Académique Documents
Professionnel Documents
Culture Documents
3.1 Components
Typically, a Fire Sprinkler Systems are made up from a series of components
including; pressure gauge, alarm gone, automatic air release valve, water tank, control
valve, sprinkler heads, main fire pumps and jockey pump. In addition to this there are
additional components that support this arrangement including a pressure switch and
flow switch.
The pressure gauge measures the water pressure within the automatic fire
sprinkler system. The water pressure is measured by two units, Bar and PSI. In figure,
the Bar unit is showed in red color and The PSI unit is showed in black color.
15
A flow alarm works by a pressure switch that indicates a pressure drop when a
sprinkler head (or test valve) opens, or an actual in-flow mechanism (a propeller or a
movable flap) that moves when water flows. Some early models (still in existence)
run water through an impeller that moves a clapper in a gong while water is flowing.
The automatic air release valve is useful for automatic fire sprinkler system.
When the water pressure is get more than required pressure within the riser pipe, the
water is released from the automatic air release valve. So, the riser pipe and pipe
joints are not occurring in broken condition.
According to the NFPA, closed valves are the main cause of sprinkler system failure.
There will likely be several control valves located throughout your system that
separate the system into designated sections.
The control valve for automatic fire sprinkler system, which is attached in
riser pipe and range pipe. When the fire extinguish is finished, the fire fighter is
closed the control valve which is situated in the range pipe. They do for that, this is
preventing for other damage caused by water.
Common wet fire sprinklers are available in two primary sizes: 1/2" and 3/4".
A 1/2" sprinkler is the most common for office buildings, hotels, and schools. 3/4", on
the other hand, are larger and used when extended coverage is necessary. For the
purpose of this article, we're only going to highlight 1/2" sprinklers but most
manufacturers also offer 3/4" variants.
Physically, the only difference between a standard response fire sprinkler and
a quick response fire sprinkler is the size of the bulb standard response sprinklers have
a 5 mm glass bulb, while quick response fire sprinklers have a 3 mm glass bulb.
The deflector is curved downward, which helps to direct the water out into a
cone pattern. Commercial pendent fire sprinklers are bet used in offices, hotels,
factories, etc.
These sprinklers are commonly found in buildings with exposed ceilings, like
many chic restaurants or mechanical rooms. It may be useful to think of an upright
fire sprinkler like an upside down pendent fire sprinkler, only with a concave
deflector.
They are designed to be installed on the wall, instead of in the ceiling, along or
under a beam. However, sidewall sprinklers perform the same basic functions as other
fire sprinklers.
It's probably easy to figure out where a sidewall fire sprinkler is meant to be
installed. They protrude through the wall and basically only have half of a deflector,
which sprays water in a half circle or crescent shape.
The cover plate will fall off at a temperature about 20 degrees lower than the
fire sprinkler, allowing the deflector of the concealed sprinkler to drop and be exposed
to the heat from the fire.
While the finish of the cover plate might concern you more than the finish of
the concealed fire sprinkler itself, these fire sprinklers are available in brass and are
available in quick response and standard response. The cover plates are available in
white, chrome, and black, with special colors available upon request.
Fire pumps are also essential parts of building fire sprinkler systems. When
the sprinkler system is activated by a heat or smoke detector, sprinklers set into the
walls or ceilings distribute water throughout the building. Again, high pressure is
required to ensure the entire building or area is saturated. The pump provides water
flow at a higher pressure to the sprinkler system risers and hose standpipes.
The fire pump starts when the pressure in the fire sprinkler system drops
below a threshold. The sprinkler system pressure drops significantly when one or
more fire sprinklers are exposed to heat above their design temperature, and opens,
releasing water. Alternately, other fire hoses reels or other firefighting connections are
opened, causing a pressure drop in the fire-fighting main.
Fire pumps are needed when the local municipal water system cannot provide
sufficient pressure to meet the hydraulic design requirements of the fire sprinkler
system. This usually occurs if the building is very tall, such as in high-rise buildings,
or in systems that require a relatively high terminal pressure at the fire sprinkler in
order to provide a large volume of water, such as in storage warehouses. Fire pumps
are also needed if fire protection water supply is provided from a ground level water
storage tank.
A smaller pump, called a jockey pump, is attached to the fire pump to
maintain this high pressure while the sprinkler system is operating.
designed to keep the pressure in the system elevated to a specific level when the
system is not in use, so that the fire pump doesn't have to run all the time and the
system doesn't go off randomly. It can also help prevent the system from damage
when a fire happens and water rushes into the pipes.
Sprinkler systems consist of pipes with pressurized water in them and heads
that are designed to open when they reach a certain temperature. When the heads
open, the water pressure in the pipes drops, since water is flowing out of them. When
this happens, a large device called a fire pump starts to send more water through the
pipes so that the system can continue to put out the fire.
The purpose of the jockey pump is to keep the water pressure in the pipes
within a specific range when there's not a fire, so that the sprinklers won't go off
randomly. Since pipes leak, over time, the water pressure inside them automatically
goes down. The jockey pump senses this, and then fills them back up to normal
pressure. If a fire happens and the pressure drops dramatically, the jockey pump won't
be able to keep up, and the drop in pressure will trigger the large fire pump to start
sending water.
Secondarily, this pump prevents sprinkler systems from being damaged when
the fire pump begins sending water. If a system does not have a jockey pump keeping
it pressurized, it may have a relatively low pressure. When the fire pump starts
sending highly pressurized water through the pipes, the sudden change in pressure can
damage or destroy the system.
26
The type of motor used also depends largely on the size of the sprinkler
system. The two main choices for jockey pump motors are single-phase and three-
phase. Both work largely the same way, though single phase motors are typically used
for smaller, lower pressure systems since they're not as powerful. Controllers can also
be either single-phase or three-phase, and differ primarily in the complexity of their
assembly.
class IP20 and designed for installation in a control cabinet. The fig 3.2 shows a S7-
1500 series PLC design.
The Simatic S7-1500 series are famous for its convincing functionalities. They
are-
1. High performance (probably the fastest controller worldwide)
2. Integrated system diagnostics (fast failure detection and correction)
3. Functional design (easy handling and installation)
4. Security integrated (reliable protection of investments and expertise)
5. Safely integrated (fail-safe control for all functions)
6. Technology integrated (optimally prepared for all technological tasks)
7. Engineering in the TIA Portal (efficient engineering in the TIA Portal) [18].
The function of a water flow switch is to detect water flow in the sprinkler
system, usually during a fire event, to signal a local electrical fire alarm, or fire alarm
panel to activate the alarm devices in the building.