Job No Sheet No Rev

1
Part
Software licensed to
Job Title Ref

By PSK Date14-Oct-17 Chd

Client File Facade Design.std Date/Time 05-Nov-2017 22:48

Section Properties
Prop Section Area Iyy Izz J Material
(cm2) (cm4) (cm4) (cm4)
1 TUB1001003.6 13.700 212.000 212.000 322.503 STEEL
2 TUB100503.0 8.540 36.800 110.000 86.602 STEEL
3 TUB1001005.0 18.700 279.000 279.000 428.688 STEEL

Materials
Mat Name E  Density 
(kN/mm2) (kg/m3) (/°C)
1 STEEL 205.000 0.300 8E+3 12E -6
2 STAINLESSSTEEL 197.930 0.300 7.83E+3 18E -6
3 ALUMINUM 68.948 0.330 2.71E+3 23E -6
4 CONCRETE 21.718 0.170 2.4E+3 10E -6

Primary Load Cases


Number Name Type

1 DL Dead
2 LL Live
3 WL-1 Wind
4 WL-2 Wind

Print Time/Date: 05/11/2017 22:52 STAAD.Pro V8i (SELECTseries 6) 20.07.11.50 Print Run 1 of 10
Job No Sheet No Rev
2
Part
Software licensed to
Job Title Ref

By PSK Date14-Oct-17 Chd

Client File Facade Design.std Date/Time 05-Nov-2017 22:48

Combination Load Cases


Comb. Combination L/C Name Primary Primary L/C Name Factor

101 1.4DL+1.6LL 1 DL 1.40


2 LL 1.60
102 1.2DL+1.2LL+1.2WL1 1 DL 1.20
2 LL 1.20
3 WL-1 1.20
103 1.2DL+1.2LL+1.2WL2 1 DL 1.20
2 LL 1.20
4 WL-2 1.20
104 1.4DL+1.4WL1 1 DL 1.40
3 WL-1 1.40
105 1.4DL+1.4WL2 1 DL 1.40
4 WL-2 1.40
106 1.0DL+1.4WL1 1 DL 1.00
3 WL-1 1.40
107 1.0DL+1.4WL2 1 DL 1.00
4 WL-2 1.40
201 1.0DL+1.0LL 1 DL 1.00
2 LL 1.00
202 1.0DL+1.0LL+1.0WL1 1 DL 1.00
2 LL 1.00
3 WL-1 1.00
203 1.0DL+1.0LL+1.0WL2 1 DL 1.00
2 LL 1.00
4 WL-2 1.00
204 1.0DL+1.0WL1 1 DL 1.00
3 WL-1 1.00
205 1.0DL+1.0WL2 1 DL 1.00
4 WL-2 1.00

Print Time/Date: 05/11/2017 22:52 STAAD.Pro V8i (SELECTseries 6) 20.07.11.50 Print Run 2 of 10
Job No Sheet No Rev
3
Part
Software licensed to
Job Title Ref

By PSK Date14-Oct-17 Chd

Client File Facade Design.std Date/Time 05-Nov-2017 22:48

Combination Load Cases Cont...


Comb. Combination L/C Name Primary Primary L/C Name Factor

206 1.0DL+1.0WL1 1 DL 1.00


3 WL-1 1.00
207 1.0DL+1.0WL2 1 DL 1.00
4 WL-2 1.00

3D Rendered View

Print Time/Date: 05/11/2017 22:52 STAAD.Pro V8i (SELECTseries 6) 20.07.11.50 Print Run 3 of 10
Job No Sheet No Rev
4
Part
Software licensed to
Job Title Ref

By PSK Date14-Oct-17 Chd

Client File Facade Design.std Date/Time 05-Nov-2017 22:48

1.400m
1.470m
0.800m
1.745m
2.750m
2.750m
1.500m
2.150m
2.150m
1.500m
2.750m
2.750m
1.745m
0.800m
1.470m
1.400m
1.500m

2.500m

2.500m

1.500m
0.500m

1.850m
Y
X
Z Load 4
1.850m

Whole Structure

Print Time/Date: 05/11/2017 22:52 STAAD.Pro V8i (SELECTseries 6) 20.07.11.50 Print Run 4 of 10
Job No Sheet No Rev
5
Part
Software licensed to
Job Title Ref

By PSK Date14-Oct-17 Chd

Client File Facade Design.std Date/Time 05-Nov-2017 22:48

116
115 57
114
113 67 62
112 72 132
77 131
130
111 129 192
110 82 193
128 194
109 52 195
42 127 196 213
108 212
107 47 126 197 211
125 210 58
106 37 63
27 124 191 209
105 123 189 73 68
32 190 208 78 148
104 122 207 147 59
103 22 188 83 146
102 121 186 206 145 69 64
101 12 17 74 164
60
120 205 53 144 16365 180
7 119 187 43 79 162
2 118 204 143 70 179
16175178
185 203 48 84 239
117 142160 80 177 240
183184 38
182
202 28 141
159 85
54
176 242241 259
201 140 44 243
181 33 15855 175 257 56
200 139 49 61
199 157 45 174 244
198 23 138 39 255 71 66
29 156 50 173 238 228
13 18 137 15540 172 237 254 76 227
8 34 226
3 136 154 30 171 253 81 225
135 24 170 236 224
134 153 35 51
133 14 19 15225 169 234 41 223
9 151 235 251
4 15015 20 168 222
14910 166 167 233 250 36
5 165 26
231232 249
220
230 31
229 247 219
Y 21
245
X 11 16 218
Z 6 217 Load 4
1 216
215
214

BEAM NUMBER

Print Time/Date: 05/11/2017 22:52 STAAD.Pro V8i (SELECTseries 6) 20.07.11.50 Print Run 5 of 10
Job No Sheet No Rev
6
Part
Software licensed to
Job Title Ref

By PSK Date14-Oct-17 Chd

Client File Facade Design.std Date/Time 05-Nov-2017 22:48

68
76
88 82
94 69
75
100 87 81
64 93
52 99
58 114
63 115
46 51 117116
34
57 118
40 45 119 70
28 33 77
113
16 22 39 111 89 83
10 112 95 71
2 27 78 72
15 21 110 101 90 84 74
108
9 65 96 86 80
3 109 53 92
102 130
107 59 98 131
47 66 133132
105106 35 54 62
104 50 134
103 60 67
41 48 56 135 73
29 36 44 129 85 79
32 91
17 23 42 128
11 38 97
4 30
26 127
18 24 125 49
61
12 14 20
5 8 126
6 124 43
31
122123
Y 121 37
X 120 25
Z Load 4
13 19
7
1

NODE NUMBER

Print Time/Date: 05/11/2017 22:52 STAAD.Pro V8i (SELECTseries 6) 20.07.11.50 Print Run 6 of 10
Job No Sheet No Rev
7
Part
Software licensed to
Job Title Ref

By PSK Date14-Oct-17 Chd

Client File Facade Design.std Date/Time 05-Nov-2017 22:48

TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0TUB100503.0 TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0 TUB100503.0TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0
TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6 TUB1001003.6 TUB1001003.6
TUB1001003.6
TUB1001005.0
TUB1001003.6
TUB1001003.6 TUB1001003.6 TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0TUB100503.0 TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0 TUB100503.0TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0

TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6 TUB1001003.6 TUB1001003.6
TUB1001003.6
TUB1001005.0
TUB1001003.6
TUB1001003.6 TUB1001003.6 TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6

TUB1001005.0
TUB1001005.0
TUB1001005.0
TUB1001005.0
TUB1001005.0 TUB1001005.0
TUB1001005.0
TUB1001005.0
TUB1001005.0
TUB1001005.0
TUB1001005.0 TUB1001005.0
TUB1001005.0
TUB1001005.0
TUB1001005.0
TUB1001005.0

TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6 TUB1001003.6 TUB1001003.6
TUB1001003.6
TUB1001005.0
TUB1001003.6
TUB1001003.6 TUB1001003.6 TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6

TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0TUB100503.0 TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0 TUB100503.0TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0
TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6 TUB1001003.6 TUB1001003.6
TUB1001003.6
TUB1001005.0
TUB1001003.6
TUB1001003.6 TUB1001003.6 TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0TUB100503.0 TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0 TUB100503.0TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0
TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6 TUB1001003.6 TUB1001003.6
TUB1001003.6
TUB1001005.0
TUB1001003.6
TUB1001003.6 TUB1001003.6 TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0TUB100503.0 TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0 TUB100503.0TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0

TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6 TUB1001003.6 TUB1001003.6
TUB1001003.6 TUB1001003.6
TUB1001003.6 TUB1001003.6 TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6

TUB100503.0 TUB100503.0 TUB100503.0 TUB100503.0


TUB100503.0 TUB100503.0
TUB100503.0 TUB100503.0 TUB100503.0 TUB100503.0
Y
Z X TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6 TUB1001003.6 TUB1001003.6
TUB1001003.6 TUB1001003.6
TUB1001003.6 TUB1001003.6 TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6
TUB1001003.6
Load 4
TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0TUB100503.0 TUB100503.0
TUB100503.0 TUB100503.0
TUB100503.0 TUB100503.0TUB100503.0
TUB100503.0
TUB100503.0
TUB100503.0

SECTION PROPERTY

Print Time/Date: 05/11/2017 22:52 STAAD.Pro V8i (SELECTseries 6) 20.07.11.50 Print Run 7 of 10
Job No Sheet No Rev
8
Part
Software licensed to
Job Title Ref

By PSK Date14-Oct-17 Chd

Client File Facade Design.std Date/Time 05-Nov-2017 22:48

-0.315 kN/m
-0.315
-0.315 kN/m kN/m
-0.150
kN/m
-0.315 kN/m-0.150
-0.150 kN/m
kN/m
-0.315 kN/m-0.150 kN/m-0.525
-0.525 kN/m
kN/m
-0.525 kN/m
-0.315 kN/m-0.150 kN/m-0.525 kN/m -0.250 kN/m
-0.315-0.150
kN/m kN/m -0.250
-0.250 kN/mkN/m
-0.150 kN/m
-0.315 kN/m -0.525 kN/m-0.250 kN/m
-0.150 kN/m -0.525 kN/m
-0.315 kN/m -0.525 kN/m
-0.315-0.150
kN/m kN/m -0.250 kN/m -0.525
-0.525 kN/m
kN/m
-0.525 kN/m -0.250 kN/m
-0.315 kN/m-0.150 kN/m -0.525 kN/m -0.250 kN/m -0.525 kN/m-0.250 kN/m
-0.250 kN/m -0.250 kN/m
-0.315 kN/m-0.150 kN/m-0.525-0.525 kN/m
kN/m -0.250 kN/m
-0.525 kN/m-0.250 kN/m -0.315 kN/m
-0.315
-0.315 kN/m
-0.150 kN/m
kN/m -0.250 kN/m -0.525 kN/m-0.250 kN/m -0.315 kN/m kN/m
-0.150
-0.315 kN/m
-0.150
-0.315-0.150
kN/m kN/m -0.525 kN/m-0.250 kN/m -0.525 kN/m -0.315 kN/m-0.150-0.740
kN/m kN/m
kN/m -0.150 kN/m
-0.050 kN/m
-0.315-0.150
kN/m kN/m -0.525 kN/m-0.250 kN/m -0.525 kN/m -0.250 kN/m -0.740 kN/m
-0.150 kN/m-0.050 kN/m kN/m
-0.150 kN/m -0.525 kN/m -0.250 kN/m -0.315 kN/m -0.050 kN/m
-0.390
-0.525 kN/m -0.525 kN/m
-0.525 kN/m -0.250 kN/m -0.525 kN/m -0.250 kN/m -0.315 kN/m-0.150 kN/m-0.050 kN/m
-0.740 kN/m -0.390 kN/m
-0.740 kN/m
-0.185
-0.250
-0.525 kN/m-0.250 kN/m
kN/m -0.250 kN/m -0.315-0.150
kN/m kN/m-0.050 kN/m -0.740 kN/m
-0.740
-0.525 kN/m-0.250 kN/m -0.740 kN/m -0.185 kN/m
-0.250 kN/m -0.150
-0.315 kN/m kN/m -0.740 kN/m -0.390 kN/m
-0.250 kN/m -0.525 kN/m-0.250 kN/m -0.740-0.050
kN/m kN/m -0.390 kN/m
-0.150 kN/m
-0.315 kN/m -0.050-0.390
kN/m kN/m-0.740 -0.390
-0.390 kN/m
kN/m
-0.525
-0.525 kN/m
kN/m -0.315-0.150
kN/m kN/m -0.185 kN/m
-0.250 kN/m -0.050 kN/m
-0.390 kN/m -0.390 kN/m
-0.525 kN/m -0.315 kN/m-0.150 kN/m -0.740 kN/m
-0.185
-0.250
-0.525 kN/m-0.250 kN/m
kN/m -0.740-0.050
kN/m kN/m -0.740 kN/m -0.390 kN/m
-0.185
-0.250 kN/m -0.315 kN/m-0.150 kN/m-0.050 kN/m
-0.740 kN/m -0.390 kN/m
-0.250 kN/m -0.315 kN/m-0.150 kN/m -0.390 kN/m
-0.315 kN/m -0.050 kN/m -0.390 kN/m
-0.150
-0.315-0.150
kN/m -0.740 kN/m
kN/m -0.740 kN/m
-0.315-0.150
kN/m-0.740 -0.050 kN/m-0.390 kN/m-0.185
kN/m
kN/m
kN/m
-0.050 kN/m -0.740 kN/m
-0.150 kN/m-0.050 kN/m -0.390 kN/m-0.185 -0.390 kN/m
-0.740-0.050
kN/m kN/m
-0.050 kN/m-0.390 kN/m -0.740 kN/m
-0.185
-0.740 kN/m -0.390 kN/m
-0.390-0.740-0.740
-0.185
kN/m kN/m kN/m
-0.390 kN/m
-0.740 kN/m -0.390 kN/m
-0.185
Y -0.390 kN/m
X -0.390 kN/m
Z -0.390 kN/m
Load 1

DL

Print Time/Date: 05/11/2017 22:52 STAAD.Pro V8i (SELECTseries 6) 20.07.11.50 Print Run 8 of 10
Job No Sheet No Rev
9
Part
Software licensed to
Job Title Ref

By PSK Date14-Oct-17 Chd

Client File Facade Design.std Date/Time 05-Nov-2017 22:48

3.100
2.480kN/m
kN/m
3.100
3.100 kN/m
kN/m
2.480 kN/m
3.100 2.480
kN/m kN/m 0.930 kN/m
2.480 kN/m 0.930 kN/m
0.9303.100
3.100 3.100 2.480kN/m
kN/m
kN/m kN/m
2.480kN/m
kN/m 0.930 kN/m
3.100 kN/m
2.480
2.480 kN/mkN/m
0.930 kN/m
3.100 kN/m 0.930 3.100
kN/m
2.480kN/m
kN/m 0.930 kN/m
3.100 2.480 kN/m 0.930 kN/m
2.480kN/m
kN/m 3.100
2.480kN/m
0.930 kN/m kN/m 0.930 kN/m
3.100
2.480kN/m 3.100
3.100
kN/m 0.930 kN/m
3.100 kN/m
2.480 kN/m 0.930 kN/m 3.100 2.480kN/m
kN/m
3.100 2.480kN/m
kN/m 0.9303.100
kN/mkN/m 3.100
2.480kN/m
kN/m kN/m
2.480kN/m
kN/m
0.9303.100
kN/mkN/m
2.480 kN/m
0.930 kN/m 3.100 2.480
kN/m kN/m
0.930
0.930 kN/m
kN/m
2.480 kN/m 0.930 kN/m
3.100
2.480kN/m
kN/m 0.930 kN/m 2.480 kN/m 0.930 kN/m 3.100 kN/m
3.100
3.100 kN/m 3.100 2.480kN/m
kN/m kN/m 0.930 kN/m 2.480 kN/m 0.930 kN/m
2.480 kN/m 0.930 kN/m
2.480 kN/m 3.100
3.100 kN/m 3.100
0.930 kN/m 2.480kN/m
kN/m 0.930 kN/m 2.480 kN/m
3.100
3.100
2.480
kN/m
kN/m
2.480
kN/mkN/m 2.480kN/m
0.930 kN/m kN/m 0.930 kN/m 3.100
2.480kN/m
kN/m
0.930 kN/m
2.480
2.480 kN/mkN/m
0.930 kN/m
3.100 2.480 kN/m 0.930 kN/m
3.100 kN/m 3.100 kN/m 2.480 kN/m 0.930 kN/m
2.480kN/m
kN/m
0.930
0.930 kN/m
3.100
kN/m
2.480
kN/m kN/m 0.930 kN/m
3.100 kN/m
2.480 kN/m 0.930 kN/m 0.930 kN/m
3.100 kN/m
2.480 kN/m 2.480 kN/m 0.930 kN/m 2.480 kN/m 0.930 kN/m
0.930 kN/m
2.480 kN/m 0.930 kN/m 3.100 kN/m 0.930 kN/m
3.100
2.480kN/m 0.930 kN/m 2.480 kN/m0.930 kN/m 0.930 kN/m kN/m
3.100
2.480kN/m
kN/m
kN/m0.930 kN/m 3.100 kN/m 0.930 kN/m 2.480 kN/m 0.930 kN/m 0.930 0.930
kN/m
0.930 kN/m 2.480 kN/m 2.480 kN/m 0.930 kN/m 0.930 kN/m
0.930 kN/m
0.930 kN/m 0.930 kN/m
3.100
2.480kN/m
kN/m 0.930 kN/m 2.480 kN/m 0.930 kN/m 0.930 kN/m 2.300 kN/m
3.100 kN/m 0.930 kN/m
3.100 kN/m
2.480 kN/m
2.480 kN/m 0.930 kN/m 2.480 kN/m 0.930 kN/m 0.930 kN/m 2.300 kN/m
3.100
2.480kN/m
kN/m 0.930 kN/m 2.480 kN/m0.930 kN/m 0.930 kN/m
3.100
2.480kN/m 0.930 kN/m 0.930 0.930
kN/m kN/m
kN/m
0.930 kN/m 2.480 kN/m 0.930 kN/m 0.930 kN/m 2.300 kN/m
0.930 kN/m 0.930 kN/m
2.480 kN/m 0.930 kN/m 0.930 kN/m 2.300 kN/m 1.150 kN/m
0.930 kN/m 1.150 kN/m
2.480 kN/m0.930 kN/m 0.930 kN/m
0.930 kN/m 2.300 kN/m 1.150 kN/m
2.480 kN/m 1.150 kN/m
2.480 kN/m 0.930 kN/m 0.930 kN/m
2.480 kN/m 0.930 kN/m 0.930 kN/m
0.930 kN/m 0.930 kN/m 1.150 kN/m
0.930 kN/m 0.930 kN/m 2.300 kN/m
0.930 0.930 kN/m
kN/m 1.150 kN/m
0.930 kN/m
0.930 kN/m 2.300 kN/m 1.150 kN/m
0.930 0.930
kN/m kN/m
0.930 0.930
kN/m kN/m 2.300 kN/m
0.930 kN/m
2.300 kN/m 1.150 kN/m
2.300 kN/m 1.150 kN/m
Y 1.150 kN/m
X 1.150 kN/m
Z 1.150 kN/m Load 3
1.150 kN/m
1.150 kN/m

WL-1

Print Time/Date: 05/11/2017 22:52 STAAD.Pro V8i (SELECTseries 6) 20.07.11.50 Print Run 9 of 10
Job No Sheet No Rev
10
Part
Software licensed to
Job Title Ref

By PSK Date14-Oct-17 Chd

Client File Facade Design.std Date/Time 05-Nov-2017 22:48

-0.930 kN/m
-0.930 kN/m
-2.480
-0.930 kN/m
-2.480 -3.100kN/m
kN/m kN/m
-0.930 kN/m -2.480 kN/m
-3.100 kN/m
-3.100-0.930
kN/m kN/m
-0.930 kN/m -2.480
-3.100kN/m
-0.930
kN/m kN/m
kN/m-2.480
-0.930
-2.480 -3.100kN/m
kN/m kN/m
-0.930 kN/m -2.480
-3.100kN/m
-0.930 kN/m
kN/m -2.480 kN/m
-3.100 kN/m
-0.930 kN/m -2.480 -3.100
kN/m kN/m
-2.480
-3.100kN/m
-0.930 kN/m -3.100 kN/m
kN/m
-0.930 kN/m-2.480
-3.100 kN/m
kN/m -0.930 kN/m
-0.930 kN/m-2.480 kN/m -0.930 kN/m -2.480
-3.100kN/m
kN/m -0.930 kN/m
-0.930 kN/m -3.100
-0.930
kN/mkN/m-2.480 -0.930 kN/m -2.480
-3.100kN/m
-2.480
-3.100kN/m
-0.930
kN/m kN/m -2.480 -3.100kN/m
kN/m kN/m -0.930 kN/m -2.480
-2.480 kN/m
-3.100 kN/m
kN/m
kN/m
-2.480
-0.930 kN/m -3.100 kN/m
kN/m -3.100 kN/m -3.100 kN/m
-0.930 kN/m-2.480 kN/m -0.930 kN/m -2.480 kN/m
-3.100 kN/m
-0.930 kN/m -2.480 -3.100 kN/m
-3.100kN/m
-0.930 kN/m
kN/m -2.480
-3.100kN/m -0.930 kN/m -2.480 -0.930 kN/m
-0.930 kN/m-2.480 kN/m -2.480 kN/m kN/m -3.100kN/m
kN/m -0.930 kN/m
-0.930 kN/m -0.930
-3.100 kN/m kN/m -3.100 kN/m -0.930 kN/m
-2.480 kN/m -0.930 kN/m -2.480 kN/m
-0.930 kN/m -2.480
-2.480 kN/mkN/m -2.480 kN/m -0.930 kN/m -2.480 -3.100
kN/m kN/m -0.930 kN/m -2.480
-2.480 kN/mkN/m
-0.930 kN/m -3.100
-3.100 kN/m kN/m
-0.930 kN/m -3.100 kN/m -3.100 kN/m -0.930 kN/m
-2.480
-3.100 kN/m
-0.930
kN/m kN/m -0.930 kN/m -2.480 kN/m -0.930 kN/m -2.480 kN/m
-0.930 kN/m
-0.930 kN/m
-2.480 kN/m -2.480
-0.930 kN/m -3.100 kN/m kN/m -3.100 kN/m -0.930 kN/m
-3.100
-0.930kN/m -0.930 kN/m-2.480 -0.930 kN/m
-0.930 kN/m
kN/m -2.480
-2.480
-3.100 kN/m
-3.100 kN/m
kN/mkN/m -2.480 -3.100kN/m
kN/m kN/m -0.930 kN/m -2.480 kN/m -0.930 kN/m
-0.930 kN/m
-2.480 -0.930 kN/m -3.100 kN/m -0.930 kN/m -0.930 kN/m
-2.480 -3.100kN/mkN/m -2.480 kN/m
-0.930 kN/m
-3.100kN/m
kN/m -0.930 kN/m -2.480
-3.100kN/m
kN/m -0.930 kN/m-2.480 kN/m -0.930 kN/m
-0.930 kN/m -0.930 kN/m -2.480 kN/m -0.930 kN/m -2.300 kN/m
-0.930 kN/m -2.480-3.100kN/m
kN/m -0.930 kN/m -0.930-0.930
kN/m kN/m
-0.930 kN/m -2.480
-2.480 kN/mkN/m -2.480-0.930
kN/m kN/m
-0.930 kN/m -2.300 kN/m
-3.100 kN/m
-0.930 kN/m-2.480 -3.100 kN/m -0.930 kN/m -2.480 kN/m-0.930 kN/m
-2.480 -3.100kN/mkN/m -0.930 kN/m -1.150 kN/m
-3.100kN/m
kN/m -0.930 kN/m -2.480 kN/m -0.930-0.930
kN/m kN/m -2.300 kN/m -1.150
-1.150 kN/m kN/m
-0.930 kN/m-2.480 kN/m -0.930 kN/m -1.150 kN/m
-0.930 kN/m -0.930 kN/m -2.300 kN/m
-0.930 kN/m -2.480
-2.480 kN/mkN/m -0.930 kN/m -2.300 kN/m -1.150 kN/m
-0.930 kN/m -0.930 kN/m
-2.480-0.930
kN/m kN/m
-0.930 kN/m
-2.480 kN/m-0.930 kN/m -1.150 kN/m
-0.930-0.930-0.930
kN/m kN/mkN/m -1.150 kN/m
-0.930-0.930
kN/m kN/m -2.300 kN/m
-0.930 kN/m -2.300 kN/m
-2.300 kN/m -1.150 kN/m
Y
X -2.300 kN/m -1.150 kN/m
Z -1.150 kN/m Load 4
-2.300 kN/m
-1.150
-1.150 kN/m kN/m
-1.150 kN/m
-1.150 kN/m
WL-2

Print Time/Date: 05/11/2017 22:52 STAAD.Pro V8i (SELECTseries 6) 20.07.11.50 Print Run 10 of 10

Vous aimerez peut-être aussi