Vous êtes sur la page 1sur 1

Segments Specifications & Illustration (Continued)

Humidifier Segment (Option)


Type High pressure spray humidifier
• Dry steam humidifier, it consists of chamber, control valve and
nozzle etc., with advantage of compact size, light weight and
Under the following operating conditions, select suitable
humidifier model according to the required humidifying
easy installation.

load and technical parameter table:

High pressure spray humidifier, it has stainless steel water
distributor and nozzles, single row or double rows spray. High Water supply: City water, purified water or similar water
pressure water is supplied by pump, removable dirt separator supply;


can also be equipped.
• Pressure of water supply: 1~3.5Kg/cm2
Electrode humidifier, it consists of humidifier host and steam
• Temperature of water supply: 5~40°C

distributor with high control precision, and it can provide
steam humidification without steam source. Inlet air on velocity: 1~2.5m/s
• Evaporative humidifier, with advantage of high saturation
efficiency, space saving, cleanness, safety and reliability. • Inlet air on temperature: 20~60°C

• Electric heater humidifier,it consists of humidifier box and


controller with high control precision, and it can provide
Electrode humidifier
steam humidification without steam source. Humidifier is selected according to required humidfication
load and unit width dimension.
Dry steam humidifier
Humidifier is selected according to control method, steam Electric heat humidifier
pressure supply, required humidfication load and unit width Humidifier is selected according to humidification load.
dimension.

Evaporative humidifier performance


Humidifying capacity to fresh air (kg/h) Humidifying capacity to mixed air (kg/h)
Model Evaporative humidifier thickness Evaporative humidifier thickness
50mm 100mm 150mm 200mm 50mm 100mm 150mm 200mm
0507 4.0 7.7 9.8 11.2 3.5 5.9 8.0 9.4
0511 7.4 14.1 17.9 20.5 6.4 10.9 14.7 17.3
0707 6.0 11.5 14.7 16.8 5.2 8.9 12.1 14.2
0709 8.5 16.3 20.8 23.7 7.4 12.6 17.1 20.0
0713 13.5 25.9 32.9 37.6 11.8 20.0 27.1 31.8
0715 16.0 30.7 39.0 44.6 13.9 23.7 32.0 37.6
0909 11.4 21.8 27.7 31.7 9.9 16.8 22.7 26.7
0911 14.7 28.1 35.8 40.9 12.8 21.7 29.4 34.5
0915 21.4 40.9 52.0 59.4 18.6 31.6 42.7 50.2
1111 18.4 35.2 44.8 51.1 16.0 27.2 36.8 43.2
1115 26.7 51.1 65.0 74.3 23.2 39.5 53.4 62.7
1117 30.9 59.1 75.2 85.9 26.8 45.6 61.7 72.5
1120 37.1 71.0 90.4 103.3 32.3 54.9 74.2 87.1
1313 27.1 51.8 65.9 75.3 23.5 40.0 54.1 63.5
1315 32.0 61.3 78.0 89.2 27.9 47.4 64.1 75.2
1318 39.5 75.6 96.3 110.0 34.4 58.4 79.1 92.8
1515 37.4 71.5 91.1 104.1 32.5 55.3 74.8 87.8
1518 46.1 88.2 112.3 128.4 40.1 68.2 92.3 108.3
1520 52.0 99.4 126.5 144.6 45.2 76.8 103.9 122.0
1524 63.6 121.7 154.9 177.0 55.3 94.0 127.2 149.3
1527 72.4 138.4 176.2 201.3 62.9 107.0 144.7 169.9
1719 56.0 107.2 136.5 156.0 48.7 82.9 112.1 131.6
1722 66.0 126.3 160.8 183.8 57.4 97.6 132.1 155.0
1726 79.4 151.8 193.2 220.8 69.0 117.3 158.7 186.3
1728 86.0 164.6 209.4 239.4 74.8 127.2 172.0 202.0
2020 69.3 132.5 168.7 192.8 60.2 102.4 138.5 162.6
2022 77.0 147.4 187.6 214.4 67.0 113.9 154.1 180.9
2028 100.4 192.0 244.3 279.2 87.3 148.3 200.7 235.6
2222 85.3 163.2 207.7 237.4 74.2 126.1 170.6 200.3
2224 93.9 179.6 228.6 261.3 81.7 138.8 187.8 220.5
2228 111.1 212.6 270.5 309.2 96.6 164.2 222.2 260.9
2424 103.0 197.0 250.8 286.6 89.6 152.2 206.0 241.8
2429 126.6 242.1 308.2 352.2 110.1 187.1 253.2 297.2
2433 145.4 278.2 354.1 404.7 126.5 215.0 290.9 341.5
2436 159.6 305.3 388.6 444.1 138.8 235.9 319.2 374.7
2828 143.4 274.3 349.1 398.9 124.7 211.9 286.7 336.6
2834 176.7 338.0 430.1 491.6 153.6 261.2 353.3 414.8
3036 201.8 386.1 491.4 561.7 175.5 298.4 403.7 473.9
3232 190.4 364.2 463.6 529.8 165.6 281.5 380.8 447.0
3236 215.9 413.1 525.7 600.8 187.8 319.2 431.9 507.0
Note: 1. Evaporative humidifier includes four kinds of thickness: 50mm, 100mm, 150mm, 200mm, and their humidifying efficiency are 40%,60%,75%,85% respectively.
2. The fresh air inlet condition: DB28°C. 10%RH, air velocity is less than 3.0m/s.
3. The mixed air inlet condition (fresh air ratio 20-30%): DB28°C. 25%RH, air velocity is less than 3.0m/s.
4. Humidifying capacity in table is maximum capacity and based on 3m/s air velocity. Humidifying capacity will reduce a little when air velocity is less than 3m/s.