X AS3500.5.

2012
4.10 Note: drains should be
located externally to the building
wherever practicable.

If X exceeds 1000mm
all junctions need
All Lagging = 40mm thick in H2+ class soils expansions joints/swivels
as per AS 2870-2011 Clause 5.6.4 (a)
SWIVEL JOINT
(with 50mm Expansion)
IO breakage protection
X Product Code:
EXPANDA Joints on all Insert Footing
SJ10015
Firm clay
horizontal Drains to help
maintain the pipe line. Drain
(Code: DW 100150) Trench
Additional Pier depth
under Footings that
align a trench, allows
Pier the trench to be closer
without undermining
concerns. Use the
45º correct Angle of
Repose per soils.
Back fill as per
AS 2870-2011
Ground Level

=Y
All Footing penetrations in middle of edge beam thickness. Add another Joint if pipe
Ensure Trench does exceeds 6 mtrs.in length
not remove support
from footings.
Please refer to Storm Plastics Table No. SP -1 for additional details on flow gradients and installation
(See insert above)
Drawing No.SP 101A LAGGED PIPEWORK ON 45 Deg SYSTEM NOT DRAWN TO SCALE
Y = 45 deg for Firm CLAYS
Y = 30 deg for SAND
SOIL
CLASSIFICATION
Class E - Strip Footings with stumps or pads
For further clarification 75 + mm Differential Movement
and other soil types Residential Installation Guide ONLY for use of
see Clause/Figure 4.15.2 AS 2870-2011 Mechanical Expansions Joints in Reactive Soils.
AS/NZS 3500.5 2012.
COMPANY STORM PLASTICS (SA) Pty Ltd
Manufactured under a quality system certified GRADE 1:40 (250mm Fall in 10 Mtrs)
as complying with ISO 9001 by an accredited
WP Trentini
certification body PIPE MATERIAL Poly Vinyl Chloride - PVC May 2014 v 2