The LVCS is a compact and powerful capacitor ready for connection. It offers high modularity, unmatched
performances and a state of the art integrated protection system.
The LVCS wide power and voltage ranges allow its use for all power factor correction systems with or without
reactors.
Contactor-type terminals
Interconnection bars
Fixation holes
Slot system
Slot system
Fixation holes
2
Safe
Contactor-type terminals
Thermo-setting resin
Insulating enclosure
Reliable
In-house metallized film Testing includes long-term ageing, temperature,
The dielectric of the LVCS windings is made of in-house humidity, dielectric, self-healing, current and voltage
metallized polypropylene film giving: tests.
• high voltage withstand capability
• excellent peak current handling capacity ISO 9001
• high capacitance stability Our ISO 9001 Quality System registration provides the
• long life even under high electrical stress strongest assurance of our product quality.
• very low losses
• exceptional self-healing properties ISO 14001
The LVCS has a dry type dielectric and is free from
Fully automated manufacturing process liquids or other impregnating agents. It has been
The LVCS fully automated manufacturing process results designed for environmentally friendly manufacturing.
in high reliability, fully controlled performance and a Our ISO 14001 certification guarantees our commitment
continuous guaranteed quality. to the environment.
3
Accessories
Interconnection bars
(option)
10 + 20 = 30 kvar 10 + 20 + 25 = 55 kvar
10 + 25 = 35 kvar 20 + 20 + 20 = 60 kvar
4
Technical specification
Voltage range 50 Hz: 230, 400, 415, 525 and 690 Vac.
60 Hz: 220, 240, 380, 440, 480 and 600 Vac.
Connection 3-phase.
Discharge resistors Built-in and sized for discharge of the capacitors to less than 50V in 1 min.
Minimum time between disconnection and re-energization: 40 seconds.
Terminals Contactor-type terminals with captive screws (Max. cable size: 35mm2 )
Earth No earth connection needed.
Color RAL 7012 (dark gray).
Weight (unpacked) +/- 2.5 kg / LVCS unit
Fixation M6-through-hole bolts, M6-insertion-hole screws.
Execution Indoor.
Protection IP 20.
Maximum ambient temperature Class D (+55°C).
Minimum ambient temperature -25°C.
Dielectric losses < 0.2 Watt/kvar.
Total losses < 0.5 Watt/kvar (discharge resistors included).
Tolerance on capacitance 0 +10 %.
Voltage test Between terminals : 2.15 Un for 10 sec.
Lightning impulse voltage test Between terminals and container: 15 kV.
Acceptable overloads Overvoltage tolerance : 10 % max. intermittently.
according to IEC 60831 1& 2 Overcurrent tolerance : 30 % permanently.
Important : the installation of capacitors on networks disturbed by harmonics may require special precautions,
especially when there is a risk of resonance.
Dimensions (mm)
Max cable size: 35 mm2
83 163 243
M6-screws
66
80
83
M6-screws
(not provided)
198
212
5
Range
(4)
Network Network Associated Tuning Net Power Current per Phase-to-Phase Article number
Voltage (1) Frequency (2)
Reactor (3) Frequency Phase Capacitance (5) for ordering
(V) (Hz) (%) (Hz) (kvar) (A) (µF)
Notes
(1) Network voltage (V) : voltage of the supply network.
(2) Network frequency (Hz) : frequency of the supply network.
(3) Associated reactor (%) : value of the detuned reactor to be combined with the capacitor unit. Reactors are not provided.
(4) Net power (kvar) : net reactive power output in combination with the associated reactor. Reactors are not provided.
(5) Phase-to-phase capacitance (µF): capacitance measured between two of the unit terminals.
6
(4)
Network Network Associated Tuning Net Power Current per Phase-to-Phase Article number
Voltage (1) Frequency (2)
Reactor (3) Frequency Phase Capacitance (5) for ordering
(V) (Hz) (%) (Hz) (kvar) (A) (µF)
7
Max. net output rating per module
70
60 60 60 60 60 60 60 60
60
kvar (net output)
50
40
30 30
20
10
0
0% 0% 5.67 % 7% 12.5 % 0% 5.67 % 7% 12.5 % 0% 5.67 % 7% 12.5 % 0% 5.67 % 7% 12.5 %
230 400 400 400 400 415 415 415 415 525 525 525 525 690 690 690 690
Reactor (%)
Voltage (V)
70
60 60 60 60 60
60
kvar (net output)
50
40
35 35 35 35 35
30
20
10
0
0% 0% 6% 7% 12.5 % 0% 6% 7% 12.5 % 0% 0% 6% 7% 12.5 % 0% 6% 7% 12.5 %
220 240 240 240 240 380 380 380 380 440 480 480 480 480 600 600 600 600
Reactor (%)
Voltage (V)
2GCS301012A0032
While all care has been taken to ensure that the information contained in this publication is correct, no responsibility
can be accepted for any inaccuracy. We reserve the right to alter or modify the information contained herein at
any time in the light of technical or other developments. Technical specifications are valid under normal operating
conditions only. We do not accept any responsibility for any misuse of the product and cannot be held liable for
indirect or consequential damages.