Project Varibles
FPC-500 Battery Calculator
Project Name:
Project ID:
Edit Device Database
Standby Hours:
Alarm Mins:
Print Page
60
15
Print Circuit Detail
8
9 Prepared By:
10
11 Date:
12
13
14
15 Panel ID: Model: FPC500-8 Max Circuit Cur: 2.5 Amps
16
17 Location: Volts: 24 VDC Max Panel Cur: 5 Amps
18
19 Current
Circuit Type Type Quantity
20 Standby Alarm
21 Zone 1 Not Used 0 0.00 0.00
22 Zone 2 Not Used 0 0.00 0.00
23 Zone 3 Not Used 0 0.00 0.00
24 Zone 4 Not Used 0 0.00 0.00
25 Zone 5 Not Used 0 0.00 0.00
26 Zone 6 Not Used 0 0.00 0.00
27 Zone 7 Not Used 0 0.00 0.00
28 Zone 8 Not Used 0 0.00 0.00
30 ProgramInput 1 Not Used 0.00 0.00
31 ProgramInput 2 Not Used 0.00 0.00
32 Aux Power 0.000 0.00 0.00
33 Sounder 1 0.000 0.00 0.00
34 Sounder 2 2.000 2.00 40.00
35 OC1~4 0.000 0.00 80.00
36 OC5~8 0.000 0.00 80.00
37 FPA-500 Panel 120.00 150.00 Total Internal Alarm Current (mAmps)
38 Total Internal Standby Current (mAmps) 122.00 350.00 Total External Alarm Current (mAmps)
39 Total External Standby Current (mAmps) 0.00 0.00 Alarm Time In Min
40 Standby Time In Hours 60 15 Total Alarm AH Required
41 Total Standby AH Required 7,320 88
42 Total Combined AH Required 7,408
Conductor Properties NEC Chap. 9
Wire Type Ohms Per 1000 ft.
#12 Solid 2.01
#12 Stranded 2.05
#14 Solid 3.19
#14 Stranded 3.26
#16 Solid 5.08
#16 Stranded 5.29
#18 Solid 8.08
#18 Stranded 8.45
Unused
Bosch
Users Choice
1500
1000
500
0
0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
18 Power (18)
18 16 14
0.1 2250 2194.277 3291.534 5485.691
0.2 1050 1100.337 1650.565 2750.842
0.3 740 734.8082 1102.252 1837.021
0.4 550 551.7725 827.6886 1379.431
0.5 450 441.8319 662.7717 1104.58
Circuit: OC1~4
If we only let the AUX power supply max 500mA current then:
Device FCS-LWM-1 is 590mA over than the aux power max current when 15 connect together as SRS.
Device Fireray 2000 is 590mA over than the aux power max current when 15 connect together as SRS.
Device Fireray 50RV/100RV is 1222mA over than the aux power max current when 32 connect together as SRS .
Device Fireray 5000(low current mode) is 550mA over than the aux power max current when 5 connect together as SRS .
Device FCS-320-TP2 is 1205mA over than the aux power max current when 1 connect together as SRS .
Device FCS-320-TP1 is 930mA over than the aux power max current when 1 connect together as SRS .
For the Aux Creeping Short and Aux Short configuration:
Im---max current for good product including Alarm
Inom---standby and nomal working current
Ics---currnt for creeping short
Imax---max current with buffer and with different nunmber connection devices
N---number of connection devices
Formula:
Ics==Round up [(Im*N*1.055+5.5)/12.5,0]*12.5 mA
Imax==Ics*1.055+(Im-Inom)*N+5.5 mA
So for each type device we could set the Ics according to the" Im", and set the Imax according to the "Im and (Im-Inom)"
Uparity Im Inom P Pges Pbin Pquer Pparity Ics Imax
0 150 50 0 0 00000000 0 0 0 0 13 18
1 130 110 1.4 0 00000000 0 0 0 0 13 18
0 58 3.5 0 0 00000000 0 0 0 0 13 18
0 25 15 0 0 00000000 0 0 0 0 13 18
0 25 15 0 0 00000000 0 0 0 0 13 18
0 25 15 0 0 00000000 0 0 0 0 13 18
0 25 15 0 0 00000000 0 0 0 0 13 18
1 58 15 0 0 00000000 0 0 0 0 13 18
1 58 15 0 0 00000000 0 0 0 0 13 18
0 155 100 2 0 00000000 0 0 0 0 13 18
0 250 100 2 0 00000000 0 0 0 0 13 18
0 545 240 6.8 0 00000000 0 0 0 0 13 18
0 675 240 7.9 0 00000000 0 0 0 0 13 18
UP quer UP parity
2 0
3 1
2 0
2 0
4 0
2 0
2 0
3 1
4 0
4 0
4 0
4 0
gether as SRS .
nnect together as SRS .
the "Im and (Im-Inom)"
DIP-Switches:
Imax_aux Rcalc R V P
500 93.5 10111011 00100100 00000000
500 506.0 11001000 11010101 00000000
500 616.0 11001000 01010001 00000000
500 533.5 11001000 01010100 00000000 15
500 451.0 11001000 01010111 00000000 15
500 533.5 11001000 01010100 00000000 32
500 533.5 11001000 01010100 00000000 32
500 313.5 11001000 11011100 00000000 5
500 313.5 11001000 11011100 00000000 5
500 258.5 11001000 01011110 00000000
500 258.5 11001000 01011110 00000000
500 258.5 11001000 01011110 00000000
500 258.5 11001000 01011110 00000000
DIP
50.0 01100100
00100010
Bit7: Parity R
15
15
32
32
5
5
4-Wire Aux 4-Wire Aux
Standby Alarm
Standby Alarm
[in mAmps] [in mAmps]
Manufacture Model Description [in mAmps] [in mAmps]
Unused - - 0 0 - -
Bosch FNS-320-Sxx Optical Device 1 88 - -
Bosch SG 200 Acoustic Device 1 32 - -
Bosch MSS 300 standalone Acoustic Device 1 20 - -
Bosch MPA Optical Device 1 20 - -
FNM-320-FRD
Bosch Acoustic Device 1 20 - -
FNM-320-SWH
Bosch BL 200 Optical Device 1 30 - -
Bosch FNM-320-LEDSRD Optical/Acoustic Device 1 175 - -
EASY AV-R
Bosch Optical Device 1 36 - -
(SG 200)
Bosch FAA-420-RI Optical Device 1 10 - -
User can modify the
Bosch MSS 300 Acoustic Device 1 20 -
colored part freely to -
Users Choice NAC Device 1 (Modify it freely) - 0 0 -
add support for -
Users Choice NAC Device 2 (Modify it freely) - 0 0 custom- devices. -
Users Choice NAC Device 3 (Modify it freely) - 0 0 - -
Users Choice NAC Device 4 (Modify it freely) - 0 0 - -
Users Choice NAC Device 5 (Modify it freely) - 0 0 - -
Users Choice NAC Device 6 (Modify it freely) - 0 0 - -
Users Choice NAC Device 7 (Modify it freely) - 0 0 - -
Users Choice NAC Device 8 (Modify it freely) - 0 0 - -
Users Choice for Aux Power Aux Power Device 1 (Modify it freely- 0 0 - -
Users Choice for Aux Power Aux Power Device 2 (Modify it freely- 0 0 - -
Users Choice for Aux Power Aux Power Device 3 (Modify it freely- 0 0 - -
Users Choice for Aux Power Aux Power Device 4 (Modify it freely- 0 0 - -
Users Choice for Aux Power Aux Power Device 5 (Modify it freely- 0 0 - -
Users Choice for Aux Power Aux Power Device 6 (Modify it freely- 0 0 - -
Users Choice for Aux Power Aux Power Device 7 (Modify it freely- 0 0 - -
The max
Users Choice for Aux Power Aux Power Device 8 (Modify it freely- 0 0 - - is
value
OpenCollector Relay Extension Board Output 0.00 80 - -
80mA.
OpenCollector Open Collector Extension Board Output 0.00 80 - -
BOSCH Detector FCP-Ox-320/FCH-T320 2-Wire Automatic Detector 0.10 30.00 - -
BOSCH Detector FMC-120-DKM/FMC-300-RW Manual Call Point 0.10 3.50 - -
BOSCH Detector Fireray 50RV 4-Wire Automatic Detector 0.10 40.00 4 15
BOSCH Detector Fireray 100RV 4-Wire Automatic Detector 0.10 40.00 4 15
BOSCH Detector Fireray 2000 4-Wire Automatic Detector 0.10 40.00 14 22
BOSCH Detector Fireray 5000 4-Wire Automatic Detector 0.10 40.00 12 52
BOSCH Detector Fireray 5000-EN 4-Wire Automatic Detector 0.10 40.00 12 52
BOSCH Detector FCS-LWM-1 4-Wire Automatic Detector 0.10 40.00 25 25
BOSCH Detector ADW 511 A 4-Wire Automatic Detector 0.10 40.00 90 99
BOSCH Detector FCS-320-TM 4-Wire Automatic Detector 0.10 40.00 105 140
BOSCH Detector FCS-320-TM-R 4-Wire Automatic Detector 0.10 40.00 170 175
BOSCH Detector FCS-320-TP1 4-Wire Automatic Detector 0.10 40.00 200 210
BOSCH Detector FCS-320-TP2 4-Wire Automatic Detector 0.10 40.00 220 240
08/15/2019 13