Type of input Differential Unipolar single ended Unipolar single ended Unipolar single ended
30 mV to 75 mV linear, or
TC types B, C, E, J, K, L, N,
R, S, T and U
Range See Table 1 0...20 mA, 0...5 V, 4... 20 0...20 mA, 4... 20 mA 4...20 mA
mA, 1... 5V
Front LED’s F(ault), R(un), W(arning) F(ault), R(un), W(arning) F(ault), R(un), W(arning) F(ault), R(un), W(arning),
O(SP)
Feature AI843 AI845 AI880A AO845
Supervision Module error if: reference Module error if: analog read Internal voltage, field power
channels outside limits, back, reference voltage, input, field power output
power supply low Module error: Internal per channel
Channel error if: open- power supply, checksum,
circuit, out of range watch dog and memory
<-40°C (-40°F) and >100°C error
(212°F) (only Cold Junction Internal error: output
channel) readback,
Linear: none External error: open load,
process power,
Internal channel error if: low
pass filter, multiplexer and
test channels error
External channel error if:
external power supply
low, transmitter power and
external shunt error
Status indication of supervision Module Error, Module Module Error, Module Module Error, Module Module Error, Module
Warning, Channel error Warning, Channel error Warning, Channel error Warning, Channel error
Profibus parameters bytes CI801, CI840 16/20/2 13/17/0 Not supported 18/1/16
(User/Input/Output)
Execution time per scan using CI801 0.40 ms, 0.80 ms for a 3.00 ms, 6.00 ms for a 1.20 ms, 2.40 ms for a
or CI840 redundant pair redundant pair redundant pair
Maximum field cable length 600 meters (656 yd.) or 600 meters, (656 yd.) 600 meters, (656 yd.) 600 meters (656 yd.)
max. 500 Ω
Temperature drift Typ. 10 ppm/°C Max. 50 ppm/°C Max. 50 ppm/°C Max. 50 ppm/°C
Max. 25 ppm/°C
Filter (integration) 50 Hz or 60 Hz
Maximum ambient temperature (1) 55/40°C, (131/104°F) 55/40°C, (131/104°F) 55/40°C, (131/104°F) 55/40°C, (131/104°F)
Module termination units, single TU830, TU833, TU842 or TU810, TU812, TU814, TU844 or TU845 TU810, TU812, TU814,
applications TU843 TU830, TU833, TU835, TU830, TU833, TU844 or
TU838, TU844 or TU845 TU845
Dielectric test voltage 500 V a.c. 500 V a.c. 500 V a.c. 500 V a.c.
Isolation Groupwise isolated from Groupwise isolated from Groupwise isolated from Groupwise isolated from
ground (RIV=50 V) ground (RIV=50 V) ground (RIV=50 V) ground (RIV=50 V)
Equipment class Class I according to IEC Class I according to IEC Class I according to IEC Class I according to IEC
61140; (earth protected) 61140; (earth protected) 61140; (earth protected) 61140; (earth protected)
Protection rating IP20 according to IEC IP20 according to IEC IP20 according to IEC IP20 according to IEC
60529 60529 60529 60529
Depth 97 mm (3.8”), 106 mm (4.2”) 97 mm (3.8”), 106 mm (4.2”) 97 mm (3.8”), 106 mm (4.2”) 97 mm (3.8”), 106 mm (4.2”)
including connector including connector including connector including connector
Weight 0.157 kg (0.35 lbs.) 0.23 kg (0.51 lbs.) 0.15 kg (0.33 lbs.) 0.21 kg (0.46 lbs.)
GOST certificates CoC, GGTN CoC, GGTN CoC, GGTN CoC, GGTN
Electrical safety EN 3810, EN 50178, IEC 601131-2, UL 508, CSA 22.2 No.142-M1987
Climatic operating conditions 0 to +55 °C (Storage -25 to +70 °C), RH=5 to 95 % no condensation, IEC/EN 61131-2 (3)
(1) 40°C (104°F) applies to compact MTUs with I/O-modules or S800L-modules mounted on vertical DIN rail.
(2) 250 ohm load, 70% of nominal current, all channels activated.
(3) 0 to +40 °C compact MTUs on vertical DIN-rail. Approvals are issued for +5 to +55 °C.
Table 1
Input Type Temperature Range Input Type Temperature Range
TC type B (1) 44...1820°C, 111...3308°F TC type N (1) -270...1300°C, -454...2372°F
TC type L -200...900°C, -328...1652°F Pt100 RTD (for CJC) (2) -40...100°C, -40...212°F
(1) Linearization per IEC 584-1 1995, and following ITS 90 requirements.
(2) Sensor Type applies to Cold Junction channel only, for the measuring of the
Cold Junction Compensation temperature.
3BSE039128R0101
© Copyright 2005 ABB. All rights reserved. Specifications subject to change without notice. Pictures, schematics and other graphics contained herein are published
for illustration purposes only and do not represent product configurations or functionality. User documentation accompanying the product is the exclusive source for
functionality descriptions. The IndustrialIT wordmark, Aspect Objects, and all above-mentioned names in the form XXXXXXIT are registered or pending trademarks of
ABB. All rights to other trademarks reside with their respective owners.