Vous êtes sur la page 1sur 5

Experimental Validation of the BAC Factor Method

for Lighting Systems


M. Beccali, M. Bonomolo, M. G. Ippolito, V. Lo Brano, G. Zizzo, Member, IEEE
Università di Palermo
Department of Energy, Information Engineering and Mathematical Models
viale delle Scienze, Edificio 9, 90128 Palermo, Italy

Abstract— In the last few years, many buildings have been and energy performance of lighting control strategies. The
equipped with Building Automation and Control (BAC) systems. standard EN 15232 [1] provides a list of BAC and TBM
BAC systems can be used to achieve a significant reduction of the functions that can affect the energy performance of buildings
electrical consumption and to have all the well acknowledged and introduces four different BAC efficiency classes and the
benefits from the daylight (e.g. occupant comfort, health, well- simplified BAC factor method for estimating the energy savings
being and productivity). For this reason, Standard EN 15232 due to the application of BAC and TBM functions. Nevertheless,
“Energy performance of buildings - Impact of Building as Pellegrino et. Al. have underlined in their work [9],
Automation, Controls and Building Management” puts into sometimes the outcomes obtained from the monitored data can
evidence the importance of the presence of BAC and Technical
show some significant differences from the expected and
Building Management (TBM) systems, suggests a classification of
these systems, explains their main functionalities and presents a
previously estimated energy saving results.
simplified method to estimate their impact on the energy The aim of this paper is to check the soundness of this
consumption of the building. The aim of this paper is to verify this simplified BAC factor method using the results of an
simplified BAC factor method using the results of an experimental experimental measurements campaign. In the paper the BAC
measurements campaign. In the paper, the BAC factors are factors are evaluated for a residential and an office environment,
evaluated for a residential and an office environment, using a big using a big set of data measured for 8 months every 5 minutes at
set of data measured for one year every 5 minutes at the laboratory
the laboratory of the DEIM (University of Palermo), where a
of the DEIM (University of Palermo), where a BACs for lighting
BAC system for lighting control is installed.
control is installed.
II. THE LABORATORY SET-UP
Keywords— buildings controls; energy efficiency in buildings;
lighting; BAC factors. As well known, the characteristics of the space and of the
environment can highly influence the behavior of the light and
I. INTRODUCTION the performance of the lighting system. In this section, a short
EN Standard 15232 [1] deals with the effects of Building description of the characteristics of the laboratory, of the
Automation Control (BAC) and Technical Building environment and of the tested system are reported. More detailed
Management (TBM) systems on the final energy consumption information can be found in [10].
in buildings. The standard is in-line with the EPB Directive A. The laboratory
2010/31/EU [2], that recognizes the important role of The laboratory is located at the third floor of the DEIM
automation, control and monitoring systems in energy saving (Department of Energy, Information Engineering and
actions, and encourages the use of smart control and metering Mathematical Models) of the University of Palermo. The
systems for energy saving purposes. Also Directive 2012/27/EU building is located in Palermo in the climatic zone B, according
[3] refers to automation as a way to reduce the energy to the Decree DPR 412/93 [11] classification. It is characterized
consumption also having recourse to innovative demand by and area of 106 square meters in size and an height of 4.40
response (DR) strategies, and to the application of smart meters. m, including the false ceiling, and an height of 3.40 m high,
In addition, the most recent research literature [4]-[6] shows excluding the false ceiling.
that a great potential for energy savings in buildings is in the The room has four windows, equipped by double-glazing
control and interaction of air-conditioning systems, appliances with aluminum frames (without thermal break). They are located
and, in general, electric devices, also thanks to specific on the South East side overlooking the green roof (albedo
algorithms able to coordinate all the energy facilities in the average value= 0.25) and are 2.40 meters of width by 2.90
building. Many studies demonstrated the advantages of BAC meters of height. Medium height plants on the green roof cover
systems. Indeed, this kind of systems can play a key role to two windows. Furthermore, the façade is partially shaded by a
achieve a significant reduction of the electrical consumption for solar shelter of 2.70x19 meters on which an hybrid PV/Thermal
lighting and all the well-acknowledged benefits from the system is installed. This solar system is connected with the air-
daylight (e.g. occupant comfort, health, well-being and conditioning system (a solar thermally driven advanced DEC
productivity) [5]-[7]. Aste et. al. [8] proposed a method for system) and with the electric grid though a storage/management
optimizing BAC systems performance both in terms of energy system.
savings and of comfort and Shen et al. investigated both visual
The project has been funded by Italian Minister of University and
Research in the framework of the PON Smart Cities Smart Cities and
Communities and Social Innovation "I-Next".

978-1-5386-3917-7/17/$31.00 ©2017 IEEE


B. The lighting system Fig. 1 represents the layout of the laboratory while Table I
In the following sections, different scenarios for different reports the lighting controls implemented in each zone.
end-uses are described. In particular, in the laboratory some III. THE MEASUREMENT CAMPAIGN
typical occupancy schedules for residential and office buildings
have been set. The luminaires have been chosen and located in During the experimental campaign, the following measures
order to achieve the illuminance values suggested, for different have been taken:
tasks, by the Standard EN 12464-1 [12]. - illuminance values measured indoor;
For the residential case, the laboratory has been divided - diffuse illuminance value measured outdoor (on the
ideally in some typical apartment zones: roof);
- an entrance zone; - diffuse solar radiation measured outdoor (on the roof);
- a living room; - energy absorbed by the lighting system.
- a dining room; In order to obtain realistic energy consumption values,
- a kitchen; various scenarios have been tested for different occupancy
schedules, seasons and sensors configuration. The illuminance
- a bedroom; sensor placed on the ceiling, has been set to achieve on the work-
- a bathroom. plan 200-300 lux for the residential scenario and 400-500 lux for
the office scenario.
For the office case, the space has been ideally divided in:
TABLE I. LIGHTING CONTROLS IMPLEMENTED IN EACH ZONE.
- an entrance zone;
Zones Function
- three work stations;
Manual on/off control i3 e
- a director office; Residential Office
i4
- a kitchen; Kitchen Kitchen
Manual on/off control i1 e
i2
- a bathroom. Entrance Entrance Manual on/off control S4
The lighting system is composed by: Bedroom Manager room Scenario control
Living Workstation Dimmer control S1 e S2
• pendant luminaires, equipped with 54W LED Manual on/off control S1 e
lamps in all the zones Dining Workstation
S2
• mono-optic indoor downlight with 15W LED
lamps in the kitchen and in the entrance zone. Tables II and III report the occupancy schedule for the
residential and the office scenario.
C. Electric control system
The lighting system is managed by a BAC system TABLE II. OOCCUPANCY SCHEDULES FOR THE RESIDENTIAL SCENARIO.
configurable by the My Home Suite [13] software. The software
is also used for managing the devices of the automation, energy Zone Scenario time
management, and temperature control systems, is preset for Kitchen 08:00-09:30 12:00-12:30
virtual configuration and for integrating the control of some
devices that require programming (for example touch screen, Bedroom 07:00-07:30 22:00-00:00
web server, scenarios programmer, advanced video handsets). It
Entrance 17:50-18:05 18:10-18:25
is designed for being easily usable by anyone, also by not
technical personnel; indeed, its interface is very user-friendly. Living Room Variable with season
The main function of My Home Suite are:
- Lighting control (switching on and off the lamps, TABLE III. OCCUPANCY SCHEDULES FOR THE OFFICE SCENARIO.
luminous flux regulation of lamps);
Zone Scenario time
- Automation control (control of motors);
Kitchen 12:00-12:30
- Scenario module control (recalling and/or changing
lighting/thermal scenarios saved in the scenario module); Manager
07:00-07:30
Room
- Sound system control (switching on and off the sound
system, adjusting the volume, switching and managing an Entrance 09:00-09:15 18:10-18:25
amplifier source)
Office Variable with seasons
- Video door entry system (opening of a door lock,
control of internal video entry system panel, switching on and
off the lamps in staircase).
Fig. 1. Layout of the laboratory.

IV. RESULTS For each scenario considered in Section III, the energy
consumption of the lighting system has been measured:
The experimental validation of the BAC factors for lighting
systems proposed in this paper, has been done starting from the • in absence of automatic control of all the lamps;
assumption that whichever realistic scenario includes automatic
control of some lamps as long as manual control of other lamps. • in presence of automatic ON/OFF control of
Therefore, the manual control of lamps i1-i4 in Table II has been luminaries S1-S3 as function of the established
considered as an acceptable condition for the experiments. illuminance set-point;

BAC factors are usually referred to a reference scenario with • in presence of dimming control of the artificial
a slight presence of automation (class C) and assume the values lighting.
in Table IV. However, for the aim of our study, BAC factors According to EN Standard 15232, in the first case the
have been calculated assuming class D (no automation) as lighting system is considered of class D, while in the other cases
reference. In this way, the values in Table V are obtained. the lighting system can be assumed of class C and A,
respectively.
TABLE IV. BAC FACTORS FOR ELECTRICITY CONSUMPTION IN
RESIDENTIAL AND OFFICE BUILDINGS [1]. The actual BAC factor BF is calculated as the rate:
D C B A E AUT
Residential BF = (1)
1.08 1 0.93 0.92 ED
Buildings
Office
1.10 1 0.93 0.87 where EAUT is the daily energy consumption of the lighting
Buildings
system in presence of automation and ED is the theoretical
TABLE V. CORRECTED BAC FACTORS FOR ELECTRICITY CONSUMPTION
consumption that the lighting system would have in the same
IN RESIDENTIAL AND OFFICE BUILDINGS WITH REFERENCE CLASS D. day in absence of automatic control.
D C B A Tables VI and VII report for each season the average of the
Residential values calculated with (1). The two tables contain also the
1 0.93 0.86 0.85
Buildings average Daylight Autonomy (DA) and continuous Daylight
Office Autonomy (cDA) for each season. The first index is the
1 0.91 0.85 0.79
Buildings percentage of the time-in-use that a certain user-defined lux
threshold is reached through the use of just daylight. cDA
is similar to DA, but cDA awards partial credit for daylight
levels below a user-defined threshold in a linear fashion [14].

TABLE VI. CALCULATED AVERAGE VALUES OF BF FOR RESIDENTIAL


BUILDINGS.

Residential BF for BF for DA cDA


Buildings Class C Class A
lighting lighting
system system
Summer 0.89 0.61 30% 48%
Winter 0.99 0.95 1% 2%
Yearly 0.94 0.78 16% 25%

TABLE VII. CALCULATED AVERAGE VALUES OF BF FOR OFFICE


BUILDINGS.
Fig. 2. Correlation between BF and cDA (ON/OFF control).
Office BF for BF for DA cDA
Buildings Class C Class A
lighting lighting
system system
Summer 0.95 0.64 52% 76%
Winter 0.93 0.72 39% 62%
Yearly 0.94 0.68 46% 69%

Indeed, a correct evaluation of BF must take into


consideration the actual contribution of natural lighting during
daytime, especially in presence of dimming control that, during
winter or in rooms characterized by insufficient natural lighting
can become ineffective. Nevertheless, as it can be noticed from
Figures 2 and 3, there is not a good correlation between BF and
cDA values in the presence both of ON/OFF and of dimming
control. This is probably due to the quota of energy consumption
due to not controllable loads (lamps i1-i4 and S4) and stand-by
consumption.
Fig. 3. Correlation between BF and cDA (dimming control).
Table IX reports a comparison of the actual calculated BAC
factors and those given by [1].

TABLE VIII. COMPARISON BETWEEN ACTUAL AND THEORETICAL BAC FACTORS.


Residential Actual Theoretical Percentage Actual Theoretical Percentage
Buildings Class C Class C difference Class A Class A difference
lighting lighting lighting lighting
system system system system
Summer 0.89 0.93 4.3% 0.61 0.85 28.2%
Winter 0.99 6.4% 0.95 11.8%
Yearly 0.94 1.1% 0.78 8.2%
Office Actual Theoretical Percentage Actual Theoretical Percentage
Buildings Class C Class C difference Class A Class A difference
lighting lighting lighting lighting
system system system system
Summer 0.95 0.91 4.4% 0.64 0.79 18.9%
Winter 0.93 2.2% 0.72 8.9%
Yearly 0.94 3.3% 0.68 14.0%

The comparison shows that, for the scenarios examined in schedules of the residential scenario considered the presence of
this study, the calculated BAC factors values for C and A classes people after twilight and therefore the control of the lamps as
are quite close to the theoretical values. In the case of residential function of natural daylight was very limited and the luminaires
scenarios tested during winter period, it can be noted that there were, for the most part of the time period, at 100% of their rated
are not significant energy savings with respect to the case power.
without automation. In fact, during winter, the occupancy
It is worth noticing that in the practice only comparing yearly REFERENCES
average values is meaningful. Indeed, single values of BF can [1] European Technical Standard EN 15232, “Energy Performance of
greatly differ from the theoretical BAC factors, being highly Buildings – Impact of Building Automation, Control, and Building
dependent on the natural lighting contribution of the specific Management”, second ed., CEN, Brussels, 2012.
day. In addition, being BAC factors defined for assisting in the [2] Directive 2010/31/EU of the European Parliament and of the Council of
estimation of the buildings yearly consumption, a comparison on 19 May 2010 on the energy performance of buildings.
the basis of seasonal values is not useful, even if it provides [3] Directive 2012/27/EU of The European Parliament and of the Council of
important indications on the behavior of the system throughout 25 October 2012 on energy efficiency, amending Directives 2009/125/EC
and 2010/30/EU and repealing Directives 2004/8/EC and 2006/32/EC,
the year. Official Journal of the European Union. L 315/1, 14.11.2012.
Another important indication deducible from Table VIII is [4] B. Poel, G. van Cruchten, and C. A. Balaras, “Energy performance
that, both for the residential and for the office case, the measured assessment of existing dwellings”, Energy and Buildings, Vol. 39, No. 4,
pp. 393-403, 2007.
BAC factor for the C Class lighting systems take values very
[5] L. Klein, J. Y. Kwak, G. Kavulya, F. Jazizadeh, B. Becerik-Gerber, P.
close to the theoretical one. Indeed, in these cases the percentage Varakantham and M. Tambe, “Coordinating occupant behavior for
differences are not over 10%. building energy and comfort management using multi-agent systems”,
Automation in construction, Vol. 22, pp. 525-536, 2012.
A more detailed study could be carried out comparing the
[6] Y. Xu, S. Yuehong, “Daylight availability assessment and its potential
results of the proposed calculation made for different system’s energy saving estimation-A literature review”, Renewable and
hardware or systems made by different manufactures. Sustainable Energy Reviews, Vol. 52, pp. 494-503, 2015.
[7] R. Yang and L. Wang, “Multi-objective optimization for decision-making
V. CONCLUSIONS AND FUTURE WORKS of energy and comfort management in building automation and control”,
The results of the study allow one to affirm that the BAC Sustainable Cities and Society, Vol. 2, pp. 1-7, 2012.
factor method, besides characterized by a certain degree of [8] N. Aste, M. Manfren, G. Marenzi, “Building Automation and Control
Systems and performance optimization: A framework for analysis”,
approximation, can be used with sufficient precision for Renewable and Sustainable Energy Reviews Vol. 75, pp. 313-330, 2017.
evaluating the final energy consumption of C or A class lighting
[9] A. Pellegrino, V. R. M. Lo Verso, L. Blaso, A. Acquaviva, E. Patti and A.
systems, both in residential and in office buildings. Osello, “Lighting Control and Monitoring for Energy Efficiency: A Case
Nevertheless, the results presented in the paper are only a part of Study Focused on the Interoperability of Building Management Systems”,
a wider research aiming at comprising how the BAC factor IEEE Transactions On Industry Applications, Vol. 52, No. 3, pp. 2627 -
method can be improved and made more accurate. 2637 May/June 2016.
[10] M. Beccali, M. Bonomolo, A. Galatioto, M.G. Ippolito, and G. Zizzo. “A
Indeed, several factors are able to influence the outcome of laboratory setup for the evaluation of the effects of BACS and TBM
this study: systems on lighting”, 2015 International Conference on Renewable
Energy Research and Applications (ICRERA), pp. 1388 - 1393, 22-25
• the influence of daylight on dimming control; November 2015, Palermo (Italy).
[11] D.P.R. n. 412, “Regolamento recante norme per la progettazione,
• the usage pattern assumed for the lighting system; l'installazione, l'esercizio e la manutenzione degli impianti termici degli
edifici ai fini del contenimento dei consumi di energia, in attuazione
• the imposed illuminance set-point; dell'art. 4, comma 4, della L. 9 gennaio 1991, n. 10” (in Italian), August
1993.
• the effects of motion detectors;
[12] EN 12464-1 “Lighting of work spaces - Part I: Indoor work places”
• the stand-by energy consumption of lamps and [13] MyHome Suite web page, Available:
control devices. http://www.bticino.com/myhome_suite/index.html (Last view: February
2017).
In a future work a more comprehensive study will be [14] C. F. Reinhart, J. Mardaljevic, and Z. Rogers, “Dynamic Daylight
presented that will show how BAC factors can depend on the Performance Metrics for Sustainable Building Design”, Leukos, Vol. 3,
above-listed factors. No. 1, pp. 7-31, 2006.

Vous aimerez peut-être aussi