Technical Report No. 64.290.15.00099.

01
Rev. 00
Dated 2015-3-5

Client: Name: B&B Power Co., Ltd.


Address: 3rd Floor, Block A, Xin YongFeng Industry Park, Tian Bao 2nd road,
ShiYan Town, BaoAn District, Shenzhen, PEOPLE'S REPUBLIC OF CHINA
contact person: Mr. Wang Yadong
Manufacturing place: Manufacturer’s name: B&B Power Co., Ltd.
Address: 3rd Floor, Block A, Xin YongFeng Industry Park, Tian Bao 2nd road,
ShiYan Town, BaoAn District, Shenzhen, PEOPLE'S REPUBLIC OF CHINA
Factory’s name: Moso Power Supply Technology Co., Ltd.
Address: 6F, Sangtai Industrial Park, Guanwai Xiaobaimang Songbai Road,
Nanshan District, 518108 Shenzhen, Guangdong, PEOPLE'S REPUBLIC OF
CHINA
Test subject: Product: PV grid-interactive inverter
Type: ST10000TL, ST12000TL, ST15000TL, ST17000TL, ST20000TL

Trade mark (if any): ,


Test specification:
IEC 61727:2004
IEC 62116:2014
Purpose of examination:  Test according to the test specification
TPS_GCN_F_09.20E – Rev. 1

Test result: The test results show that the presented product is in compliance with the
specified requirements

This technical report may only be quoted in full. Any use for advertising purposes must be granted
in writing. This report is the result of a single examination of the object in question and is not
generally applicable evaluation of the quality of other products in regular production.
2012-10-29 (Positive Report No64.290.15.00099.01.)

TÜ V SÜ D Certification and Testing (China) Co., Ltd.


Project No: 64.290.15.00099.01 Telephone : +86 20 38320668 Guangzhou Branch, TÜ V SÜ D Group
Rev.: 00 Telefax : +86 20 38320478
Date: 2015-3-5 5F, Communication Building, 163 Pingyun Rd, Huangpu
Page: 1 of 3 http://www.tuv-sud.cn Ave. West,Guangzhou, 510656, P.R.China
1 Description of the test subject

1.1 Function
Manufacturer’s specification for intended use:

1. The units are non-isolated PV grid-interactive inverters for connection with public low voltage grid.
2. The grid connection protection system is evaluated according to IEC 61727:2004. Clause 5.3 of IEC
61727:2004 islanding protection test is performed according to IEC 62116:2014.
3. Low voltage electrical installations shall comply with national and local regulation.

1.2 Consideration of the foreseeable misuse


Not applicable
Covered through the applied standard
Covered by the following comment
Covered by attached risk analysis

1.3 Technical Data


Model ST10000TL ST12000TL ST15000TL ST17000TL ST20000TL
Vmax. PV (Vd.c.) 1000 1000 1000 1000 1000
Isc PV (A) 25/25 25/25 25/25 25/25 25/25
MPPT range (full load) 300 - 800 380 - 800 380 - 800 430 - 800 500 - 800
(Vd.c.)
Nominal AC voltage (Va.c.) 3N~ 3N~ 3N~ 3N~ 3N~
230/400 230/400 230/400 230/400 230/400
Nominal AC frequency (Hz) 50 50 50 50 50
Nominal active output power 10000 12000 15000 17000 20000
(W)
Max. cont. output current (A) 16 19 24 25 30

Power factor 0.9 under- 0.9 under- 0.9 under- 0.9 under- 0.9 under-
TPS_GCN_F_09.20E – Rev. 1

range(adjustable) excited - excited - excited - excited - excited -


0.9 over-excited 0.9 over-excited 0.9 over-excited 0.9 over-excited 0.9 over-excited
Ingress protection IP 65 IP 65 IP 65 IP 65 IP 65
Overvoltage category II(DC), II(DC), II(DC), II(DC), II(DC),
III(AC) III(AC) III(AC) III(AC) III(AC)
Protective class I I I I I

2 Order

2.1 Date of Purchase Order, Customer’s Reference


2012-10-29 (Positive Report No64.290.15.00099.01.)

31 December 2014

2.2 Receipt of Test Sample, Location


TÜV SÜD Certification and Testing (China) Co., Ltd. Guangzhou Branch
5F, Communication Building, 163 Pingyun Rd, Huangpu Ave. West, Guangzhou 510656,
P. R. China

2.3 Date of Testing


31 December 2014 – 2 March 2015

TÜ V SÜ D Certification and Testing (China) Co., Ltd.


Project No: 64.290.15.00099.01 Telephone : +86 20 38320668 Guangzhou Branch, TÜ V SÜ D Group
Rev.: 00 Telefax : +86 20 38320478
Date: 2015-3-5 5F, Communication Building, 163 Pingyun Rd, Huangpu
Page: 2 of 3 http://www.tuv-sud.cn Ave. West,Guangzhou, 510656, P.R.China