.: Distance to Fau lt indi c ati o n o n the LCD

s c re e n i n km. State

.4.2.39 A c c u ra c v of D is t a nc e to fa u l t location Stalt!

4.4.2.4 0 In l o rm at i o n n ro v i d e d with Iau I t l o c a l io n Stu,�

Issued by: N e a d of S e c t i o n , S t u n d a rt l s D e v c l u p m c u t A u t h o ri ze d by: Head of D c p u ru n e u t , S u u n l u rd s

Signed: Signed:
q ,----
�-·_
Date: 20 I ?-06-07 lJ u t c : 2019-06-07
TITLE: Onr. No.
K P I /JCP./TSP/02/004

\'_ P R O T F. C T I V E R E L A Y S , CONTROL Issue No.


I

-
-
nnviczs A N D INSTRUMENTS-

S P F. C l F I C A T I O N
Rc•vii;io,, Nu.
,
J

Kenya Power narc nf Issue


2019-06-07

Page 52 o f 7 2

CLAUSE KPLC R E O U I R E M E N T S B I D D E R ' S OFFER

.4.2.41 Fault d e t a i l s to disnlav on the LCD State

.4.2.42 Canacitv or disturbance recorder Stale

4.4.2.43 Canaci tv o I' storage or event records State

4.4.2.44 Capacity o r storage or t r i p records State

�.4.2.45 Relay c onfi gu rati on & parameter settings, Event & F a u l t records ancl LF:D

status arc retained upon loss or relay DC power s u p p l y Stale

.4.2.46 Power svstem instantaneous parameters displayed on the LCD Stale

4.4.2.4 7 Number of binary inputs State

'1.4.2.48 Number of binary o u t p u t s State

.4.2.49 S t a b i l i t y against s w i t c h i n g inrush currents and reverse faults State

.4.2.50 Clear faulted phase i n d i c a t i o n State

.4.2.51 Clear f a u l t i d e n t i f i c a t i o n even for boundary c o n d i t i o n s State

'.4.2.52 IN umber or LEDs State

.4.2.53 C o m m u n i c a t i o n orotocols State

.4.2.54 Relay terminals type and size State

.4.2.55 C o m m u n i c a t i o n norts nrovided State

4.4.2.56 Software for relay configuration and parameter setting and IULII( data

A n a l y s i s offered for use with the relay. Software to be offered in CD form State

.4.2.57 Relay Lo Lanton connection cables offered State

.4.2.58 Relay c o n fi g u r a t i o n duri nu FAT Stale c o m p l i a n c e

.4.3 Distant Protection Rclav Tvne I I

Manufacturer's Name State

Ivoc or Designation name of R e l a y State

Comnlctc order number for offered Relay State

4.4.3. I Experience in ma nufacture or Distance P ro t e c t i o n Relay State

Experience in Manufacture o f D i g i t a l Distance R e l a y State

.4.3.2 U t i l i t i e s and Reuions/contincnts where the relay is already in service Stale

.4.3.3 I las relay failed in service or mal-oneratcd on the Kenyan Power System? State

.4.3.4 Relay Warranty Period i n vears State

4.4.3.5 A n n l i c at i o n or the relay .State

4.4.J.6 s h a l l a ut o m a t i c a l l y d i s p l a y the distance to fault i n km n I he LCD screen

L111on fault i n t e rrup t i o n State

.4.3.7 A b i l i t y lo Access the distance to fault d e t a i l s u s i n g the Keypad or a laptop State

4.4.J.8 Number of analouuc current i n p u t channels State

Number o fa n a l o u u e Voltage i n p u t channels Stale

4.4.3.9 S u i t a b i l i t v for flush m o u n t i n g on the protection panel State

4.4.3. I O Numeric/Digital Design with complete digital pr icessing or measured

values State

.4.3. 1 1 Ful I d i s ta nee Protection Scheme, i . e .. 11011-swi tchcd State


"
'

Issued by: Head of Section, S ta n d a rd s Development Authorized hy: Head of D e p a r t m e n t , S t a n d n rds

Siguccl: Signed:
,.. �:':-l ') ,;;: ) �.
v
-
Date: 2019-06-07 D a t e : 2019-06-07
TITLE: Dul', No.
KI' 1 /3CO/TSl'/02/004

't P R O T E: C T I V IL R E L A Y S , C O N T R O L Issue No.


I

- -
O E V I C £ S A N D INSTIHJIVIENTS- Revisiun Nu.
3
SPECIFICATION
Kenya Power D:1ll' of Issue
2019-06-07
f--

l'agc 5) ot'72

CLAUS[ KPLC R E O U I R IL M £ N T S BIUDEH'S OFFER

4.4.3.12 Under Impedance S t a r t i n g criteria. Other s t a rt i n g criteria in a d d i t i o n to the

under imocdance s t a rt i n g are acceptable State

4.43.13 I'hree phase t r i p p i n g Criteria, since it s h a l l be used on s u b - t ra n s m i s s i o n

und d i s t r i b u t i o n l i n e s Stale

4.4.3.14 Four 7.UllCS of Phase distance protect ion (for Phase-phase l u ul t s ) with

selectable Mho and Quadri l a r e ru l elm racteri st i cs. Parumcters (resistive

reach, reactive reach and t i m e delay) for each Zone indcnenderulv set State

4.4.3.15 [l'oLLr zones of Ground distance protection, (Ior phase- Ground/Phase-Earth

F a u l t s ) w i t h s e l e c t a b l e Mho and Quadrilateral characteristics with residual

c u rre n t c o m p e n s a t i o n . Parumeters ( r e s i s t i v e reach, reactive reach and t i m e

delay) Ior each Lone s h a l l be i n d e p e n d e n t l y set State

4.4.3.16 Distance Protection Zones dir ec t io n s h a l l be i n d e p e n d e n t l y set as forward

or reverse or n o n - d i re c t i o n Stute

cl . 4 . J . 1 7 M i n i m u m on e ra i i n u t i m e s h a l l not exceed 40rns State

4.4.3.18 I 'he d i s ta nee Relay shall have Comm 1111 icut ion channel Aided Scheme

logic for the distance ororection w i t h at least the lo l l o w i n u schemes Stale

( i) P e r m i s s i v e Under-reach Transfer scheme State

(ii) P e r m i s s i v e Overreach T ra n s f e r scheme and


State

(iii) Direct T ra n s f e r T r i p p i n g Scheme State

.4.3.19 Load encroachment D i s c ri m i n at i o n Feature State

.4.3.20 Fuse I a i l ure s u n e rv i s i o n Lollie State

.4.3.21 V o l i a u e Memorv Feature State

4.4.3.22 A u t o m at i c Switch on to l'a u h l'caturc(SOTF), enabled when the l i n e is de-

energised and only active for a set time delay alter the l i n e c i r c u i t breaker

is closed Stale

4 . 4 . 3 23 Di reel ional Earth l' a u l t P ro t e c t i o n , with comm u n i cut ion channel aided

scheme as f o l l o w s Stute

(i) D i r e c t i o n a l Comparison Scheme


State

(ii) B l o c k i n g Scheme
S tare

14 . 4 . 3 . 2 4 Back lip three phase o v c rc urre r u & Earth fault protection, with the

I o l l o w i n u protection [ u n c t i o n s Stale

( i) High set element tor l'hase and Earth fau] t o v c rc urre n t with

selectable d e f i n i t e t i m e d e l ay State

(ii) l.ow set element for Phase .i ml Earth Iau I t OVCl'CLll'J'CLll with

inverse c urre n t - t i m e characteristics as per !EC 60255 State

"1.4.3.25 S e n s i t i v e Earth Fault Protection Swte

.4.3.26 S t u b BL1s overcurrcnt o roi cc tion State

.4.3.27 C i r c u i t Breaker Failure P ro t e c t i o n State

lssued by: l Ieatl of Section, Standanls Dcveloptuuut A u t h o r i z e d by: Head of Dcp:11·t111c11t, Stantlanls

Signed:
�-:) Signed:
< ?) 6-·

JI
Duk: 2019-06-07 D a t e : 2UJ 9-U6-07
T I T l , F; ; Dnc. Nn.
KP I /3CB/TSP/02/004

l
Issue No.
PROTIJ:CTIVI� R E L A VS, C O N T R O L I

- -
DEVI ES A N D I N S T R U M E N T S -

SPECIFICATION
llc,•isio11 Nn.
3

Kenya Power Dntc or l.��IIC


2019-06-07

Pngc 54 or 72

CLAUSE K P L C R E Q U I R F: M E N T S B I D D F: R ' S O F F E R

.4.3.28 Under-freouencv and rate of change or l re q u e n c v protection Stale

.4.3.29 Overvoltanc protection State

4.4.3.30 Broken conductor detection for A l a rm purposes State

4.4.3.31 Aulo-reclosc fu n c t i o n for three phases. s u i t a b l e for high speed and delayed

a u t o - rc c l o s c , f'ault types and Zones that initiate auto-rcclosc to be

selectively enabled Stille

•.4.3.32 !'he A utn-rcc I osc scheme will be selectable as enabled or disabled

)referablv on the relay LCD screen Sta t e

.4.J.33 O n l y the selected fu nctions i n t h e di s t a n c e r el ay shal] initiate a ut o - re clo s c S tat e

�.4.3.34 T he a u t o - re c l o s c fun ction s h a l l be c a p a b le or tw o a u t o - rc c l o s c shots , w ith

s e p a ra t e l y set dead i
t m es Stme

:4 .4.3 .35 Fa ul t L o cat or ; w ti h a utomatic d i s p l a y on t he R elay l�CD Screen or t he

di s t a nce In fault in t er m s o f L inc p ercen t a ge or d i s t a n c e in km. The l a st

i
d sta n c e to fau lt s h a l l a lw a y s be di s p l a y ed on the sc reen State

14 .4.3.36 T he a c c u ra c y o f Di s t a nce to fa u l t location s hall be :1.2% as a i i


1 1 1 n 1 11 1 1 1 1 1 S t at e

4 .4.3.37 T he fo ll o w in g a dditional infor m a t i o n s h a l l be p rovi d ed with fault locatio n State

(i) The short-ci rcu i l loop which was used to determine the faul I

rcactance
Stat e

(ii) The reactance X Der nhasc in O h m s Primary and seconda ry State

(iii) The reactance R per phase in Ohms Primary and secondary State

(iv) The distance to fault in p ercentage and km or l i n e lenath State

4.4.3.38 A b i l i t y to d i s p l a y F ault d e t a i l s on the LCD Screen such as Fault- L oop or

Faulty phases, the Zon e , and the Relay Operate t i m e State

cl.4.3 . 3 9 Internal Disturbance recorder w ith capacity lo record ei g ht anal o gue and

twelve d i g i t a l signals. The rela y s hall have apacity to store th e latest,

twentv (20), disturbance records State

4.4.3.40 Storaae or at l e ast Fi fly (50) event records State

4.4.3.41 Storage of at least twent y (20) t rip records. Th e following fault d a t a w ill

be a vailable State

(i) Mag ni t u d e a nd p hase an g le o f ph ase curren t s an d l


vo tag e s before

t he Fa ult State

( ii) M a g ni t ude and p hase a n g l e of phase c u rrent s an d vol t a g es d u r i n g

t he fau lt S t a te

( iii) The s e q u e n c e o f eve nt s of d igital signals, s t a rt a nd op e ra t e ( Trip)

s i g n a l s inv o lved i n fau l t d et ec t i n n an d c l e a ra nce . Th e even ts s hall

me t ime t a u a ed to I Oms lev e l State

4 .4. 3 .42 E ve n t s an d fa u l t records s hall no t be erased even when t he aux iliary DC

supply is sw itch e d oil St a te

Issued by: Ilcad of Section, S t a n d a rd s Development Authru-izcd by: Head ol' Department, S t a n d a r d s

Sigucd: ( ( < , _, {..., : /') Si!(llCcl; /_


-i .......--::::::
,

Da tc: 20 19-06-07 I D a t e : 201?-06-07


TITLI�: Dol'. Nu.
Kl' I /3 13/TS P/02/004

\'_ P R O T E C T I V E Rl!:LA YS, C O N T R O L Issue No.


I

- UEVICES AND INSTRUMENTS-

SPECIFICATION
Rc\lisiv11 Nu.
3

Kenya Power Dale of Issue


2019-06-07

l'ugc 55 vf72

CLAUSE Kl'LC R l!: O U J R £ M E N T S LI I D D E H ' S OFFER

4.4.3.43 M e t e ri n g and d i s p l a y on the LCD screen of the f o l l o w i n g Power system

instantaneous p a ra m e t e rs including
Slalc

(i) Vohauc State

(ii) Load current Slate

(iii) A c t i v e Power ( l r n p o rtf + ) or Export (-) Slate

(i vJ Reactive Powerf l m p o rt (+) or Export {-) State

Iv) Aonurent Power State

(vi) Power Factor and State

(\Iii) Frequency State

'.4.3.44 M i n i m u m ten ( 1 0 ) Binary inputs Slate

.4.3.45 M i n i m u m twelve ( 1 2 ) B i n a ry outputs Slate

.4.3.46 S t a b i l i t y al.(ainst s w i t c h i n ).( inrush currents and reverse laults State

.4.3.47 Clear f a u l t e d phase i n d i c u t i o n Stat..:

.43.48 Clear Ca u l ! i d e n t i f i c a t i o n even for boundary c o n d i t i o n s Stale

4.4.3.49 /\L least twelve ( 1 2 ) LEDs for i n d i c a t i o n of the following; - Relay trip,

Phase L I , Phase L2, Phase I J. Zone I , Zone 2, Zone 3, DEF, C h a n n e l

aided t ri p , SOTF, etc. Slate

�.4.J.50 Relay h e a l t h y L.ED Slate

�.4.3.51 Relay sel l - s u p e rv i s i o u , w i t h LED for h e a l t h y status indicatiorugrccn) and

Error i n d i c a t i o n (reel) and watchdog contact State

i.4.3.52 Protocol a p p l i c a b l e : !EC 6 1 8 5 0 - 8 - 1 . Appropriate c o m m u n i c a t i o n pons 10

be provided on the relay State

4.4.J.53 Relay Term i nals-sha 1 1 be SCr<.'W type terminals large enough lo

accommodate ut least 2 x 2 . 5 r n m 2 cable and shall be located ,I! the back or

the relay Sw1e

4.4.3.54 Front S e r i a l RS232 or U S IJ or Optical or Ethernet Port shall be provided State

for relay configuration and parameter s e l l i n g and download or Data u s i n g

u Lamoo Computer

4.4.J.55 Software f o r P ro g ra m m i n g t h e c o n f l g u ra t i o n and Relay S e t t i n g s and a l s o shall be provided

download in!.( and a n a l y s i n g the Relay Data

.4.3.56 Relay lo l . a o i o n connection cable State

4.43.57 Relay c o n f i g ura t i o n lo be carried out by the m u n ul a c t urc r shall at the

Faclory to s u i t i n s t a l l a t i o n in e x i s t i n g transmission substations in KPLC

Network. E x i s t i n g P ro t e c t i o n mid control drawings Ior the substations shall

be handed over lo the m a n ufa c t ure r/ s u p p l i e r lor relay c o n f i g ura t i o n .

l'hc 1:ATs shall be carried out once the relays have been configured.

Correct fu n c t i o n a l i t y or a l l relay Prot ection and Control Functions sh<1II

checked during the FATS Slate

Issued by: I-Ica,I of S c c t i u n , S t a n d a rd s Development Authorized by: Head of Dcparuncnt, S taud ar ds

Signed: Signed:
b•
C J
�)
Dale: 2019-06-07 Dale: 2019-06-07
TITLE: Doc, No.
KP i /3Cl3!rSr/02/004

\:_ l'ROTF: TIVE R E L A VS, C O N T R O L


Issue No.
I

-
-
DEVICES AND INSTRUMENTS-

S P E C I Fl C A T I O N
Revision No.
3

Kenya Power DAie or Issue


2019-06-07
--
l'agc Sfi of 72

CLAUSE l(f'LC REQUIREMl�NTS RIDDER ' S O F F E R

>.4.4 Biased Differential Protection Relay for a Two or Three W i n d i n g Power

T ra n s f o rm e r State

Manufacturer's Na111e State

Tvne or Designation name or A u x i l i a r y Relav State

Complete order number for offered A u x i l i a rv Relav State

Man II foci II re r's Ex pericncc a n d Prod uct Q u a l l flea tion Stale

4.4.4.1 1 he Relay manufacturer s h a l l have a m i n i m u m experience of 25 years i n

the manufacture or Biased Differential Protection relays, 1 5 years of w h i c h

s h a l l be i n the manufacture ofNurnerical Distance Protection relays State

4.4.4.2 The Relay type o ff e re d must have been in Service and given reliable

service for a m inimum p erio d o f 8 years, i n a t lea s t two utilities. in ea ch of

the fo llowin g rc u i o n s State

a. Europe State

b . N orth Ame rica S ta t e

c. A fr ic a and St a te

d. Asia S t a te

4 .4.4 3 R elays th a t have failed in s ervice or mal-operated on th e K e nya n Po wer

Svstern s h a l l not be a ccepted S t a te

".4.4.4 W ar ra n t y F or Off ered relay s hall be F iv e ( 5) y ears from t he d a t e of r ela y

d c l i v c rv to the KP L C stor e Stat e

F u n c t i o n s and Features State

4 .4 . 4 . 5 Suitable f or p ro t ec t ion of a two or three w in d i ng p ower t ra n s f o rm e r, with

·1 pow er r a t in g o r up to 90 M V A , wi th I-IV w i n d i n g rated u p lo 245kV.

Speci e
fi req u i rcmcnts w ill be st ated Ill t he Scope of s u p p l y or Pric e

s c h e d u les S ta t e

.4 .4.6 Rclav m u s t be o f Num eric a l d e s iu n State

.4.4. 7 Flush moununa d esign State

4.4.4. 8 Pick u p s e t t i n g range, for I D I F F > 0 . 1 to 1 . 0 x rated current, as a m i n i m u m State

. 4. 4 .9 P i c k u p on switch-on (factor of J l) I F F >) 1 . 0 to 2 . 0 S t ate

4 . 4 . 4 . 1 () High-set Element (I DIFF>>) w i t h a s e t t i n g range o f 1 . 0 to 20 . 0 x rared

current State

4.4.4. I I In d e p en d ent d e fi n i t e l i m e delay selling for I D I F F > and J'nr J f) I F P > > or

0 . 00 lo 3 0 . 0 0 se c onds as a 111ini111u111 S t ate


1
4.4.4.12 M a g n e t i z i n g current inrush restrain t feature, u s i n g 2'" harmoni c restraint

and /or zero crossinu on the s i n e wave State

. 4.4.13 S e u i n u ranee o f 12 f n/l f n o f I O to 50% as a 111i11i111u111 State

4.4.4.14 Com p ensation for zero sequence current s that may a p p ear on o n l y one

w i n d i n u o r the Dower t ra n s f o rm e r S tat e

Issued by: Head of Section, Staurlards Development A u t h o ri z e d hy: Head of D e p a rt m e n t , S t a n d a r d s

Signed: I
Signed:
(" -, � - �
r-::::::i
'
I
na1·c: 2019-06-07 D a t e : 2019-06-117
TITLE: IJOl'. Nt).
KP I /3 C BITS I' /02/004

t
-
P R O T E C T I V E RELAYS, CONTROL

D F: V I C E S A N O I N S T R U M E N T S -

Issue Nu.
I

- S P F. C l Fl C A T I O N
llcvi.sio11 No.
3

Kenya Power Dalt: of Issue


2019-06-07

l'uit.i.: 57 ut'72

CLAUSE KPLC R E Q U l l { E M E N T S UIODER'S OFFER


4.4.4.15 Mcasurcmcru ,111(1 indication 011 the LCD screen, or phase - H V & L V

k;u1Tc111s and relay d i lf c rc n t i a l and bias currents Sime

�A.4 16 Storaue or at least Five (5) F a u l t records and Ten ( I OJ Event records state

�.4.4.17 Events and fa u l t records shall not be erased even when the a u x i l i a ry DC con II rrn

s u p p l y is switched o f f

.4.4.18 1'11<.: Fault flags s h o u l d be v i s i b l e on the LCD screen, and provide details

o ft h e phases t h a t have operated and the f o u l t current values. State

4.4.4.19 O v e r - f l u x i n g protection [u n c t i o n w i t h al least two stages ofalarm und t r i p

functions
Stutc
5111
4.4.4.20 h a rm o n i c rcstra i 111 I e a t ure on the d i ff e re n t i a l Element to prevent

unnecessary t r i p p i n � due to CT s a tura tion or transformer o v e r- e x c i t a t i o n . State

4.4.4.21 Over-excitation P ro t e c t i o n w i t h both a l a r m und trip elements State


i.4.422 S t a b i l i z e d against transient and steady-state l a u l t currents caused q;. by

ovcr-cxciuuion or transformers, using l i f'l h h arm o n i c . State

4.4.4.23 Insensitive a g a i n s t DC o ff s e t currents and c u rre n t t ra n s f o r m e r s at urat i o n ,


State

.4.4.24 I l i u h s t a b i l i t y also for d i ff e re n t current transformer s at u ra t i o n Stale

.4.4.25 High-speed i n s t a n t a n e o us t r i p on hiuh-curreut transformer l u u l r s .


State

4.4.4.26 I ndc pcnden I ur the cond i Ii tin in g or t he s tar po i nt(s) or t he p ow e r

t ra n s f o r m er.
State

4.4.4.27 I ligh earth-fault sensitivity by d e t e c t ion or th e sta r poin t c u rr e n t or an

e a rt h e d t ru n s fo rr n e r w i n d i n g Stat e

.4.4.28 In t e g ra t e d m at c h i n g of t he t ra ns fo r m er c o nn e c t i o n grou p State

4.4.4.29 lruegrutcd matching of t he uu n s f o rr m u i o n r at io including differ e n t rated

cL11Te11ts or th e tran s fo r me r windings


S t a te

t4.4.JO Du a l Bias charactcrisucs with \WO s lopes to ensure relay stability for

he a v y t hrou g h f au l t s . The s t a rt mid end o ft h e two s l opes s h a l l be scuablc .

in terms of t he rated c urrent. St at e

.4.4.31 U n b a lanced Load P ro r e c i i o n S tate

.4.4.32 lh c rm a l O v e rl o u d P ro t e c t i o n
Staie

4.4.4.33 Baek up O v c rc urrc n t a nd E a rt h Fa L i l t I ro r c c t i o n fo r flV and/or L V

winding State

4 .4.4.34 l'he fo llowing m e a s u r e m e n t s s h a l l be a v u i l ab l e in the relay: State

Mag nitudes ,111d phase a n g le s of th e p h ase c u rr e n t s fo r the th r ee phases on

the I-I V s ide o rT ra n s f o rm e r


S tate

Mag ni t u de s ,111d p h ase a ngles ofthe ph as e I


CL ITClllS fu r t he th r ee phases o n

the L V sid e o fTrn n s fo rm e r


State

M a g ni t u de or d i ffc rc n r i u l CU ITC I ll and rc s t ru i n i u g C:UITi:11\ lor the three


)bases Stu le

lssued by: I-lend of Section, Standards Devclopmeut Authorized by: Heud of UqJH1·t111cnt, Staudurds

Sigurd: Signed:
c ( (
11 )
Lu<'.
-...
.
l. ,,
c J e.-
Date: 201 9- 06-(17 r Date: 2019-06-07
Doc. No.
TITLE: K r I /3C 13/TS P/02/004

1 l'ROTF.CTIVE RELA VS, CONTROL Issue No.


I

- -
OE VICES A N O I N S T R U M E N T S -

S l ' E C I Fl CAT ION


Revision No.
3

Kenya Power natc or 1�s11C!


2019-06-07

l'agc 5R nf 72

CLAUSE K P L C R E O lJ I R E M E N T S R I D D E R 'S O F V E R

4.4.4.35 n,c disturbance recorder function shall have a capacity for eight (8)

analogu · and twelve ( 1 2 ) d i g i t a l s i g n a l s . The last lour disturbance records

w i l l be a v a i l a b l e in the rc l a v , State

.4.4.36 Reel L . E . D to indicate that the relav has onerated/issued t r i p c o m m a n d �late

4.4.4.3 7 Relay Self diagnostic, w i t h LED to i n d i c a t e Relay f a i l u r e and a contact f o r

remote i n d i c a t i o n of rclav f a i l u r e status St.ite

4.4.4.38 The relay s h a l l have at least eight (8) LF.Ds for trip 1111c\ alarms and at least

four (4) binary inputs. Stale

4.4.4.39 lhe relay s h a l l have at least our (4) outputs relays w i t h n o r m a l l y open

contacts l<)r circuit breaker tripping and alarm a n n u n c i a t i o n . Two pairs o f

contacts s h a l l be rated lo directly cneruisc the c i r c u i t breaker t ri n n i n u c o i l . �tale

4.4.4.40 1 he relay s h a l l have the a b i l i t y to select output contacts to latched or nnn-

latched s t a t u s and the LCD screen where the settings and measurands can

be read. State

4.4.4.41 l'hc relay s h a l l have keypad for m a n u a l p ro gr am ming of s e t t i n g s and data

access. State

4.4.4.42 1 he relay s h a l l have front serial R S 2 3 2 or US\3 or Ethernet Port for Relay

com mun ica I i Oil with a laptop computer for relay con figuration and

parameter settings and download 01· fault records. events records and

disturbance record. State

4.4.4.43 Relay term i na ls-shal I be S TeW type terminals large enough to

accommodate at least 2x2m1112 cable and s h a l l be located at the back or

he relav. State

4.4.4.44 Four (4) sets of i n s t a l l a t i o n . c o m m i s s i o n i n g . operation and maintenance

m a n u a l s s h a l l be provided. State

4.4.4.45
Relay to Laptop connection cable s h a l l be provided.
State

4.4.4.46 Software for relay c o n fi g u ra t i o n and settings programming using Laptop

computer s h a l l be n ro v i d e d , State

.4.5. Restricted Earth F a u l t Relay State

Manufacturer's Name Stale

[vne or D e s i un a t i o n m1111e of A u x i l i a r y Rclav State

Cornnlctc order n u m b e r for offered A u x i l i a rv Relav State

M a u u fa c t u rc rt s F:x,1cric11cc und Product Ouulification

4.4.5.1 M i n i m u m o f ' 2 5 years i n the manufacture o f Restricted Earth Fault Relays,

I O years of which shal I be in the manufacture o f numerical Restricted Earth

F a u l t relays State

4.4.5.2 The relay type offered m u s t have been i n service and given r e l i a b l e service

for a m i n i m u m period or 8 years. in at l.east two u t i l i t i e s . i n each of the

followinu re u i o n s State

Issued hy: Head of Section, S t a n d a r d s Development A u t h o ri z e d by: Hearl of D ep a rt m e n t , S t n n d a rd s

Signed: Signed: (.,-


� ,) c: i)
DMc: 2019-06-07 DMc: 2019-06-07
TITLE: lluc. Nu. KPI/JCB/TSP/02/004

l
-
l ' R O T F. C T I V E R E L A Y S , CONTROL

DEVICES ANO INSTL{UMENTS-


Issue No.

3
I

-
Rcvlslun Nu.

S l ' i£ C I F L C A T I O N
Kenya Power Date uf Issue 2019-06-07

Pngc 59 or 72

CLAUSE Kl'LC R E Q U I R E M E N T S B I D D E R ' S OFFER

a. Europe State

b. North America State

c. A Irica and Stale

d. Asia Stute

4.4.5.3 Relays that have failed in service or ma I-operated on the Kenyan Power

Svsiern s h a l l not be accepted. State

4.4.5.4 Warranty lor offered relay s h a l l be Jive (5) ycurs from the date o f relay

del i verv to KP LC store State

Functious and F c u t u re s Slate

.4.5.5 S h a l l be used lor p ro t e c t i o n o lo n e w i n d i r u; ofa power t ra n s fo r m e r State

4.4.5.6 S h a l l have the l o l l o w i r u; fu n c t i o n s and fe a t u re s : State

R e l a y sh al I be o 1· N u m e ri c a l . static type or E l e c t ro - M e c h a n i c a l rvne. State

(i) The Relay shall operate on high impedance p r i n c i p l e . State

(ii) The relay s h a l l be of n u m e r i c de s i u n . State

(iii) The relay s hu l l be s u i t ab l e f o r llush m o u n t i n g on panel [ re n t . State

4.4.5. 7 Relay s h a l l be ot'un independent re l a y and not a function in the d i ff e re n t i a l

relay S1a1e

4.4.5.8 Relay shall reject harmonics produced by the system p a rt i c ul a rl y third

harmonics state

4.4.5.9 S t a b i l i s i n g resistor and voltage dependent resistor ( m e t ro s i l ) or suitable

rating s h a l l be o f f e re d w i t h the Relay based on m a x i m u m through F a u l l of

3 lkA.
State

4.4.5.10 The relay current s e l l i n g range shall be 0 . 0 5 - 0.8 x rated current ( I n ) as a

111ini111un1 and an op e ra t i n g t i m e < 2 5 m s at 5 t i m e s the s e u i n a , State

4.4.5.11 l'he relay s h a l l have lour (4) LliDs Ior relay status i n d i c a t i o n and Jar t r i p

and alarms annunciation as a m i n i m u m and two (2) binary inputs as a

Ill I 111 Ill U rn State

4.4.5.12 1 he relay shall have four (4) B i n a ry O u t p ut s as a m i n i m u m with LCD

screen where the seuinus and measurands can be read Swte

4.4.5. 1 3 The r e l a y ' s R E F operate c urre n t s h a l l be displayed on the LCD screen and

kevoad for manual programming \li'S<:llings and data access State

4.4.5.14 l'hc relay shall have serial RS 23 2, SB or Ethernet Port for relay

c o n fl g ura u o » and p ro g ra m m i n g ur p a ra m e t e r settings and data download

using a la1JIOD c o r n n u r e r. State

4.4.5.15 l'he re l a y s h a l l have an event recorder with capacity LO store the last J·iJly

(50) events State

14 . ' 1 . 5 . I 6 l'hc relay s h a l l have fault recorder w i t h capacity 10 store the last ten ( I 0)

foult records Slate

Issued by: Head of Section, S t a n d a rd s Development Anlhurizcd by: Head of D e p u rt m e u t , S t a u d u rd s

l),olc: 20 t 9-06-07
- ' v Dale: 2019-06-07
Doc. No.
TITLE: KP I /3Cl3/TSP/02/004

\:_ PROTECTIVE R E L A VS, C O N T R O L issue No.


I

,
-
-
D E V I C E S A N D I N S T R l J M F. N T S - Revision No. .,

SPECIFICATION
Kenya Power Dute of Issue
2019-06-07

I'agc 60 oJ' 72

CLAUSE K P L C R E Q U I R I<: M E N T S Ill D D E R 'S O F F E R

4.4.5.17 he relay s h a l l have a disturbance record w i t h capa ity 10 store the last

four (4) disturbance records State

4.4.5.18 'he relay t e rm i n a l s shall be screw type terminals large enough lo

accommodate .ii least 4 rnm2 cable and shal I be localed at the back of the

rel av S1a1e

4.4.5.19 Stabilizing Resistor

Each R E F relay s h a l l be s u p p l i e d with an adjustable s t a b i l i z i n g resistor.

For d i m e n s i o n i n g o f the s t a b i l i z i n g resistor consider m a x i m u m t h ro u g h

fault chase -carth current of 3 1 . S k A State

4.4.5.20 Voltage Dependent Resistor (Merrosll)

Each REF relay s h a l l be s u p p l i e d with a voltage dependent resistor (VDR)

or m e t ro s i l to l i m i t voltage across the R E F h i g h impedance c i r c u i t . The

basis for the rated voltage ofthe V D R is the 111axi11111111 phase-earth through

fa u l t of 3 1 . S k A State

.4 . 6 Feeder Protection Rclav State

M a n u fa c t u r e r ' s Name State

Fvnc or Designation name o f A u x i l i a r y Relav Stale

Co11111lc1c order number for offered A u x i l i a r y Rclav S1,1te

••anufnclurcr's Exncrlcncc and P ro d u c t O u a l i f i c a t i n n State

4.4.6.1 lhc relay 111a11 u facturer shall have a m 1111 m u m of 25 years 111 the

manufacture of Feeders Protection relay, 1 5 years o f which shall be in the

manufacture o f nume rical Distance Protection relays State

4.4.6.2 n he relay type offered must have b en in service and given r e l i a b l e service

for a m i n i m u m period of 8 years, in at Least two u t i l i t i e s . i n each o r the

followine rcnions: State

a. Europe State

b. North America State

c. Africa and State

d. Asia St.ate

4.4.6.3 Relays that have Jailed in service or mal-operaied on the Kenyan Power

Svsiem sh,111 1101 be accepted State

4.4.6.4 Warranty for offered relays s h a l l be live (5) years 1,·0111 the date or relay

lclivcrv to the Kl'LC store State

4.4.6.5 The Relay s h a l l have the following protection fu n c t i o n s and features i n a

s i n u l c casino as a m i n i m u m : State

I. Three nhase overcurrent State

11. Earth fault Stute

111. Sensitive Earth F a u l t State

IV. Broken Conductor detection State

Issued by: I-lead of Section, S t a n d a r d s Development Authorized hy: Head of Department, S t a n d a r d s

Signed: Signed: --,


_..., .eh :'\.
� · · ')
- c a �


T
Date: 2019-06-07 D a l e : 2019-06-07
TITI.F: Dur. Nu.
K P 1 /3C'B/TSl'/02/004

Nu.

1
lssuc
l'R0'1'1£CTIVE R�LA YS, CONTROL I

- -
DEVICES ANO INSTRUMENTS-

SPECIFICATION
Revlaiun No.
'
J

Kenya Power Dale or Issue


2019-06-07

l'ugc 61 or 72

CLAUSE KPLC ltEOUIREMENTS B I O O E H ' S OJ•FER

V. Auio-reclose function Ior three phase auto-reclosc, State

VI. Under and Over Frequency Protection, i n c l u d i n g rate of' change

f re qu e n c y p ro t e c t i o n Suuc

4.4.6.6 I'here shall be independent CT input t o r Earth F a u l t and l'or S e n s i t i v e Earth

Fault Protection 10 allow independent connectiun or t h e Scnsiuve E a rt h

Fault P ro t e c t i o n Function 10 a separate Con: type CT Sta t e

'.4.G.7 Re l ay 111 u s1 be 01· Numerical dcsiu n Suuc

'.4.6.8 Rel a ys t h at have In i l c d in service or ruul-opcruted shall n ot be accep t ab l e State

.4.6.9 The relay s shall be s u i t a b l e for llush mounting on the l ro n t o ft h c p a n e l S tate

4.4.6.10 C u rr e nt selling ra n ge for o v e rc urre r u fu ncti o n shall be O.Sln-2.0ln as a

minimum S 1 u t \!

4.4.6.1 1 C urre n t scuing range tur e arth fou I t function shall be 0 . 0 5 1 n - 0 . 8 1 n as a

n11111111un1 Suuc

4.4.6.12 J'wo stages of H i g h Se1 Element for both o ve re u rren t mid earth I au l t

p ro t e c t i o n iu n c i i o u . w i t h a setting range or 1 - 2 0 1 1 1 as a m i n i 1 1 1 u 1 1 1 und ,1

l e f i n i t c t i m e delay s e t t i n g oro 60 seconds as a m i n i m u m State

i.4.6.13 l . D . M . 'J' characteristics [ o r ov crc urrcnt and Earth l'ault p rotection function

according lo B S 1 4 2 or lliC60255 i . e . Standard Inverse (SI), Very Inverse

( V I ) . E x t r e m e l y Inverse ( E l ) , Long T i m e Inverse ( L T ! ) , i n c l u d i n g d e fi n i t e

t i m e for the hiuh -sct E l e m e n t s State

.4.6.14 l'imc s e l l i n g i u u l t i p l i e r 0 . 0 5 - 1 . 0 as a 1 11 ini1 11u111 State

t4.6.15 Curre n t sel li ng range tor se n s itiv e eanh f a ul t function 0 . 0 1 1 n - 0.81nasa

1 11 i n imu111 State

t4.6.16 Definite t i m e dela y c h a ra c t e ri s t i c for Se nsit i ve eart h fau l t l u n c t i o n : se l l i ng

ra nge , 0- 30 s e co n d s as a 111 i11 i m u1 11 Sta l e

i.4.6.17 Requ i reme n t s tor the auto r ecluse [unction: S ta l e

I. Three phases aut o recluse Stat e

11. Selectable I - 3 auto-rcclosc s h ot s Sw t e

Ill. Ind epe n de ntl y set dead t i m e tor eac h shot State

iv. Auio-reclose i n h i b i t a rt e r m a n u a l clo s e: State

v. Each uuto-rcclosc shot s h a l l be in i tiat ed by the selected l'rotcciion

F unc I i 011( s ). Operation o f Pro te ction Function nut selected Lo i n i t i a t e

a p a rt i c u l a r shut or Auio-reclosc s h a l l lead to L u ck-out Stntc

VI. A u to-recluse i n h i b i t i o n l<ir over current hiuh s et clement State

,.4.6.18 Data Storaue S l ate

( i) S torage or al least l ive ( 5 ) t a u l t / t ri n records Suuc

(ii) Ten ( I O event records State

(iii) F i v e (5) d i s t u rb a n c e records State

Iss u e d by: I I cad of Se c t i o n , S u u ul u rd s Developmen t Authorized by: Head of D c p u ru n e u t , Standanls

Signed: Signed: �


,---- �j�
Ua te: 2019-06-07 Da t e : 2019-0(,-07
TITLE: Dor. No.
KP I /JCR/TSP/02/004

l
Issue No.
PROTECTIVE RELA VS, CONTROL I

- -
0 1£ V I C E S A N O I N S T R LJ M F:NTS- Revlslon No.
3
SPECIFICATION
Kenya Power Date of Issue 2019-06-07

l'ngc (l1 of 72

CLAUSE K P L C R F. Q U I R F. M E N T S Il l D O E R ' S O F F E R

4.4.6.19 C o n fi g u ra b l e output relays for protection e l e m e n t p i c k up (start) and Trip

o u t p u t s which can be used to back-trip upstream c i rc u i t breakers and for

i m p l e m e n t i n g b l o c k i n g schemes for busbar protection State

4.4.6.20 Red L.L,.D to indicate that the protection functions have operated and

issued a 1ri11 o ut p u t to Trip the circuit breaker Stale

t4.6.21 Relay sel l-diagncstic. with LCD to indicate relay healthy status (green

colour) and relay railed status (red colour) and a watch dog contact ror

remote alarm Stale

t4.6.22 LEDs: The relay shall have a n11 n I rn um eight (8) LEDs for alarms

annunciation. Stale

t4.6.23 Binary Outputs: The relay s h a l l have as a 1 11 i n i 1 1 1 u m twelve ( 1 2 ) H i n a ry

inputs. State

i . 4. 6 . 2 4 B i n a ry Outputs: The relay s h a l l have a m i n i m u m four (4) o u t p u t s Relays.

One ( I ) of the o u t p u t relays s h a l l be adequately rated 10 directly opcrat

the circuit breaker 1ri11 c o i l . State

i.4.6.25 LCD screen where t h e settings and mcasurands can be read Sta t e

.
.4 6 2. 6 Keypad for manual p ro g r a m m i n g o f scuings an d da t a access State

4 .4.6.27 R el a y Term inals-shal I be screw type term i na Is l arge en o u g h lo

a c co m m o da t e at least 41111112 c ab le a nd s h a l l be loc ated a l the b ack o f t he

rel a y Stale

.4.6.28 The re l a y ap p lica b le p ro toc o l s hall e


b IEC 61850-8-1 S tat e

4 .4.6 . 2 9 f ront S erial R S2 3 2 or U S B or E the rne t Po rt or relay


f communication with

a laptop co m p u t e r for rela y c o n fi g u ra t i o n a nd p arameter settings an d

downlo a d or fau lt records. events re cords a nd d is turb a n c e reco rd, for

a nalysis. St a t e

4.4.6.30 Software fo r c o n fi g u ra t i o n a nd rel a y parameter s ettings a nd l


a so

downloadina a nd a n a l v s i m; the rel ay fa ult da t a sh a l l be pro v ided. State

.4.6.31 R el a y 10 Laptop co n nec t ion cabl e s h a l l be p ro v ided S ta t e

4.4.6.32 A u t o re c l u se re l ay f unc t ion i n t he feeder p ro t ection rel a y. T h is auto reclosc

fu nction s h a l l be ho u sed w i t h i n the fe eder pr o t ection rela y : Stat e

I. Selec t ab l e I - 3 aut o re cl o s c s hots Stute

11. I n d e p e n d c n tl v set dead t i me for each sho t State

111. A u to - recl u se i nhibit a ft er ma n u a l close S ta te

IV. E ach a ut o - rc c l o s c s h o t shall be i n i t i a t e d by the selected p ro t e cti o n

funct i o n( s ). O p e ra t i o n ol' p r o tection ru n ct i o n no l se lec t ed to

initiate a p a rti c ul a r s ho t o f' u u to - re c l o s e s h a l l lead lo l o ck - o u t o f t h e

rel a y.

Stale

V. A ut o - rc c l o s e inhibition for over curre n t i


h p,h set e lement. Stat e

Issued hy: I-lead of Section, S t n n r l a rd s Development A u l h o r i i c d by: Head of D e p a rt m e n t . S t a n d a rd s

Signed: Signed:
C-l'.'L<"6, J\) �- l I,
'
-�l

-v
Date: 2019-06-07 Date: 20 l 9-06-07
TITLE: Due. Nu.
KP I /JCBffSP/02/004

t
-
l'l<OTECTIVE R F. L A VS, C O N T l { O L

D E V I C E S AND INSTRUMENTS-
Issue Nu.
I

- SPECIFICATION
Rcvlsiun Nu.
3

Kenya Power Dute uf Issue


2019-06-07

1';1ge 63 or 72

CLAUSE Kl'LC R E Q U I R E M E N T S B I D D E R ' S OFFER


4.4.7 Electrical Reset - Trip Relay
State

M a n u f a c t u re r ' s Na111e
Suue

l'ype or Designation name of A u x i l i a ry Relay


State

Complete order n u m b e r Ior offered A u x i l i a r y Relay


State

M a 1 1 1 1 f a c l u r c r � s E x p e ri e n c e u u d Product Q u u l i t i c u t i o n
State

.4.7.1 M i n i m u m or 1 5 years in the m a n uf a c t u re ofTrip re l a y s


�late

�.4.7.2 lhe o ffe re d re lays m us t ha ve been so ld o


t at lea s t two utilities outside the

� o u n t ry 01· r n u n u t a c t urc , and operated re l i a b l y f o r al least 8 years. Copy or

Ex po rt sales c ont ra ct sh all be pro vided w thi the i


b d 10 s up p o rt this

req L I i re m e n t S tate

4.4.7.3 Relays that fo i l e d i n S e r vice or Ma l -o p e ra te d o n th e Ken ya n Power System

shal I not be a c c e p te d
�late

4. 4.7.4 Wa r ra n t y fu r offered r e la y s shal l be i


F v e (5) years from t he dale or rela y

d e l i v e r y to the K P I . C store State


F u n c t i o n s and Features
Slate

4 .4.7.5 I l i g h b u rd e n t r i p p i n g rela y , i111111L111e to capacitance disc h arge currents and

leukaue c urrents Stale

4 .4. 7 .6 A l least Four (4) pairs of n o rm a l l y open (NO) and I wo (2) pairs o f nu rm a l l y

closed ( N C ) or 4NO/NC OL1tpu1 co nt act s . Slate

. 4. 7 .7 Instantaneous o p e ra t i c » : t i m e < I 5111s $Lale

.4.7.8 n he Relay shall b e s u i t a b l e for fl u s h m o ur u i n a Siute

.4.7.9 F l a g or target sh a l l be a red; 1 .. E . D . or d u ra b l e b u l b or Red Mechanical Ila!!, State


4 . 4 . 7 . 1 ( )
l'he R el ay shall b e e l e c t ri c a l l y r es e t, and t he r s
e et b ut t o n sh al l b e i n b u i l t

011 th e rel ay an d access ible w i t h out o pe ni ng t he re l ay cover o r s h a ll b e

sup p lied s e p a ra t e l y ror


p nela flush mounting, in which case the re se t

b ut t o n shall b e il lumina ted w i t h red c o l o u r.


Stale

4 .4. 7 . 1 I Con tact ra t in g - ca pa b le o r c a rr yi ng 30Arnps ror 3 secon d s an d I OJ\,

cont i 1
1 LIOLISI V
S ta l e

4.4 7. 2 1 Re l ay t e rm i n a l s - s h a l l be sc r e w t yp e l r
a ge enough to uccornmoduic at least

4 111111 2 cab le an d s h a l l be located at the back ofthe rela y State

<1 . 4 . 7 . 1 3 Relay t e r m i n a l s s h a l l be c l e a r l y marked State

•.4 . 7 1 4 Re l ay c ontacts c o n f i g u ra t i o n s h a l l p re f e ra b l y be d ra w n on the relay casing . Sta l e

. 4.7.15 A l t e rn u t i v c l y . a c o n n e c t i o n d raw i n u s h a l l be s u p p l i e d w i t h t h e relay . State

.4.7. 6 1 Size not g reater t h a n 24x I 9x6 cm State

.4.8 Self-Reset Trip Rela y Stale

M a n u l ac t ure r ' s Name

Ty1Je or Designation name (JI' A u x i l i a r y Relay State

Issued by: I-lead of Section, Standards Development Au t horized by: I-lead of Department, S ta n da rd s

Signed: Signed:

�·
)
/---:)
·�- -
Date: 2019-06-07 Date: 2019-06-07
rrru; n,u�. Nf,.
KP i /JCl:3frSP/02/004

l PROTECTIVE R E L A VS, CONTROL ls.!iul' No. I

- -
DEVICES AND INSTRUMENTS-
Rcviston No. "
J

SPECIFICATION
Kenya Power Dntc or Issue
2019-06-07

Pugc h4 or 72

CLAUSE KPLC R E O l l l R E M E N T S R I D D F. R ' S O F F E R



Cornnlere order numb er for offered A u x i l i a r y Relay :, tare

M a n u f a c t u r e r ' s E x n c ri c n c e a n d Product O u a l l f i c n t i o n State

4.4.8. I M i n i m u m o f 1 5 years in the manufacture of" trip relays State

4.4.8.2 The offered relays must have been sold lo at least two u t i l i t i e s outside the

country of' manufacture, and operated r e l i a b l y for at least 8 years. Copy of

Export sales contract shall be provided with the bid to support this

reo LI i rerncn t. State

4.4.8.3 Relays that have failed i n service or mal-operaicd on the Kenyan Power

Svstcm s h a l l not be acceoted. Staie

4.4.8.4 Warranty tor offered relays s h a l l be five (5) years Ihm, the elate 01· re l a y

delivery lo KPLC store. State

4.4.8.5 H i g h burden tripping relay, i m m u n e to capacitance discharge currents and

leakage currents State

4.4.8.6 /\t least Four (4) pairs of n o r m a l l y open (NO) and two (2) pairs of n or m a l l y

closed (NC) or 4NO/NC o u t p u t contacts. State

4.4.8. 7 Instantaneous o p e ra t i o n ; t i m e < I 5111s State

4.4.8.8 The Relay s h a l l be suitable for flush m o u n t i n g or for m o u n t i n g on 35111111

DIN m i l , i n which case the relay s h a l l be supplied complete w i t h the base State

4.4.8.9 Flag or target s h a l l be a red; L . E . D . or d u ra b l e b u l b or Reel Mechanical ilag State

.4.8.10 T'11c Relay s h a l l be sell-reset, once the relay i n i t i a t i n g the t r i p resets . State

t4.8. I I Contact rating - capable or carrying 30/\mps for 3 seconds and I O A ,

c on t i n u o us l y and the Relay te rm i nals s h a l l be c l e a r l y marked State

4.4.8. I 2 Relay T c rm i nals-shal I be screw type terminals large enough to

accorn mod ate at least State

.4.8.JJ 2 x 2.5 1111112 cable and shall be located at the back of the rel av State

.4.8. 1 4 D ra w i n g for relay connection s h a l l be provided with the rclav Slate

'.4.8.15 Relay contacts c o n fi g u ra t i o n s h a l l preferably be drawn on the relav casinu. State

.4.8.16 A l t e rn a t i v e l y , a connection drawing shall be supplied w i t h the relav, State

.4.8.17 Size not greater than 24x I 9x6 cm State

.4.9 Trin C i r c u i t Suncrvislon Rclav Type I State

Manufacturer's Name �tale

Tvne or D e s i a n a t i o n n a m e of A u x i l i a r y Relay State

Complete order n u m b e r for offered A u x i l i a r y Relay State

M a n u fa c t u rc rs Exnerieuce and Product O u u l i fl c u t i o n State

.4.9.1 M i n i m u m or I 5 years i n the manufacture of Trip C i r c u i t Suncrvision relavs State

4.4. 9.2 n he offered relays must have been sold to at least two u t i l i t i e s outside the

country or manufacture, and operated reliably for at least 8 years. Copy of'

Export sales contract shall be provided with the bid to support this

rcq LI i rcrncnt. State

Issued hy: Head of Section, Stnnrlnrds Development Authorlzcrt hy: llead of D c p a r 1 1 1 1 c 1 1 t , Standards

Signed: Signed: -,
CCi.1r: � ·) _. < � �

Date: 21119-116-07 v
Date: 21119-06-07
TITLE: nuf. No.
KP I /3 C 13/TS P/02/004

1
-
P R O T E C T I V E R E L A VS, C O N T R O L

DEVICES AND INSTRUMENTS-


Issue No.
I

- SPECI Fl CATION
Rcvlsiou No.
3

Kenya Power Dale of Issue


2019-06-07

Pag,i.! 65 u !' 72

CLAUSI, KPLC REQUIREMENTS 13 1 D D E R ' S O F F E R


4.4.93 Relays that have fa i l e d i n service or rnal-opcraied on the Kenyan Power

System shall not be accepted. Stale

4.4.9.4 Warranty for Offered relays shall be live (5) years from the date o fd e l i v e ry

lo K PLC store, Stale

Functions Hiid F e a t u re s State


14 . 4 . 9 . 5 Cont inuous s u p e rv i s i o n o r tr i p circu it for circui t breaker in b o h t OPEN &

C C OS ED p osi i t o n s
State

. 4 9 . .6 Trin Ci rc uit Hea lth y - R e d / G re e n L .E.D ON


State

. 4 . 9 . 7 J'r i p ci r cu i t la i l -Green/Red L.L.D OFF


Staie

4.4. 9.8
l'wo (2) n or m ally cl o e
s d (N C ) and tw o (2) n o rma l ly o pen(NO) or 2 C/0

( c h a n g e - o v e r) output contacts
S tate

4 .4.9. 9 I'hc re l ya s h a l l h ave a t im e dela y of al least


l 5 0 rn S o
t a voi d uu n s i e n r

op e ra t i o n s
St at e

.4.9. 1 0 Contact ru l i ngs - 30 Amps fo r 3 s conds and 5 Amps c o


e n ti n uously . Stat"
.4.9. 1 1 S u i t a b l e Ior Flus h mo u nt n i g on the re l a v 1J,111el State

4.4.9.12 Rela y Tern, nals-shul I i be screw t yp e term na Is i large eno gh u to

accommodate at least 4mm2 cables and shall be located at the back or the

relay and relay t e r m i n a l s sh al I be c l e a rl y marked. State

'.4.9.13 Rela y s h a l l be supulicd complete w i t h the base. State

.4.9.14 Rclav con acts c o n t i u u ra t i o n s h a l


t l preferab y be drawn on the relay casing,
l
St ate

.4.9.1 5 A t e rn a i v e y , a conne
l t l ct ion d ra w n g s h a l l be supplied with the
i r elay . State

4.4.9.16 Size 1101 gr eater t han I 6x9x9 cm State

4.4.10 A u x i l i a r y relays Fu1· 'I ' ru n s fo rm e r M e c h a n i c a l P ro t c c t i u n Trip F u n c t i o n

I'ype I S tulc

M u nu fu c t u rc r- s Ex n c r-i c n c e a n d l'ruduct O u a l i l i r .a l i o n State

M a n u fa c t ure r ' s N ame S tate

l'ypc or Designation n ame or A u x i l i a r y Relay State

C o m o l e i e orde r nu m b e r for off red A e u xiliar y Relav Stall!

.4. I 0. I Years o f Ex p er en
i c e i n the m a n u f a c t ure of A n n u n c i a t o r rela y s State

4.4. I 0 2 .
U t i l i t i e s o ut si de t h e ma n ufactur er' s c o u n t rv w h ere t he r l e ay h as bee n s o ld
State

N um b e r o r s i m i l a r i\ 1 1
1 1 un ci a l o r Relay s o dl to date l
o t he e x p o rt ma rke t:

M i n i m u m ; 1000 S t a l e

4 . 4 .10.3 H av e t h e o f f e re d A n n u n c i a t o r Re l ay ta iled in se r i v ce or r n a l - o p c ra t c d on

t h e Ke n y a n Pow er System?
Sl ate

.4.10 . 4 R ela y Wa r ra nt y p e iod i


r n yea r s
State

Fuuctiuns aud F e a t u re s :

.4. I0 . 5 Annlicarion State

4 . 4 . 1 0 . 6 R elay l e a t urc s :

I. R el a y o p e ra t i n g t i m e
S Ill IC

I ssued by: Head of Scctio 1 1 , S t a n d a rd s D e vc l u p m e u t


A u t h o ri z eu by: I-lead uf Ocp a tmcu
r t, Suuulurtls

S g i n ed: r Sigucd:
&� C'") b
•.
'
Dale: 2019-06-07 r D a tc: 2019-06-07
T I T J . F. : Doc. No.
KP I /3C 13/TSP/02/004

\'_ P R O T E C T I V E R E L A VS, C O N T R O L Issue No.


I

-
-
DEVICES A N D INSTRUMENTS- Revision No.
3
SPEC I Fl ATION
Kenya Power D a l e of Issue
2019-06-07

l'ngc '16 or 72

CLAUSE Kl'LC R E Q U I R E M E N T S R I D D E H ' S O F F F: R

I I. Number of rel av clements ner casinu State

11 I. I-land reset contacts and red llau Staie

JV, S u i t a b l e for 35111111 DIN R a i l m o u n t i n g State

v. Number o f ' N O contacts State

.4.10.7 Type and size o r relay t e r m i n a l s for cable t e r m i n a t i o n State

.4.10.8 Contact ra t i n n s Stale

.4.10.9 Relav t e r m i n a l s are i n d e l i b l y marked State

.4.10.10 S u n n l i c d c o m u l c t c w i t h base State

.4.10.11 Relay contacts con Ii aurat ion State

.4.10.12 W i ri r n; d ra w i n n s Stale

.4.10.13 S i z e : lxhxb State

4.4.11 A n n u n c i a t o r Rclav Tvne l State

M a n u f a c t ure r ' s Name State

voe or Desiunation name of A n n u n c i a t o r Relay State

Comulcte order number for offered Annunciator R e l a y Stale

.4.11.1 Years o f Experience in the m a n u f a c t u re of A n n u n c i a t o r relays State

4.4.11.2 U t i l i t i e s o u t s i d e the m a n u fa c tu re r ' s country where the relay has been sold Stale

Number of s i m i far Ann unciaror Relay sold to date to the export market:

Minimum; I 000 Stale

4.4.11.3 I lave the offered Annunciator Relay railed in service 01· ma I-operated on

he Kcnvan Power Svstern? State

.4.1 1.4 Rclav Warrantv neriod in vcars State

4.4.1 1 . 5 Rclav ao o l i c a r i o n State

4.4.11.6 Dcsiun o r the A n n u n c i a t o r Relav Stale

<L.4. I I . 7 Sui tabi I i tv i n read i 1111 and acknowlcdnina alarms State

o.4.11.8 Method of n ro a ra m m i n a the alarms State

.4.11.9 Behaviour o la l a rm s unon loss of a u x i l i a r y DC s u n n l v Stale

.4 . 1 1 . 1 0 A farm rnanauerncnt buttons Stale

.4.1 1 . 1 I Number or alarm clements/windows Stale

.4.1 1 . 1 2 N u m e r i c a l / D i n i ta! desi un State

�.4.11.13 S u i t a b i l i t v lor Panel flush mountinu desiun State

� . 4 1 1 1 4 A l a rm elements freely c o n fi g u ra b l e to URGENT or N O N - U l { G i.o N T a l a r m State

bus and to cutout relays

.4.11.15 LED colour for alarm ON Indication State

.4.11.16 Imrnunitv auainst electrical interference State

.4.11.17 Relav t e rm i n a l s rvoe and size State

.4.11.18 Marki nu or rel av t e r m i n a l s State

.4.11.19 Relav c o n fi a u ra t i o n State

.4.11.20 Number or contacts for out nut relays Stale

Issued by: I-lead of Section, St;rndanls Development A u t h o r i z e d by: Hcud of Department, S t a n d a r d s

Sigucd: Signed:

c [7 -i;,-

Dn I c: 2019-06-07 � Date: 2019-06-07


TITLE: Dor. No.
KP l/3Cl3/TSP/02/004

\:. !'ROTE T I V E IU:LA YS, C O N T R O L lssuc Nu.


I

-
-
DEVICES A N D INSTRUMENTS-

SPF. 'I Fl CATION


Revision Nl1,
3

Kenya Power Dale ur I s s ue


2019-06-07

l'ug,i.:: 67 of'72

C L A U S F. KPLC REQUIREMENTS B I D O !.: R ' S O F F E R


4.4.11.21 Field c o n t i g u ru b l c labels Stale

.4.11.22. Number or N o r m a l l y Open (NO) o u t - p ut contacts State

'.4.12 A n n u n c i a t o r R e l a v Tv11c I I

M a n u f a c t ure rs Name State

vpe or D e s i u n a t i o n name of A n n u n c i a t or Relav State

C o m u l c t e order number for o ff e re d A n n un c i a t o r Relay State

.4.12.1 Years or Ex11ericnce i n the m a n u f a c t u re 01· A n n u n c i a t o r rclavs Sime

4.4.12.2 U t i l i t i e s outside the m a n ufa c t urc rs country where the relay has been sold State

Number o ls i r n i l n r Annunciator Relay sold to date lo the export market: State

M i n i m u m ; I 000

4.4.12.3 I J u v e the offered Annunciator Relay t a i l e d i n service or mal-operuted on

the Kenyan Power Svs1e111·> State

.4.12.4 Relay Warranty period i n years Sime

.4.12.5 AJJJJI icat ion State

�.4.12.6 Desiun 0 1 · the A n n u n c i a t o r Relay State

.4.12. 7 S u i t a b i l i t y in reading and uc k n o w l e d u i n u a l a r m s State

.4.12.8 Method or n ro a ra m m i n u the alarms State

.4.12.9 Beha vio ur o fa l a rm s unon loss of a u x i l i a r y DC s u p p l y State

4.4.12.10 N u m e ri c a l / D i u i t a l design Sime

4.4.12.11 S u i r a b i l i t v for P a n e l flush mounting design Sime

' . 4 . 1 2 . 12 Alarm management buttons State

.4.12.13 N u m b e r or alarm elements/windows State

4.4.12.14 Has relay operated i n Kenya power System s uc c e s s fu l l y for the last 4 State

"ears?

4.4.12.15 Has the re l a v o ff e re d been s u o o l i c d before'! Stale

4.4.12.16 Alarm e l e m e n t s freely configurable lo U R G E N T u r N O N - U R G E N T a l a r 1 1 1 State

bus and lo o u t p u t relays

4.4.12.17 LED colour for alarm ON l n d i c a i i o n State

s.4.12.18 J111111uni1v a g a i n s t electrical interference State

4.4.12.19 Relav t e r m i n a l s type and size State

.4. 1 2 . 2 0 M a rk i n u of relay t e r m i n a l s State

.4.12.21 Relay c o n fi u u ra i i o n State

.4.12.22 N u m b e r or contacts lor o u t p u t relays Stale

.4.12.23 W i r i n g d ra w i n g s Provide

A.13 Disercnnncv Switch for C i r c u i t Hrcukcr Control State

M a n u l a c t u re rs Name State

J"voc or D c s i u n a t i o n name or Discrepancy switch State

Comnlctc order number for o f f e re d Discrepancy switch State

4.4.13.1 M n n u l u c t ure rs experience in m n n u f u c r urc of Discrepancy switch State

Issued by: Head of S e c t i o n . Standards D e v e l o p m e n t A u t h o ri z e d I.Jy: I-lead of D e p u rt m e n r , S t u u d u rd s

Sigucd: Sigucd:
(" ( � �
,.;:- c: i) �
.,

Date: 2(119-06-07 v Date: 2019-06-07


Doc. No,
TITLE: I< P 1 /3CI3/TS l'/02/004

'l
Issue No.
PROTECTIVE RF.LA VS, C O N T R O L I

- -
D E V I C E S A N O INSTRUMENTS- Revisfnu N<1.
'
j

SPECIFICATION
Kenya Power D11tc of lssuc
2019-06-07

Page (18 of' 72

CLAUSE KPLC R E Q U I R F. M E N T S BIDDER'S OFFER

i.4.13.2 U t i l i t i e s o u t s i d e the manufacturer's country where the Discrepancy control

switch has been sold Stute

N11111bcr o f s i m i l a r Discrepancy switches sold to dare to the export market:

Requirement: I 000 State

4.4.13.3 Have the offered Discrepancy switches foiled in service or r n a l - o p e ra t e d

on the Kenyan Power System? State

.4.13.4 Discrepancy Switch Warranty Period in years State

.4.13.5 S u i t a b i l i t y for flush m o u n t i n g State

.4.13.6 Application State

4.4.13.7 Number mid c o n f i u u ra t i o n o r contacts for close and oncn operations State

.4.13.8 I n d i c a t i o n for discrepancy in c i r c u i t breaker status State

.4.13.9 D u ra b i l i t y and sturdy discrepancy switch State

4.4.13.10 Indelibly marked rectangular escutcheon plate w i t h c l o s i n g and opening

Josi tions clearly marked State

4.4.13.1 I Shape o r Top ofthe switch State

.4.13.12 Type and size or switch contacts for cable t e r m i n a t i o n State

.4.13.13 M a r k i n g of the switch t e r m i n a l s State

.4.13.14 Switch c o n fi g u ra t i o n drawing Provide

.4.13.15 Rating or discrepancy white i l l u m i n a t i o n b u l b State

.4.13.16 Type ofswiich offered Stale

.4.14 Se m aphor e for Isolator a n d Earth Switch Position I n d i c a t i o n

Manufacturer's Name State

I'ypc or Designation name or L�D I n d i c a t i n g Lamps State

.4.14.1 Manufacturer's experience in manufacture o r Semaphores State

.4.14.2 A n n l i c a t i o n of the semaphores State

4.4.14.3 U t i l i t i e s outside the manufacturer's country where the Semaphore has State

been sold

Number of Semaphores sold to the Export Market - M i n i m u m : I 000 State

4.4.14.4 Have the offered Semaphores failed in service or ma I-operated on the State

Kenyan Power System?

.4.14.5 Warranty period for Semaphores i n years State

.4.14.6 S u i t a b i l i t y for Panel Flush m o u n t i n g State

�.4.14.7 Indications for Closed and Open status State

i.4.14.R Front anoearance State

t4.14.9 I vpe and size on semaphore terminals for cable connection State

M a r k i n g of the te rmina ls State

.4.15 Ll�D I n d i c a t i n g Lamps

Manufacturer's Name State

Type or Designation name or LED l n d i c a t ing Lamps State

Issued by: Head of Section, S t a n d a rd s Development Authorized hy: Head or D e p a rt m e n t , S t a n d a r d s

Signed: Signed:
< rJ'lfl 'I,�· .
)
_ c t9 4--.

Date: 2019-06-07 II Date: 2019,06-07


TITLE: Dot', Nu.
KJJ I /3 C 13/TS P/02/004

\'_ l'ROTl�CTIVE R E L A Y S , CONTROL lssul' Nu.


I

-
-
DEVICES ANU INSTRUMENTS-
1 l l' v i s i u 1 1 Nu.

.)

Sl'ECI F I C A T I O N
Kenya Power Dute of Issue
2019-06-07

Pagi.! ()9 ol'72

CLAUSE KPLC R E Q U I R E M E N T S B I D D E R ' S OFFER

.4.15.1 M a n u f a c t ure r ' s experience in the M a n uf a c t u re or LED I n d i c a t i n g Lamps. Slate

4.4.15.2 Utilities outside the munulacturers country where the L E LJ indicating Stute

l a m p has been sold

Number or I. E D in d i c at i n g Lamps sold Lo the Export Market Minimum: State


1000

.4.15.3 I law the o t t e re d L [ D lndicuting Lamps failed in se rvice or ma I - o p e ra ted S tate

on t he K en y a n Power System"!

.4.15.4 W ar r a nty in y e ars. S tate

�.4.15.5 S u pp l i e d c o m p l ete w ith lamp a nd mounting base


State

.4.15.6 S uitable fo r flush mo unting St at e

.4.15.7 l'ypc or LED I ndicating l.arnps


S1a1 e

.4.15.8 LE D lam p ra t i n g in waus


S t att:

.4.15.9 M i n i m u m o p e ra t i n g l i f e St a t e

.4.15.10 Red LED i n d i c a t o rs are or the hi g h b riu h t n e s s tvne


State

.4. I(, Multi - F u n c t i o n a l P ower Meter

M a n u f a c t u re rs Name S tale

ypc or Dcsiunation name or Multi-functional Pow er meter State

4.4.16.1 M a n u l a c t ure rs experience in the M a n uf a c t u re or M ul t i - fu n c t i o n a l rower State


meter

4.4.16.2 U u l i u c s o u t s i d e the manufacturer's countr y where the M u l t i - F u n c t i o n a l St ate

Power M eter has been s old

N u m b e r of M ul t i - fu n c t i o n a l Power Meter, sold tu the l�xport Market - State

Mini111u111: I 000

4.4.16.3 Has the offered M u l r i - t u n c r i o n a l Power meter fa i l e d i n service or mal- State


o p erated o n the Kenya n Power System'!

.4.16.4 Warranty period for M u l t i - l - u n c t i o n a l M e t e r in year s Stal e

.4.16.5 Suitability for fl ush mounting


Stale

'.4.16.6 D esign S tat e

4.4.16.7 Type or display Stat e

N u m b e r of m e as u ra n d s di s pl a y e d sirnultaneouslv S tate

.4.16.8 Keypad i
s m plicity t o a llow s c ro l l i n u bet w e e n th e vari ous m c as ura n d s S t a te

.4.16.9 Th e i n s um u u r c o u s values me a su r ed by th e unit St a t e

4.4.16.10 A bility o
L me asur e L mei stam ped i
111ax 111 u111 and 1 nini111u111 d emand for S tat e

c u rre n t a nd powe r ( MW & M VAJ

.4.16.11 Sh all m e as ur e u n b a l a n c e vol t a g e a nd cu rr e n t State

4.4.16.12 S ha ll measure T o t al harmonic d i s r o rt i o n f 'I' ! JD) and Total Demand State

D istorlion(T D D) for c u rrent and v o ltage

4.4.16.13 Rared current and V o l tage S tate

4.4.16.14 M a x i m u m current and voltage the u n i t can withstand c o n t i n u o u s l y S tale

Issued h.)': I-lead uf S e c tio n , S t andan l s Dcvclupmcnt Authurizcd 1.,y: I-lead of Dcpuruucut, S t a u du rd s

Signt'tl: Signed: (5
�T I ,_,_' �J -,} .:;::;;;: i)-
-
Datt': 21119 - 06 - 117 I/ D a t e : 2019 - 06 - 07
T I T L l3 : noc. No. K P ! /JCR/TSP/02/004

l
Issue No.
PROTF.CTIVE R E L A VS, C O N T R O L I

--
- -
DEVICES AND INSTRUMENTS- Rcvlslou No.
'
J

S P E C I Fl C A T I O N
Kenya Power Dute or Issue
2019-06-07

Page 70 11f 72

CLAUSE KPLC R E Q U I R E M E N T S B I O O F. R ' S O F F E R

.4.16.15 S u i l a b i l i t v for fl u s h 111ou111in£'. State

.4.16.16 3 phase, 4-wirc connection Slate

4.4.16.17 Port for n ro a ra m r n i n u State

-T and VT ratio » ro a r a m m a b l e State

.4.16.18 C o m m u n i c a t i o n ports State

.4.16.19 C o m m u n i c a t i o n nrotocols Stale

.4.16.20 Accuracy class State

.4.16.21 I n b u i l t re a l - t i m e clock and calendar feature State

.4.16.22 Disnlav oneration State

4.4.16.23 Software nrovidcd Slate

PC to Measurement U n i t connection cable nrovided State

4.4.16.24 le rm i n a l s c l e a rl v m a rk e d Stale

Ivnc & size or t e rm i n a l s State

4.4.16.25 Measurement ranue for MVA State

4.4.17 A d d i t i o n a l snccification for relays

.4.17.1 Dcsiun o fa l l measurement relays State

.4.17.2 Use or electromechanical relays used State

.4.1 !I Relay P r o a ru m m i n a Software and C o n n e c t i o n Cables

.4.18.1 Software suonlicd for a l l numerical relays and numerical instruments State

4.4.18.2 Number or computers that can be installed a software without any State

a d d i t i o n a l License Cost

Number of CDs fnr each d i ff e re n t tvnc o fS o ft w a re State

.4.18.3 Number o f software user uuides State

Tvne of c o m m u n i c a t i o n nort lo f a c i l i t a t e connection to a Laoton State

.4.18.4 Number o f c o m m u n i c a t i o n cables for each set of relays State

NL1111ber of c o m m u n i c a t i o n cables for each set of transducers State

Number of c o m m u n i c a t i o n cables for newer measurement uni I Stale

4.4.18.5 C o m m u n i c a t i o n facility provided l'or re11101e interrogation and State

orouramminu o f the numerical relavs

4.4.18.6 Type M M l p ro v i d e d to f a c i l i t a t e manual relay programming and data State

access.

.4.18.7 Relay o ne ra iio n d uri n u system fault i n d i c a t i o n s State

A rESTING

Al. R e s n o n s i b i l i t v of carrvina out tests S111te

/\2. Conics o fTv u c Test Renorts submitted with lender State

AJ. rest reuuirernerus State

n WARRANTY

B.I 1 here s h a l l be no defect a ris i n u from design, materials or workmanship State

13.2 Warranty period for protection measurement relays State

Issued by: Hearl of Section, S ra r n l n rd s Development A u t h n ri z c d hy: Head of D e p a r t m e n t , S t a n d a rd s

Signed: Signed: >


rl . .I " "I .:;, ) cc)-4
v

Date: 2019-06-07 7 l),i te: 20 I 9-06-07


TITLE: Due. No.
KI' I /3 C BITS P/02/004

1 P R O T E C T I V E RELA VS, lssuu No.


ONTROL I

- -
DEVICES AND INSTRUMENTS-

SPECIFICATION
Rcvisiuu No.
3

Kenya Power Dute of lssue


2019-06-07

PagL·7l ot'72

CLAUSE l<PLC l { E O U I R E M E N T S B I D D E R ' S OFFEl{

B.3 W a rra n t y period for a u x i l i a r y relays and control devices SIU le

R c p l u c c m c n t wi t h o ut charue tor i t e m s w i t h i n the warranty ucriod Sime

c '.1 U A L I T Y M A M N A G F: M F. N T SYSTEM

C. I 9 u a l i 1 v Assurance !'Ian SI ale

C.2 Copy or ISO 9 0 0 1 :2008 Ccni ficutc State

M anu facturcr · s cxnerience S t a le

M a n u f u c r uri n u Capacity (units per m o n t h ) State

L i s t or p re v i o us customers State

' �us1 01 1 1er reference letters


State

I) l'ECI-INICAL DOCUMENTATION

D.I Documents 10 be s u b m i t t e d tor te nd e r e v a l u a t i o n Staie

D.2 D ocu me n ts 10 be s u b m i t t e d for a no ro v a l befo r e m a n u fa c t u re S tat e

DJ Routine les t repons submitted for a p p ru v a l b e fore s h i p m e n t State

DA Documentation i n c l u d e d i 1 1 th e e cu i n m e m packag e St ate

E rECHNICAL M A N U A L S / G U I D E A N D OPERATION A N D MAINTENANCE

MANUALS

E.1 N u m b er of hard CODY t e c h n i c a l m a n ua l and gu i des T.Statc

S,1n COPY m a n u al s p ro v i d e d State

E.2 N u m b e r or u ser/operator uuidcs S tate

F FACTORY A C C E P T A N C E TESTS, I N S P E C T I O N A N D T R A I N I N G
r, _ I FAT to be conducted bv 2 K P I . C c nu i n e e rs and t ra i n i n g State

F.2 lnspcction State

1-'J Cost or local t ra n s o o rt to be b orne by the m a n u f a c t ure r d u ri n u FAT S taie

r,.4 N u m b e r o f clays for factory t ra i n i n g for Distance protec t ion relavs S tate

N u m b e r ofdays [or l ac t u ry t ra i n i n g for Biased D i ff e re n t i a l Protection State

Rcluv

Number or davs lor factory t ra i n i n g for lccdcr Protection & Control R c l a v S tute

N u m b e r o fd a v s for factory t ra i n i n g lor Power Measurement U n i t S1a1e

F.5 Assessment of the t ra i n i n g by the m a n u f a c t u re r S taie

G LOCAL T R A I N I N G I N N J\ 1 1 { 0 8 1

G.I. Number or days for local t ra i n i n g t o r Distance p ro tect i on relavs SLaLe

N u m b e r of clays for locu] uu i n i r n; for Biased D i ff e re n t i a l Protecti o n Relay State

N u m b er or clays for local t ra i n i n g for l'ccdcr P ro t c c t i un & Control Rcluv Stu e I

N u m b e r or days for lo c al t ra i n i ru, for Power Meas u remen t U n i t S tate

G.2 N u m b e r or workinu clays tor t he t ra i n i n g S tale

N u mbe r o r Enuineers/Technicians to be tra i ned S1,11e

G.3 'f'he s u o n l i e r 10 meet a l l costs and provide a l l t ra i n i n g ma t eria l s State

G.4 A ssessment or the t ra i n i n g by the m a n u f a c t ure r St ate

r:

Issued hy:Jlcad of' Scc1iu11, S t u n d u rd s Devclupmcut t\ u l h o r i z c d by: Head uf' Dcpsu-un eut. Staudurds

Signed:
C{) b=-
Slgued:
c::::t3'· s
-
Date: 2019-06-07 D a t e : 2019-06-07
TITLE: Doc. No. K P 1/3CR/TSP/02/004

1
PROTECTIVE RELA VS, CONTROL Issue No.
I

- -
D E V I C E S AND I N S T R U M E N T S - Revision No.
3
SPECIFICATION
Kenya Power D:Hc or Issue
2019-06-07

Pngc 72 of 72

CLAUSE KPLC R E Q L I I R E M F: N T S B I D D E R ' S OFFER

H PACKING AND M A R K I N G

1-1. I Packing D e t a i l s State

1-l.2 M a rk i n u Details State

I DELIVERY

I. I Delivery to K P J , C b u l k Stores at l s i o l o Road. N a i ro b i . State

1.2 Inspection at K P J . C stores State

1 . 3 One week n o t i fi c a t i o n before del ivory State

1.4 S u p p l y w i t h i n the stipulated time as per the contract State

Statement of com pl lance to spcci fication State

Note: Words like 'agrced , 'confirmed ·


. 'As pe,. Kl'LC specifications ·. etc. shall not he accepted and

shall he considered non-responsive .

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

M n n u fa c r u r c r ' s N a m e , S i g n a tu r e , S t a m p a n d Date

Issued hy: I lead of Section, S t a n d a rds Development Authorized hy: Head of' D e p a r t m e n t , Staurlnrds

,
�.