Vous êtes sur la page 1sur 14

B C D E F G H I J K

4
5
6
7
Project Varibles
FPC-500 Battery Calculator

Project Name:

Project ID:
Edit Device Database

Standby Hours:

Alarm Mins:
Print Page

60

15
Print Circuit Detail

8
9 Prepared By:
10
11 Date:
12
13
14
15 Panel ID: Model: FPC500-8 Max Circuit Cur: 2.5 Amps
16
17 Location: Volts: 24 VDC Max Panel Cur: 5 Amps
18
19 Current
Circuit Type Type Quantity
20 Standby Alarm
21 Zone 1 Not Used 0 0.00 0.00
22 Zone 2 Not Used 0 0.00 0.00
23 Zone 3 Not Used 0 0.00 0.00
24 Zone 4 Not Used 0 0.00 0.00
25 Zone 5 Not Used 0 0.00 0.00
26 Zone 6 Not Used 0 0.00 0.00
27 Zone 7 Not Used 0 0.00 0.00
28 Zone 8 Not Used 0 0.00 0.00
30 ProgramInput 1 Not Used 0.00 0.00
31 ProgramInput 2 Not Used 0.00 0.00
32 Aux Power 0.000 0.00 0.00
33 Sounder 1 0.000 0.00 0.00
34 Sounder 2 2.000 2.00 40.00
35 OC1~4 0.000 0.00 80.00
36 OC5~8 0.000 0.00 80.00
37 FPA-500 Panel 120.00 150.00 Total Internal Alarm Current (mAmps)
38 Total Internal Standby Current (mAmps) 122.00 350.00 Total External Alarm Current (mAmps)
39 Total External Standby Current (mAmps) 0.00 0.00 Alarm Time In Min
40 Standby Time In Hours 60 15 Total Alarm AH Required
41 Total Standby AH Required 7,320 88
42 Total Combined AH Required 7,408
Conductor Properties NEC Chap. 9
Wire Type Ohms Per 1000 ft.
#12 Solid 2.01
#12 Stranded 2.05
#14 Solid 3.19
#14 Stranded 3.26
#16 Solid 5.08
#16 Stranded 5.29
#18 Solid 8.08
#18 Stranded 8.45

Conductor Properties NEC Chap. 9


Wire Type Ohms Per 1000 ft.
#12 Solid 2.01
#14 Solid 3.19
#16 Solid 4.03
#18 Solid 6.41

Unused
Bosch
Users Choice

ProgramInput Panel ID OC Standby Hours Alarm Min


Used FPC500-2 Not Used 12 5
Not Used FPC500-4 Relay Extension Board 24 15
FPC500-8 Open Collector Extension Board 36 30
48
60
72

Two Wire Device ALL Device


Not Used Not Used
FCP-Ox-320/FCH-T320 FCP-Ox-320/FCH-T320
FMC-120-DKM/FMC-300- FMC-120-DKM/FMC-300-RW
Fireray 50RV
Fireray 100RV
Fireray 2000
Fireray 5000
Fireray 5000-EN
FCS-LWM-1
ADW 511 A
FCS-320-TM
FCS-320-TM-R
FCS-320-TP1
FCS-320-TP2
Chart Title
2500

2000 f(x) = 221.56 x^-0.9958

1500

1000

500

0
0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
18 Power (18)

18 16 14
0.1 2250 2194.277 3291.534 5485.691
0.2 1050 1100.337 1650.565 2750.842
0.3 740 734.8082 1102.252 1837.021
0.4 550 551.7725 827.6886 1379.431
0.5 450 441.8319 662.7717 1104.58

OC Alarm Current Power


0 Internal
20 External
40
60
80
4 0.45 0.5 0.55
Max Current with 10%
Circuit: Aux Power
Safety:
450 Amps
Current Draw Each Current Draw Total
Qty Device
Standby Alarm Standby Alarm
1 Aux Power Device 1 (Modify it freely) 0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0
Total Amps 0 0

Max Current with 10%


Circuit: Sounder 1
Safety:
450 Amps
Current Draw Each Current Draw Total
Qty Manufacture Device
Standby Alarm Standby Alarm
2 Unused - 0 0 0 0
- 0 0 0 0
- 0 0 0 0
- 0 0 0 0
0 0
Total Amps 0 0

Max Current with 10%


Circuit: Sounder 2
Safety:
90 Amps
Current Draw Each Current Draw Total
Qty Manufacture Device
Standby Alarm Standby Alarm
2 Bosch MPA 1 20 2 40
Unused - 0 0 0 0
- 0 0 0 0
- 0 0 0 0
0 0
Total Amps 2 40

Circuit: OC1~4

Current Draw Each Current Draw Total


Qty Device
Standby Alarm Standby Alarm
1 Relay Extension Board 0 80 0 80
Total Amps 0 80
Parameter calculation for FLM-320-EOL4W-S

Detector used auxiliary Usource Umin Uround Ubin Uquer


DCA1192/SB3 BCM-B BCM-B 20.4 18 18 100100 2
ADW 511 A BCM-B LSN 20.4 10.5 10.5 010101 3
FCP-500 BCM-B 20.4 8.5 8.5 010001 2
FCS-LWM-1 BCM-B 20.4 10 10 010100 2
Fireray 2000 BCM-B 20.4 11.5 11.5 010111 4
Fireray 50RV BCM-B 20.4 10 10 010100 2
Fireray 100RV BCM-B 20.4 10 10 010100 2
Fireray 5000 BCM-B 20.4 14 14 011100 3
Fireray 5000-EN BCM-B 20.4 14 14 011100 3
FCS-320-TM BCM-B 20.4 15 15 011110 4
FCS-320-TM-R BCM-B 20.4 15 15 011110 4
FCS-320-TP1 BCM-B 20.4 15 15 011110 4
FCS-320-TP2 BCM-B 20.4 15 15 011110 4

Wiring loop impedance [Ohm


73.2

Minimum auxiliary voltages:


BCM-B: 20,4V
LSN: 27V

Imax: maximum possible


Comments:
current on auxiliary
Ics: Creeping
(activation short
step threshold for auxiliary --> value for trouble message
of elements
to be considered!)
--> this value determines number of connected detectors
Ics has to be rounded up to 12.5mA units (due to BCM-B parameterization resolution)
Maximal possible current (Imax) for LSN-module: 500mA
Maximal possible current (Imax) for BCM-B-module: 500mA
R has to be rounded to 0.5Ohm units
Maximal possible value for R: 100Ohms

For formulas see:

If we only let the AUX power supply max 500mA current then:
Device FCS-LWM-1 is 590mA over than the aux power max current when 15 connect together as SRS.
Device Fireray 2000 is 590mA over than the aux power max current when 15 connect together as SRS.
Device Fireray 50RV/100RV is 1222mA over than the aux power max current when 32 connect together as SRS .
Device Fireray 5000(low current mode) is 550mA over than the aux power max current when 5 connect together as SRS .
Device FCS-320-TP2 is 1205mA over than the aux power max current when 1 connect together as SRS .
Device FCS-320-TP1 is 930mA over than the aux power max current when 1 connect together as SRS .
For the Aux Creeping Short and Aux Short configuration:
Im---max current for good product including Alarm
Inom---standby and nomal working current
Ics---currnt for creeping short
Imax---max current with buffer and with different nunmber connection devices
N---number of connection devices
Formula:
Ics==Round up [(Im*N*1.055+5.5)/12.5,0]*12.5 mA
Imax==Ics*1.055+(Im-Inom)*N+5.5 mA
So for each type device we could set the Ics according to the" Im", and set the Imax according to the "Im and (Im-Inom)"
Uparity Im Inom P Pges Pbin Pquer Pparity Ics Imax
0 150 50 0 0 00000000 0 0 0 0 13 18
1 130 110 1.4 0 00000000 0 0 0 0 13 18
0 58 3.5 0 0 00000000 0 0 0 0 13 18
0 25 15 0 0 00000000 0 0 0 0 13 18
0 25 15 0 0 00000000 0 0 0 0 13 18
0 25 15 0 0 00000000 0 0 0 0 13 18
0 25 15 0 0 00000000 0 0 0 0 13 18
1 58 15 0 0 00000000 0 0 0 0 13 18
1 58 15 0 0 00000000 0 0 0 0 13 18
0 155 100 2 0 00000000 0 0 0 0 13 18
0 250 100 2 0 00000000 0 0 0 0 13 18
0 545 240 6.8 0 00000000 0 0 0 0 13 18
0 675 240 7.9 0 00000000 0 0 0 0 13 18

UP quer UP parity
2 0
3 1
2 0
2 0
4 0
2 0
2 0
3 1
4 0
4 0
4 0
4 0

gether as SRS .
nnect together as SRS .
the "Im and (Im-Inom)"
DIP-Switches:
Imax_aux Rcalc R V P
500 93.5 10111011 00100100 00000000
500 506.0 11001000 11010101 00000000
500 616.0 11001000 01010001 00000000
500 533.5 11001000 01010100 00000000 15
500 451.0 11001000 01010111 00000000 15
500 533.5 11001000 01010100 00000000 32
500 533.5 11001000 01010100 00000000 32
500 313.5 11001000 11011100 00000000 5
500 313.5 11001000 11011100 00000000 5
500 258.5 11001000 01011110 00000000
500 258.5 11001000 01011110 00000000
500 258.5 11001000 01011110 00000000
500 258.5 11001000 01011110 00000000

DIP
50.0 01100100

18.0 01100100 Bit8: Parity UP; Bit7: Parity R

00100010
Bit7: Parity R
15
15
32
32
5
5
4-Wire Aux 4-Wire Aux
Standby Alarm
Standby Alarm
[in mAmps] [in mAmps]
Manufacture Model Description [in mAmps] [in mAmps]
Unused - - 0 0 - -
Bosch FNS-320-Sxx Optical Device 1 88 - -
Bosch SG 200 Acoustic Device 1 32 - -
Bosch MSS 300 standalone Acoustic Device 1 20 - -
Bosch MPA Optical Device 1 20 - -
FNM-320-FRD
Bosch Acoustic Device 1 20 - -
FNM-320-SWH
Bosch BL 200 Optical Device 1 30 - -
Bosch FNM-320-LEDSRD Optical/Acoustic Device 1 175 - -
EASY AV-R
Bosch Optical Device 1 36 - -
(SG 200)
Bosch FAA-420-RI Optical Device 1 10 - -
User can modify the
Bosch MSS 300 Acoustic Device 1 20 -
colored part freely to -
Users Choice NAC Device 1 (Modify it freely) - 0 0 -
add support for -
Users Choice NAC Device 2 (Modify it freely) - 0 0 custom- devices. -
Users Choice NAC Device 3 (Modify it freely) - 0 0 - -
Users Choice NAC Device 4 (Modify it freely) - 0 0 - -
Users Choice NAC Device 5 (Modify it freely) - 0 0 - -
Users Choice NAC Device 6 (Modify it freely) - 0 0 - -
Users Choice NAC Device 7 (Modify it freely) - 0 0 - -
Users Choice NAC Device 8 (Modify it freely) - 0 0 - -
Users Choice for Aux Power Aux Power Device 1 (Modify it freely- 0 0 - -
Users Choice for Aux Power Aux Power Device 2 (Modify it freely- 0 0 - -
Users Choice for Aux Power Aux Power Device 3 (Modify it freely- 0 0 - -
Users Choice for Aux Power Aux Power Device 4 (Modify it freely- 0 0 - -
Users Choice for Aux Power Aux Power Device 5 (Modify it freely- 0 0 - -
Users Choice for Aux Power Aux Power Device 6 (Modify it freely- 0 0 - -
Users Choice for Aux Power Aux Power Device 7 (Modify it freely- 0 0 - -
The max
Users Choice for Aux Power Aux Power Device 8 (Modify it freely- 0 0 - - is
value
OpenCollector Relay Extension Board Output 0.00 80 - -
80mA.
OpenCollector Open Collector Extension Board Output 0.00 80 - -
BOSCH Detector FCP-Ox-320/FCH-T320 2-Wire Automatic Detector 0.10 30.00 - -
BOSCH Detector FMC-120-DKM/FMC-300-RW Manual Call Point 0.10 3.50 - -
BOSCH Detector Fireray 50RV 4-Wire Automatic Detector 0.10 40.00 4 15
BOSCH Detector Fireray 100RV 4-Wire Automatic Detector 0.10 40.00 4 15
BOSCH Detector Fireray 2000 4-Wire Automatic Detector 0.10 40.00 14 22
BOSCH Detector Fireray 5000 4-Wire Automatic Detector 0.10 40.00 12 52
BOSCH Detector Fireray 5000-EN 4-Wire Automatic Detector 0.10 40.00 12 52
BOSCH Detector FCS-LWM-1 4-Wire Automatic Detector 0.10 40.00 25 25
BOSCH Detector ADW 511 A 4-Wire Automatic Detector 0.10 40.00 90 99
BOSCH Detector FCS-320-TM 4-Wire Automatic Detector 0.10 40.00 105 140
BOSCH Detector FCS-320-TM-R 4-Wire Automatic Detector 0.10 40.00 170 175
BOSCH Detector FCS-320-TP1 4-Wire Automatic Detector 0.10 40.00 200 210
BOSCH Detector FCS-320-TP2 4-Wire Automatic Detector 0.10 40.00 220 240

08/15/2019 13
English