Vous êtes sur la page 1sur 9

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/272093708

INSTRUMENT TRANSFORMER DIMENSIONING: PAST AND FUTURE

Conference Paper · November 2008

CITATIONS READS

0 1,626

4 authors:

Rainer Krebs Johann Jaeger


Siemens Friedrich-Alexander-University of Erlangen-Nürnberg
205 PUBLICATIONS   509 CITATIONS    90 PUBLICATIONS   407 CITATIONS   

SEE PROFILE SEE PROFILE

Andrzej Bachry Dieter Braisch


Siemens Friedrich-Alexander-University of Erlangen-Nürnberg
17 PUBLICATIONS   96 CITATIONS    9 PUBLICATIONS   7 CITATIONS   

SEE PROFILE SEE PROFILE

Some of the authors of this publication are also working on these related projects:

DynaGridCenter View project

Technical Performance of Renewable Generation and Energy Storage Systems View project

All content following this page was uploaded by Rainer Krebs on 11 February 2015.

The user has requested enhancement of the downloaded file.


INSTRUMENT TRANSFORMER DIMENSIONING:
PAST AND FUTURE

J. JAEGER A. BACHRY, D. BRAISCH, R. KREBS∗

UNIVERSITY OF ERLANGEN SIEMENS AG

GERMANY GERMANY

Keywords: instrument transformers, current and necessity of the new perspective for the instrument
potential transformer dimensioning, power system transformer dimensioning is accentuated.
protection, secondary engineering, protection
coordination 2 Current Transformers Physical
Behaviour
1 Introduction
In order to understand the standards and give a
As the development of digital measurement and background to them the physical behaviour of the
protection equipment has progressed over the last years, current transformer must be shortly mentioned at first.
the criteria used for sizing the necessary instrument The most important is the fact that a CT due to its
transformers have changed as well. Whereas in the past, physics always tries to draw such a secondary current Is
due to the high burden of electromechanical relays, it through its secondary circuit that equalizes the magnetic
was the rated power of the current transformers (CT) flux Ψp or induction Bp excited by the primary current Ip
and potential transformers (PT) that was the crucial (Figure 1).
parameter. Nowadays, it is the transient performance of It means that each current transformer is forced to
instrument transformers that has gradually become the introduce such a secondary current Is so that the
over-riding influence within the digital world of relays, secondary magnetic flux Ψs. linked with it equalizes at
measuring and controlling devices. every point of time the primary flux Ψp.
Firstly, due to paradigm change in the technology of the
power system substations the traditional usage of high
VA-rated instrument transformers can become even
dangerous both for themselves and for the secondary
circuits and equipment connected to them. Secondly, the
reduction of the switchgear dimensions, especially Gas
Insulated Switchgear (GIS), leads to a reduction of the
available instrument transformer compartments. That is
the reason why the volume of the instrument
transformers have to be optimized and adapted to the
actual needs of modern measurement and protection
equipment connected to them.
This paper shows in structured form the state-of-the-art
of the instrument transformer dimensioning. Thereby
the physical behaviour and the standards regarding
instrument transformers are shortly discussed and the
Figure 1: Simplified equivalent of an ideal CT


Siemens AG, Energy Sector, Power Technologies International, Freyeslebenstrasse. 1, 91058 Erlangen, Germany
The primary core flux for sinusoidal quantities is given the higher the primary current, the higher voltage must
by eqation (1): be induced to allow the secondary current flow.
Ip In practice the construction of the CT for a simple
Φ p = w p ⋅ µ0 ⋅ µ r ⋅ ⋅ AFe (1) design is close to the one presented in Figure 2, where
l Fe
the primary conductor is going symmetrically through
and the secondary core flux by eq. (2) respectively: the iron core. On this iron core there are windings
I wounded symmetrically over the core that build
Φ s = ws ⋅ µ 0 ⋅ µ r ⋅ s ⋅ AFe (2) secondary winding of such CT-core. For the comparison
l Fe
to the simplified CT equivalent in Figure 1 the length of
with magnetic path lFe and the core cross-sectional area AFe
Φ = B ⋅ AFe (3) are shown in Figure 2, correspondingly. The inductance
where B is magnetic flux density, AFe is the core cross- of such CT can be described
sectional area, lFe is the mean length of magnetic path A
and wp, ws are the number of primary and secondary L = ⋅µ 0 ⋅ µ r ( H ) ⋅ ws 2 Fe (9)
l Fe
windings, respectively. For ideal conditions as shown
simplified in Figure 1, where winding resistance and where µ0 is the absolute permeability = 4π ⋅ 10-7 H/m
leakage flux were totally neglected, one can write the and µr is the relative permeability of the material used.
equation for the core flux: In case of iron, µr is a non-linear function of the
Φ p − Φ s = Φ m = 0 or : Φ p / Φ s = 1 (4) magnetic field H and varies usually between 1000 and
Considering the relation in eq. (4) and using eq. (1) and 50000.
eq. (2) one can write the following relation:
Ip ws
= (5)
Is wp
which describes the law of Ampere-turn balance and is
the basics of the whole CT performance [1]. That means
that no magnetizing flux Φm is inside of an ideal CT
core, or, in other words, ideal working-conditions for a
CT are given when its core is fully balanced and no
magnetic flux is present.
In reality, there are no ideal conditions as described
above. There exists always some secondary burden as
resistance or impedance, e.g. at least the inner
secondary winding burden, which causes a voltage drop Figure 2: Typical design of CT within GIS switchgear
in the secondary circuit. Thereby, the total linked flux
(coil flux) relevant in the secondary circuit is At this stage, for the simplicity, the influence of leakage
Ψ m, s = ws ⋅Φ m = ws ⋅ Bm ⋅ AFe (6) inductance as well as the inductance of the secondary
wires and the inductance of the input burden of the
where the inner induced voltage on the secondary CT
instrument/relay are neglected. The first assumption
side equals to:
cannot be made if for example the distance between
dΨ m, s dBm
Um = ∝ (7) primary winding and core is high and the primary
dt dt winding has unsymmetrical layout with respect to the
The magnetizing curve measured from the secondary core or there exists close proximity to return or
side in steady-state conditions usually with RMS – neighbouring conductors. All those issues will be
values describes the non-linear magnetic characteristic treated in foregoing papers and are mentioned here only
(eq.(8) and Figure 4) of the iron core on the shunt for the sake of completeness. For almost all practical
inductance L. purposes the performance of CT can be described by its
U m = f (I m ) (8) simplified equivalent circuit shown in Figure 3.
Practically, the current transformer during its duty of Ip
‘core-balancing’ by drawing the secondary current Ip Is Is
Kn Kn Rct
through the secondary circuit always has to overcome a
couple of ‘burden’. In other words it is forced to Im
magnetize itself (i.e. the magnetizing flux in the core primary secondary
Φm≠0) to produce such a voltage (on the inductance L) clamps L U m (Im )
clamps
Rb
that draws the secondary ampere-turns current which
equalizes the ampere-turns of primary current. Such
‘burden’ for the CT are internal impedance of the
secondary winding and the total impedance that is connected
connected to its secondary clamps (i.e. wire and burden
instrument burden). Thereby, the higher the burden or Figure 3: Simplified equivalent circuit of a CT
The current ratio Kn of the CT is the ratio of primary Ipn magnetizing current may be required to ensure enough
and secondary Isn nominal currents: Kn = Ipn /Isn. This is fault sensitivity, for example:
symbolized in Figure 3 by the ideal transformer. The I knee ≤ I m, max (11)
nonlinear magnetic characteristic of the iron core is
described by the shunt inductance L on the electrical More detailed information about practical hints how to
side. The typical magnetizing curve Um (Im) of this shunt proceed with CT dimensioning within IEC class PX
inductance L is shown in Figure 4. Before the secondary (BS X) will follow in the next papers. At this stage the
current reaches the CT secondary clamps and the dimensioning process of the current transofrmer can be
connected burden it passes the internal resistance Rct.(so finished. So that at least the following main physical
called: ‘internal CT burden’). data of the equivalent circuit must be given on the rating
plate: Ipn, Isn ,Uknee, Iknee, and Rct.
3 Standards for Current Transformers 3.2 IEC protective class P and IEC measuring class
Starting the discussion of the international standards
The CT description within IEC class P standard is a
describing CTs it is worthy to discuss at first IEC class
little bit different. The retrospective look to the past
PX standard [2], former British Standard (BS) class X,
generation of the secondary protection and measuring
since it is defined very close to the physical description
equipment used within power systems brings more light
presented above.
to the idea behind the nameplate parameters of the IEC
class P CTs. Namely, those devices had much more
3.1 IEC protective class PX burdens than nowadays. It was necessary to feed the
Within this standard a characteristic knee point on the secondary equipment with sufficient power in order to
magnetizing curve is defined, where a voltage rise by generate enough electromagnetic force that moves the
10% leads to a current rise of 50% (Figure 4). This knee elements (moving-iron or moving-coil) inside
point voltage and the corresponding current are given on electromechanical relays. Therefore, usage of higher
the rating plate. In addition, the secondary winding secondary current was indispensable. So CTs with 5A
resistance Rct as inner burden is given for 75°C. At the nominal current have been used for many decades.
secondary terminals any external burden Rb may be During development process of the electromechanical
connected. The specification of such burden is not relays-technology the hunger for VAs was a little bit
subject to this standard. reduced so that also CT with 1A nominal secondary
current appeared. Nevertheless, in the past the CTs were
used to feed protection cubicles full with
U m [Vrms ]
electromechanical relays and therefore ‘burden’ was the
1.1U knee useful term used in the CT nomenclature, however,
physically, it is the impedance (when cosϕ <0.8) or
U knee resistance that should be mentioned for simplicity. One
should note that the following relation is essential:
Sb = Rb ⋅ Isn2, (12)
which implies that 30VA for a 5A CT equals to 1.2 Ω,
1.5 I knee and for a 1A CT equals to 30 Ω.

I knee I m [ Arms ] Summarizing, for the CT nameplate the straight-forward


idea was to put there such nominal power Sbn that will
Figure 4: Magnetizing curve of the shunt inductance of
be needed to feed typical protection cubicle and in
the CT in Figure 3; Knee-point definition acc. to
addition to provide information about some multiple of
IEC Standard, class PX
the nominal current that CT will be able to transform
without too high current error (which is described by the
It is to underline here that this CT class describes the
CT error class) due to excessive saturation. In this way
CT in a very clear physical manner giving the parameter
on the nameplate of IEC class P the following parameter
of the magnetizing characteristic of inductance L and
have to be specified: Ipn, Isn ,Ksscn, and Sbn. , where
the internal burden Rct (Figure 3).
I psc
The typical requirement of a protection device for CT K sccn = (13)
dimensioning is for example: I pn
I psc, max is the overcurrent factor and Ipsc is the primary
U knee ≥ ⋅ (Rct + Rb ) (10)
Kn symmetrical short-circuit current. In such way, the
where the maximum detectable short-circuit current typical 5P20 30VA has often been used.
Ipsc,max on the CT secondary side must not lead to a It is very important to recognize that no other parameter
voltage drop higher than the knee point voltage in order is necessary to describe the CT behaviour for the
to avoid too high error of the secondary current due to symmetrical short-circuit current. Indeed, when CT is
magnetic saturation. Furthermore, the limit of the burdened with operating burden that is close to the rated
one on the nameplate, the overcurrent factor will be
similar to the indicated one on the nameplate, so the 4 Dimensioning of IEC class P CTs;
information about the internal burden Rct. is not Example for 1 A and 5 A cores
necessary.
As an example a traditional 5P20, 30VA CT will be
Such definition of the IEC class P CT can be seen as a considered.
heuristic description of the CT behaviour at nominal
operating conditions of the CT, which are in turn 4.1 CT with 1 A secondary nominal current
defined by its nominal burden. This is the most
important issue considering IEC class P specification. At first it is assumed that this CT has the secondary
The exact definition of IEC class P is specified by nominal current Isn of 1 A and the internal resistance Rct
maximum transformation errors ε for the nominal equals to 5 Ω. In Figure 5 the error diagram (error εc
current Ipn and a well defined overcurrent Ipsc when the versus overcurrent factor Kssc ) is given for this CT.
nominal burden Sbn is connected to the terminals [2]. ( Rct = )
This is shown in the following table. ε [%] I p Is
K sscn FSn ;
I pn I sn
Table 1 Definition IEC class P, acc. to IEC 60044-1, Ip Is
Edition 1.2 (2003)
at Overcurrent
Accuracy at Nominal current Ipn
Ips=Ksscn ⋅ Ipn Rbn
Current Phase Composite
Class error displacement error
εi [%] δ [min] εc [%] 2
Sbn [VA] = Rbn ⋅ I sn
5P ±1 ± 60 5 Sb = Sbn Sb << Sbn
10P ±3 not specified 10
Figure 5: Error diagram for IEC class P CT with 1A
secondary nominal current: 5P20, 30VA, Rct =5 Ω
It can be seen from Table 1 that CT class P is specified
and relation to IEC measuring class
for nominal primary current, as well. The most
important issue is to keep in mind that the exactness
Remembering the fact that the error limits for protective
specified at Ipn can only be guaranteed by the CT
classes in Table 1 are maximum values, the actual errors
manufacturer, when the CT is burdened with rated
have to be lower. This is a minimum requirement for
burden Sbn.
dimensioning of protective class CTs and it is shown in
As a further remark, one must consider that the error
Figure 5 by the grey area with description ‘5P20’ It can
values given in the table for the overcurrent behaviour
be also understood as ‘forbidden’ area for the error of
are maximum allowable errors, which fall in practice
such protective-core CT.
always below the limits specified. So, practically, in the
The CT manufacturer has to verify by test that these
last column the limits should be written as ≤ 5 and ≤ 10,
requirements are fulfilled. Before the test he will
respectively.
estimate the characteristic accuracy limiting point
Ual(Ial) on the magnetizing curve. For class P the
Definition for measuring classes according to IEC are
maximum error current Ial as magnetizing current at
based on the same principle, namely, on the nominal CT
nominal overcurrent factor Ksscn can be estimated from
conditions that are defined by its nominal burden Sbn.
the accuracy class (Figure 6) according to equation (14):
The only differences are as follows:
I al = ε c ⋅ K sscn ⋅ I sn (14)
1. Accuracy (current error εi and phase displacement δ)
is specified for more working points that lie not only at which in our example leads to:
the nominal current Ipn but start below it up to slightly I al = 5% ⋅ 20 ⋅ 1 A = 1 A (15)
above the nominal current (e.g. at 1%, 5%, … up to The corresponding calculated accuracy limiting voltage
120% of Ipn). Ual can be estimated, as well, using equation (16) :
2. Instead of overcurrent factor, an instrument security
U al = K sscn ⋅ I sn ⋅ ( Rct + Rbn ) (16)
factor (FS) is specified, at which the composite error
must be at least 10%. This is to protect the connected which for the analyzed CT will lead to:
measuring devices against too high over-currents. U al = 20 ⋅ 1A ⋅ (5Ω + 30Ω ) = 700 V (17)
Thereby, the most important are the following remarks: with nominal burden Rbn in Ω calculated from eq. (12):
Ad. 1. The accuracy class of metering CT can be only S 30VA
maintained when the CT is burdened with operational Rbn = bn2
= = 30 Ω (18)
I sn (1 A) 2
burden Sbo that lies between 25% .. 100% of its nominal
burden Sbn, and The actual magnetizing curve has to be higher than this
Ad. 2. The nominal instrument security factor FSn is calculated point for the worst case. An exemplary of
defined at nominal working conditions of the CT, i.e. such curve is shown in Figure 6.
when the CT is burdened with its nominal burden Sbn.
U m [Vrms ] 1A CT Now, for a 5A CT the nominal burden of 30 VA equals
875 V U FS to 1.2 Ω. The calculated magnetizing curve can be
constructed analogously, too, using equations (14), (16),
700 V U al and (18). In such way one can find the results, as shown
in Figure 8.

U m [Vrms ]
U FS
I al I FS I m [ Arms ] U al
1A 2.5 A
Figure 6: Magnetizing curve of the CT from Figure 5

The protective class 5P20, 30 VA in this example may


also fulfill a measuring class if desired, for example:
0.5FS25, 30 VA, where for the instrument security I al I FS I m [ Arms ]
factor FS the error must be at least 10% in order to
protect measuring devices against too high overcurrents Figure 8: Magnetizing curve of the CT from Figure 7
by limitation of the CT secondary current. This is a
maximum requirement for dimensioning of measuring Comparing the results of calculations for the examples
class CTs and it is shown in Figure 5 by the grey area shown the following can be stated:
with description ‘0.5FS25’ It can be also understood as 1. Only form the VA-rating no-one can draw
‘forbidden’ area for the error of such measuring-CT. conclusions about CT performance, so the statement:
A similar approach is applied for the factor of security ‘the more VA the better CT’ is completely false
FS. The magnetizing curve has to be lower than the 2. Considering nominal burden of the CT from the
point UFS(IFS) shown exemplarily in Figure 6. example shown it can be observed that 30VA seems to
Acc. to IEC standard the winding resistance Rct is be right nominal burden for a 5A CT (wire and devices
usually not given on the rating plate because this connected have total resistance of <1.2Ω, which
calculation is done by the CT manufacturer only. nowadays looks reasonable). However, for the 1A CT
Normally, the CT should be dimensioned and ordered the 30VA (i.e. 30Ω) seems to be too high nominal
by the customer for the maximum detectable short- burden considering modern digital relays and measuring
circuit current Ipsc,max which leads to the nominal instruments. As a result of this the CT works under-
overcurrent factor Ksscn whereas the nominal burden burdened. The consequences of this be then analyzed in
should be slightly higher than the actual total burden the next chapter.
Rbo. Up to here, no winding resistance Rct is needed, 3. For the performance the CT magnetizing curve
since it was assumed that the CT is burdened with an should be always analyzed. So the usage of resistances
actual burden that is close to its nominal burden, i.e. and voltages is the right way. On the contrary, the usage
30 VA, which means for 1A CT 30Ω. of power (burden) and overcurrent factor can be
misleading. How far misleading it is, the current
4.2 CT with 5 A secondary nominal current practice by the dimensioning of the CTs shows very
clearly, whereas high VA for 1A CT are now the less
Now, also a 5P20, 30VA CT will be considered. suitable state-of-the-art.
However, for comparison, the CT has the secondary
nominal current Isn of 5 A. The internal resistance Rct
will be assumed to be 0.3 Ω. As this CT shall fulfil the
5 Dimensioning practice: Past and Future
same IEC class P standard its error diagram (Figure 7) As described above, in the past, electromechanical
can be constructed analogously to the 1A CT. protection relays worked with 5 A nominal current and
( Rct = ) had burdens up to many VAs. The potential
ε [%] Ip I transformers have also supplied many relays in the
K sscn FSn ; s protection cubicles. Nowadays, the power consumption
I pn I sn
Ip Is of the modern digital relays is hundredth times lower.
Unfortunately, the dimensioning practice of the
instrument transformer has not been changed through
Rbn the years. Therefore, a new perspective is necessary to
be given for the instrument transformers dimensioning
2
practice. This is discussed in this chapter.
Sbn [VA] = Rbn ⋅ I sn
At first, Table 2 presents an overview on power
Sb = Sbn Sb << Sbn
consumption of current and voltage input circuits of the
Figure 7: Error diagram for IEC class P CT with Isn=5A secondary instruments comparing old-technology with
5P20 30VA, Rct =0.3 Ω the new one [3].
Table 2 Input circuits power consumption of relays calculation the winding resistance must be known.
Description
Power consumption for input
Current Voltage
Considering the CT data from the example in section
VA VA 4.1: 5P20 30VA with Rct =5Ω (Figure 5 and Figure 6) it
Current measurement
(moving-iron)
0.1 - 1.6 can be written:
Voltage measurement
0.9 - 4
U al = K sscn ⋅ I sn ⋅ (Rct + Rbn ) =
(moving-iron) (20)
electro- Power-factor meas. 3.8 1.4
K ssco ⋅ I sn ⋅ ( Rct + Rbo ) = 700 V
mechanical Power meter 2 4.4 This calculated accuracy limiting voltage Ual influences
O/C protection 15 - 20 - 30 directly the size of the iron core according to eq.(6) and
Distance prot. (MV) 3 - 30 13 - 120 eq. (7) and provides the possibility of CT core
Distance prot. (HV) 2 - 6 - 20 35 - 120 optimization especially in small GIS CT compartments.
Eq. (20) leads to:
O/C protection 0.1 - 6
static
Line diff. prot. 4 - 11 R + Rbn 5 Ω + 30 Ω
K ssco = K sscn ct = 20 = 93 (21)
Distance prot. 0.35 - 1.35 15 Rct + Rbo 5 Ω + 2 .5 Ω

numerical Digital protection and 0.05 - 0.1 (1A CT)


As a result the requirement of actual overcurrent factor
0.1 - 0.3
measuring devices ~0.3 (5A CT) Kssco ≥ 80 is fulfilled. Such practice is still used
A big difference can be observed between the burdens nowadays as a state-of-the-art. Often it is assumed that
of electromechanical relays and numerical relays used for class P protective cores it has no significant
nowadays. Therefore in the past high nominal burden drawbacks against the straight-forward way (i.e.
have been chosen for both CTs and PTs. Unfortunately, 5P80 2.5VA). But the two following issues must be
this approach still continuous to be applied nowadays. pointed-out:
Coming back to the examples from section 4 it is now 1. Using under-burdened protective CT with turn-
clear that in the past the typical operating burdens Sbo of compensation and measuring CTs (see below) can
up to 20 .. 30 VA were the result, because relays that exceed the error at nominal current (the error curve is
were connected consumed many VAs. Furthermore, as lower for lower burdens than nominal burden – dotted
the relay pick up setting was rarely higher than 20 ⋅ Ipn curve shown in Figure 5).
the standard CT 5P20 30 VA has been used for many 2. Using under-burdened CTs with small current ratio
purposes. The DC component of the short-circuit Kn can damage the connected relays in case of strong
current, which is very critical for CT saturation within close-in fault (very high secondary current that flow on
the first cycles after fault inception, has been considered the CT secondary due to high Kssco).
for special cases only due to slower operation times of These two critical and very important facts have to be
the relay. considered in the same way for the factor of security FS
Nowadays, modern digital protection devices work with for measuring classes, too. The operating factor of
1 A nominal current and have burdens lower than security FS0 for the under-burdened measuring CT from
0.1 VA so only the burden of secondary wiring is the our example can be calculated:
most significant one. Maximum operation times have R + Rbn 5 Ω + 30 Ω
FS o = FS n ct = 25 = 116 (22)
been shortened to a few milliseconds up to a few cycles, Rct + Rbo 5 Ω + 2.5 Ω
so the DC component must be now considered by an That means that the CT will be surely in saturation for
additional transient dimensioning factor Ktd [4]. The more than 100 times the nominal current!
typical requirement of a protection device for CT Such very high operating factor of security FS0 can be
dimensioning will now be: dangerous to the connected devices, especially in the
I psc, max case of low current ratios. Here the nominal burden
K sscn ≥ K td ⋅ (19)
I pn cannot be chosen arbitrary for the same CT.
As already mentioned above, for measuring classes, the
Considering CT Data as from example in section 4.1 new error curve may exceed also the accuracy limit for
and assuming Ktd = 4, the CT with 5P80 should be nominal currents (Figure 5 dotted line), because acc. to
specified (4 ⋅ 20 = 80). Assuming that the real IEC these limits are required to be valid only for
operational burden Rbo is less than 2.5Ω, which is burdens between 25% .. 100% of its nominal burden Sbn.
almost true in the new GIS switchgears, the straight- This requirement leads very often to additionally
forward specification should be 5P80 2.5VA. installed resistors in order to compensate too low
However, as a state-of-the-art for class P CTs at first burdens, which is surely a dangerous practice of
some arbitrary burden is chosen as nominal burden (e.g. introducing new elements into the secondary circuit of a
30VA) then the calculation of the actual operational CT and should be abandoned. Such additional resistive
overcurrent factor Kssco is done since the CT is introduce a risk as day may be damage by overcurrents
connected to a small burden only (<2.5VA). When the and lead to interruption of the CT secondary circuit.
connected operational burden Rbo is much lower than Furthermore a general drawback must be mentioned for
nominal burden Rbn the actual overcurrent factor Kssco the sake of completeness. When a CT 5P20, 30 VA is
rises up because the fix accuracy limiting voltage Ual of used for the real burden of approx. 2.5VA (instead of
the CT is reached for higher currents than nominal 5P80, 2.5 VA), the conversion of the overcurrent factor
overcurrent indicated on the nameplate as Ksscn. For this must be done, as shown above. For this purpose the
winding resistance Rct is needed which must be asked It can been observed that the under-burdened CT
additionally at the CT manufacturer. delivers very high current to the relay (Figure 9). Its
Summarizing, there is no need to choose the nominal instantaneous peak value reaches more than 500 A and
burden much higher than the connected one and an the steady-state rms value is close to 300 A. Such a
overcurrent factor much lower than the required one portion of energy is very dangerous and may damage
from the physical point of view. Such practice can lead the connected digital relay, where the input circuits of
to some dangerous or unwanted issues, like: such relay cannot handle such currents. Exemplarily, the
• for non-gapped protective cores, (like IEC class current inputs of the used digital relay are limited to
P) in cases of turn-compensated CTs and small- 250 A peak current and 100 A steady-state rms current
ratio CTs for 1 s.
• for gapped protective cores (like IEC class PR, In general, such critical situations occur for busbars
TPY, TPZ): Importance of the correct VA-rating with high short-circuit power and feeders with low rated
in general, otherwise secondary time constant currents, where low CT ratios are chosen. This fact is
and transient behaviour changes also valid for the HV substations.
• Measuring CTs: Accuracy issue and necessity for
secondary current limitation in case of fault in Such situations require detailed analysis that includes
the primary system; dangerous practice of adding strong co-operation with the CT manufacturer and worst
an resistor into the secondary circuit to reach the case considerations. More details on this subject will
accuracy of high VA-rated CTs. follow in foregoing publications. For the purpose of this
• Potential transformers: Accuracy issue and raise paper the strong relation between traditional practice of
of resonance danger by under-burdened PTs. CT dimensioning should be underlined. Due to
Some issues need further explanations and are therefore unnecessarily high VA-rating of the CT an unclear and
shortly commented in the next subsections. confusing situation appears. The risk of such high
currents can be easily seen and counter-measured if the
5.1 High VA-rated Small Ratio CTs corresponding CT will be ordered as 5P20, 1.5VA, as a
typical medium voltage CT core.
As a short example from a medium voltage switchgear,
the transient behaviour of 100 A/1 A CT, 5P20, 10 VA, 5.2 Gapped-cores CTs
with assumed internal resistance Rct of 0.5 Ω will now
be analyzed. In this example it is assumed that the In cases when some protection approach limits the
actual operating burden equals to 1 Ω, which usage of classic methods of instrument transformer
corresponds to burden of a digital relay (0.05 VA) that design it is often impossible to obtain good and usable
is connected via approx. 80m 4mm2 copper wire (0.9 Ω) results with classic non-gapped cores. This is the case,
to the CT clamps. Using eq. (21) the operating accuracy for example, with high values of fault current, low
limiting factor Kssco is calculated: values of current transformer transformation ratio and
high network time constants. E.g. for auto-reclosing the
R + Rbn 0.5 Ω + 10 Ω
K ssco = K sscn ct = 20 = 140 (23) hysteresis and remanence of the iron core have to be
Rct + Rbo 0.5 Ω + 1Ω
taken into account.
Figure 9 shows the transient behaviour of the CT for The standards organizations have reacted to the
40 kA primary short circuit current with 50 ms primary changing circumstances in the methods of sizing current
time constant and fault inception angle of 0°. The transformers as shown in IEC Standard [4], which
simulation of the CT transient behaviour was carried out classifies a number of current transformer classes, such
using the transient simulation module of the software as TPS, TPX, TPY and TPZ, for transient operation.
tool CTDim [6]. Thereby cores TPY and TPZ are gapped cores, whereby
their transient operation is specified through several
primary current parameters. Moreover with amendment 1 in Year 2000
secondary current to the Standard [2] a gapped anti-remanence core class
PR was introduced, as well.
Especially for gapped cores (IEC class PR, TPY, TPZ)
the time constant of the CT secondary circuit Ts
L
Ts = (24)
Rct + Rbn
is the key parameter for the transient performance and
must be much lower than for non-gapped CTs (class P,
TPX, PX, TPS). If such CTs are connected to too low
burdens than nominal burden, the time constant rises up
and the desired performance won’t be fulfilled. Such
Figure 9: CTDim Simulation of transient behaviour of cases may lead to critical situations, when not
IEC CT 100/1 5P20 10VA, Rct =0.5 Ω on Ipsc=40 kA considered carefully.
with Tp=50 ms
5.2 Under-burdened Potential Transformer dimensioning, the required lower burden and high
overcurrent factor are converted to a high nominal
Some remarks with respect to the instrument burden and low overcurrent factor via the often
transformer dimensioning practice should be also given unknown winding resistance. This conversion is a long
with respect to potential transformers. Within IEC there way around and totally unnecessary for P class CTs
exists a Standard [5] describing inductive potential without turn compensation.
transformers that are, with exception of ultra-high For measuring CTs class and protective CT class with
voltage air-insulated switchgears, the state-of-the-art turn compensation operational burdens much lower than
within the electrical power systems. nominal burden can violate the requirements of the
Here the paradigm change took place too and nowadays accuracy class. Moreover, it was shown, that a mixture
almost exclusively digital equipment is connected to of high rated powers of CTs with modern low burden
them. However, the practice of sizing the PT remained relays may lead to a damage of the secondary
unchanged. Considering the values given in Table 2 for equipment, especially when small-ratio under-burdened
the power consumption in the PT circuits the same, as CTs are used. The remark and the background
for the CTs can be stated. Namely, the PTs that are information that the problems of resonances within
currently ordered are extremely under-burdened. The under-burdened PT circuits raise in the last time was
PT manufacturer designs and produces a PT with e.g. a given, as well.
nominal burden of 100 VA, whereas in the substation Summarizing, it is strongly recommended that the
only several VA or sometimes below 1VA is then current practice of instrument transformer dimensioning
connected. should be abandoned and CT and PT nominal burdens
As a result dangerous situation is introduced. The PT should be chosen appropriately to the operational
was designed (together with its accuracy turn- burden with a realistic safety margin included.
compensation and anti ferro-resonance measures) to More information related to the subject of CT and PT
some nominal burden. Now it is burdened with very low dimensioning within the modern digital relaying and
burden, i.e. close to the open clamps conditions. This measuring technology also with relation to other
has the following drawbacks: standards like ANSI will be described in the foregoing
1. The accuracy class cannot be guaranteed (acc. to IEC publications.
these accuracy is valid only for burdens between
25% .. 100% of its nominal burden Sbn). This, in turn,
leads very often to additionally installed parallel
References
resistors in order to compensate too low burdens, which [1] M. E. Korponay, “Application Guide to IEC
is surely no good practice. Standard IEC 44-6” (1995)
2. Increase of resonances or ferro-resonances danger [2] International Standard: IEC 60044-1, “Instrument
due to under-burdening of VT secondary circuit and de- transformers – Part 1: Current transformers”,
tuning of anti-resonance counter-measures (if Edition 1.2, (2003)
applicable). In the last years the number of resonance or [3] Interessengemeinschaft Energieverteilung (ABB,
ferro-resonance phenomena has increased, and it can be AEG, Siemens): ‘Auslegung und Ausführung von
partially explained by the traditional sizing approach Strom- und Spannungswandlerkreisen’ (1992)
mentioned above. [4] International Standard: IEC 44-6, “Instrument
transformers – Part 6: Requirements for protective
6 Conclusions current transformers for transient performance”,
First Edition , (1992)
The paper described different instrument transformer [5] International Standard: IEC 60044-2, “Instrument
definitions acc. to IEC Standard with relation to the transformers – Part 2: Inductive voltage
physics of an iron-cored current transformer. The transformers”, Edition 1.2, (2003)
background of instrument transformer dimensioning [6] CTDim: Software Program for Current
with 5A sec. currents and requirements of Transformer Dimensioning;
electromechanical relays was presented, in comparison www.siemens.com/ctdim
to 1A sec. currents and modern numerical relays.
Thereby, different protection functions with their
requirements and their impact on the dimensioning of
instrument transformers in the past and today were
described and discussed.
In the past protection and measuring devices connected
to current transformers had much higher burdens than
nowadays. Nominal burdens of CTs had been chosen
accordingly. Nowadays device burdens are much lower
but CT nominal burdens are still ordered traditionally
very high and nominal overcurrent factors too low.
As the accuracy limiting voltage (or knee point voltage)
is the physical quantity which is important for CT

View publication stats

Vous aimerez peut-être aussi