Vous êtes sur la page 1sur 8

Sl.

Total Erection
Item Description Units
No. Quantity Rate

NEW 11 KV OVER HEAD LINE


GPS Survey & route alignment, pole spotting, preparation of survey report and uploading in the web portal after
1 63.95 KM 0
taking approval of Project Manager.
Excavation of pole pit (of depth 1/6th of pole length) in normal soil & Erection of poles for 11 KV overhead line by
supplying concrete base slab & cement concrete foundation made of 1 part cement, 3 part sand, 6 part 40 mm size
stone aggregate chips (1:3:6) and muffing made of 1 part cement, 2 part sand, 4 part 40 mm size stone aggregate
chips (1:2:4) as per TS and including painting by red oxide, aluminium paint , black anti corrosive paint along with
providing and installing of danger plate, anti-climbing devices (barbed wire)as per scope of work and technical
specification.
2 13 m long H-Beam 152x152 mm, 37.1 kg/mtr 1363 NO 2025
Erection, testing &commissioning of prefabricated galvanized steel items like V cross arm, top adopter, top channel
3 ,cross bracing, bracing, clamps, T off bracket for overhead structures including supply of required CI packing piece ,GI 52.26 MT 3285
nuts, bolts & washers as per technical specification, approved drawings and scope of work.
4 Fixing of cradle guard (including fixing of lead wire GI Wire 6 SWG and cross lacing wire GI Wire 8 SWG ) 2 MT 8085
Earthing arrangement using Earth Spike (1853x20)mm & 6 SWG GI Wire as per technical specifications, approved
5 1027 SET 83
drawings and scope of work.
Excavation of stay pit in all type of soils as per scope of work, approved drawings and specifications & Erection of
complete stay set having anchor plate (230x230x6),1.83 m long, 20 mm diameter solid GS stay rod with GI stay wire
6 (7/3.15 mm dia), binding of stay wire, by providing Guy stay insulator (1 Nos.), 1 No turn buckle by 0.2 cmt concreting 1559 SET 285
1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) and ramming by earth & brickbat as per
technical specifications, approved drawings and scope of works.
Erection, testing and commissioning of 11 kV insulator including their hardware fittings as per technical specification,
approved drawings and scope of work.
7 11 kV polymer Pin insulator with GI pin (Composite) 3675 SET 12
8 11 kV polymer Disc insulator with strain hardware (Composite) 1404 SET 14
Erection, testing , commissioning & jumpering of ACSR Conductor 100 sqmm (Dog) including supply and fixing of
9 aluminium tie wire , PG Clamps, compression joints , flat armour tape etc as required as per approved drawings, scope 51.35 CKM 4425
of work and technical specifications
11 KV UNDERGROUND RAILWAY CROSSING
11 KV LINE FOR UNDER GROUND RAILWAY/HIGH ROAD CROSSING BY 2 Nos (INCLUDING ONE SPARE) 3Cx300 Sqmm
XLPE Armoured Cable (0.15 KM each) including supply of 160 mm DIA, 10mm thick HDPE PIPE by Jack Push method
(Average Boring length 120 meter) and 30 meter length for riser , with sealing or plugging & earthing complete at
1.1 both end and laying of (3C) 300 sqmm XLPE CABLE, OUTDOOR HEAT SHRINKABLE CABLE JOINTING KITS, 4 Nos GI 3- 84 SET 90,125
METERS LONG EARTHING PIPE, 6SWG GI WIRES , CABLE MARKERS, BI METALLICK CLAMPS, JUMPERING WITH ACSR
DOG CONDUCTOR(10 Mtrs), 12 KV LIGHTENING ARRESTOR DISTRIBUTION CLASS 5 KA (2 SET.), etc AS REQUIRED AS
PER TECHNICAL SPECIFICATIONS, APPROVED DRAWING AND SCOPE OF THE WORK. (1SET=3 NoS)
11 KV line for Under Ground railway/high road crossing by 2 nos. (including one spare) 3C x 300 sq mm. XLPE Armored
cable (0.15 km each) including supply of 160 mm dia, 10mm thick HDPE pipe by jack push method (average boring
length 120 meter) and 30 meter length for riser , with sealing or plugging & earthing complete at both end and laying
10 of (3C) 300 sq mm. XLPE cable, outdoor heat shrinkable cable jointing kits, 4 nos GI 3-meters long earthing pipe, 6 4 SET 90,125
SWG GI wires, cable markers, bi metallic clamps, jumpering with ACSR DOG conductor (10 Mtrs), 12 KV lightening
arrestor distribution class 5 KA (2 set.), etc. as required as per technical specifications, approved drawing and scope
of the work. (1set=3 nos.)
11 KV NEW LINE BY HT AB
GPS Survey & route alignment , pole spotting, preparation of survey report and uploading in the web portal after
11 126.07 KM 530
taking approval of Project Manager.
Excavation of pole pit (9 mt PCC pole) ( depth 1/6th of pole length) in Normal soil & Erection of poles for 11 KV
12 overhead line (AB Cable) with supply of base plate as per TS which will be well rammed with earth mixed with brick 3152 NO 645
bats with excavated earth ( Brick bats : Earth ; 60:40) , etc as per scope of work, approved drawings and specifications
Erection, testing &commissioning of pre-fabricated galvanized steel items for suspension clamps using MS Flat (65x6)
for overhead structures including supply of GI nuts, bolts & washers(to be supplied by Bidder) in 9 MT PCC single pole
13 10.06 MT 3285
as per technical specification, approved drawings and scope of work. (GI nuts, bolts & washers to be supplied by the
bidder)
Excavation of stay pit in all type of soils as per scope of work, approved drawings and specifications & Erection of
complete stay SET having anchor plate (230x230x6),1.83 m long, 20 mm diameter solid GS stay rod with GI stay wire
14 (7/3.15 mm dia), binding of stay wire, by providing Guy stay insulator (1 Nos.), 1 No turn buckle by 0.2 cmt concreting 2521 SET 285
1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) and ramming by earth & brickbat as per
technical specifications, approved drawings and scope of works.
Erection, testing & commissioning of new aerial bunched XLPE cable 95x3 +80x1 including supply of GI hook, tension
15 clamps for dead end, suspension clamps, , MS nuts & bolts ,other clamps as required as per technical specification, 126.07 KM 5365
approved drawings and scope of work:
Straight through joints, outdoor joints, tee tap joint etc for connectivity with DTR & OH Line of 11 KV new aerial
bunched XLPE cable 95x3 +80x1 sqmm
STRAIGHT THROUGH JOINT OF HT (11 KV) AB CABLE, SIZES 1C X 95 SQ.MM ALONG WITH SUPPLY OF HEAT
16 126 SET 465
SHRINKABLE JOINTING KIT.(1 SET=3 Nos)
OUT DOOR TERMINATION OF 1C X 95 SQ.MM ALONG WITH SUPPLY OF HEAT SHRINKABLE JOINTING KIT. (1SET = 3
17 252 SET 465
NoS)
TEE JOINT TAP FROM HT ABC TO DTR FOR 1C X 95 SQ.MM CONTAINS 2 NoS. POLY SA 1 No. 1.5M. BUS TUBING FOR
18 630 SET 465
11 KV & 1 No ALUMUNIUM BUSBAR WITH JOINTING KIT (1SET = 3 NoS)
Earthing arrangement using Earth Spike (1853x20)mm & 6 SWG GI Wire as per technical specifications, approved
19 3152 SET 83
drawings and scope of work.
159 13 m long H-Beam 152x152 mm, 37.1 kg/mtr 806 NO 2025
DISTRIBUTION TRANSFORMER SUBSTATION
Excavation of pole pit (of depth 1/6th of pole length) in Normal soil & Erection of poles for 11 KV DTR S/stn by
supplying concrete base slab & cement concrete foundation made of 1 part cement, 3 part sand, 6 part 40 mm size
stone aggregate chips (1:3:6) and muffing made of 1 part cement, 2 part sand, 4 part 40 mm size stone aggregate
chips (1:2:4) as per TS and including painting by red oxide, aluminium paint , black anti corrosive paint by providing
and installing of danger plate, anti-climbing devices( barbed wire)as per scope of work and technical specification.

20 13 m long H-Beam 152x152 mm 37.1 kg/m 632 NO 2025


Erection, testing &commissioning of all pre-fabricated galvanized steel items as per drawing and scope of works
21 including supply of required galvanized nuts, bolts, washer etc and supply & fixing of barbed wire for ant climbing 74.53 MT 3285
device and danger plate as per drawing and scope of work
Excavation of stay pit in all type of soils as per scope of work, approved drawings and specifications & Erection of
complete stay SET having anchor plate (230x230x6),1.83 m long, 20 mm diameter solid GS stay rod with GI stay wire
22 (7/3.15 mm dia), binding of stay wire, by providing Guy stay insulator (1 Nos.), 1 No turn buckle by 0.2 cmt concreting 1264 SET 285
1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) and ramming by earth & brickbat as per
technical specifications, approved drawings and scope of works.
Erection, testing and Commissioning of 11 KV, 200 A, 3-pole Vertical Mounting type Gang Operated ,AB Switch for
23 316 SET 175
Distribution Transformer Substation as per Technical Specification, approved Drawing & Scope of works
Erection, Testing and Commissioning of Distribution Transformer 315/100 KVA (11/0.415 kV) Aluminium wound
(ONAN) Energy Efficiency Level-2 as specified in IS 1180(PART-I): 2014 with all accessories using turn buckle and
numbering of Transformer as per scope of work, approved drawings and specifications:
24 New 315 KVA (11/0.415 kV) DTR 15 NO 2265

25 New 100 KVA (11/0.415 kV) DTR 301 NO 1785


Erection, testing and commissioning of 11 kV insulator including their hardware fittings and making of necessary
connection up to DTR incoming by ACSR conductor including supply and erection of required PG Clamp , making of
horn gap fuse unit as per technical specification, approved drawings and scope of work.
26 11 kV Polymer Pin insulator with GI Pin (composite) 2844 SET 12

27 11 kV Polymer Disc insulator with strain hardware (composite) 948 SET 14

28 PG Clamp for DOG Conductor 948 NO 7


Erection, testing and commissioning of 12 KV, 5 KA Distribution Class Lightning Arrester for DT as per technical
29 316 SET 56
specification, approved drawings and scope of work.
Erection, testing and Commissioning of Outdoor mounting type Distribution box made of MS sheet of thickness Not
less than 2 mm, dust and moisture vermin, weather proof with degree of protection IP 33 as per IS 13947 with
suitable bus bars, earthing bus, earthing terminals, box illumination, front door operated with proper locking
arrangement, Nonmagnetic 4 mm thick gland plate, double compression brass cable glands, lugs, mounting channel
frame, internal wiring with FRLS cables, danger plate, numbering, back clamps, hardware as per scope of the work,
technical specifications and approved drawings suitable for following transformer:
3 Ph 315 KVA Transformer having 600 A TPN isolator, 500 A HRC fuse (incomer) and 12 Nos. 120 A SP MCCB
30 15 NO 326
(outgoing)
31 3 Ph 100 KVA Transformer having 200 A TPN isolator, 160A HRC fuse (incomer) and 6 Nos. 90 A SP MCCB (outgoing) 301 NO 239
Erection, testing and Commissioning of 3 NoS Pipe earthing by 40 mm dia ,3000 mm long GI pipe Earth electrode
making earth grid and riser using 50X6 MM GI Flat / (5 MM) GI WIRE and connecting riser to various equipment’s
32 316 SET 621
complete as per scope of work for Distribution Transformer Substations, approved drawings and technical
specifications .
Erection, testing and Commissioning of 1.1 KV XLPE single core Aluminium Conductor, Stranded, unarmoured cable
(300 / 120) sqmm for connection of transformer LV bushing to Meter incoming end & Meter Outgoing end to
Distribution Box and (185 / 95) sqmm from Distribution box to LT line along with supply & erection of necessary cable
sockets ,nut bolts, plastic tape etc. & proper dressing as per Scope of work, technical specification and approved
drawings
Laying of XLPE SINGLE CORE 1.1 KV GRADE 300 SQ. MM FROM LV BUSHING TO METER INCOING END & METER
33 0.6 KM 8085
OUTGOING END TO DISTRIBUTION BOX
34 Laying of XLPE CABLE SINGLE CORE 1.1 KV GRADE 185 SQ. MM FOR DISTRIBUTION BOX TO LT LINE 1.8 KM 7185
Laying of XLPE SINGLE CORE 1.1 KV GRADE 120 SQ. MM FROM LV BUSHING TO METER INCOING END & METER
35 12.04 KM 5965
OUTGOING END TO DISTRIBUTION BOX
36 Laying of XLPE CABLE SINGLE CORE 1.1 KV GRADE 95 SQ. MM FOR DISTRIBUTION BOX TO LT LINE 36.12 KM 4765
LT AB NEW
GPS Survey & route alignment , pole spotting, preparation of survey report and uploading in the web portal after
37 15.56 KM 0
taking approval of Project Manager.
Excavation of pole pit (of depth 1/6th of pole length) in normal soil & Erection of the poles for LT overhead line in
38 pole pit with supply of concrete base slab and the pit will be well rammed with earth mixed with brick bats & 467 NO 415
excavated earth ( Brick bats : Earth ; 60:40) etc. as per scope of work, approved drawings and specifications (8 mt PCC)
Excavation of stay pit in all type of soils & Erection of complete stay set with anchor plate (150x150x6mm), 65x6mm
stay clamp, LT guy insulator, nut bolts, 1 Nos turn buckle, 1.68 m long, 16 mm diameter solid GS Stay rod & 7/2.5 mm
39 233 SET 285
Dia GI stranded wire and . 0.2 cmt concreting 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips
(1:3:6) and ramming as per specification and scope of work
Erection, testing & commissioning of new areal bunched cable 50x3+35x1+16x1 ,providing and erecting tension
40 clamps for dead end, suspension clamps as per technical specification, approved drawings and scope of work including 15.56 KM 4185
supply of required galvanized nuts and bolts
IPC , Bimetallic Crimping type water proof lugs & straight through joints including supply of cable end cap & cable tie
for LT AB Cable (50x3+35x1+16x1) sqmm & its erection
41 Supply & Fixing of IPC for connecting neutral wire messenger to street light cable (for 35 & 50 sqmm) phase side 467 NO 0
42 Supply & Fixing of IPC for connecting phase side to street light cable (16 sqmm) 467 NO 0
43 Supply & Fixing of IPC for 50 sqmm both main and service cable for connecting Distribution Box 1867 NO 0
44 Supply & Fixing of insulating piercing connector for ABC Tee connection including connection with AB Cable 389 NO 0
Supply & Fixing of pre insulated straight through joint for 50 sqmm power cable ,35 sqmm neutral messenger ,16
45 78 NO 0
sqmm 1 ph street light along with cable tie and its locking arrangement
46 Supply & Fixing of bimetallic crimping tool type water proof lug for 50 sqmm power cable 47 NO 0
47 Supply & Fixing of bimetallic crimping tool type water proof lug for 35 sqmm neutral messenger 16 NO 0
48 Supply & Fixing of bimetallic crimping tool type water proof lug for 16 sqmm 1 Ph Street light 16 NO 0
49 cable end cap for aforesaid cable 389 NO 0
50 Cable tie with adjustable locking arrangement 5133 NO 0
Earthing arrangement using Earth Spike (1853x20)mm & 6 SWG GI Wire as per technical specifications, approved
51 467 SET 83
drawings and scope of work.
Erection, fitting, fixing & engineering of SMC Box on the pole with fittings & connection at SMC (charging) as per
52 467 SET 52
specification and scope of work
Shifting connection from existing line to new line as per site requirement
53 Dismantle of Existing service connection and reconnection through SMC Box (single phase) 778 NO 36
54 Dismantle of Existing service connection and reconnection through SMC Box(three phase) 31 NO 56
LT LINE : NEW FEEDER ACSR RABBIT
GPS Survey & route alignment , pole spotting, preparation of survey report and uploading in the web portal after
55 8.56 KM 0
taking approval of Project Manager.
Excavation of pole pit (8 mtr PCC) (of depth 1/6th of pole length) in Normal soil & Erection of the poles for LT
56 overhead line in pole pit with supply of concrete base slab and the pit will be well rammed with earth mixed with brick 206 NO 415
bats & excavated earth ( Brick bats : Earth ; 60:40) etc. as per scope of work, approved drawings and specifications
Erection, testing &commissioning of pre-fabricated galvanized steel items like LT angle bracket , DI clamps etc. of
57 given sizes for overhead structures in 8 MT PCC as per technical specification and scope of work ( MS nuts, bolts & 3.15 MT 3285
washers to be supplied by the bidder)
Earthing arrangement using Earth Spike (1853x20)mm & 6 SWG GI Wire as per technical specifications, approved
58 206 SET 83
drawings and scope of work.
Excavation of stay pit in all type of soils & Erection of complete stay SET with anchor plate (150x150x6mm), 50x8mm
stay clamp, LT guy insulator, nut bolts, 1 Nos turn buckle, 1.68 m long, 16 mm diameter solid GS Stay rod & 7/2.5 mm
59 171 SET 285
Dia GI stranded wire and . 0.2 cmt concreting 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips
(1:3:6) and ramming as per specification and scope of work
Erection, testing and commissioning of shackle insulator including their hardware fittings as per technical specification,
60 1028 NO 6
approved drawings and scope of work.
Erection, testing commissioning & jumpering of ACSR Conductor of 50 SQMM sizes including supply and erection
61 jointing sleeves, Aluminium binding wire,LT spacer etc as required as per approved drawings, scope of work and 8.56 CKM 2655
technical specifications
Augmentation, Renovation and Modernisation of existing lines and substations
LT AB CONVERSION
GPS Survey & route alignment , pole spotting, preparation of survey report and uploading in the web portal after
62 397.81 KM 0
taking approval of Project Manager.
Excavation of pole pit for additional poles (of depth 1/6th of pole length) in Normal soil & Erection of the poles for LT
overhead line in pole pit with supply of concrete base slab and the pit will be well rammed with earth mixed with brick
63 3978 NO 415
bats & excavated earth ( Brick bats : Earth ; 60:40) etc. as per scope of work, approved drawings and specifications (8
mtr PCC)
Excavation of stay pit in all type of soils & Erection of complete stay SET with anchor plate (150x150x6mm), 65x6mm
stay clamp, LT guy insulator, nut bolts, 1 Nos turn buckle, 1.68 m long, 16 mm diameter solid GS Stay rod & 7/2.5 mm
64 3978 SET 285
Dia GI stranded wire and . 0.2 cmt concreting 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips
(1:3:6) and ramming as per specification and scope of work
Erection, testing & commissioning of new areal bunched cable 50x3+35x1+16x1 ,tension clamps for dead end,
65 suspension clamps, piercing connectors MS nuts & bolts , as per technical specification, approved drawings and scope 397.81 KM 4185
of work including supply of required galvanized nuts and bolts
IPC , Bimetallic Crimping type water proof lugs & straight through joints including supply of cable end cap & cable tie
for LT AB Cable (50x3+35x1+16x1) sqmm & its erection
66 Supply & Fixing of IPC for connecting neutral wire messenger to street light cable (for 35 & 50 sqmm) phase side 11934 NO 0
67 Supply & Fixing of IPC for connecting phase side to street light cable (16 sqmm) 11934 NO 0
68 Supply & Fixing of IPC for 50sqmm both main and service cable for connecting Distribution Box 47737 NO 0
69 Supply & Fixing of insulating piercing connector for ABC Tee connection including connection with AB Cable 9945 NO 0
Supply & Fixing of pre insulated straight through joint for 50 sqmm power cable ,35 sqmm neutral messenger ,16
70 1989 NO 0
sqmm 1 ph street light along with cable tie and its locking arrangement
71 Supply & Fixing of bimetallic crimping tool type water proof lug for 50 sqmm power cable 1193 NO 0
72 Supply & Fixing of bimetallic crimping tool type water proof lug for 35 sqmm neutral messenger 398 NO 0
73 Supply & Fixing of bimetallic crimping tool type water proof lug for 16 sqmm 1 Ph Street light 398 NO 0
74 cable end cap for aforesaid cable 9945 NO 0
75 Cable tie with adjustable locking arrangement 131277 NO 0
Dismantling of existing overhead line conductor & fittings (if any) and depositing the dismantled materials to the
76 397.81 CKM 1465
respective Divisional stores of WBSEDCL
Earthing arrangement using Earth Spike (1853x20)mm & 6 SWG GI Wireas per technical specifications, approved
77 3978 SET 83
drawings and scope of work.
Erection of SMC Box on the pole with fittings, earthing and dismantling of single phase and three phase connection
and refixing as per specification and scope of work
78 Erection of SMC Box with all fittings 11934 SET 52
79 Dismantle of Existing service line and refixing again(single phase) 39781 NO 36
80 Dismantle of Existing service line and refixing again(three phase) 796 NO 56
Erection, testing &commissioning of pre-fabricated galvanized steel items like GI clamps etc of given sizes for
161 overhead structures in 8 MT PCC as per technical specification and scope of work ( MS nuts, bolts & washers to be 47.19 MT 3285
supplied by the bidder) (REQUIRED AS PER SITE CONDITION)
11 KV LINE AUGMENTATION
GPS Survey & route alignment , pole spotting, preparation of survey report and uploading in the web portal after
81 83.67 KM 0
taking approval of Project Manager.
Excavation of additional pole pit (of depth 1/6th of pole length) in normal soil & Erection of poles for 11 KV overhead
line by supplying concrete base slab & cement concrete foundation made of 1 part cement, 3 part sand, 6 part 40
mm size stone aggregate chips (1:3:6) and muffing made of 1 part cement, 2 part sand, 4 part 40 mm size stone
82 335 NO 2025
aggregate chips (1:2:4) as per TS and including painting by red oxide, aluminium paint , black anti corrosive paint by
providing and installing of danger plate, anti-climbing devices( barbed wire)as per scope of work and technical
specification. (12.8 mtr long Rail Pole (52/kg mtr) (single pole)
Erection, testing &commissioning of prefabricated galvanised steel items like V cross arm, top adopter, top channel
,cross bracing, clamps for overhead structures , CI packing piece, GI nuts, bolts & washers, supply and fixing of danger
83 20.78 MT 3285
plate (at DP) , supply of barbed wire and installation of anti-climbing device (at DP) as per technical specification,
approved drawings and scope of work. (GI nuts, bolts & washers & CI packing piece to be supplied by the bidder).
84 Fixing of cradle guard (including fixing of lead wire and cross lacing wire ) 3.26 MT 8085
Excavation of stay pit in all type of soils as per scope of work, approved drawings and specifications & Erection of
complete stay set having anchor plate (230x230x6),1.83 m long, 20 mm diameter solid GS stay rod with GI stay wire
85 (7/3.15 mm dia), binding of stay wire, by providing Guy stay insulator (1 Nos.), 1 No turn buckle by 0.2 cmt concreting 1171 SET 285
1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) and ramming by earth & brickbat as per
technical specifications, approved drawings and scope of works.
Erection, testing and commissioning of 11 kV insulator including their hardware fittings as per technical specification,
approved drawings and scope of work.
86 11 kV polymer Disc insulator with strain hardware (Composite) 502 SET 14
87 11 kV polymer Pin insulator with GI pin (Composite) 753 SET 12
Erection, testing ,commissioning & jumpering of ACSR Conductor of 100 sqmm including supply and fixing of
88 aluminium tie wire, PG Clamps, compression joints , flat armour tape etc. as required as per approved drawings, 83.67 CKM 4425
scope of work and technical specifications
Dismantling of existing overhead line conductor & fittings (if any) and depositing the dismantled materials to the
89 83.67 CKM 1465
respective Divisional stores of WBSEDCL
Earthing arrangement using ( Spike Earthing 1853X20 mm solid Rod, using 5 mm GI wire) as per technical
90 837 SET 83
specifications, approved drawings and scope of work.
11 KV LINE CONVERSION BY HT AB
GPS Survey & route alignment , pole spotting, preparation of survey report and uploading in the web portal after
91 178.57 KM 0
taking approval of Project Manager.
Excavation of pole pit (9 mtr PCC pole) ( depth 1/6th of pole length) in Normal soil & Erection of poles for 11 KV
92 overhead line (AB Cable) with supply of base plate as per TS which will be well rammed with earth mixed with brick 1786 NO 645
bats with excavated earth ( Brick bats : Earth ; 60:40) , etc. as per scope of work, approved drawings and specifications
Erection, testing &commissioning of prefabricated galvanized steel items like clamps etc. made of MS flats 65x6 for
93 overhead structures 9 mt PCC (Single pole) as per technical specification, approved drawings and scope of work (GI 14.25 MT 3285
nuts, bolts & washers to be supplied by the bidder)
Excavation of stay pit in all type of soils as per scope of work, approved drawings and specifications & Erection of
complete stay SET having anchor plate (230x230x6),1.83 m long, 20 mm diameter solid GS stay rod with GI stay wire
94 (7/3.15 mm dia), binding of stay wire, by providing Guy stay insulator (1 Nos.), 1 No turn buckle by 0.2 cmt concreting 1786 SET 285
1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips (1:3:6) and ramming by earth & brickbat as per
technical specifications, approved drawings and scope of works.
Erection, testing & commissioning of new aerial bunched XLPE cable 95x3 +80x1 including supply of GI hook, tension
95 clamps for dead end, suspension clamps, , MS nuts & bolts ,other clamps as required as per technical specification, 178.57 KM 5365
approved drawings and scope of work:
Straight through joints, outdoor joints, tee tap joint etc. for connectivity with DTR & OH Line of 11 KV new aerial
bunched XLPE cable 95x3 +80x1 sqmm
STRAIGHT THROUGH JOINT OF HT (11 KV) AB CABLE, SIZES 1C X 95 SQ.MM ALONG WITH SUPPLY OF HEAT
96 179 SET 465
SHRINKABLE JOINTING KIT.(1 SET=3 Nos)
OUT DOOR TERMINATION OF 1C X 95 SQ.MM ALONG WITH SUPPLY OF HEAT SHRINKABLE JOINTING KIT. (1SET = 3
97 357 SET 465
NoS)
TEE JOINT TAP FROM HT ABC TO DTR FOR 1C X 95 SQ.MM CONTAINS 2 NoS. POLY SA 1 No. 1.5M. BUS TUBING FOR
98 893 SET 465
11 KV & 1 No ALUMUNIUM BUSBAR WITH JOINTING KIT (1SET = 3 NoS)
Dismantling of existing overhead line conductor & fittings (if any) and depositing the dismantled materials to the
99 178.57 CKM 1465
respective Divisional stores of WBSEDCL
Earthing arrangement using (Spike Earthing 1853X20 mm solid Rod, using 5 mm GI wire) as per technical
100 1786 SET 105
specifications, approved drawings and scope of work.
162 13 m long H-Beam 152x152 mm 37.1 kg/m 466 MT 2025
Augmentation of 11/0.415 kV Distribution Transformer Substation
Erection, testing & commissioning of augmented Transformer 100 KVA (11/0.415 kV) Aluminium wound DTR
(ONAN),Energy Efficiency Level-2 as specified in IS 1180 (PART-I): 2014 with all accessories using turn buckles as
101 137 NO 1785
required and numbering including supply and fixing of danger plate (at DP) , supply of barbed wire and erection of
anti-climbing device (at DP) as per technical specifications, approved drawings and scope of the work.
102 Dismantling of existing DTR & unused materials and depositing it to respective Divisional stores 137 NO 285
Erection, testing & commissioning of new outdoor mounting type Distribution box made of MS sheet of thickness Not
less than 2 mm, dust and moisture vermin, weather proof with degree of protection IP 33 as per IS 13947 with
suitable bus bars, earthing bus, earthing terminals, box illumination, front door operated with proper locking
arrangement, Nonmagnetic 4 mm thick gland plate, double compression brass cable glands, lugs, mounting channel
frame, internal wiring with FRLS cables, danger plate, numbering, back clamps, hardware as per scope of the work,
technical specifications and approved drawings suitable for 3 Ph 100 KVA Transformer having 200 A TPN isolator, 160A
HRC fuse (incomer) and 6 Nos. 90 A SP MCCB (outgoing)
103 3 Ph 100 KVA Transformer having 200 A TPN isolator, 160A HRC fuse (incomer) and 6 Nos. 90 A SP MCCB (outgoing) 137 NO 239
Erection, testing and Commissioning of 1.1 KV XLPE single core Aluminium Conductor, Stranded, unarmoured cable
(120) sqmm for connection of transformer LV bushing to Meter incoming end & Meter Outgoing end to Distribution
Box and (95) sqmm from Distribution box to LT line along with supply & erection of necessary cable sockets ,nut
bolts, plastic tape etc & proper dressing as per Scope of work, technical specification and approved drawings
Laying of XLPE SINGLE CORE 1.1 KV GRADE 120 SQ. MM FROM LV BUSHING TO METER INCOMMING END & METER
104 5.48 KM 5965
OUTGOING END TO DISTRIBUTION BOX
105 Laying of XLPE CABLE SINGLE CORE 1.1 KV GRADE 95 SQ. MM FOR DISTRIBUTION BOX TO LT LINE 16.44 KM 4765
Erection, testing and Commissioning of 3 NoS Pipe earthing by 40 mm dia ,3000 mm long GI pipe Earth electrode
making earth grid and riser using 50X6 MM GI Flat / (5 MM) GI WIRE and connecting riser to various equipment’s
106 137 SET 623
complete as per scope of work for Distribution Transformer Substations, approved drawings and technical
specifications .
Erection, testing and commissioning of 12 KV, 5 KA Distribution Class Lightning Arrester for DT as per technical
107 137 SET 56
specification, approved drawings and scope of work.
Erection, testing &commissioning of Pre-fabricated hot dip galvanized steel items like DTR Base channel , all clamps
made of MS Channel (100x50x6), MS flats (65x6mm) of given sizes for DTR base Channel including supply of required
163 10.936 MT
CI packing piece ,GI nuts, bolts & washers as per technical specification, approved drawings and scope of work.
(REQUIRED AS PER SITE CONDITION)
LT LINE : AUGMENTATION TO ACSR RABBIT
GPS Survey & route alignment , pole spoting, preparation of survey report and uploading in the web portal after
108 125.74 KM 0
taking approval of Project Manager.
Excavation of pole pit (8 mt PCC) (of depth 1/6th of pole length) in Normal soil & Erection of the poles for LT
109 overhead line in pole pit with supply of concrete base slab and the pit will be well rammed with earth mixed with brick 629 NO 415
bats & excavated earth ( Brick bats : Earth ; 60:40) etc as per scope of work, approved drawings and specifications
Erection, testing &commissioning of pre-fabricated galvanized steel items like LT angle bracket , DI clamps etc. of
110 given sizes for overhead structures in 8 MT PCC as per technical specification and scope of work ( GI nuts, bolts & 15.18 MT 3285
washers to be supplied by the bidder)
Earthing arrangement using Earth Spike (1853x20)mm & 6 SWG GI Wire as per technical specifications, approved
111 1257 SET 83
drawings and scope of work.
Excavation of stay pit in all type of soils & Erection of complete stay set with anchor plate (150x150x6mm), 50x8mm
stay clamp, LT guy insulator, nut bolts, 1 Nos turn buckle, 1.68 m long, 16 mm diameter solid GS Stay rod & 7/2.5 mm
112 1257 SET 285
Dia GI stranded wire and . 0.2 cmt concreting 1 part cement, 3 part sand, 6 part 40 mm size stone aggregate chips
(1:3:6) and ramming as per specification and scope of work
Erection, testing and commissioning of shackle insulator with accessories as per technical specification, approved
113 3143 NO 5
drawings and scope of work.
Erection, testing commissioning & jumpering of ACSR Conductor 50 sqmm providing and using jointing sleeves
114 ,Aluminium binding wire ,LT spacer etc ,refixing of service lines as required as per approved drawings, scope of work 125.74 CKM 2655
and technical specifications
Dismantling of existing overhead line conductor & fittings (if any) and depositing the dismantled materials to the
115 125.74 CKM 1465
respective Divisional stores of WBSEDCL
CONVERSION OF 11 KV O/H LINE BY UG CABLE AND NEW 11 KV UNDERGROUND LINE
GPS Survey & route alignment , pole spoting, preparation of survey report and uploading in the web portal after
116 95.9 KM 0
taking approval of Project Manager.
Laying of heavy duty HDPE Pipe by Jack Push method without disturbing the regular railway or vehicular traffic above
maintaining statutory depth under highway carriageway with sealing or plugging & earthing complete at both end
117 10.09 KM 4,76,185
including supply of 160 mm (dia) NB HDPE pipe 10 mm (thickness) and associated materials and laying of 3C X 300
sqmm XLPE CABLE as per IS:4984-1995
Laying of heavy duty HDPE Pipe by microtunelling work without disturbing the regular railway or vehicular traffic
above maintaining statutory depth under highway carriageway with sealing or plugging & earthing complete at both
118 70.66 KM 4,76,185
end including supply of 160 mm (dia) NB HDPE pipe 10 mm (thickness) and associated materials and laying of 3C X 300
sqmm XLPE CABLE as per IS:4984-1995
Soil excavation by cutting of metalled road/cement concrete/brick soiling/paver block etc , laying of 11 kV (E) 3C x 300
Sq.mm XLPE Cable (Single Run) in trench, cable bonding & earthing, providing adequate brick (first class) & sand
119 (coarse) protection to the laid cable, backfilling of earth, compaction, levelling i.e re-instatement of the same as per 5.05 KM 1,43,500
instruction etc. complete as per drawing No PLN/(D)/SS/104 & IS .Completion certificate to be obtained from local
authority
Soil excavation by cutting of metalled road/cement concrete/brick soiling/paver block etc , laying of 11 kV (E) 3C x 300
Sq.mm XLPE Cable (Double Run) in trench, cable bonding & earthing, providing adequate brick (first class) & sand
120 (coarse) protection to the laid cable, backfilling of earth, compaction, levelling i.e re-instatement of the same as per 2.52 KM 2,07,500
instruction etc. complete as per drawing No PLN/(D)/SS/104 & IS.Completion certificate to be obtained from local
authority
Soil excavation, digging of burried trench of proper dimension maintaining statutory depth from the formation level as
per TS , dressing, laying of 11 kV (E) 3C x 300 Sq.mm XLPE Cable (Single Run) in trench, cable bonding & earthing,
121 providing adequate brick (first class) & sand (coarse) protection to the laid cable, backfilling of earth, compaction, 5.05 KM 1,06,200
levelling etc. complete as per drawing No PLN/(D)/SS/104 & IS.Completion certificate to be obtained from local
authority
Soil excavation, digging of burried trench of proper dimension maintaining statutory depth from the formation level as
per TS , dressing, laying of 11 kV (E) 3C x 300 Sq.mm XLPE Cable (Double Run) in trench, cable bonding & earthing,
122 2.52 KM 1,410,00
providing adequate brick (first class) & sand (coarse) protection to the laid cable, backfilling of earth, compaction,
levelling etc. complete as per drawing No PLN/(D)/SS/104 & IS.
Making of Heat Shrinkable Cable Jointing for 11 KV 3C x 300 sq.mm. XLPE cable

123 Making of Heat Shrinkable Outdoor Termination at DTR end for 11 KV, 3 C x 300 sq mm XLPE cable 1000 NO 570

124 Making of Heat Shrinkable Indoor Termination at RMU/BREAKER end for 11 KV, 3 C x 300 sq mm XLPE cable 244 NO 570

Making of Heat Shrinkable Cable Jointing for 11 KV 3C x 300 sq.mm. XLPE cable

125 Making of Heat Shrinkable Straight through Termination for 11 KV, 3 C x 300 sq mm XLPE cable 201 NO 570
Design, engineering, construction, supply of labour, material, curing, machine mix/hand mix for construction of Cable
126 201 NO 4425
straight through jointing pit as per technical specification and scope of work as per Drawing No PLN (D)/SS/106
Design, Engineering, labour, material and construction of RCC pedestal including the cost of excavation, concrete,
reinforcement, inserts, curing, form work, grouting, fixing of foundation bolts etc for Outdoor RMU as per (Ref Drg No
PLN(D)/SS/103,dt 05.05.2015) & Erection testing and commissioning of 11 KV, 3-Phase, 50 Hz, Outdoor Type SCADA
compatible SF6 Ring Main Unit and other accessories complete on pedestal as per TS (Foundation bolts to be supplied
by bidder)
Design, Engineering, labour, material and construction of RCC pedestal including the cost of excavation as per scope of
127 72 NO 4425
work and technical specification
128 Erection of 3 Way RMU 44 NO 1065

129 Erection of 4 Way RMU 28 NO 1095


Earthing Of outdoor 3/4 way RMU as per drawing consisting of 1 Nos , 3 meters long 40 mm dia medium gauge GI
130 Pipe (M) , installation & connection in between earth pipe and other equipments using 2 Nos GI Flat 40 mmx6 mm by 72 Job 245
welding complete and as per instruction of the Site Engineer ( including supply of all materials)
Supply and erection of Cast Iron Cable Marker on concrete foundation blocks for straight run, road crossing ,joint
131 1918 NO 36
location etc as per drawing ,specification and scope of work.
Complete dismantling of existing overhead conductors, poles & all pole top accessories and loading ,transportation
132 73 CKM 1785
,unloading ,handling over the same to respective Divisional stores of WBSEDCL .
Cable termination and making bus bar arrangements including holding arrangements (clamps) and fixing of 11 kV
133 polymer Pin insulator with GI pin (Composite), including supply of PG Clamps as per technical specification and scope 566 NO 1465
of work.
LT NEW UG LINE
GPS Survey of and preparation of provisional route plan for the upcoming underground cabling work to interconnect
134 23.6 KM 0
various newly installed Feeder Pillar Boxes with the LT Junction Box(Plot/Service).
Design, Engineering, construction, supply of labour, material of RCC /Cement concrete/masonary plinth /foundation
suitable for Feeder Pillar Box as per drg No (PLN(D)/SS/102),dt 05.05.2015 & Erection, Testing & Commissioning of 415
Volt, 3 Phase, 50 Hz, 400 Amp Outdoor type Feeder Pillar Box with all accessories complete(GLANDS AND LUGS TO BE
PROVIDED BY BIDDER) as per scope of work & technical specification.
Design, Engineering, construction, supply of labour, material of RCC /Cement concrete/masonary plinth /foundation
135 118 NO 1465
suitable for Feeder Pillar Box as per drg No (PLN(D)/SS/102),dt 05.05.2015
Erection, Testing & Commissioning of 415 Volt, 3 Phase, 50 Hz, 400 Amp Outdoor type Feeder Pillar Box with all
136 118 NO 239
accessories complete(GLANDS AND LUGS TO BE PROVIDED BY BIDDER)
Design, Engineering, construction, supply of labour, material of RCC /Cement concrete/masonary plinth /foundation
suitable for Junction Box as per drg No (PLN(D)/SS/102),dt 05.05.2015 & Erection, Testing & Commissioning of 415
Volt, 3 Phase, 50 Hz, 160 Amp weatherproof Junction Box(Service/Plot) as per requirement with all necessary
accessories including cable glands etc. complete (ALL GLANDS AND LUGS TO BE PROVIDED BY BIDDER) as per scope of
work & technical specification.
Design, Engineering, construction, supply of labour, material of RCC /Cement concrete/masonary plinth /foundation
137 236 NO 1280
suitable for Junction Box as per drg No (PLN(D)/SS/102),dt 05.05.2015
Erection, Testing & Commissioning of 415 Volt, 3 Phase, 50 Hz, 160 Amp weatherproof Junction Box with all necessary
138 236 NO 239
accessories including cable glands etc. complete (ALL GLANDS AND LUGS TO BE PROVIDED BY BIDDER)
Complete earthing of Feeder Pillar Box and Junction Box with GI Earth spike made of 1853 x 20 mm solid rod & G.I wire
139 708 NO 83
(5 mm) as per technical specification & scope of work .
Erection, testing and Commissioning of 1.1 KV XLPE 120 sqmm Aluminium Conductor, Stranded, unarmoured cable for
140 connection of transformer LV bushing to Feeder Pillar Box ,using plastic tape, necesary cable socket ,nut bolts etc as 59 NO 4765
per Scope of work, technical specification and approved drawings:(cable sockets & nut bolts to be supplied by bidder )
Laying of heavy duty HDPE Pipe by microtunelling work without disturbing the regular railway or vehicular traffic
above maintaining statutory depth under railway track or highway carriageway with sealing or plugging & earthing
141 1.18 KM 4,76,185
complete at both end including supply of 160 mm (dia) NB HDPE pipe 10 mm (thickness) and associated materials and
laying of 95 sqmm XLPE CABLE (4C) as per IS:4984-1995
Soil excavation by cutting of metalled road/cement concrete/brick soiling/paver block etc , laying of 1.1 kV (E) 4C x 95
Sq.mm XLPE Cable (Single Run) in trench, cable bonding & earthing, providing adequate brick & sand protection to the
142 11.8 KM 1,17,400
laid cable, backfilling of earth, compaction, levelling i.e re-instatement of the same as per instruction etc. complete as
per drawing No PLN/(D)/SS/104.Completion certificate to be obtained from local authority
Soil excavation, digging of burried trench of proper dimension maintaining statutory depth from the formation level as
per TS , dressing, laying of 1.1 kV (E) 4C x 95 Sq.mm XLPE Cable (Single Run) in trench, cable bonding & earthing,
143 10.62 KM 90,125
providing adequate brick & sand protection to the laid cable, backfilling of earth, compaction, levelling etc. complete
as per drawing No PLN/(D)/SS/104.
Soil excavation by cutting of metalled road/cement concrete/brick of soiling/paver block proper dimension
maintaining statutory depth from the formation level, dressing, laying of 1.1 kV 2C x 6 Sq.mm/4C X 10 Sq.mm/4C X 25
144 Sq.mm PVC Cable (Single Run) in trench, earthing, jointing, as per site requirement, termination at equipment ends by 5 KM 1,06,200
providing adequate brick & sand protection to the laid cable, backfilling of earth, compaction, levelling etc. complete
as per drawing no PLN/(D)/SS/104 & IS .Completion certificate to be obtained from local authority
Soil excavation, digging of burried trench of proper dimension maintaining statutory depth from the formation level,
dressing, laying of 1.1 kV 2C x 6 Sq.mm/4C X 10 Sq.mm/4C X 25 Sq.mm PVC Cable (Single Run) in trench, earthing,
145 jointing, as per site requirement, termination at equipment ends by providing adequate brick & sand protection to 20 KM 69,000
the laid cable, backfilling of earth, compaction, levelling etc. complete as per drawing no PLN/(D)/SS/104 & IS
.Completion certificate to be obtained from local authority
Complete dismantling of existing overhead conductors, LT poles ,top accessories and loading ,transportation
146 ,unloading ,handling over the same to respective stores and dismantling of service lines (single phase and three 23.6 CKM 1785
phase),service bracket from existing support and return to stores.
DTR METERING
Erection, testing & commissioning of 3-Phase, 4-Wire CT Operated Fully Static AMR Compatible Tri-vector Energy
Meter, Accuracy Class 0.5S for Distribution Transformer fitted with Pilfer Proof Single Chamber/Double Chamber
147 316 NO 81
Meter Box along with Kiosk fitted with 4 Nos. Resin Cast LTCT (Ring Type) of CT Ratio:600/5A for 315KVA DTRs and
200/5A for 100KVA DTRs

6. PAYMENT TERMS/ PRICE SCHEDULE

6.1 The Price schedule is as below:

6.2 100% payment will be made after 20 days of receiving of invoice.