Vous êtes sur la page 1sur 42

Part Number D301452X012

Document No. S1400CW


April 2017

Site Considerations for Equipment Installation,


Grounding, and Wiring

FB1100/1200 Flow Computer FB2100/2200 Flow Computer

ControlWave Family of Flow Computers and RTUs

Remote Automation Solutions


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

Device Safety Considerations


 Reading these Instructions
Before operating the device, read these instructions carefully and understand their safety
implications. In some situations, improperly using this device may result in damage or injury.
Keep this manual in a convenient location for future reference. Note that these instructions
may not cover all details or variations in equipment or cover every possible situation regarding
installation, operation, or maintenance. Should problems arise that are not covered sufficiently
in the text, immediately contact Customer Support for further information.
 Protecting Operating Processes
A failure of this device – for whatever reason -- may leave an operating process without
appropriate protection and could result in possible damage to property or injury to persons. To
protect against this, you should review the need for additional backup equipment or provide
alternate means of protection (such as alarm devices, output limiting, fail-safe valves, relief
valves, emergency shutoffs, emergency switches, etc.). Contact Remote Automation Solutions
for additional information.
 Returning Equipment
If you need to return any equipment to Remote Automation Solutions, it is your responsibility
to ensure that the equipment has been cleaned to safe levels, as defined and/or determined by
applicable federal, state and/or local law regulations or codes. You also agree to indemnify
Remote Automation Solutions and hold Remote Automation Solutions harmless from any
liability or damage which Remote Automation Solutions may incur or suffer due to your
failure to ensure device cleanliness.
 Grounding Equipment
Ground metal enclosures and exposed metal parts of electrical instruments in accordance with
OSHA rules and regulations as specified in Design Safety Standards for Electrical Systems, 29
CFR, Part 1910, Subpart S, dated: April 16, 1981 (OSHA rulings are in agreement with the
National Electrical Code). You must also ground mechanical or pneumatic instruments that
include electrically operated devices such as lights, switches, relays, alarms, or chart drives.
 Protecting from Electrostatic Discharge (ESD)
This device contains sensitive electronic components which be damaged by exposure to an
ESD voltage. Depending on the magnitude and duration of the ESD, it can result in erratic
operation or complete failure of the equipment. Ensure that you correctly care for and handle
ESD-sensitive components.

ii Revised April-2017
Site Considerations for Equipment Installation, Grounding, and Wiring Manual

Contents
Chapter 1 – Overview 1
1.1 Introduction ......................................................................................................................................... 1
1.2 Major Topics ....................................................................................................................................... 1

Chapter 2 – Protection 3
2.1 Protecting Instrumentation Systems .................................................................................................. 3
2.1.1 Quality is Conformance to Requirements ............................................................................ 3
2.2 Protecting Equipment and Personnel................................................................................................. 4
2.2.1 Considerations for the Protection of Personnel ................................................................... 4
2.2.2 Considerations for the Protection of Equipment .................................................................. 5
2.3 Other Site Safety Considerations ....................................................................................................... 6

Chapter 3 – Grounding and Isolation 7


3.1 Power and Ground Systems .............................................................................................................. 7
3.2 Importance of Good Grounds ............................................................................................................. 7
3.3 Earth Ground Connections ................................................................................................................. 8
3.3.1 Establishing a Good Earth Ground ...................................................................................... 8
3.3.2 Ground Wire Considerations.............................................................................................. 13
3.3.3 Other Grounding Considerations ....................................................................................... 14
3.4 Isolating Equipment from the Pipeline.............................................................................................. 15
3.4.1 Meter Runs Without Cathodic Protection ........................................................................... 15
3.4.2 Meter Runs With Cathodic Protection ................................................................................ 17

Chapter 4 – Lightning Arresters and Surge Protectors 21


4.1 Strokes and Strikes .......................................................................................................................... 21
4.1.1 Chance of Being Struck by Lightning ................................................................................. 21
4.1.2 Antenna Caution ................................................................................................................ 24
4.1.3 Ground Propagation ........................................................................................................... 27
4.1.4 Tying it all Together ........................................................................................................... 27
4.1.5 Impulse Protection Summary ............................................................................................. 28
4.2 Use of Lightning Arresters and Surge Protectors ............................................................................ 28
4.2.1 Installation of Lightning Arresters and Surge Protectors ................................................... 29

Chapter 5 – Wiring Techniques 31


5.1 Overview .......................................................................................................................................... 31
5.2 Instrument Wiring ............................................................................................................................. 31
5.2.1 Common Returns ............................................................................................................... 32
5.2.2 Use of Twisted Shielded Pair Wiring (with Overall Insulation) ........................................... 33
5.2.3 Grounding of Cable Shields ............................................................................................... 33
5.2.4 Use of Known Good Earth Grounds .................................................................................. 33
5.2.5 Earth Ground Wires ........................................................................................................... 34
5.2.6 Working Neatly and Professionally .................................................................................... 34
5.2.7 High Power Conductors and Signal Warning .................................................................... 34
5.2.8 Use of Proper Wire Size .................................................................................................... 34
5.2.9 Lightning Arresters & Surge Protectors ............................................................................. 35
5.2.10 Secure Wiring Connections ............................................................................................... 36

Revised April-2017 Contents iii


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

[This page is intentionally left blank.]

iv Contents Revised April-2017


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

Chapter 1 – Overview

1.1 Introduction
This document provides information pertaining to the installation of
RTUs, controllers, and flow computers from Emerson Remote
Automation Solutions including the ControlWave family of flow
computers and RTUs and the FB1100, FB1200, FB2100, and FB2200
flow computers. More specifically, this document provides information
covering reasons, theory and techniques for protecting your personnel
and equipment from electrical damage. Your instrumentation system
affects the quality of service provided by your company and many
aspects of its operational safety. Loss of instruments means lost
production and profits as well as increased expenses.

Note: Information contained in this document is for educational


purposes. Emerson Remote Automation Solutions offers no
warranties or guarantees on the effectiveness of the safety of
techniques described herein. Where the safety of installations
and personnel is concerned, refer to the National Electrical Code
Rules and rules of local regulatory agencies.

1.2 Major Topics


Topics are covered in seven sections designed to pinpoint major areas of
concern for the protection of site equipment and personnel. The
following provides an overview of each of the major chapters.
 Chapter 2 - Protection
This section provides the reasons for protecting instrumentation
systems. An overview of the definition of quality and what we are
trying to accomplish in the protection of site installations and how to
satisfy the defined requirements is presented. Additionally, this
section provides considerations for the protection of personnel and
equipment.
 Chapter 3 - Grounding & Isolation
This section provides information pertaining to what constitutes a
good earth ground, how to test and establish such grounds, as well
as when and how to connect equipment to earth grounds.
 Chapter 4 - Lightning Arresters & Surge Protectors
This section presents some interesting information dealing with
lightning strikes and strokes in technical and statistical form along
with a discussion of how to determine the likelihood of a lightning
strike. Protecting equipment and personnel during the installation of
radios and antenna is discussed in a review of the dangers to
equipment and personnel when working with antennas. Reasons for
Revised April 2017 Overview 1
Site Considerations for Equipment Installation, Grounding, and Wiring Manual

the use of lightning arresters and surge protectors are presented


along with overviews of how each device protects site equipment.
 Chapter 5 - Wiring Techniques
This section discusses installation of power and “measurement &
control” wiring. Information on obscure problems, circulating
ground and power loops, bad relays, etc. is presented. Good wire
preparation and connection techniques along with problems to avoid
are discussed. This sections list the ten rules of instrument wiring.

2 Overview Revised April-2017


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

Chapter 2 – Protection
In This Chapter

2.1 Protecting Instrumentation Systems ................................................... 3


2.1.1 Quality is Conformance to Requirements ............................... 3
2.2 Protecting Equipment and Personnel ................................................. 4
2.2.1 Considerations for the Protection of Personnel ....................... 4
2.2.2 Considerations for the Protection of Equipment...................... 5
2.3 Other Site Safety Considerations ....................................................... 6

2.1 Protecting Instrumentation Systems


Electrical instrumentation is susceptible to damage from a variety of
natural and man-made phenomena. In addition to wind, rain and fire, the
most common types of system and equipment damaging phenomena are
lightning, power faults, communication surges, noise and other
electrical interference caused by devices such as radios, welders,
switching gear, automobiles, etc. Additionally there are problems
induced by geophysical electrical potential and noise plus things that are
often beyond our wildest imagination.

2.1.1 Quality is Conformance to Requirements


A quality instrumentation system is one that works reliably, safely and
as purported by the equipment manufacturer (and in some cases by the
system integrator) as a result of good equipment design and well defined
and followed installation practices. If we accept the general definition of
quality to be, “conformance to requirements,” we must also accept the
premise that a condition of “quality” can’t exist where requirements for
such an end have not been evolved. In other words, you can’t have
quality unless you have requirements that have been followed. By
understanding the requirements for a safe, sound and reliable
instrumentation system, and by following good installation practices (as
associated with the personnel and equipment in question), you enhance
the operational integrity of the equipment and system.
Understanding what is required to properly install equipment in various
environments, safely, and in accordance with good grounding, isolating
and equipment protection practices goes a long way toward maintaining
a system which is healthy for the owner and customer alike.
Properly installed equipment is easier to maintain and operate, and is
more efficient and as such more profitable to our customers. Following
good installation practices minimizes injury, equipment failure and
customer frustration that accompanies failing and poorly operating
equipment (of even the finest design).

Revised April-2017 Protection 3


Site Consideration for Equipment Installation Grounding and Wiring Manual

Additionally, personnel involved in the installation of a piece of


equipment add to or subtract from the reliability of a system by a degree
which is commensurate with their technical prowess, i.e., their
understanding of the equipment, site conditions and the requirements for
a quality installation.

2.2 Protecting Equipment and Personnel


Installations must be performed in accordance with National Electrical
Code Rules, electrical rules set by local regulatory agencies, and
depending on the customer environment (gas, water, etc), other national,
state and local agencies. Additionally, installation at various customer
sites may be performed in conjunction with a “safety manager” or utility
personnel with HAZMAT (hazardous material) training on materials
present (or potentially present) as required by OSHA, the customer, etc.

2.2.1 Considerations for the Protection of Personnel


Always evaluate the site environment as if your life depends on it. Make
sure that you understand the physical nature of the location where you
will be working. Table 2-1 provides a general guideline for evaluating
an installation site.

Table 2-1. Consideration for the Protection of Personnel


# Guide
1 Indoor or outdoor – Dress Appropriately
If outdoor, what kind of environment, terrain, etc. Watch out for local
2
varmints (bees, spiders, snakes, etc.)
If indoor or outdoor – determine if there are any pieces of dangerous
3
equipment or any processes which might be a risk to your safety
If in a tunnel, bunker, etc. watch out for a build up of toxic or
4 flammable gases. Make sure the air is good. Watch out for local
varmints (bees, spiders, snakes, etc.)
Hazardous or Non-Hazardous Environment – Wear appropriate safety
5
equipment and perform all necessary safety measures.
Before installing any equipment or power or ground wiring, make sure
that there are no lethal (life threatening) voltages between the site where
6
the instrument will be installed and other equipment, pipes, cabinets, etc.
or to earth itself.
Never assume that adjacent or peripheral equipment has been
properly installed and grounded. Determine if this equipment and the
7
RTU or flow computer can be touched simultaneously without hazard
to personnel and/or equipment?
Before embarking to remote locations where there are few or no human
8 inhabitants ask a few simple questions like, should I bring water, food,
hygienic materials, first aid kit, etc? Be Prepared!
9 Observe the work habits of those around you – for your own safety!

Some of the items that a service person should consider before ever
going onsite can be ascertained by simply asking questions of the

4 Protection Revised April-2017


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

appropriate individual. Obviously other safety considerations can only


be established at the installation site.

2.2.2 Considerations for the Protection of Equipment


You must evaluate the site installation/service environment and
equipment. Understand the various physical interfaces you will be
dealing with such as equipment mounting and supporting, RTU/flow
computer analog and digital circuits, power circuits, communication
circuits and various electrical grounds. Table 2-2 provides a general
guideline for evaluating the equipment protection requirements of an
installation site.
Table 2-2. Consideration for the Protection of Equipment
# Guide Reference Section
Environment - Class I, Division 2 –
Nonincendive See appendices in
1 Environment - Class I, Division 1 - hardware instruction
Intrinsically Safe manual.
Other - Safe or unrated area
Earth Ground - Established by
2 mechanical/electrical or See Chapter 3
(both) or not at all.
3 Is the area prone to lightning strikes? See Chapter 4
Are there surge suppressors installed
4 See Chapter 4
or to be installed?
Are there overhead or
underground power or
5 See section 2.3
communication cables in
the immediate area?
Is there an antenna in the immediate
6 See section 4.1.2
area?

How close is other equipment? Can


someone safely touch this equipment
7 See section 2.3
and the RTU/flow computer
simultaneously?
Determine equipment ground
requirements. How will the RTU/flow
computer and its related wiring be
8 See Chapter 3
grounded? Consider Earth Ground,
Circuit Ground, Conduit Ground, Site
Grounds!
Are there any obviously faulty or
9 See section 2.3
questionable power or ground circuits?

Revised April-2017 Protection 5


Site Consideration for Equipment Installation Grounding and Wiring Manual

2.3 Other Site Safety Considerations


You must identify overhead or underground power or communication
cables prior to installing a new unit. Accidentally cutting, shorting or
simply just contacting power, ground, communication or process
control I/O wiring can have potentially devastating effects on site
equipment, the process system and or personnel.
Don’t assume that it is safe to touch adjacent equipment, machinery,
pipes, cabinets or even the earth itself. Adjacent equipment may not
have been properly wired or grounded, may be defective or may have
one or more loose system grounds. Measure between the case of a
questionable piece of equipment and its earth ground for voltage. If a
voltage is present, something is wrong.
AC powered equipment with a conductive case should have the case
grounded. If you don’t see a chassis ground wire, don’t assume that it is
safe to touch this equipment. If you notice that equipment has been
grounded to pipes, conduit, structural steel, etc., you should be leery.

Note: AWWA’s policy on grounding of electric circuits on water pipes


states, “The American Water Works Association (AWWA)
opposes the grounding of electrical systems to pipe systems
conveying water to the customer’s premises….”
Be sure that the voltage between any two points in the instrumentation
system is less than the stand-off voltage. Exceeding the stand-off
voltage will cause damage to the instrument and will cause the
instrument to fail.

6 Protection Revised April-2017


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

Chapter 3 – Grounding and Isolation


In This Chapter

3.1 Power and Ground Systems ............................................................... 7


3.2 Importance of Good Grounds ............................................................. 7
3.3 Earth Ground Connections ................................................................. 8
3.3.1 Establishing a Good Earth Ground ......................................... 8
3.3.2 Ground Wire Considerations ................................................. 13
3.3.3 Other Grounding Considerations........................................... 14
3.4 Isolating Equipment from the Pipeline .............................................. 15
3.4.1 Meter Runs Without Cathodic Protection .............................. 15
3.4.2 Meter Runs With Cathodic Protection ................................... 17

3.1 Power and Ground Systems


Controllers and flow computers from Emerson Remote Automation
Solutions support DC power systems. AC power supplies are not
provided. Our devices typically include a ground lug that
accommodates up to a #4 AWG size stranded copper wire for
establishing a connection to Earth ground.

3.2 Importance of Good Grounds


Controllers and flow computers are utilized in instrument and control
systems that must operate continually and within their stated accuracy
over long periods of time with minimum attention. Failures resulting
from an improperly grounded system can become costly in terms of lost
time and disrupted processes. A properly grounded system helps
prevent electrical shock hazards resulting from contact with live metal
surfaces, provides additional protection of equipment from lightning
strikes and power surges, minimizes the effects of electrical noise and
power transients, and reduces signal errors caused by ground wiring
loops. Conversely, an improperly grounded system may exhibit a host
of problems that appear to have no relation-ship to grounding. It is
essential that the reader (service technician) have a good under-standing
of this subject to prevent needless troubleshooting procedures.

Revised April-2017 Grounding and Isolation 7


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

This device must be installed in accordance with the National Electrical


Warning Code (NEC) ANSI/NEPA-70. Installation in hazardous locations must
also comply with Article 500 of the code. For information on the usage
of this device in a hazardous location, see appendices in the applicable
hardware instruction manual. For information on the usage of
ControlWave units in Class I, Division 1, Groups C & D hazardous
locations, see appendix B of the applicable hardware instruction
manual.

3.3 Earth Ground Connections


To properly ground the device, the unit’s chassis ground must ultimately
be connected to a known good earth ground. Refer to Establishing a
Good Earth Ground and Ground Wire Considerations (located in this
chapter).

3.3.1 Establishing a Good Earth Ground


A common misconception of a ground is that it consists of nothing more
than a metal pipe driven into the soil. While such a ground may function
for some applications, it will often not be suitable for a complex system
of sophisticated electronic equipment. Conditions such as soil type,
composition and moisture will all have a bearing on ground reliability.
A basic ground consists of a 3/4-inch diameter rod with a minimum 8-
foot length driven into conductive earth to a depth of about 7-feet as
shown in Figure 3-1. Number 3 or 4 AWG braided copper wire should
be used for the ground wire. The end of the wire should be clean, free of
any coating and fastened to the rod with a clamp. This ground
connection should be covered or coated to protect it from the weather
and the environment.

Figure 3-1. Basic Ground Rod Installation

8 Grounding and Isolation Revised April-2017


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

3.3.1.1 Soil Conditions


Before installing a ground rod, the soil type and moisture content should
be analyzed. Ideally, the soil should be moist and moderately packed
throughout to the depth of the ground rod. However, some soils will
exhibit less than ideal conditions and will require extra attention.
Soil types can be placed into two general categories with respect to
establishing and maintaining a good earth ground, i.e., “good soil” and
“poor soil”.
To be a good conductor, soil must contain some moisture and free ions
(from salts in the soil). In rainy areas, the salts may be washed out of the
soil. In sandy or arid area the soil may be to dry and/or salt free to a
good conductor. If salt is lacking add rock salt (NaCl); if the soil is dry
add calcium chloride (CaCl2).

3.3.1.2 Soil Types


Good Poor

Damp Loam Back Fill

Salty Soil or Sand Dry Soil

Farm Land Sand Washed by a Lot of Rain


Dry Sand (Desert)
Rocky Soil

Ground beds must always be tested for conductivity prior to being


placed into service. A brief description of ground bed testing in “good
soil” and “poor soil” is provided herein. Details on this test are
described in the National Electrical Code Handbook. Once a reliable
ground has been established, it should be tested on a regular basis to
preserve system integrity.

Revised April-2017 Grounding and Isolation 9


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

Figure 3-2. Basic Ground Bed Soil Test Setup

Figure 3-3. Basic Ground Bed Soil Test Setup with Additional Ground Rods

Figure 3-2 shows the test setup for “good soil” conditions. If the
Megger* reads less than 5 ohms, the ground is good. The lower the
resistance, the better the earth ground. If the Megger reads more than 10
ohms, the ground is considered “poor”. If a poor ground is indicated,
10 Grounding and Isolation Revised April-2017
Site Considerations for Equipment Installation, Grounding, and Wiring Manual

one or more additional ground rods connected 10 feet from the main
ground rod should be driven into the soil and interconnected via bare
AWG 0000 copper wire and 1” x ¼-20 cable clamps as illustrated in
Figure 3-3). *
Note: Megger is a Trademark of the Biddle Instrument Co. (now
owned by AVO International). Other devices that may be
used to test ground resistance are “Viboground”; Associated
Research, Inc., “Groundmeter”; Industrial Instruments, Inc.,
and “Ground-ohmer”; Herman H. Sticht Co., Inc.

If the Megger still reads more than 10 ohms, mix a generous amount of
cooking salt, ice cream salt or rock salt with water and then pour about
2.5 to 5 gallons of this solution around each rod (including the test
rods). Wait 15 minutes and re-test the soil. If the test fails, the soil is
poor and a ‘Poor Soil Ground Bed’ will have to be constructed.
Figure 3-4 shows a typical poor soil ground bed electrode. A poor soil
ground bed will typically consists of four or more 10-foot long
electrodes stacked vertically and separated by earth. Figure 3-5 shows
the construction of a poor soil ground bed. For some poor soil sites, the
ground bed will be constructed of many layers of “capacitive couplings”
as illustrated. In extremely “poor soil” sites one or more 3’ by 3’ copper
plates (12 gauge or 1/16” thick) will have to be buried in place of the
electrodes.

Figure 3-4. Ground Electrode Construction for poor soil conditions

3.3.1.3 Dry, Sandy or Rocky Soil


A very dry soil will not provide enough free ions for good conductance
and a single ground rod will not be effective. A buried counterpoise or
copper screen is recommended for these situations. It will be necessary
to keep the soil moist through regular applications of water.

Sandy soil, either wet or dry, may have had its soluble salts leached out
by rain water, thereby reducing conductivity of the ground. High
currents from lightning strikes could also melt sand and cause glass to
form around the ground rod, rendering it ineffective. A buried
counterpoise or copper screen is preferred for these installations along
with regular applications of salt water.

Revised April-2017 Grounding and Isolation 11


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

Rocky soil can pose many grounding problems. A counterpoise or


copper plate will probably be required. Constructing a trench at the
grounding site and mixing the fill with a hygroscopic salt such as
calcium chloride may help for a time. Soaking the trench with water on
a regular basis will maintain conductivity.

Units with phone modems require the use of a lightning arrester. The
lightning arrester must be situated at the point where the
communication line enters the building.

Figure 3-5. Poor Soil Ground Bed Construction Diagram

12 Grounding and Isolation Revised April-2017


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

3.3.2 Ground Wire Considerations


Controllers and flow computers are provided with a ground lug that
accommodates up to a #4 AWG wire size. A ground wire must be run
between the chassis ground lug and a known good earth ground. The
cases of the various modules are automatically connected to the chassis
ground when they have been installed and secured in the chassis.

For ControlWave Devices Only:


A #14 AWG wire be run from PSSM (Chassis Ground) (PSSM
Connector TB1-3 for ControlWave Micro unit) (SCM Connector TB1-
3 for ControlWave EFM) to the same known good earth ground.

General Considerations
The following considerations are provided for the installation of
controller/flow computer system grounds:
 Size of ground wire (running to earth ground should be #4
AWG. It is recommended that stranded copper wire is used for
this application and that the length should be as short as possible.
 This ground wire should be clamped or brazed to the ground
bed conductor (that is typically a stranded copper AWG 0000
cable installed vertically or horizontally).
 The wire ends should be tinned with solder prior to installation.
 The ground wire should be run such that any routing bend in
the cable has a minimum radius of 12-inches below ground and
8-inches above ground.

The unit earth ground cable should be clamped to an exposed ground


rod or to an AWG 0000 stranded copper ground cable that in turn
should be connected to either an earth ground rod or earth ground bed.
Both ends of the unit earth ground cable must be free of any coating
such as paint or insulated covering as well as any oxidation. The
connecting point of the ground rod or AWG 0000 ground cable must
also be free of any coating and free of oxidation. Once the ground
connection has been established (at either the ground rod or ground
cable) it should be covered or coated to protect it from the environment.

Revised April-2017 Grounding and Isolation 13


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

3.3.3 Other Grounding Considerations

Figure 3-6. Grounding of Phone Line

For applications employing equipment that communicates over


telephone lines, a lightning arrester must be provided. For indoor
equipment the lightning arrester must be installed at the point where the
communication line enters the building as shown in Figure 3-6. The
ground terminal of this arrester must connect to a ground rod and/or a
buried ground bed.
Gas lines also require special grounding considerations. If a gas meter
run includes a thermocouple or RTD sensor installed in a thermowell,
the well (not the sensor) must be connected to a gas discharge-type
lightning arrester as shown in Figure 3-7. A copper braid, brazed to the
thermal well, is dressed into a smooth curve and connected to the
arrester as shown. The curve is necessary to minimize arcing caused by
lightning strikes or high static surges. The path from the lightning
arrester to the ground bed should also be smooth and free from sharp
bends for the same reason.

14 Grounding and Isolation Revised April-2017


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

Figure 3-7. Grounding of Thermometer Well in Gas Line

3.4 Isolating Equipment from the Pipeline

3.4.1 Meter Runs Without Cathodic Protection


Some (but not all) flow computers may be mounted directly on the
pipeline. For example, the FB1100/FB1200 can be mounted directly
using the traditional mounting kit or a coplanar mounting kit but only if
the pipeline includes a process manifold. If direct mount is not allowed
or supported (for example in the FB2100/FB2200) the flow computers
may be mounted remotely on a vertical stand-alone two-inch pipe (see
Figure 3-8). The earth ground cable is to run between the flow
computer’s Ground Lug and Earth Ground (rod or bed) even though the
flow computer’s Multivariable Transducer may be grounded to the
pipeline. If any pressure transmitters or pulse transducers are remotely
mounted, connect their chassis grounds to the pipeline or earth ground.

Revised April-2017 Grounding and Isolation 15


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

Figure 3-8. Remote Installation without Cathodic Protection

16 Grounding and Isolation Revised April-2017


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

3.4.2 Meter Runs With Cathodic Protection


Dielectric isolators are available and are always recommended as an
added measure in isolating the flow computer from the pipeline even
though the flow computer does provide 500V galvanic isolation from
the pipeline and should not be affected by cathodic protection or other
EMF on the pipeline. Some (but not all) flow computers may be
mounted directly on the pipeline (see Figure 3-9) or remotely on a
vertical stand-alone two-inch stand-pipe (see Figure 3-10). It is
recommended that isolation fitting always be used in remotely mounted
meter systems. An isolation fittings or gasket should be installed
between the following connections:

 All conductive tubing that runs between the pipeline and


mounting valve manifold and/or the unit’s multivariable pressure
transducer.
 All conductive connections or tubing runs between the flow
computer and turbine meter, pulse transducer, or any other
device that is mounted on the pipeline.
 Any Temperature Transducer, Pressure Transmitter, etc. and
their mount/interface to the pipeline.

Revised April-2017 Grounding and Isolation 17


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

Figure 3-9. Direct Mount Installation (with Cathodic Protection)

The ground conductor connects between the Ground Lug and a known
good earth ground. Connect the cases of Temperature Transducers,
Pressure Transmitters, etc., to the known good earth ground. If the
mounting 2-inch pipe is in continuity with the pipeline it will have to be
electrically isolated from the flow computer. Use a strong heat-shrink
material such as RAYCHEM WCSM 68/22 EU 3140. This black tubing
will easily slip over the 2-inch pipe and then after uniform heating (e.g.,
with a rose-bud torch) it electrically insulates and increases the strength
of the pipe stand.

18 Grounding and Isolation Revised April-2017


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

Figure 3-10. Remote Installation (with Cathodic Protection)

Revised April-2017 Grounding and Isolation 19


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

[This page is intentionally left blank.]

20 Grounding and Isolation Revised April-2017


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

Chapter 4 – Lightning Arresters and Surge Protectors


In This Chapter

4.1 Strokes and Strikes ........................................................................... 21


4.1.1 Chance of Being Struck by Lightning .................................... 21
4.1.2 Antenna Caution .................................................................... 24
4.1.3 Ground Propagation .............................................................. 27
4.1.4 Tying it all Together ............................................................... 27
4.1.5 Impulse Protection Summary ................................................ 28
4.2 Use of Lightning Arresters and Surge Protectors ............................. 28
4.2.1 Installation of Lightning Arresters and Surge Protectors ....... 29

4.1 Strokes and Strikes


Lightning takes the form of a pulse that typically has 2 µS rise and a 10
µS to 40 µS decay to a 50% level. The IEEE standard is 8 µS by 20 µS
waveform. The peak current will average 18 KA for the first impulse
and about half of that for the second and third impulses. Three strokes
(impulses) is the average per lightning strike. The number of visible
flashes that may be seen is not necessarily the number of electrical
strokes.
A lightning strike acts like a constant current source. Once ionization
occurs, the air becomes luminous conductive plasma reaching up to
60,000° F. The resistance of a struck object is of little consequence
except for the power dissipation on the object (I2 x R). Fifty percent of
all lightning strikes will have a first impulse of at least 18 KA, ten
percent will exceed the 60 KA level, and only about one percent will
exceed 120 KA.

4.1.1 Chance of Being Struck by Lightning


The map of Figure 4-1 shows the average annual number of
thunderstorm days (Isokeraunic level) for the various regions within the
continental U.S.A. This map is not representative of the severity of the
storm or the number of lightning strikes since it does not take into
account more than one lightning strike in a thunderstorm day. The
Isokeraunic or Isoceraunic number provides a meteorological indication
of the frequency of thunderstorm activity; the higher the Isokeraunic
number the greater the lightning strike activity for a given area. These
levels vary across the world from a low of 1 to a high of 300. Within the
United States the Isokeraunic level varies from a low of 1 to a high of
100.

Revised April-2017 Lightning Arresters and Surge Protectors 21


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

Figure 4-1. Chance of Being Struck by Lightning

Thunderstorms are cloud formations that produce lightning strikes (or


strokes). Across the United States there is an average of 30
thunderstorm days per year. Any given storm may produce from one to
several strokes. Data on the subject indicates that for an average area
within the United States there can be eight to eleven strokes to each
square mile per year. The risk of stroke activity is increased for various
areas such central Florida where up to 38 strokes to each square mile per
year are likely to occur.
To determine the probability of a given structure (tower, building, etc.)
(within your location) being struck, perform the following computation:
1. Using the map of Figure 4-1 (or a comparable meteorological map
for your location), find the Isokeraunic level (I) for your area. Then
using Chart 1, find “A” for your area.
2. Refer to Figure 4-1 to find the latitude. Then using Chart 2, find “B”
for your latitude (Lat.°).
3. Multiply “A” x “B” to get “C”.
4. To calculate the number of lightning strikes per year those are
likely to strike a given object (tower, mast, etc.), use the equation
that follows (where “C” was calculated in step 3 and “H” is equal to
the height of the object.
Strikes Per Year = (“C” x H2) ÷ (.57 x 106 )

22 Lightning Arresters and Surge Protectors Revised April-2017


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

Chart 1 Chart 2
I “A” LAT.° “B”
5 8 25 .170
10 26 30 .200
20 85 35 .236
30 169 40 .280
40 275 45 .325
50 402
60 548
70 712
80 893
90 1069
100 1306
Note for these charts:
I = Thunderstorm Days Per Year (Isokeraunic Number)
A = Stroke activity for associated Isokeraunic Area
B = Height/Stroke coefficient for associated latitude

For Example: On Long Island, New York (Isokeraunic number 20),


Chart 1 gives “A” to equal 85. The latitude is approximately 40°.
Referring to Chart 2, “B” is found to be equal to .28. “C” for this
example is equal to 23.80. Using the equation for strikes per year, it is
determined that a 100-foot tower has .4 chances per year of being
struck by lightning.
Assuming that no other structures are nearby, the tower will more than
likely be struck by lightning at least once in three years.

Note: The Isokeraunic activity numbers connoted as “I”, “A” and “B”
in Charts 1 and 2 above are provided for the continental United
States. Isokeraunic data for various countries is available from
various federal or state Civil Engineering or Meteorological
organizations. This information is typically available from
manufacturers of lightning strike protection equipment (such as
Lightning Arresters).

Revised April-2017 Lightning Arresters and Surge Protectors 23


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

Since controllers and flow computers use DC operated systems that are
isolated from AC grids, they are typically immune to lightning strikes to
power lines or power equipment (except for inductive flashover due to
close installation proximity). However, once a radio or modem has been
interfaced to the controller or flow computer, the possibility of damage
due to a lightning strike on power or telephone lines or to a radio
antenna or the antenna’s tower must be considered. It is recommended
that the additional lightning protection considerations listed below be
followed for units installed in areas with a high possibility or history of
stroke activity.
Units interfaced to a modem: In series with the phone line (as far
away as possible from the equipment) - for indoor installations the
lightning arrester should typically be located at the point where the line
enters the structure.
Units interfaced to a radio: Mount antenna discharge unit (lightning
arrester) as close as possible to where the lead in wire enters the
structure. See Antenna Caution below.

4.1.2 Antenna Caution


Each year hundreds of people are killed, mutilated, or receive severe
permanent injuries when attempting to install or remove an antenna or
antenna lead. In many cases, the victim was aware of the danger of
electrocution but failed to take adequate steps to avoid the hazard. For
your safety, and for proper installation maintenance, please read and
follow the safety precautions that follow - they may save your life.
 When installing or servicing an antenna:
DO NOT use a metal ladder. DO NOT step onto or touch an antenna
mast while power is applied to an associated radio unless the radio is
a low power (low current) type.
DO NOT work on a wet or windy day, especially during a
thunderstorm or when there is lightning or thunder in your area.
Dress properly; shoes with rubber soles and heels, rubber gloves,
long sleeve shirt or jacket.
 The safe distance from power lines should be at least twice the
height of the antenna and mast combination.
 Antenna Grounding per National Electrical Code Instructions:
A. Use AWG 10 or 8 aluminum or AWG 1 copper-clad steel or
bronze wire, or larger as ground wires for both the mast and
lead-in. Be mindful of dissimilar metals resulting in a corrosion
problem. Securely clamp the wire to the bottom of the mast.
B. Secure lead-in wire from antenna to antenna discharge (lightning
arrester) unit and the mast ground wire to the structure (building,
shed, etc.) with stand-off insulators spaced from 4 feet (1.22
meters) to 6 feet (1.83 meters) apart.

24 Lightning Arresters and Surge Protectors Revised April-2017


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

C. Mount antenna discharge unit as close as possible to where the


lead-in wire enters the structure.
D. The hole drilled through the wall for the lead-in wire should be
just large enough to accommodate the cable. Before drilling this
hole, make sure there are no wires or pipes, etc. in the wall.
E. Push the cable through the hole and form a rain drip loop close
to where the wire enters the exterior of the structure.
F. Caulk around the lead-in wire (where it enters the structure) to
keep out drafts.
G. Install lightning arresters (antenna discharge units). The
grounding conductor should be run in as straight a line as
practicable from the antenna mast and/or the antenna discharge
units to grounding electrode(s).
H. Only connect the antenna cable to the radio after the mast has
been properly grounded and the lead-in cable has been properly
connected to lightning arresters which in turn have each been
properly connected to a known good earth ground.

Revised April-2017 Lightning Arresters and Surge Protectors 25


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

Figure 4-2. Radio Antenna Field Installation Site Grounding Diagram

26 Lightning Arresters and Surge Protectors Revised April-2017


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

For all systems it is best to have all communication equipment


input/output grounds tied together. In the case of ControlWave units,
this is accomplished via the unit's chassis ground (Typically at a
ground lug, ground bus or ground plate). However additional
communication equipment lightning arresters and surge protectors
should be tied to the same system ground. System ground consists of the
tower leg grounds utility ground and bulkhead equipment ground stakes
that are tied together via bare copper wire.

4.1.3 Ground Propagation


As in any medium, a dynamic pulse, like R.F., will take time to
propagate. This propagation time will cause a differential step voltage to
exist in time between any two ground rods that are of different radial
distances from the strike. With a ground rod tied to a struck tower, the
impulse will propagate its step voltage outwardly from this rod in ever-
expanding circles, like a pebble thrown into a pond. If the equipment
house has a separate ground rod and the power company and/or
telephone company grounds are also separate, the dynamic step voltage
will cause currents to flow to equalize these separate ground voltages.
Then if the coax cable (associated with a radio) is the only path linking
the equipment chassis with the tower ground, the surge can destroy
circuitry.

4.1.4 Tying it all Together


To prevent this disaster from occurring, a grounding system must be
formed which interconnects all grounds together. This will equalize and
distribute the surge charge to all grounds, and at the same time, it will
make for a lower surge impedance ground system. This interconnection
can be done as a grid, where each ground has a separate line to each
other ground, or by using a “rat race” ring which forms a closed loop
(not necessarily a perfect circle) which surrounds the equipment house
completely.
By making this interconnection, it will be necessary to use proper I/O
protectors for the equipment. Of course, these should be a requirement
regardless of whether this grounding technique is used. I/O protectors
are used for power lines (even those these don’t feed into a
controller/flow computer), telephone lines, and also to minimize EMI
pick-up from a strike. Ideally it is best to place all I/O protectors on a
common panel that has a low inductance path to the ground system. The
controller/flow computer would then have a single ground point from its
chassis ground terminal/ground lug to this panel. In lieu of this, the
controller/flow computer in question should be tied to a ground rod that
in turn is connected to the earth/system ground created for the site.
Your protected equipment connected to a common single ground
system, will now be just like a bird sitting on a high tension wire. When
lightning strikes, even with a 50 ohm surge impedance ground system,
the entire system consisting of equipment, ground system, building, etc.,

Revised April-2017 Lightning Arresters and Surge Protectors 27


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

will all rise together to the one million volt peak level (for example) and
will all decay back down together. So long as there is no voltage
differential (taken care of by protectors and ground interconnections,
there will be no current flow through the equipment and therefore
no resulting equipment damage.

4.1.5 Impulse Protection Summary


 Use more than one ground rod.
 Place multi-ground stakes more than their length apart.
 Tie Power, Telco, Tower, Bulkhead and equipment ground together.
 Make all ground interconnect runs that are above ground with
minimum radius bends of eight inches and run them away from
other conductors and use large solid wire or a solid strap.
 Watch out for dissimilar metals connections and coat accordingly.
 Use bare wire radials together where possible with ground stakes to
reduce ground system impedance.
 Use I/O protectors (Phone line, Radio) with a low inductance path to
the ground system.
 Ground the Coaxial Cable Shield (or use an impulse suppressor) at
the bottom of the tower just above the tower leg ground connection.

4.2 Use of Lightning Arresters and Surge Protectors


Units equipped with radios or modems use lightning arresters and surge
protectors to protect equipment from lightning strikes, power surges and
from damaging currents that have been induced onto communication
lines.
The first line of defense is the Lightning Arrester. These devices
typically use gas discharge bulbs that can shunt high currents and
voltages to earth ground when they fire. The high current, high voltage
gas discharge bulb has a relatively slow response time and only fires
when gas has been ionized by high voltage.
The second line of defense is the Surge Protector, which is made of
solid state devices, fires very quickly and conducts low voltages and
currents to ground. Surge protectors are built into some modems.
Lightning Arresters are applied to circuits as follows:
 Equipment or circuits that can be exposed to lightning strikes,
falling power lines, high ground currents caused by power system
faults, by operational problems on electric railways, etc.
 Equipment installed in dry, windy areas, such as the Great Plains
and the Southwest Desert in the United States. Wind and windblown
dust can cause high voltages (static) to appear on overhead wires,
fences, and metal buildings.

28 Lightning Arresters and Surge Protectors Revised April-2017


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

Note: Lightning Arresters may explode if a lightning strike is very


close. Mount lightning arresters where flying parts won't cause
injury to equipment or personnel.

4.2.1 Installation of Lightning Arresters and Surge Protectors


1. Install lightning arresters external to equipment cabinets, racks or
buildings.
2. Each lightning arrester requires a separate ground connection to the
nearest available earth ground. Use the manufacturer’s specified
wire size.

Figure 4-3. Lightning Arresters and Surge Protectors

Figure 4-4. Protecting Equipment with Lightning Arresters and Surge Protectors

Revised April-2017 Lightning Arresters and Surge Protectors 29


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

Figure 4-5. Protecting Equipment with Lightning Arresters

30 Lightning Arresters and Surge Protectors Revised April-2017


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

Chapter 5 – Wiring Techniques


In This Chapter

5.1 Overview ........................................................................................... 31


5.2 Instrument Wiring .............................................................................. 31
5.2.1 Common Returns .................................................................. 32
5.2.2 Use of Twisted Shielded Pair Wiring
(with Overall Insulation) ......................................................... 33
5.2.3 Grounding of Cable Shields .................................................. 33
5.2.4 Use of Known Good Earth Grounds ...................................... 33
5.2.5 Earth Ground Wires ............................................................... 34
5.2.6 Working Neatly and Professionally ....................................... 34
5.2.7 High Power Conductors and Signal Warning ........................ 34
5.2.8 Use of Proper Wire Size ........................................................ 34
5.2.9 Lightning Arresters & Surge Protectors ................................. 35
5.2.10 Secure Wiring Connections ................................................... 36

5.1 Overview
This section provides information pertaining to good wiring practices.
Installation of Power and “Measurement & Control” wiring is
discussed. Information on obscure problems, circulating ground and
power loops, bad relays, etc. is presented. Good wire preparation and
connection techniques along with problems to avoid are discussed.

5.2 Instrument Wiring


Each of the rules listed below is briefly discussed; the emphasis herein
is placed on the avoidance of problems as well as equipment safety.

 Rule 1 – Never utilize common returns.


 Rule 2 – Use twisted shielded pairs (with overall insulation) on all
Signal/Control circuits.
 Rule 3 – Ground cable shields at one end only.
 Rule 4 – Use known good earth grounds (Rod, Bed, System) and
test them periodically,
 Rule 5 – Earth connections must utilize smoothly dressed large
wire.
 Rule 6 – Perform all work neatly and professionally.
 Rule 7 – Route high power conductors away from signal wiring
according to NEC Rules.
 Rule 8 – Use appropriately sized wires as required by the load.
 Rule 9 – Use lightning arresters and surge protectors.

Revised April-2017 Wiring Techniques 31


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

 Rule 10 – Make sure all wiring connections are secure.

5.2.1 Common Returns


Use of common returns on I/O wiring is one of the most common
causes of obscure and difficult to troubleshoot control signal problems.
Since all wires and connections have distributed resistance, inductance
and capacitance, the chances of a achieving a balanced system when
common returns are present is very remote. Balanced systems (or
circuits) are only achieved when all currents and voltages developed in
association with each of the common returns are equal. In a balanced
system (or circuit) there are no noise or measurement errors introduced
due to by “sneak circuits.”
The illustration of Figure 5-1 shows the difference between testing an
I/O circuit that is discrete and has no sneak circuits and one that utilizes
common returns. Common sense tells us that it is tough to mix up
connections to a twisted shielded pair (with overall vinyl covering) to
every end device. Do yourself a favor; to make start up easier, DON’T
USE COMMON RETURNS!

Figure 5-1. Field Wired Circuit Without a Common Return


Note: Without a common return, there are no sneak circuits and testing
is easy.

Figure 5-2. Field Wired Circuit with a Common Return

32 Wiring Techniques Revised April-2017


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

Note: With a common return, sneak circuits are created! A lot of


equipment must be disconnected to find a sneak circuit!

5.2.2 Use of Twisted Shielded Pair Wiring (with Overall Insulation)


For all field I/O wiring the use of twisted shielded pairs with overall
insulation is highly recommended. This type of cable provides discrete
insulation for each of the wires and an additional overall insulated
covering that provides greater E.M.I. immunity and protection to the
shield as well.

5.2.3 Grounding of Cable Shields


DO NOT connect the cable shield to more than one ground point; it
should only be grounded at one end. Cable shields that are grounded at
more than one point or at both ends may have a tendency to induce
circulating currents or sneak circuits that raise havoc with I/O signals.
This will occur when the ground systems associated with multipoint
connections to a cable shield have a high resistance or impedance
between them and a ground induced voltage is developed (for whatever
reason, i.e., manmade error or nature produced phenomena).

5.2.4 Use of Known Good Earth Grounds


Controllers/flow computers should only have one connection to earth
ground; this connection is provided via the Ground Lug. Since these
units are DC-based systems, grounding does not take into account AC
power grounding considerations. Earth grounding the unit is absolutely
necessary when the unit is equipped with a radio or modem.
Additionally, these units should be connected to earth ground when
they are installed in areas that have frequent lightning strikes or are
located near or used in conjunction with equipment that is likely to be
struck by lightning or if struck by lightning may cause equipment or
associated system failure. Earth Grounds must be tested and must be
known to be good before connecting the controller/flow computer.
Earth grounds must be periodically tested and maintained (refer to
Chapter 4).

Revised April-2017 Wiring Techniques 33


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

5.2.5 Earth Ground Wires


Earth connections must utilize smoothly dressed large wire. Use AWG
3 or 4 stranded copper wire with as short a length as possible. Exercise
care when trimming the insulation from the wire ends. Twists the
strands tightly, trim off any frizzes and tin the ends with solder. The
earth ground wire should be clamped or brazed to the Ground Bed
Conductor (that is typically a standard AWG 0000 copper cable. The
earth ground wire should be run such that any routing bend in the cable
is a minimum 8-inch radius above ground or a minimum 12-inch radius
below ground.

5.2.6 Working Neatly and Professionally


Take pride in your work and observe all site and maintenance safety
precautions. After properly trimming the stranded pair wire ends, twist
them in the same direction as their manufacturer did and then tin them
with solder. Install the tinned wire end into it’s connector and then
secure the associated connector’s clamping screw. Remember to check
these connections for tightness from time to time. If solid copper wire is
use (in conjunction with the DC Power System or for Earth Ground)
make sure that the conductor is not nicked when trimming off the
insulation. Nicked conductors are potential disasters waiting to happen.
Neatly trim shields and whenever possible, coat them to protect them
and prevent shorts and water entry.

Remember loose connections, bad connections, intermittent


connections, corroded connections, etc., are hard to find, waste time,
create system problems and confusion in addition to being costly.

5.2.7 High Power Conductors and Signal Warning


When routing wires, keep high power conductors away from signal
conductors. Space wires appropriately to vent high voltage inductance.
Refer to the National Electrical Code Handbook for regulatory and
technical requirements.

5.2.8 Use of Proper Wire Size


ControlWaves utilize compression-type terminals that accommodate up
to #14 AWG gauge wire. FB1100/FB1200/FB2100/FB2200 flow
computer terminal blocks accept 28-12 AWG gauge wire. A connection
is made by inserting the bared end (1/4 inch max.) into the clamp
beneath the screw and securing the screw.

Allow some slack in the wires when making terminal connections.


Slack makes the connections more manageable and minimizes
mechanical strain on the PCB connectors. Provide external strain relief
(utilizing tie wrap, etc.) to prevent the loss of slack at the
controller/flow computer.

34 Wiring Techniques Revised April-2017


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

Be careful to use wire that is appropriately sized for the load. Refer to
equipment manufacturer’s specifications and the National Electrical
Code Handbook for information on wire size and wire resistance. After
installing the field wiring, test each load to determine if the correct
voltage or current is present at the load. If you know the resistance of
the field wires (Circular Mills x Length) you should be able to calculate
the load voltage. Conversely, if you know the minimum load voltage
and current, you should be able to derive the maximum voltage loss
that is allowable due to line resistance and then the correct wire size.
Referring to Figure 5-2, a relay that is picked by 100 mA, with a loop
supply voltage of 24V
and a total line resistance of 20 ohms, the load voltage (voltage across
the relay) should be:

VL = VS - (VC + VC) where VC + VC = (RC + RC) I


22 = 24 - 2 where 2V = (20 Ω) x 0.1 A

Figure 5-3. Calculating Load Voltage due to Line Resistance

5.2.9 Lightning Arresters & Surge Protectors


Use lightning arresters in association with any radio or modem
equipped unit. Some modems are equipped with surge protection
circuitry. Lightning arresters or Antenna Discharge Units should be
placed on the base of the antenna and at the point where the antenna
lead (typically coax) enters the site equipment building. When a
modem is used, a lightning arrester should be placed at the point where
the phone line enters the site equipment building. If you use a modem
that does not include surge protection circuitry it is recommended that
you also install a surge suppressors or lightning arrester on the phone
line as close to the modem as possible. Any unit interfaced to a radio or
modem must be connected to a known good earth ground.

Revised April-2017 Wiring Techniques 35


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

5.2.10 Secure Wiring Connections


Make sure that all wiring connections are secure. In time wires that
were once round will become flattened due to the pressure applied by
screw compression type terminals and site vibrations. After a while
these compression screws have a tendency to become loose. Part of a
good maintenance routine should be to check and tighten all screws
associated with wiring terminal connections. Avoid nicking the wire(s)
when stripping insulation. Remember, nicked conductors will lead to
future problems. Also remember to provide some cabling slack and
strain relief.

If installing stranded or braided wiring that has not been tinned, be sure
to tightly twist the end (in the same direction as manufactured) and then
trim off any frizzed wires.

36 Wiring Techniques Revised April-2017


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

[This page is intentionally left blank.]

Revised April-2017 Wiring Techniques 37


Site Considerations for Equipment Installation, Grounding, and Wiring Manual

For customer service and technical support,


visit www.EmersonProcess.com/Remote/Support.
Global Headquarters,
North America, and Latin America:
Emerson Automation Solutions
Remote Automation Solutions
6005 Rogerdale Road
Houston, TX 77072 U.S.A.
T +1 281 879 2699 | F +1 281 988 4445
www.EmersonProcess.com/Remote
Europe:
Emerson Automation Solutions
Remote Automation Solutions
Unit 8, Waterfront Business Park
Dudley Road, Brierley Hill
Dudley UK DY5 1LX
T +44 1384 487200 | F +44 1384 487258
Middle East/Africa:
Emerson Automation Solutions
Remote Automation Solutions
Emerson FZE
P.O. Box 17033 © 2005–2017 Remote Automation Solutions, a business unit of Emerson Automation
Jebel Ali Free Zone – South 2 Solutions. All rights reserved.
Dubai U.A.E.
T +971 4 8118100 | F +971 4 8865465 This publication is for informational purposes only. While every effort has been made to ensure
accuracy, this publication shall not be read to include any warranty or guarantee, express or
Asia-Pacific: implied, including as regards the products or services described or their use or applicability.
Emerson Automation Solutions Remote Automation Solutions (RAS) reserves the right to modify or improve the designs or
Remote Automation Solutions specifications of its products at any time without notice. All sales are governed by RAS terms
1 Pandan Crescent and conditions which are available upon request. RAS accepts no responsibility for proper
Singapore 128461 selection, use or maintenance of any product, which remains solely with the purchaser and/or
T +65 6777 8211| F +65 6777 0947 end-user.

Remote Automation Solutions

Vous aimerez peut-être aussi