Vous êtes sur la page 1sur 9

Mark 2 Control Startup Issue

Mark-2 speedtronic control startup failure as soon as 14HS signal appears.

By Haroon on 29 May, 2018 - 3:58 pm

We have speedtronic control for frame-1 GT control. Recently Gas Turbine


was stopped for overhauling and after maintenance activities unit was
started. however it is continuously tripping during startup at 82% HP speed
as soon as 14HS signal appears. At the Same time PCD FAILURE ALARM
also appears.

We have checked compressor discharge pressure transmitter PCD which is


OK, speed picks, thermocouples and their groundings which are
appropriate.

Please find below relevant parameters at the stage where unit trip.
Exhaust average temp = about 390 deg C
PCD = 4.5 bar
HP SPEED = 82%
LP SPEED = 71%

We have attempted to replace calibrated SSKC startup card, STKK cards


and tried for startup various times, however results are same.

Please suggest failure cause and its rectification.


Please feel free in case of any query.

Best Regards,

By otised on 29 May, 2018 - 8:43 pm

Haroon,

What was overhauled? What, if anything, was done to the control system
during the overhaul? Is 82% HP SPEED the correct setting for 14HS? Can
you provide the logic for the PCD FAILURE ALARM? Are there any
other alarms appearing - both before and after the event? I am inclined to
believe the problem is NOT with the control.
Note: It's been a really long time since I looked at a Frame 1 - early 1977, I
think. The control originally supplied with the Frame 1 GT's was sort of a
half breed. It used the Mark II analog control module, but retained the
Mark I relay sequencing.

By glenmorangie on 29 May, 2018 - 10:34 pm

Yes, Nuovo Pignone called MK 1.5 just to confuse everyone. From


memory, 14HS is around there, it is a twin shaft.

By glenmorangie on 29 May, 2018 - 9:23 pm

I don't have any MKII drawings at the moment. What is in the "PCD
Failure" alarm rung. It looks like the system sees a PCD Failure when it
hits 14HS, I know you have checked the transmitter but maybe you just
have a rung problem in the alarm.

By Haroon on 30 May, 2018 - 3:10 pm

Thanks for ur response.

One important thing I want to share. We have replaced sensing point of


PCD transmitter from its original tapping to another point of compressor
discharge. same casing because original sensing point was badly choked.
As per mechanical team the replaced point are same. Please advise if is
ok?

Secondly, we have recorded PCD pressure from field gauge and control
room indicator which is showing 4.5 bar till 14HS signal. Please advise
how we can catch the problem.
By glenmorangie on 30 May, 2018 - 7:57 pm

No problem in changing the PCD tapping point. Yes, you are getting
PCD pressure but you still haven't told us what the logic is for the
Alarm?

By adeel on 3 June, 2018 - 3:09 am

Dear Control Gurus,

Further to above problem in Speedtronic Mark-II system.

We have checked the control system in detail and also carried out the
"Dry run test" its a simulation with GE provided calibrator. Everything
worked fine and complete sequence was achieved. However, in actual
startup problem remains the same, and unit tripped as soon as 14HS
signal was achieved. Detailed investigation carried out and following
was observed.
1. When HP speed raised to 14HS (82% NHP) main protective signal
"4" becomes "0" and unit tripped.

2. Verified the tripping logic by connecting the recorders at test points


of VMPA cards. NO protection signal was generated.

3. In dry run test everything worked fine however, problem appeared in


actual unit running condition.

4. there is SLEH card where two major inputs 14HS and 4 signal
"AND" and latched. Before the 14HS signal 4 signal =1 , 14HS=0

5. As per requirement as soon as 14 HS achieved 14HS= 1 , 4 signal


=1 and both latched to provide 14HSX = 1.

6. However, in our case as soon as 14HS=1 the 4 signal = 0 and unable


to latch the 14HSX signal as well.

7. Please note that at 14HS signal bleed valve solenoid also operate at
field.
In last startup we concluded that main master protective signal '4"
becomes "0" as soon as 14Hs signal appeared. we have already
replaced corresponding logic cards. The system tripped without any
alarm . The PCD alarm discussed above appear after tripping as its
value decrease below minimum set point. Hence, we are sure problem
in not due to PCD.

We are unable to identify the signal which cause tripping of unit as no


alarm is available at annanciator.

Further, please advice if we can bypass master protective signal "4" by


providing external power source .

Best Regards,

By otised on 3 June, 2018 - 5:22 pm

adeel,
I would advise you to look into any external trip inputs to the Mark II
panel. I don't know what the load equipment is, maybe a compressor?
Typically there is at least one hardwired input from the load or other
equipment external to the gas turbine that will trip the gas turbine.
Sometimes these trips are enabled only after the gas turbine reaches a
certain point in the startup sequence like 14HS or 14HSX. The fact
that you were able to simulate a successful startup using the calibrator
leads me to suspect the source of the problem is outside of the Mark
II panel. I would also look at any outputs from the turbine control that
are used in external logic that operates the external trip input to the
turbine control.

Maybe there was work on the load equipment during your


maintenance outage. I have personally witnessed and solved this type
of issue before.

By adeel on 3 June, 2018 - 10:13 pm

In our case external load in Generator. Typically these external


signals are for Fire & Gas system, Manual trip push button at field,
generator main breaker etc. However, i will check in detail and get
back to you.

Thanks for your prompt reply and cooperation.

Regards,

Your use of this site is subject to the terms and conditions set forth under
Legal Notices and the Privacy Policy. Please read those terms and conditions
carefully. Subject to the rights expressly reserved to others under Legal
Notices, the content of this site and the compilation thereof is © 1999-2019
Nerds in Control, LLC. All rights reserved.

Vous aimerez peut-être aussi