ETP CONTROL
LOAD BREAK SWITCH

USER’S MANUAL

PT. ENTEC ELECTRIC INDONESIA

Copyright © 2018 by PT. ENTEC ELECTRIC INDONESIA all right reserved. Forerunner Distribution & Automation
SWITCH CONTROL ETS Table of Contents

TABLE OF CONTENTS
TABLE OF CONTENTS ........................................................................................................... 3

1. INTRODUCTION ........................................................................................................... 5

1.1. General Features.................................................................................................................. 5

2. SPECIFICATION ............................................................................................................ 6

2.1. Ratings................................................................................................................................. 6
2.2. Type Withstand Tests ........................................................................................................... 7
Electromagnetic Compatibility Immunity .......................................................................... 7
Environmental .................................................................................................................... 8
Safety.................................................................................................................................. 8
Etc. ..................................................................................................................................... 8

3. INSTALLATION ............................................................................................................. 9

3.1. User Interface Door and Power NFB .................................................................................. 9


3.2. Inner Structure ................................................................................................................... 10
3.3. Dimensions and Mounting .................................................................................................11
3.3.1. Control Cubicle .......................................................................................................11
3.3.2. Mount Accessories Dimensions ............................................................................. 12
3.3.3. Control Module ...................................................................................................... 12
3.4. Earth Wiring Diagram ....................................................................................................... 13
3.5. Terminal Block and Fuses ................................................................................................. 14
3.6. CT Protection Circuit ........................................................................................................ 15
3.7. Voltage Divider (VD) ........................................................................................................ 16
3.8. Voltage Transducer ............................................................................................................ 17
3.9. Control Cable Receptacle Pin Descriptions ...................................................................... 18
3.10. Control Cable Assembling / De-assembling ................................................................... 19
3.11. AC Power Receptacle Pin Descriptions .......................................................................... 19
3.12. AC Power Cable .............................................................................................................. 20
3.13. Fuses ................................................................................................................................ 20
3.14. Battery ............................................................................................................................. 21
3.14.1. Specs and Control Run Time ................................................................................ 21
3.14.2. Battery Protection................................................................................................. 22
3.14.3. Charge Circuit ...................................................................................................... 23

ENHANCED TECHNOLOGY 3
Table of Contents http://www.entecene.co.kr

3.14.4. Battery Change ..................................................................................................... 23


3.15. Connection Wiring Diagram............................................................................................ 24

4 ENHANCED TECHNOLOGY
SWITCH CONTROL ETS 2. SPECIFICATION

1. INTRODUCTION

1.1. General Features

 Control ETS is installed in Module ETMFC610 for operation.

 Sectionalizer and Tie function is already built in ETMFC610 for Loop Automation.

 ETMFC610(Multi-Function controller) has a built-in RTU and uses DNP, MODBUS for
communication.

 The basic control cubicle is provided with detection of phase and earth faults sensing from
current sensing elements and checks the live and dead line status from the voltage sensing
element.

ENHANCED TECHNOLOGY 5
Table of Contents http://www.entecene.co.kr

2. SPECIFICATION
2.1. Ratings

Systems
3phase-3wire or 3phase-4wire System

Frequency
50/60㎐ system and ABC/ACB phase rotation

Power supply
 AC Voltage Input : 220Vac (±20%)
 Nominal power : 15VA
 Maximum power : 200VA

Current Transformer Inputs (CT)


 Current Inputs IA,IB,IC
 Current Ratings
 Ratio : 600:0.6(Standard)
 Burden : 1VA/5P20
Voltage Divider (VD)
 Voltage Inputs Source(A,B,C) and Load( A,B,C)
 Voltage Ratings
 Primary resistor 100Momh
 Ratio : 1000:1

Heater
 Heater is 40W

6 ENHANCED TECHNOLOGY
SWITCH CONTROL ETS 3. INSTALLATION

2.2. Type Withstand Tests


Electromagnetic Compatibility Immunity
 Electrostatic Discharge Immunity : IEC 61000-4-2 : 2008
 Level 3 and 6㎸ contact, 8 ㎸ air
 Radiated electromagnetic field immunity : IEC 61000-4-3 : 2010
 10 V/m at 80㎒~1.0㎓ and 1.4㎓~2.7㎓
 Electrical Fast Transient Burst Immunity : IEC 61000-4-4 : 2012
 2 kV at 5 kHz (Communication Ports)
 Surge Immunity : IEC 61000-4-5 : 2017
 4 kV line to line
 4 kV line to earth
 4 kV Comm. ports
 Conducted disturbance immunity : IEC 61000-4-6 : 2013
 10 V at 150 kHz ~ 80 MHz
 Power frequency magnetic field immunity : IEC 61000-4-8 : 2009
 100 A/m (Continuous), 1 000 A/m (3s)
 Voltage dips, interruption and variation immunity : IEC 61000-4-11 : 2004
 Voltage disp immunity test : 0%, 40%, 70%, 80%
 Voltage interruptions immunity test : 0%
 Voltage variations immunity test : 70 % / 30 cycles
 Test for immunity to conducted, common mode disturbances : IEC 61000-4-16 : 2015
 30 V (continuous), 300 V (short duration)
 Oscillatory wave immunity : IEC 61000-4-18 : 2006
 Immunity test for 1 MHz burst ; Comm: 2.5 kV, Differential : 1.0 kV
 Immunity test for 100 kHz burst; Comm: 2.5 kV, Differential : 1.0 kV
 Emission test : CISPR 11 , Class A

ENHANCED TECHNOLOGY 7
3. INSTALLATION http://www.entecene.co.kr

Environmental
 Cold : IEC 60068-2-1 :2007
 Test Ad : 16 hours at -40℃
 Dry Heat : IEC 60068-2-2 :2007
 Test Ad : 16 hours at +85℃
 Damp heat, steady state : IEC 60068-2-3 : 1969
 Severity Level : 40℃, 4day,
 Relative Humidity : 93%
 Damp heat, Cyclic : IEC 60068-2-30 : 2005
 Severity Level : 25℃ to 55℃, 2cycles,
 Relative Humidity : 95%
 Vibration : IEC 60255-21-1 : 1988
 Shock and bump : IEC 60255-21-2 : 1988
 Seismic : IEC 60255-21-3 : 1993

Safety
 Dielectric Strength : IEC 60255-27 : 2013
 2000 Vac on control inputs, control outputs, and analog inputs, communication for 1minute
 Impulse : IEC 60255-27 : 2013, 0.5 J, 5 kV, 1.2/50 ㎲
 Insulation resistance : IEC 60255-27 : 2013, 100 ㏁ at 500 V d.c.

Etc.
 Degrees of protection provided by enclosures (IP Code) : IEC 60529 : 2013
 IP 55

8 ENHANCED TECHNOLOGY
SWITCH CONTROL ETS 3. INSTALLATION

3. INSTALLATION

3.1. User Interface Door and Power NFB

Door Switch
ETMFC610

Handle

V A / VR

V B / VS

VC / VT

TYPE : ETMFC610

SERIAL No : 18050001

DATE : 2018 . 05 . 17

POWER SUPPLY : 220 VAC

WEIGHT : 56 kg

Control Module

N L

User interface door


Manual Pocket Control Power NFB
AC Power Outlet

Figure 3-1. User Interface Door and Power NFB

User Interface Door


User Interface Door has two magnets upper and down(or top and bottom).To open the door,
pull the handle.

Control Power NFB


After opening the User Interface Door, you can see 2 NFB. Left side NFB is for Battery Power,
right side one is for AC Power. Turning on either one of two activates control.

AC Power Outlet
For user convenience, AC Power Outlet is located on User Interface Door. Fuse is installed for
safety from overload. Location of fuse is referred to “Figure 3-2. Inner Structure”

Manual Pocket
Space to store User’s Manual.

ENHANCED TECHNOLOGY 9
3. INSTALLATION http://www.entecene.co.kr

3.2. Inner Structure


User Available space
W350*L200*H100mm / M6

200
180
330
Terminal Block
350

Pad Lock
TYPE : ETMFC610

SERIAL No : 18050001

DATE : 2018 . 05 . 17

POWER SUPPLY : 220 VAC

WEIGH T : 56 kg

Battery

Fuse

Transducer Heater Power


SPD Control Power NFB
(option) Transformer
Left side : Battery
Right side : AC Power

Figure 3-2. Inner Structure

User Available Space


Space for additional hardware connection. Installation and space size refers to “Figure 3-4”
Control Power NFB
Left side NFB is for Battery, right side one is for 220Vac.
Fuse
TF1 are for circuit protection, refers to (see ”Table 3-6. Fuses”)
Terminal Block
Place for AC Power line, there are two ports for user.
Heater
Optional Heater is 40W
Transformer
Input:220Vac, Output: 24Vac
Battery
Use 2 of 12Vdc in series. Use (+) screwdriver for replacement.
For more detail, refer to (see “3.14. Battery”)

10 ENHANCED TECHNOLOGY
SWITCH CONTROL ETS 3. INSTALLATION

3.3. Dimensions and Mounting


3.3.1. Control Cubicle
25mm dia. 17mm dia.

34mm dia.
793.5

733.5
642
? 14
Earthing terminal
291.5 2
86
12mm hole (113mm)
17mm dia.
321.5
443

Antenna hole
(18mm)

Spare hole
(22mm)

Spare hole
VG22 series
(38mm)

Spare hole
VG28 series
(47mm)

Earthing Terminal
AC Power Cable
Control Cable Receptacle
Receptacle

Figure 3-3. Control Cubicle Structure

User Available Hole


This is additional holes for a cable when a hardware is added.

 22㎜ (0.866") : 1EA


 38㎜ (Standard Receptacle "VG22" Series) : 1EA
 47.3㎜(Standard Receptacle “ VG28” Series) : 1EA

ENHANCED TECHNOLOGY 11

12
347
3. INSTALLATION

330

4- ?
6.5
3.3.3. Control Module

닫힘
4-Φ
7

10

350
330

열림
230

128.25

ENT
ESC
5
3
1

6
4
2

FUN

C
B
A
C
B
A

SEF
BATTERY
CHARGER
3.3.2. Mount Accessories Dimensions

AC SUPPLY

VC / VT
VB / VS
VA / VR

MECHNISM LOCK
ETMFC610

ABC / RST LIVE


MULTI FUNCTION CONTROL
On Base plate, 10㎜/M6 Nut is used to fix the base plate.

ENHANCED TECHNOLOGY
304

Figure 3-5. Control Module Dimensions


Figure 3-4. Mount Accessories Dimensions

180
M10 9 2 1 3 2 1
200
RS232 1L/ACT
D BG 1SPEED

RX 2L/ACT
TX 2SPEED
- + FG N P
NTC WIFI IRIG-B RS485 RS232-2 RS232-1 Eth2 Eth1

10 9 8 7 6 5 4 3 2 F01 8 7 6 5 4 3 2 E01 5 4 3 2 D01 8 7 6 5 4 3 2 C01 07 06 05 04 03 02 B01 7 6 5 4 3 2 A01


100
950 950 950 950 950

110
SEF IN IC IB IA VT VS VR VC VB VA 108 107 106 105 104 103 102 OUT101 112 111 110 109 108 IN107 106 105 104 103 102 IN101

CT PT OUTPUT INPUT
Shows base plate measurements that can be attached in User Available Space.

INPUT OUTPUT PW2 OUT PW1 OUT(Rect') POWER IN


IN201 202 203 204 205 206 207 208 OUT 205 OUT206 OUT207 OUT208 OUT209 OUT210
PW
P N P N +24V 0V BAT+ BAT- AC24+ AC24-
+
FUSE FUSE

K01 2 3 4 5 6 7 8 9 10 I01 2 3 4 5 6 7 8 9 10 11 12 H01 2 3 4 P01 2 3 G01 2 3 4


http://www.entecene.co.kr
SWITCH CONTROL ETS 3. INSTALLATION

3.4. Earth Wiring Diagram

Figure 3-6. Earth Wiring Diagram

 After installation of Control cubicle, connect the ground.


 Earth Terminal can connect with core of cable size up to 12㎜(0.470") diameter.
 Earth cable from Pole Neutral and from Earth Terminal must be connected to the ground.

ENHANCED TECHNOLOGY 13
3. INSTALLATION http://www.entecene.co.kr

3.5. Terminal Block and Fuses

Figure 3-7. Terminal Block and Fuses

 Caution for an electric shock due to AC Power loaded in Terminal block.


 Standard AC Power is 220Vac.
 AC Power input terminal 1, 2 are connected from Receptacle to Terminal block. Terminal 3 is
the ground.
 Terminal 4, 5 are for connecting additional AC Power. Terminal 4 is connected with TF1 for
protection, terminal 5 is in series with AC Power.
 On TF1 Fuse, AC Power Outlet is connected with 40W Heater. Reference for branching.
 In AC line connection, blue wired line is for Neutral, white wired line is for Phase wire, green
wired line is for the ground.

14 ENHANCED TECHNOLOGY
SWITCH CONTROL ETS 3. INSTALLATION

Table 3-1. Terminal Block


Terminal Block FUNCTION
Switch auxiliary contact
6  Contact closed if switch close
 Rating(Resistive load) : 30Vdc/10A
Switch auxiliary contact
7  Contact closed if switch open
 Rating(Resistive load) : 30Vdc/10A
Switch auxiliary contact
8
 Common
9 User Available Terminal Block
10 User Available Terminal Block
TF1 Fuse to protect AC line number 4 of Terminal Block

3.6. CT Protection Circuit


A circuit which prevent from increasing voltage of secondary CT when Open Circuit, is built. This
circuit use TRIAC components and it is operated when the secondary voltage is 27 ~ 35V.

Figure 3-8. CT Protection Circuit

 D is Diac component and bi-directional and it works when 27~35V is applied.


 Q is Triac component and bi-directional and it works when the Voltage is applied at GATE.
 When CT secondary circuit is OPEN, the voltage is raised and D voltage is within 27~35V, D is
activated and operates Q in order to prevent a voltage increasing at both side of CT. Therefore,
the secondary voltage of CT is not increased over D voltage..

ENHANCED TECHNOLOGY 15
3. INSTALLATION http://www.entecene.co.kr

3.7. Voltage Divider (VD)


Table 3-2. Voltage Divider (VD)
Description Pin*Note Function
E VD Source Phase C

F VD Source Phase B
ETP SWITCH
G VD Source Phase A
Pin R is connected to Ground.
VD Capacity of Source Phase : 100MΩ H VD Load side Phase T
VD Capacity of Load side Phase : 100MΩ J VD Load side Phase S
For VD Protection, GAP is connected between Phase
K VD Load side Phase R
and Ground.
For voltage measuring, use High Impedance AC R Cable shield and Ground
Voltmeter(Digital Multimeter) at Output Pin.

Voltage Measuring Method 1


measure GAP voltage.
(measure a voltage between GAP arms)

Voltage Measuring Method 2


Place the resistance in parallel with GAP. and measure
MOV voltage.
Figure 3-9. VD Wiring Diagram

of ETP
*Note : See Table 3-3

16 ENHANCED TECHNOLOGY
SWITCH CONTROL ETS 3. INSTALLATION

3.8. Voltage Transducer

Figure 3-10. Voltage Transducer

 Voltage sensing device measures a voltage by using capacity of capacitor built or capacity of
resistance built in bushing of switch. Capacity of resistance 100㏁.
 Voltage sensing device divides a voltage by using Voltage Divider(VD) and secondary
resistance, and then divided voltage is supplied to RTU through Amplifier(AMP).
 GAP is used to protect surge of control.

ENHANCED TECHNOLOGY 17
3. INSTALLATION http://www.entecene.co.kr

3.9. Control Cable Receptacle Pin Descriptions


Table 3-3. Control Cable Receptacle Pin Descriptions
Pin Function Pin Function
A C.T Phase C W Manual lock 69a
B C.T Phase B X Low Pressure (com)
C C.T Phase A Z Manual lock 69a (com)
D C.T Common(G) a Motor Common
E Voltage Phase C (Source) b Motor Common
F Voltage Phase B (Source) c Motor Common
G Voltage Phase A (Source) d Close Motor
H Voltage Phase T (Load) e Close Motor
J Voltage Phase S (Load) f Close Motor
K Voltage Phase R (Load) g Open Motor
L not connected h Open Motor
M not connected j Open Motor
N not connected k not connected
P not connected m Auxiliary Contact (com)
R Cable shield and Ground n not connected
S SWITCH Status Common 52 com p Auxiliary Contact (52b)
T SWITCH Status 52b(Monitored Open) r Auxiliary Contact (52a)
U SWITCH Status 52a(Monitored Close) s not connected
V Low pressure
 Control Receptacle : VG95234B1 28-21S(Female)
 SWITCH Receptacle : VG95234B1 28-21P(Male)
 Control Cable : Shield Cable 8meter(31.5”)
 Cable Shielding layer is connected to Pin “R”

“Figure 3-11. Control Receptacle” shows Female


D C B A
J H G F E Receptacle installed in Control ETP.
R P N M L K
Z X W V U T S
f e d c b a
m k j h g
s r p n

Figure 3-11. Control Receptacle

18 ENHANCED TECHNOLOGY
SWITCH CONTROL ETS 3. INSTALLATION

3.10. Control Cable Assembling / De-assembling


 Do not turn Plug body when Control Cable assembling/de-assembling.
 For Control Cable assembling, connect with Receptacle regarding Pin Guide position.
 Turn Plug NUT clockwise carefully to prevent Pin winding or out of gearing.
 For disconnecting Control Cable, do opposite-way of Control Cable assembling.

Figure 3-12. Receptacle & Control Cable

3.11. AC Power Receptacle Pin Descriptions


Table 3-4. AC Power Receptacle Pin Descriptions
Pin Function
A AC Power Input
B AC Power Input (Neutral) A
C not connected
C B

Standard Input Voltage of Control ETS is


220Vac.

Figure 3-13. Power Receptacle

ENHANCED TECHNOLOGY 19
3. INSTALLATION http://www.entecene.co.kr

3.12. AC Power Cable


Table 3-5. AC Power Cable
TYPE VG22-2S(Female)
Cable Length 2C-3.5㎟ 6meter(236")
A PIN Wire Color White(Phase)
B PIN Wire Color Black(Neutral)
C PIN not connected

3.13. Fuses
Table 3-6. Fuses
Rating /
Positions Dimensions Purpose
External AC - Power Input

0.25×1.25"
Terminal Block TF1 7A/220Vac For AC Power Line protection
(6.385×31.75)㎜

20 ENHANCED TECHNOLOGY
SWITCH CONTROL ETS 3. INSTALLATION

3.14. Battery
3.14.1. Specs and Control Run Time
Table 3-7. Battery Specs
Nominal capacity 12V /18 amp-hours * 2pcs
Dimension 181×76×167㎜(7.126×3×6.575")
Service life Time 5 years
Battery Connector Molex Connector 3191-2R
Controller run time 48 hours
Recharge Time 60 hours

 Sealed lead - acid Battery Type, use 12Vdc 2 Batteries in series.


 The self-discharge rate of batteries is approximately 3% per month when batteries are stored at an ambient
temperature of +20℃(+68℉). The self-discharge rate varies with ambient temperature.

 The approximate depth of discharge or remaining capacity of a battery can be empirically determined from “Figure
3-15. Open Circuit Voltage”

 If the battery voltage is less than 22.5Vdc, the residual capacity is 0%. The voltage can be recharged but requires
maintenance.

Figure 3-14. Battery Figure 3-15. Open Circuit Voltage

ENHANCED TECHNOLOGY 21
3. INSTALLATION http://www.entecene.co.kr

3.14.2. Battery Protection


Battery protection is to protect the battery and discharge from the power circuit when the AC power
is cut off and before the battery is fully discharged. The CPU will measure the battery voltage and
when the battery voltage is less than 21V, it will power down after 10 minutes. If battery voltage is
below 19V, it will power down immediately.
On Power Down status, if the external power is re-supplied or the PowerSwitch is changed from
OFF to ON, Control Module is operated as normal.
When AC Power is not supplied, in order to operate it by Power Switch, OFF for 5 seconds and
turn it ON. When it is turned ON without Battery, it is Power downed after 10 minutes.

ETMFC610

DC/DC SYSTEM
G03 (Insulation) POWER
24Vac
G04 5V

DGND
CHARGER
AGND
+
±12V
-

NTC
Themistor
AGND VGND

BATTERY Under Voltage PW1 OUT(Rect')

+ CLOSE/OPEN
G01
MOTOR POWER
G02 - (24V / 20~30Vdc)
DC/DC
24Vdc/17Ah AGND (Non Insulation) PW2 OUT

+ MODEM POWER
- (24Vdc)

AGND
AGND

Figure 3-16. Power line and Power Protection

22 ENHANCED TECHNOLOGY
SWITCH CONTROL ETS 3. INSTALLATION

3.14.3. Charge Circuit


Charger uses current-control-circuit to prevent sudden-recharge and use voltage-steady-circuit to
prevent over-recharge. Charge power supply is 24Vac, equal with Relay Module. Charging device
charges up to 80 percent of battery with constant current, from 80 to 100 percent of battery with
constant voltage, it makes that there’s any danger of overcharging. To measure temperature in
charging circuit, it helps to compensate with charging voltage, 26.4V to 28.2V. When measured
temperature is 5~35℃, charging voltage is 27.3V. Below 5℃ and higher than 35℃ are measured,
charging voltages are 28.2V and 26.4V, respectively.

Charge Voltage : 27.3Vdc(26.4V~28.2V)


Charge Current : 1.2Adc
Charge Time : 80% Charging time is 11.33 hours (based on 17 Ah batteries)

3.14.4. Battery Change


Battery Mounting consists of two of Bolt M6-15L. Battery Wire consists of M5 Bolt & Nut and it
is connected to Battery Terminal. Bolt can be replaced using with (+) screwdriver.
For Battery wire de-assembling, disconnect Jumper wire first and disconnect “3191-2R” wire (red
and black). When “3191-2R” is disconnected, battery short is considered in case of worker’s
mistake.
For Battery wire connection, connect “3191-2R” wire (red and black) first and connect Jumper
wire later. Reference “Figure 3-14. Battery”

ENHANCED TECHNOLOGY 23
24
LOAD SIDE
F01
T S R IA
Protection Module F02
(CT open circuit protection) F03
IB USB-B
(VD circuit protection) Receptacle(male) Receptacle(female) F04

1A
(VG95234B1:28-21) (VG95234B1:28-21) F05
IC

CURRENT
IC IC F06
16 A A
F07
IB IB IN
17 B B F08
IA IA F09
18 C C SEF

0.16A
IG IG F10 Ethernet 1
3. INSTALLATION

9 D D
VC TD TP or FX (Option)
P3 13 E E 1
DC IN
3 VB 2
14 F F Ethernet 2
6 VA 1 1
G G E01 VA
15 2 2 TP or FX (Option)

4V
2 VT E02 VB
P1 10 H H 3 3
E03 VC Switch Port

VOLTAGE 1
5 VS 7 7
11 J J E04
1 VR 4 4 VR
12 K K E05
5 5

4V
4 E06 VS

PROTECTION C.T
L L E07 VT

VOLTAGE 2
8 8
N N E08
12
11 S S
52b K01 RS232-1
10 T T IN01 (Open)
P2 52a K02 IN02 (Close)
9 U U
K03 IN03 (Gas)
8 V V K04 IN04 (Lock) RS232-2
7 69 K05
W W IN05
VD K06 IN06
X X
K07 IN07 485+ 1
Z Z K08 IN08 RS485 485-
K09 2
a a POW SG
+ K10 3
C B A M b b
SOURCE c c I01 +
CLOSE OUT205(Open) 1
d d I02 IRIG-B
52b I03 + (Option) 2
e e OUT206(Close)
I04
f f I05 +
OPEN OUT207(Open)
g g I06 SMA
I07 + WIFI
52a OUT208(Close)
h h I08 (Option)
j j I09 +
OUT209
I10
m m +
52b I11
p p OUT210
I12
52a 12 INPUTS
r r DC Power output
(Option)
3.15. Connection Wiring Diagram

P P P01 +
P02 PW1 OUT(Rect') 8 OUTPUT RELAYS
R R
(Option)
Shield Cable P03 -
8M(standard) DC Power output

ENHANCED TECHNOLOGY
H01

Figure 3-17. Connection Wiring Diagram


Modem +
Power H02 - PW2 OUT
LEGEND DC24V or DC12V
H03 (40W / Continuous)
52a : Close status(52a closed if switch open)
H04 (60W / 1min)
52b : Open status(52b closed if switch close)
Power input
69 : Switch lock(69 closed if switch lock) Tr1
A G03
M : Motor(DC24V/25W max.I<10A) 24VAC
B G04
VD :Resistive Voltage Divider +
G01
Protection Module : CT open circuit & VD protection C BATT.
BAT1 G02 -
52,69 : 30Vdc/15A AC power input L

NFB1 : No fuse breaker 10A(Battery) Receptacle


(SVG02B1:22-2/male) ControL & RTU Module
NFB2 : No fuse breaker 6A(AC) N
ETMFC610
TF1 : Fuse 7A(Heater/outlet etc.) (Option)
SPD : Surge Protection Device
BAT1 : Battery 24V/17Ah(12Vdc * 2) PE AC
Tr1 : Transformer AC220V/24V outlet
TB1 : Terminal block(250V/25A), HYBT-25A (15)
http://www.entecene.co.kr