Contents
1. Description..................................................................... 3 8. Mounting...................................................................... 24
2. The arc flash phenomenon ............................................ 4 9. Selection and ordering data..........................................25
3. Arc fault protection system............................................. 5 10. Accessories and ordering data.................................... 25
4. Sensors........................................................................11 11. Terminal and block diagrams.......................................28
5. REA solutions............................................................... 11 12. References..................................................................30
6. REA with other ABB arc fault protection solutions.........14 13. Document revision history........................................... 30
7. Technical data.............................................................. 17
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors
that may appear in this document.
© Copyright 2019 ABB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks
of their respective holders.
2 ABB
Arc Fault Protection System 1MRS756449 B
REA 10_
Issued: 2019-06-28
Revision: B
GUID-0E5F264C-E558-4F33-9E94-8B0F75095DCE V1 EN
ABB 3
Arc Fault Protection System 1MRS756449 B
REA 10_
2. The arc flash phenomenon ageing under electrical stress. Most of these fault reasons can
The consequences of an arcing short-circuit or earth-fault be prevented by appropriate maintenance. Despite of all
inside a low voltage or medium voltage switchgear panel can be precautions, arc faults may be caused by human error, or by
very disastrous. The extremely hot electric arc can destroy animals entering the switchgear panel.
valuable equipment causing prolonged and costly distribution
downtimes. Moreover, an arc fault poses a serious threat to the Time is a critical parameter for the detection and minimization of
switchgear operating and maintenance staff. the effects of arc faults as the arc incident energy rapidly
increases by time. An arc fault lasting 500 ms may cause severe
An arc fault can arise from, for example, insulation faults and damage to the installation. If the arc lasts for less than 100 ms
weaknesses, maloperation of a switchgear device, improper the damage is often restricted, but if the arc is extinguished in
(loose) busbar or cable joints, overvoltage, corrosion, pollution, less than, for example, 4 ms the damage is insignificant.
moisture, ferro-resonance (instrument transformers) and even
kA2s
300
Steel fire
250
Copper fire
4 ABB
Arc Fault Protection System 1MRS756449 B
REA 10_
REA 101
GUID-C8243F5B-8665-4FF3-898B-26827E924DF3 V1 EN
Figure 3. The main module REA 101 detects three, two or single phase fault currents. The REA 101 module is activated when an arc fault occurs
between the phases of the busbar system. Using a loop-type fiber sensor, REA 101 provides fast tripping of the LV infeeder circuit
breaker. Moreover, either a fast tripping of the HV side circuit breaker or the circuit-breaker failure protection (CBPF) can be applied
for enhancing protection redundancy.
ABB 5
Arc Fault Protection System 1MRS756449 B
REA 10_
Circuit-breaker failure protection messages between the main modules over a signal transfer
The circuit-breaker failure protection is implemented by fiber. One of the following selectable messages, LIGHT,
delaying either the HSO2 output or the TRIP3 output, or both, if OVERCURRENT or TRIP, can be transferred over a distance of
required. Note that if both outputs are used, the delay time of max. 40 m, when plastic fiber cables (to be used with type
both outputs is the same, but the pickup time of the REA101-AAA or REA101-CAA) or up to 2 km, when glass fiber
electromechanical output relay (5...15 ms) must be added to cables (to be used with type REA101-AAAG) are used.
the TRIP3 relay.
Self-supervision
The selected delay time, 100 ms or 150 ms, starts running, The built-in self-supervision system of the REA 101 module
once the HSO1 output is activated. The delayed tripping does continuously monitors the operating voltages, the integrity of
not take place if the overcurrent signal disappears before the the cabling between the main module and the extension
specified time delay has elapsed. modules, and the fiber-optic link connections between the main
modules. Any fault or malfunction detected by the self-
Fiber-optic link communication supervision system will be used for alerting the operator. A
The REA 101 module contains two communication link detected fault will block the module to prevent incorrect
terminals: Optolink 1 and Optolink 2. The purpose of the operation.
communication links is to send and receive ON/OFF type
6 ABB
Arc Fault Protection System 1MRS756449 B
REA 10_
fault. For light detection REA 103 can use two loop-type or
Extension modules radial sensor fibers.
Extension module REA 103
REA 103 is an extension module to be used together with the The built-in self-supervision system of the REA 103 module
main arc fault protection module REA 101. The REA 103 continuously monitors the operating voltages of the module and
extension module is operating as a light detecting module in the the continuity of the sensor fiber loops. Any fault or malfunction
REA arc fault protection system. REA 103 detects light and detected will be used for alerting the operator via the REA 101
provides the operator with information about the location of the main module.
REA 101
CBF
2
Light
REA 103
GUID-D260D3EF-891E-435B-A75E-C61724D0F0FE V1 EN
Figure 4. The main module REA 101 is used for detecting phase or neutral (residual) overcurrent. The REA 101 module is activated when an arc
fault occurs between phase conductors or between a phase conductor and the grounded frame of the switchgear system. The
REA 101 module is provided with a loop-type fiber sensor for detecting arc faults appearing between the power transformer and the
busbar system. The arc fault protection system has been enlarged with a REA 103 extension module. The REA 103 module is equipped
with a loop-type fiber sensor for detecting possible arc faults occurring in the busbar system. The REA 103 module transfers a LIGHT
message to the REA 101 module, which issues a trip signal when the simultaneous current condition for tripping is met.
Extension module REA 105 simultaneously whenever the REA 101 module executes
REA 105 is an extension module to be used together with the tripping. The REA 105 module can accommodate one loop-
main arc fault protection module REA 101. The REA 105 type or radial-type sensor fiber for light detection.
module detects light and carries out tripping, if the REA 101
module simultaneously provides an overcurrent signal. When The REA 105 module contains two high-speed, galvanically
the REA 105 extension module is used for interconnecting two isolated, IGBT trip outputs HSO1 and HSO2 for CB tripping
REA 101 modules in the system, the REA 105 module also purposes. These outputs can be used in DC and AC circuits.
delivers information about the overcurrent status between
them. Moreover, the REA 105 module carries out tripping
ABB 7
Arc Fault Protection System 1MRS756449 B
REA 10_
The REA 105 module also provides circuit-breaker failure the sensor fiber loop. Any fault or malfunction detected will be
protection by delivering a delayed LIGHT signal to the REA 101 used for alerting the operator via the REA 101 module. A
module, which then trips the upstream circuit breaker. detected fault in the operating voltages will block the device to
prevent incorrect operation.
The built-in self-supervision system of REA 105 continuously
monitors the operating voltages of the device and the state of
REA 101
REA 105
I>, Trip
Light
GUID-E898CC9E-22F9-4B6C-9B0B-42BE46ED9491 V1 EN
Figure 5. The main module REA 101 detects three, two or single phase fault currents. REA 101 is equipped with a loop-type fiber sensor for
detecting arc faults occurring on one of the busbars of a double-busbar switchgear system. REA 101 also trips the bus coupler via the
extension module REA 105. The REA 105 module also uses a loop-type fiber sensor for detection of arc faults on the other busbar. The
REA 105 module trips the bus coupler on detection of light and reception of a CURRENT message from the REA 101 module.
Simultaneously, the REA 101 module trips the infeeder circuit breaker on reception of a LIGHT message from the REA 105 module.
Extension module REA 107 The built-in self-supervision system of the REA 107 module
REA 107 is an extension module to be used together with the continuously monitors the operating voltages of the device. Any
main arc fault protection module REA 101. The REA 107 fault or malfunction detected will be used for alerting the
extension module is operating as a light detecting unit in the operator via the REA 101 module. A detected fault will block the
REA arc fault protection system. REA 107 allows connection of device to prevent incorrect operation.
up to eight lens-type sensors. The sensor input specific LED
indicators of REA 107 facilitate fault location by guiding the staff The lens-type sensors are especially suitable for retrofit
to inspect the area of coverage of the sensor(s) that detected installations by providing a more convenient installation of the
the arc. sensors compared to the fiber sensor solution.
8 ABB
Arc Fault Protection System 1MRS756449 B
REA 10_
REA 101
Light
REA 107
GUID-D3C355EC-0BF7-443E-8AF8-246246EF9AF4 V1 EN
Figure 6. The main module REA 101 detects three, two or single phase fault currents. The REA 101 module is equipped with a lens-type sensor
for detecting arc faults occurring in the infeeder cubicle. The system is extended with a REA 107 module equipped with eight lens-type
sensors for detecting possible arc faults appearing in the busbar compartment, circuit-breaker feeder compartments and cable
termination compartments. The REA 107 module sends a LIGHT message to the REA 101 module, which issues a trip signal when the
simultaneous overcurrent condition for tripping is met.
ABB 9
Arc Fault Protection System 1MRS756449 B
REA 10_
REA 101 main arc Two high-speed Independently OR One loop-type or Adjustable three- CBFP fiber loop sensor,
fault protection (<1 ms) transistor via a fiber-optic radial sensor-fiber phase or two- operating voltages
module (IGBT) outputs for link by another loop sensor or one phase and neutral and cabling
tripping of CBs and REA 101 main lens-type sensor, OC condition OR between main and
an auxiliary relay module OR via a fiber- via a fiber-optic extension modules,
output for CBFP or optic link by link by another fiber-optic link
for alarm another REA 101 REA 101 main communication
purposes. One main module module OR via between the main
reset input. REA 105 by modules
another REA 101
main module OR
not used (Light
only mode)
REA 103 system One signal output - Two loop-type or By the main - Operating voltages
extension module radial fiber type module and the sensor fiber
sensors or one loops
lens-type sensor
REA 105 system Two high-speed Whenever main One loop-type or By the main Delayed light Operating voltages
extension module (<1 ms) IGBT trip module(s) trip, or radial fiber sensor module(s) signal to and the sensor fiber
outputs (high- on light detection or one lens-type REA 101, which loop
speed CB tripping and simultaneous sensor opens the up-
units) and one current condition stream CB
signal output by the main
module(s)
REA 107 system Two signal outputs - Up to eight lens- By the main - Operating voltages
extension module type sensors module
10 ABB
Arc Fault Protection System 1MRS756449 B
REA 10_
Solution examples
3 3
I>
I>
GUID-3082D816-E1E4-43B4-AEC2-CEDC94B4A79B V1 EN
Figure 7. Arc fault protection of a single-busbar switchgear system fed from two power transformers
Figure 7 shows arc fault protection of a single-busbar links. The arc fault protection system with two REA 101 main
switchgear system fed from two power transformers. The arc modules is selective. Both sections of the busbar system
fault protection system is based on two REA 101 modules, incorporate their own loop-type fiber sensor for arc fault
which are interconnected using fiber-optic links. The CURRENT detection. In this protection scheme the CBFP function is
signals are sent between the main modules via the fiber-optic implemented by tripping the HV side circuit breaker.
ABB 11
Arc Fault Protection System 1MRS756449 B
REA 10_
3 3
Figure 8. An arc fault protection system with enhanced selectivity for a single-busbar switchgear panel fed from two power transformers
Figure 8 illustrates arc fault protection of a single-busbar switchgear systems. The fault current is measured with current
switchgear system fed from two power transformers. The arc transformers located on the HV side of the power transformers
fault protection system is based on two REA 101 modules, providing a reach of the protection up to the poles of the power
which are interconnected using fiber-optic links. The CURRENT transformer. The protection of both sections of the busbar
messages are sent between the main modules via fiber-optic system is accomplished with loop-type fiber sensors
links. The system is extended with REA 105 modules for connected to two REA 105 modules. In addition, each outgoing
enhancing the selectivity of the protection system. The REA 101 feeder is equipped with REA 105 modules, which deliver
modules are provided with loop-type fiber sensors for detecting selective arc protection in case an arc fault occurs in feeder-
arc faults on the bus duct between the power transformers and cable termination compartments.
12 ABB
Arc Fault Protection System 1MRS756449 B
REA 10_
Light
Light
GUID-B24CA93E-AECF-4CCB-AB2B-957C3248418D V1 EN
Figure 9. Arc fault protection of a double-busbar switchgear system fed from two power transformers
Figure 9 illustrates an arc fault protection of a double-busbar When the bus coupler is closed and the fault current is fed via
switchgear system fed from two power transformers. The arc both incoming feeders, the circuit breakers of either infeeder
fault protection system is based on two REA 101 main modules, will trip. In both REA 101 modules the overcurrent condition will
which are interconnected using fiber-optic links over which be met and LIGHT messages will be forwarded to both
LIGHT messages are sent between the main modules. modules.
When the bus coupler is open, the REA 101 module equipped When the bus coupler is closed and the fault current is fed via
with a loop-type fiber sensor detects an arc fault occurring on only one incoming feeder, the fault detecting REA 101 module
the other busbar system. The REA 101 module which detects of the incoming feeder trips its circuit breaker after a reception
the overcurrent condition will trip the infeeder circuit breaker. of a LIGHT message from either infeeder REA 101 module.
ABB 13
Arc Fault Protection System 1MRS756449 B
REA 10_
6. REA with other ABB arc fault protection solutions protection system cover the whole area from the terminals of
the power transformer right to the switchgear busbars. One of
REA with 615 series protection relays the lens sensors can be installed to detect arc flashes on the
Figure 10 shows a switchgear arc fault protection solution bus duct between the power transformer and the switchgear
focused on redundance and selectivity. The actual case could system. Each outgoing feeder cubicle is provided with a
represent an industrial main switchgear system or a switchgear REF615 protection relay. These relays provide independent
system of an urban substation often attended by operation or protection of their respective cubicles on faults downstream of
maintenance staff. Both of the implemented arc fault protection their circuit breakers, based on their own current measurement
systems in the figure perform selective protection seen from the information and light detection by sensors located in the cable
busbar system point of view. Moreover, the arc fault protection termination, circuit breaker and busbar compartment. In case
solution based on the 615 series devices provides selective of a busbar arc fault the REF615 relay of an individual outgoing
protection on arc faults in the cable termination compartment. feeder detects light by means of its light sensor in the busbar
compartment and transmits the light information as a GOOSE
The arc fault protection system is based on two REA 101
message over the communication bus to the infeeder REF615
modules, which are interconnected using fiber-optic links. The
relay, which then trips the infeeder circuit breaker. The system
CURRENT message is sent between the main modules via
also features circuit-breaker failure protection. If the circuit
fiber-optic links. The arc fault protection system with two
breaker of an outgoing feeder fails to open in an arc fault
REA 101 main modules is selective. Both sections of the busbar
situation, the relay of the faulty outgoing feeder transfers a trip
system use loop-type fiber sensor for arc fault detection. In this
request over the communication bus to the relay of the
protection scheme the CBFP function is implemented by
infeeder.
tripping the HV side circuit breaker.
REF615 3 3 REF615
Ready Start Trip
Ready Start Trip
ESC Clear
REA 101 REA 101 ESC Clear
R
L ? R
L ?
3 I> 3
I>
3 3
ESC Clear ESC Clear
R
L ? R
L ?
REF615 REF615
GUID-D6C096C6-D07E-4968-9EAB-8124D5B9BAB7 V1 EN
Figure 10. A redundant and selective arc fault protection system of a single-busbar switchgear panel fed from two power transformers
14 ABB
Arc Fault Protection System 1MRS756449 B
REA 10_
REA 101
Trip
Light
REA 107
QRU100
PSE
Trip
GUID-882B496C-575F-41CC-8418-83EBA20EC72A V3 EN
Figure 11. Fast arc fault detection and elimination in a switchgear system fed by one power transformer
The arc fault protection system of Figure 11 incorporates arc arc fault occurs between the phases in the busbar system. The
detection and elimination hardware. In the figure a REA arc fault REA 101 module is equipped with a lens-type sensor for
protection system and an UFES have been combined. The detecting arc faults occurring in the infeeder cubicle. The
UFES comprises a QRU100 device (Quick Release Unit) and system is extended with a REA 107 module equipped with eight
PSE devices (Primary Switching Elements). The solution of the lens-type sensors for detecting possible arc faults appearing in
figure can be located in an environment, in which a fast isolation the busbar system, circuit-breaker feeder compartments and
of an arc fault is of utmost importance to minimize equipment cable termination compartments. The REA 107 module sends a
damage and prevent the fire from spreading. This also reduces LIGHT message to the REA 101 module, which issues a trip
possible risks to human beings. A typical operating time of the signal when the overcurrent condition for tripping is met. On
REA and UFES solution for detecting and eliminating an arc detection of an arc fault, the REA 101 main module sends a
fault is < 4 ms. The above case can, for example, be a TRIP signal to the Quick Release Unit (QRU100) controlling the
switchgear system of a petrochemical plant, which is Primary Switching Elements (PSE) which make a metallic three-
undergoing a retrofit installation. phase earthing, this leading to an immediate extinction of the
arc. To back up a fast isolation of the fault, the QRU100 trip is
The main module REA 101 detects fault currents. The routed further on to the circuit breaker of the HV side of the
protection function of the REA 101 module is activated when an power transformer.
ABB 15
Arc Fault Protection System 1MRS756449 B
REA 10_
3 3
PSE PSE
Trip Trip
GUID-60D93F9E-58D7-4838-A1C3-2E1753B725E8 V2 EN
Figure 12. Fast arc fault detection and elimination in a single-busbar switchgear system provided with a tie-breaker and fed by two power
transformers
The arc fault protection system of Figure 12 incorporates arc the HV side of the power transformers providing a reach of the
detection and elimination hardware. In the figure a REA arc fault protection up to the terminals of the power transformer. The
protection system and an UFES have been combined. The protection of both sections of the busbar system is
switchgear system of the figure can, for example, be located in accomplished with loop-type fiber sensors connected to two
the main switchgear of a process industry plant or a substation REA 103 modules. In addition, each outgoing feeder is
in a large city. equipped with REA 105 modules, which deliver selective arc
protection in case an arc fault occurs in feeder-cable
The arc fault protection system is based on two REA 101 termination compartments.
modules, which are interconnected using a REA 105 extension
module. The CURRENT messages are sent between the main On detection of an arc fault, the REA 101 main modules send a
modules via the REA 105 module. The system is extended with TRIP signal to the Quick Release Units (QRU100) controlling the
REA 103 and REA 105 modules for enhancing the selectivity of Primary Switching Elements (PSE), which make a rapid metallic
the protection system. The REA 101 modules are provided with three-phase earthing, this leading to an immediate
loop-type fiber sensors for detecting arc faults on the bus ducts extinguishing of the arc. To back up fast isolation of the fault,
between the power transformers and switchgear systems. The the QRU100 trip is routed further to the HV side circuit breakers
fault current is measured with current transformers located on of the power transformers.
16 ABB
Arc Fault Protection System 1MRS756449 B
REA 10_
7. Technical data
Description Value
Weight 4.6 kg
Description Value
Depth 44.6 mm
Weight 1.1 kg
Description Value
Depth 49.6 mm
Weight 1.1 kg
Description Value
Depth 28.5 mm
Weight 1.0 kg
Description Value
ABB 17
Arc Fault Protection System 1MRS756449 B
REA 10_
Description Value
REA 103 (operating voltage over the port of Power consumption of the module under ~1.6 W / ~3.3 W
REA 101) quiescent/operating conditions
REA 105 (operating voltage over the port of Power consumption of the module under ~2.7 W / ~3.7 W
REA 101) quiescent/operating conditions
REA 107 (operating voltage over the port of Power consumption of the module under ~1.7 W / ~2.7 W
REA 101) quiescent/operating conditions
Description Value
Rated frequency 50 / 60 Hz
18 ABB
Arc Fault Protection System 1MRS756449 B
REA 10_
Table 9. Outputs
Description Value
Breaking capacity for DC, when the control circuit time constant L/R < 40 5 A/3 A/1 A
ms, at 48/110/220 V DC
Continuous carry 5A
Breaking capacity for DC, when the control circuit time constant L/R < 40 5 A/3 A/1 A
ms, at 48/110/220 V DC
Continuous carry 5A
Breaking capacity for DC, when the control circuit time constant L/R < 40 1 A/0.25 A/0.15 A
ms, at 48/110/220 V DC
Description Value
Control voltages:
Description Value
ABB 19
Arc Fault Protection System 1MRS756449 B
REA 10_
Description Value
Description Value
Maximum length 1) 40 m
1) The sum of the connection cables length between the REA modules can be max. 40 m.
Description Value
Description Value
Current setting steps, In x 0.5, 1.0, 1.5, 2.5, 3.0, 5.0, 6.0
Neutral current setting steps, In x 0.05, 0.10, 0.15, 0.25, 0.3, 0.5, 0.6
Description Value
TRIP3 < 15 ms
Damp heat test cyclic r.h. > 95%, t = 20…55°C IEC 60068-2-30
20 ABB
Arc Fault Protection System 1MRS756449 B
REA 10_
Description Value
REA 103 IP 20
REA 105 IP 20
REA 107 IP 20
ABB 21
Arc Fault Protection System 1MRS756449 B
REA 10_
• Differential mode 1 kV
• Contact discharge 8 kV
• Air discharge 15 kV
• Amplitude-modulated:
• Pulse-modulated:
• Radiated RF emission
Power frequency (50 Hz) magnetic field 300 A/m, continuous IEC 61000-4-8
22 ABB
Arc Fault Protection System 1MRS756449 B
REA 10_
Description Reference
Description Requirement
Connector ST type
ABB 23
Arc Fault Protection System 1MRS756449 B
REA 10_
135
. 2±1
>20
254.3±1
~15
AB
B
D
10 D
4- .5
5 106
16.
Measure D: flush1_3
Measure D: semifl1_3
218.5 mm without protective cover 128.5 mm without protective cover
228.6 mm with protective cover 138.6 mm with protective cover
GUID-C560ED15-631E-4021-B8FA-E896D4FF564B V1 EN GUID-6AA61F44-E918-43DB-86EF-A9AD12F1B3E3 V1 EN
Figure 13. Flush mounting of REA 101 Figure 14. Semi-flush mounting of REA 101
A
M6x12 TORX
C
B
M5x8 TORX
wallmoun.
GUID-0CDA288C-B60D-43D3-A723-C2C0C5C111C2 V1 EN
24 ABB
Arc Fault Protection System 1MRS756449 B
REA 10_
Arc fault protection module REA 101 with Optolink connectors for glass REA101-AAAG1)
fiber
Un = 110…240 V AC
Un = 110…250 V DC
Arc fault protection module REA 101 with Optolink connectors for glass REA 101-CAAG1)
fiber
Un = 24…60 V DC
ABB 25
Arc Fault Protection System 1MRS756449 B
REA 10_
Table 28. Pre-manufactured fiber-cables with a lens-type sensor for REA 107
3m 1MRS 120534-3.0
5m 1MRS 120534-5.0
7m 1MRS 120534-7.0
10 m 1MRS 120534-10
15 m 1MRS 120534-15
20 m 1MRS 120534-20
25 m 1MRS 120534-25
30 m 1MRS 120534-30
Table 29. Pre-manufactured fiber-cables with a lens-type sensor for REA 101, REA 103, REA 105
2m 1MRS 120536-2
3m 1MRS 120536-3
5m 1MRS 120536-5
10 m 1MRS 120536-10
26 ABB
Arc Fault Protection System 1MRS756449 B
REA 10_
Table 31. RJ-45 cables for connecting REA to an extension module or for interconnecting extension modules
1m 1MRS 120511.001
3m 1MRS 120511.003
5m 1MRS 120511.005
10 m 1MRS 120511.010
15 m 1MRS 120511.015
20 m 1MRS 120511.020
30 m 1MRS 120511.030
40 m 1MRS 120511.040
Table 32. Plastic fiber cables for signal transfer between REA 101 main modules
1m SPA-ZF AA 1
2m SPA-ZF AA 2
3m SPA-ZF AA 3
5m SPA-ZF AA 5
10 m SPA-ZF AA 10
15 m SPA-ZF AA 15
20 m SPA-ZF AA 20
30 m SPA-ZF AA 30
40 m 1MRS 120517
ABB 27
Arc Fault Protection System 1MRS756449 B
REA 10_
6 6 lo 6 IL2
5 5 5
lo 4
4 4
X1
9
1A
CT3 5A 8
SG1/1
SG1/2 7
CURRENT
3
SG1/3 SETTINGS 1A 2
CT1
SG1/4 5A
1
OFF 6
SG4/1 1A 5
NEUTRAL CT2 5A
SG4/2 4
CURRENT
SG4/3 SETTINGS ON
SG4/4 SG4/4
SG1/6 SG1/5 X3
1
HIGHSPEED
Output 2 TRIP OUTPUT1
SG3/4
X6 SG3/1 CIRCUIT-
LIGHT DETECTION 3
SENSOR X7 AND SENSOR TESTING BREAKER HIGHSPEED
SG3/2 4
FAILURE TRIP OUTPUT2
Input SG3/3 PROTECTION
5
6 TRIP3
SG1/7
TRIP3
≥1
X4 CABLE 10
PORT A CONNECTION
8
BLOCK 9 IRF
trip
& IRF 8
SG1/8 light X2
light 9
light
≥1 10 RESET
CABLE I>
X5
PORT B CONNECTION trip SG2/1
8
BLOCK SG2/2
I> X8 Output
SG2/3 OPTOLINK1
COMMUNICATION X9 OPTOLINK1
SG2/4 Input
SG2/5
I> SG2/6
X10 Output
SG2/7 OPTOLINK2
X11 OPTOLINK2
light SG2/8 COMMUNICATION
Input
X2 1 2
L N
PE AUX. POWER SUPPLY
GUID-8DE49B80-98A0-47FD-8DEC-D2A79BE370F1 V1 EN
28 ABB
Arc Fault Protection System 1MRS756449 B
REA 10_
X1 8 9 10 4 5 6
SG1/3
IN SG1/5
Light detection
sensor 1 and testing Light1 Light2
OUT
SG1/4 SG1/2
IN
Light detection
sensor 2
and testing
OUT
SG1/1 ≥1
Port
X2 light
IN
Cable
connection
Port X3 block Power
OUT
GUID-36BCC9EC-DBBB-4EBB-9342-DD8031ABBBBD V1 EN
&
SG1/ 1 light ≥1
PORT X1 8
IN 1 Cable
I>
connection trip
PORT X2 8
OUT
block
SG1/ 2
I> ≥1
Power
PORT Cable
IN 2
X3 8
connection
I> ≥1
trip
block
GUID-A3F4E38A-1BC4-4FDA-A7EA-8B561EFCBBFA V1 EN
ABB 29
Arc Fault Protection System 1MRS756449 B
REA 10_
SG1/ 2
X1
4
5
SG1/ 1
6
≥1
PORT X2 Light
Cable Light 5 - 8
IN
connection
PORT X3 block Power
OUT 8
9
10
GUID-79DEFEC0-425E-4D3D-AFE1-C9A436B1B160 V1 EN
12. References manuals, product brochures, etc. The selection tool on the Web
The www.abb.com/substationautomation portal offers you page helps you find the documents by document category and
information about the range of distribution automation products language.
and services. You will find the latest relevant information on the
REA arc fault protection system on the product page. The Features and Application tabs contain system related
information in a compact format.
The download area on the right hand side of the Web page
contains the latest product documentation, such as, operator’s
A/2012-01-03 This document replaces the REA 101 Arc protection relay
Product guide, 1MRS750929.
30 ABB
31
—
ABB Distribution Solutions
Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland
Phone +358 10 22 11
www.abb.com/mediumvoltage
www.abb.com/substationautomation