PROYECTO: LINEA DE TRANSMISIÓN ELECTRICA ANILLO ENERGÉTICO DEL SUR 230 KV PAMPAGRANDE - CENIZAPAMPA

PLAN DE TENDIDO #1. CONDUCTOR TIPO FLINT

ACUMULADO EN
Numeración Plaqueta Torre NH-227 NH-228 NH-229 NH-230 NH-231 NH-232 NH-233 NH-234 NH-235 NH-236 NH-237 NH-238 NH-239 NH-240 NH-241 METROS

Vano Horizontal (m) 361.81 370.78 528.05 529.00 499.73 362.24 490.88 506.23 472.07 412.81 555.11 448.36 393.36 518.17 6,448.59
Desnivel entre alturas TORRE -4.50 -4.70 3.20 1.50 10.50 -12.00 1.50 4.50 4.50 -7.50 4.50 3.00 1.50 4.50
Catenaria (m) - FLINT 10.00 364.37 373.41 531.75 532.70 503.34 364.97 494.31 509.79 475.40 415.76 559.02 451.51 396.12 521.82 10.00 6,514.27
Long. Acumulada (m) - FLINT 374.37 747.78 1,279.53 1,812.23 2,315.57 2,680.54 3,174.86 3,684.65 4,160.05 4,575.81 5,134.83 5,586.34 5,982.45 6,504.27 6,514.27

EMPALMES FLINT 140.4 233.0 339.8 170.0 #REF!

515 3,000 3,000


FASE: C1 -
FASE: B1 -
FASE: A1 -

OBSTACULOS:

FRENO HIDRAULICO PULLER HIDRAULICO

NUMERO DE TORRE: NH-227 NH-228 NH-229 NH-230 NH-231 NH-232 NH-233 NH-234 NH-235 NH-236 NH-237 NH-238 NH-239 NH-240 NH-241
TIPO DE TORRE: T SL SP SL SL SL SL SL SL SL SL SL SL SL T

LONG TOTAL DE TENDIDO: 6.45 [km] horizontal

DATOS DEL CONDUCTOR: BOBINAS Nº 1 : BOBINAS Nº 2 : BOBINAS Nº 3 : SIMBOLOGÍA

TIPO: AAAC 740,8 MCM. 25,16mm FASE LARGO. (m) APLIC (m) SOBRA (m) N° Bobina FASE LARGO. (m) APLIC (m) SOBRA (m) N° Bobina FASE LARGO. (m) APLIC (m) SOBRA (m) N° Bobina

PESO UNITARIO: 1.0146 kg/m C1 - INF 3000.00 3000.00 0.00 C1 - INF 3000.00 3000.00 0.00 C1 - INF 3000.00 1605.00 1395.00 PULLER HIDRAULICO
TENSION MAXIMA SERV: B1 - INT 3000.00 3000.00 0.00 B1 - INT 3000.00 3000.00 0.00 B1 - INT 3000.00 1605.00 1395.00
TENSION DE RUPTURA: A1 - SUP 3000.00 3000.00 0.00 A1 - SUP 3000.00 3000.00 0.00 A1 - SUP 3000.00 1605.00 1395.00 FRENO HIDRAULICO
BOBINAS Nº 4 : BOBINAS Nº 5 : BOBINAS Nº 6 :
C1 - INF 0.00 C1 - INF 0.00 C1 - INF 0.00 GRAMPA TERMINAL (AMARRE)
B1 - INT 0.00 B1 - INT 0.00 B1 - INT 0.00
A1 - SUP 0.00 A1 - SUP 0.00 A1 - SUP 0.00 EMPALME TIPO PREFORME
OBSERVACIONES:
BOBINAS FLINT NUEVAS

PARA LOS CRUCES DE CAMINO Y LINEAS ELECTRICAS SE INSTALARAN PORTICOS.

............................................................. .............................................................
RESIDENTE DE TENDIDO SUPERVISOR
ENDE S&C S.A.
TENDIDO LINEA LA BELGICA - LOS TRONCOS 230kV, Tramo III
LISTADO DE EMPALMES Y PASTA PENETROX INSTALADOS POR PLANES DE TENDIDO

Pasta
Empalme Penetrox
(Pza) (Gr)
PLAN 1 12 100
PLAN 2 6 100
PLAN 3 18 170
PLAN 4 6 100
PLAN 5 6 100
PLAN 6 0 30
TOTAL 48 600

Ing. Edgar Castro Orellana Ing. Nelson Quispe C.


Residente de Obra Supervisor de Obra
SERVICIOS ALAVI ENDE Servicios y Construcciones S.A.
TENDIDO DE CONDUCTORES PORYECTO AMPLIACION SEGUNDA TERNA LINEA DE TRANSMISION LA BELGICA - LOS TRONCOS 230kV, TRAMO III, CONTRATO N° 253 / 2019

PLAN DE TENDIDO #1. CONDUCTOR TIPO FLINT


ACUMULADO
Numeración Plaqueta Torre PT-146 PT-147 PT-148 PT-149 PT-150 PT-151 PT-152 PT-153 PT-154 PT-155 PT-156 PT-157 PT-158 PT-159 PT-160 EN METROS

Vano Horizontal (m) 375.94 570.00 401.65 474.07 481.07 478.89 480.89 480.88 445.70 496.29 494.72 500.61 504.48 487.38 6,672.57
Desnivel entre alturas TORRE 10.83 0.17 -7.93 -3.69 1.41 -1.61 2.99 -3.10 0.21 4.00 -0.47 2.35 2.70 -5.09

Catenaria (m) - FLINT 10.00 377.98 572.85 403.74 476.45 483.48 481.29 483.30 483.29 447.93 498.79 497.19 503.12 507.01 489.84 10.00 6,726.26
Long. Acumulada (m) - FLINT 387.98 960.83 1,364.56 1,841.02 2,324.50 2,805.78 3,289.09 3,772.38 4,220.31 4,719.10 5,216.29 5,719.41 6,226.42 6,716.26

EMPALMES FLINT 194.2 289.1 280.6 226.4

3,000.0 3000.0 726.3


FASE: A
FASE: B
FASE: C

CAMINO, LINEA CAMINO, LINEA


OBSTACULOS: TRIFASICA
CAMINO MONOFASICA
CAMINO 2 CAMINOS CAMINO 2 CAMINOS

PULLER HIDRAULICO FRENO HIDRAULICO

NUMERO DE TORRE: PT-146 PT-147 PT-148 PT-149 PT-150 PT-151 PT-152 PT-153 PT-154 PT-155 PT-156 PT-157 PT-158 PT-159 PT-160
TIPO DE TORRE: 2a2 2s1 2s1 2s1 2s1 2s1 2s1 2s1 2s1 2s1 2s1 2s1 2s1 2s1 2a2

LONG TOTAL DE TENDIDO: 6672.57 [m] horizontal

DATOS DEL CONDUCTOR: SIMBOLOGÍA


BOBINA FLINT LANZADA Nº: 1 BOBINA FLINT LANZADA Nº: 2 BOBINA FLINT LANZADA Nº: 3
TIPO: AAAC 740,8 MCM. 25,16mm PULLER HIDRAULICO
PESO UNITARIO: 1.0146 kg/m FASE LARGO. (m) APLIC (m) SOBRA (m) N° Bobina FASE LARGO. (m) APLIC (m) SOBRA (m) N° Bobina FASE LARGO. (m) APLIC (m) SOBRA (m) N° Bobina
"A" INTERNA 3,000.00 3,000.00 0.00 150 "A" INTERNA 3,000.00 3,000.00 0.00 166 "A" INTERNA 3,000.00 727.10 2272.90 48 FRENO HIDRAULICO
"A" EXTERNA 3,000.00 3,000.00 0.00 9 "A" EXTERNA 3,000.00 3,000.00 0.00 140 "A" EXTERNA 3,000.00 727.10 2272.90 130
"B" INTERNA 3,000.00 3,000.00 0.00 147 "B" INTERNA 3,000.00 3,000.00 0.00 71 "B" INTERNA 2,272.90 727.10 1545.80 48 GRAMPA TERMINAL
"B" EXTERNA 3,000.00 3,000.00 0.00 162 "B" EXTERNA 3,000.00 3,000.00 0.00 58 "B" EXTERNA 2,272.90 727.10 1545.80 130
"C" INTERNA 3,000.00 3,000.00 0.00 88 "C" INTERNA 3,000.00 3,000.00 0.00 24 "C" INTERNA 1,545.80 727.10 818.70 48 EMPALME TIPO PREFORME
"C" EXTERNA 3,000.00 3,000.00 0.00 40 "C" EXTERNA 3,000.00 3,000.00 0.00 143 "C" EXTERNA 1,545.80 727.10 818.70 130 PARA FLINT
OBSERVACIONES:
SE INSTALARON 14 BOBINAS FLINT NUEVAS Y 4 SOBRAS DE BOBINAS FLINT.

Ing. Edgar Joaquín Castro Orellana Ing. Nelson Quispe C.


Residente de Obra Supervisor de Obra
Servicios ALAVI ENDE Servicios y Construcciones S.A.
TENDIDO DE CONDUCTORES PORYECTO AMPLIACION SEGUNDA TERNA LINEA DE TRANSMISION LA BELGICA - LOS TRONCOS 230kV
TRAMO III, CONTRATO N° 253 / 2019
PLAN DE TENDIDO #2. CONDUCTOR TIPO FLINT
ACUMULADO
Numeración Plaqueta Torre PT-160 PT-161 PT-162 PT-163 PT-164 PT-165 PT-166 PT-167 PT-168 PT-169 PT-170 PT-171 PT-172 EN METROS

Vano Horizontal (m) 486.72 502.00 490.15 512.85 447.48 459.52 478.00 398.12 376.87 469.34 508.73 233.87 5,363.65
Desnivel entre alturas TORRE 6.03 -4.54 4.42 0.44 -5.13 4.60 -2.83 -8.49 7.09 5.28 0.62 -10.45
Catenaria (m) - FLINT 10.00 489.19 504.53 492.62 515.41 449.75 461.84 480.40 400.20 378.82 471.72 511.27 235.27 10.00 5,411.03
Long. Acumulada (m) - FLINT 499.19 1,003.72 1,496.34 2,011.76 2,461.50 2,923.34 3,403.74 3,803.94 4,182.77 4,654.48 5,165.76 5,401.03

EMPALMES FLINT 76.7 403.7

3,000.0 2411.0
FASE: A
FASE: B
FASE: C

CAMINO,
CAMINO,
OBSTACULOS: LINEA
CRUCE DE RIO
CAMINO
MONOFASICA

FRENO HIDRAULICO PULLER HIDRAULICO

NUMERO DE TORRE: PT-160 PT-161 PT-162 PT-163 PT-164 PT-165 PT-166 PT-167 PT-168 PT-169 PT-170 PT-171 PT-172
TIPO DE TORRE: 2a2 2s1 2s1 2s1 2s1 2a2 2s1 2s1 2a2 2s1 2s1 2s1 2a2

LONG TOTAL DE TENDIDO: 5363.65 [m] horizontal

DATOS DEL CONDUCTOR: SIMBOLOGÍA


BOBINA FLINT LANZADA Nº: 1 BOBINA FLINT LANZADA Nº: 2
TIPO: AAAC 740,8 MCM. 25,16mm PULLER HIDRAULICO
PESO UNITARIO: 1.0146 kg/m FASE LARGO. (m) APLIC (m) SOBRA (m) N° Bobina FASE LARGO. (m) APLIC (m) SOBRA (m) N° Bobina
"A" INTERNA 2,960.00 2,411.00 549.00 50 "A" INTERNA 3,000.00 3,000.00 0.00 19 FRENO HIDRAULICO
"A" EXTERNA 2,960.00 2,411.00 549.00 138 "A" EXTERNA 3,000.00 3,000.00 0.00 119
"B" INTERNA 3,000.00 2,411.00 589.00 25 "B" INTERNA 3,000.00 3,000.00 0.00 7 GRAMPA TERMINAL
"B" EXTERNA 3,000.00 2,411.00 589.00 149 "B" EXTERNA 3,000.00 3,000.00 0.00 67
"C" INTERNA 3,000.00 2,411.00 589.00 183 "C" INTERNA 3,000.00 3,000.00 0.00 191 EMPALME TIPO PREFORME
"C" EXTERNA 3,000.00 2,411.00 589.00 132 "C" EXTERNA 3,000.00 3,000.00 0.00 3 PARA FLINT
OBSERVACIONES:
SE INSTALARON 12 BOBINAS FLINT NUEVAS.

Ing. Edgar Joaquín Castro Orellana Ing. Nelson Quispe C.


Residente de Obra Supervisor de Obra
Servicios ALAVI ENDE Servicios y Construcciones S.A.
TENDIDO DE CONDUCTORES PORYECTO AMPLIACION SEGUNDA TERNA LINEA DE TRANSMISION LA BELGICA - LOS TRONCOS 230kV, TRAMO III, CONTRATO N° 253 / 2019

PLAN DE TENDIDO #3. CONDUCTOR TIPO FLINT

ACUMULADO
Numeración Plaqueta Torre PT-176 PT-177 PT-178 PT-179 PT-180 PT-181 PT-182 PT-183 PT-184 PT-185 PT-186 PT-187 PT-188 PT-189 PT-190 PT-191 PT-192 EN METROS

Vano Horizontal (m) 417.81 369.23 411.92 408.27 516.34 493.34 513.00 501.00 508.74 479.20 504.89 475.52 481.01 477.06 458.44 464.59 7,480.36
Desnivel entre alturas TORRE -12.00 -1.12 1.89 7.31 1.06 -0.02 -3.02 9.22 -11.22 5.78 -1.34 -6.82 8.21 -7.46 4.10 -3.71 58.11

Catenaria (m) - FLINT 10.00 420.07 371.08 413.98 410.38 518.92 495.81 515.57 503.59 511.41 481.63 507.42 477.95 483.49 479.50 460.75 466.93 10.00 7,538.47

Long. Acumulada (m) - FLINT 430.07 801.15 1,215.13 1,625.51 2,144.43 2,640.24 3,155.81 3,659.40 4,170.81 4,652.44 5,159.86 5,637.81 6,121.29 6,600.80 7,061.55 7,528.47

EMPALMES FLINT 359.8 155.8 362.4 121.1 386.7 74.1

3,000.0 3000.2 987.3 551.0


FASE: A
FASE: B

EMPALMES FLINT 360.5 155.1 361.8 121.7 416.7 44.1

3,000.7 2998.9 1017.9 521.0

FASE: C
OBSTACULOS: CAMINO CAMINO CAMINO CAMINO

PULLER HIDRAULICO FRENO HIDRAULICO

NUMERO DE TORRE: PT-176 PT-177 PT-178 PT-179 PT-180 PT-181 PT-182 PT-183 PT-184 PT-185 PT-186 PT-187 PT-188 PT-189 PT-190 PT-191 PT-192
TIPO DE TORRE: 2a2 2s1 2s1 2s1 2a2 2s1 2s1 2s1 2s1 2a2 2s1 2s1 2s1 2s1 2s1 2s1 2a2

LONG TOTAL DE TENDIDO: 7480.36 [m] horizontal

DATOS DEL CONDUCTOR: SIMBOLOGÍA


BOBINA FLINT LANZADA Nº: 1 BOBINA FLINT LANZADA Nº: 2 BOBINA FLINT LANZADA Nº: 3 BOBINA FLINT LANZADA Nº: 4
TIPO: AAAC 740,8 MCM. 25,16mm PULLER HIDRAULICO
PESO UNITARIO: 1.0146 kg/m FASE LARGO. (m) APLIC (m) SOBRA (m) N° Bobina FASE LARGO. (m) APLIC (m) SOBRA (m) N° Bobina FASE LARGO. (m) APLIC (m) SOBRA (m) N° Bobina FASE LARGO. (m) APLIC (m) SOBRA (m) N° Bobina
"A" INTERNA 3,000.00 3,000.00 0.00 115 "A" INTERNA 3,000.00 3,000.00 0.00 22 "A" INTERNA 3,000.00 987.20 2012.80 114 "A" INTERNA 580.00 551.00 29.00 149 FRENO HIDRAULICO
"A" EXTERNA 3,000.00 3,000.00 0.00 139 "A" EXTERNA 3,000.00 3,000.00 0.00 181 "A" EXTERNA 3,000.00 987.20 2012.80 120 "A" EXTERNA 580.00 551.00 29.00 183
"B" INTERNA 3,000.00 3,000.00 0.00 18 "B" INTERNA 3,000.00 3,000.00 0.00 216 "B" INTERNA 2,012.80 987.20 1025.60 114 "B" INTERNA 580.00 551.00 29.00 132 GRAMPA TERMINAL
"B" EXTERNA 3,000.00 3,000.00 0.00 187 "B" EXTERNA 3,000.00 3,000.00 0.00 136 "B" EXTERNA 2,012.80 987.20 1025.60 120 "B" EXTERNA 580.00 551.00 29.00 25
"C" INTERNA 3,000.00 3,000.00 0.00 110 "C" INTERNA 3,000.00 3,000.00 0.00 178 "C" INTERNA 1,025.60 1,017.20 8.40 114 "C" INTERNA 540.00 521.00 19.00 50 EMPALME TIPO PREFORME
"C" EXTERNA 3,000.00 3,000.00 0.00 97 "C" EXTERNA 3,000.00 3,000.00 0.00 103 "C" EXTERNA 1,025.60 1,017.20 8.40 120 "C" EXTERNA 540.00 521.00 19.00 138 PARA FLINT
OBSERVACIONES:
SE INSTALARON 14 BOBINAS FLINT NUEVAS Y SE INSTALARON 10 SOBRAS DE BOBINA DE CONDUCTOR FLINT.

Ing. Edgar Joaquín Castro Orellana Ing. Nelson Quispe C.


Residente de Obra Supervisor de Obra
Servicios ALAVI ENDE Servicios y Construcciones S.A.
PROYECTO: AMPLIACION SEGUNDA TERNA LINEA DE TRANSMISION LA BELGICA - LOS TRONCOS 230kV, TRAMO III

PLAN DE TENDIDO #4. CONDUCTOR TIPO FLINT


ACUMULADO
Numeración Plaqueta Torre PT-192 PT-193 PT-194 PT-195 PT-196 PT-197 PT-198 PT-199 PT-200 PT-201 PT-202 PT-203 EN METROS

Vano Horizontal (m) 467.85 480.47 409.90 417.72 481.46 494.31 454.17 467.49 509.61 470.91 474.23 5,128.12

Desnivel entre alturas TORRE 2.81 -2.24 -6.58 3.79 4.48 -1.65 -4.99 7.40 -3.44 0.85 -3.51

Catenaria (m) - FLINT 10.00 470.20 482.88 412.00 419.83 483.89 496.78 456.47 469.89 512.17 473.27 476.61 10.00 5,173.98

Long. Acumulada (m) - FLINT 480.20 963.08 1,375.08 1,794.90 2,278.79 2,775.58 3,232.04 3,701.93 4,214.10 4,687.37 5,163.98

EMPALMES FLINT 379.1 104.8

2,174.0 3000.0
FASE: A
FASE: B
FASE: C

2 CAMINOS,
LINEA
OBSTACULOS: TRIFASICA,
ACOMETIDA

FRENO HIDRAULICO PULLER HIDRAULICO

NUMERO DE TORRE: PT-192 PT-193 PT-194 PT-195 PT-196 PT-197 PT-198 PT-199 PT-200 PT-201 PT-202 PT-203
TIPO DE TORRE: 2a2 2s1 2s1 2s1 2s1 2s1 2s1 2s1 2s1 2s1 2s1 2a2

LONG TOTAL DE TENDIDO: 5128.12 [m] horizontal

DATOS DEL CONDUCTOR: SIMBOLOGÍA


BOBINA FLINT LANZADA Nº: 1 BOBINA FLINT LANZADA Nº: 2
TIPO: AAAC 740,8 MCM. 25,16mm PULLER HIDRAULICO
PESO UNITARIO: 1.0146 kg/m FASE LARGO. (m) APLIC (m) SOBRA (m) N° Bobina FASE LARGO. (m) APLIC (m) SOBRA (m) N° Bobina
SUP INTER 3,000.00 3,000.00 0.00 134 SUP INTER 2,600.00 2,174.00 426.00 141 FRENO HIDRAULICO
SUP EXTER 3,000.00 3,000.00 0.00 172 SUP EXTER 2,600.00 2,174.00 426.00 108
MEDIA INTER 3,000.00 3,000.00 0.00 26 MEDIA INTER 2,600.00 2,174.00 426.00 128 GRAMPA TERMINAL
MEDIA EXTER 3,000.00 3,000.00 0.00 170 MEDIA EXTER 2,600.00 2,174.00 426.00 195
INF INTER 3,000.00 3,000.00 0.00 73 INF INTER 2,600.00 2,174.00 426.00 44 EMPALME TIPO PREFORME
INF EXTER 3,000.00 3,000.00 0.00 176 INF EXTER 2,600.00 2,174.00 426.00 64 PARA FLINT
OBSERVACIONES:
SE INSTALARON 6 BOBINAS FLINT NUEVAS Y SE INSTALARON 12 SOBRAS DE BOBINA DE CONDUCTOR FLINT.

Ing. Joaquín Castro O. Ing. Nelson Quispe


Residente de Obra Supervisor de Obra
Servicios ALAVI ENDE Servicios y Construcciones S.A.
PROYECTO: AMPLIACION SEGUNDA TERNA LINEA DE TRANSMISION LA BELGICA - LOS TRONCOS 230kV, TRAMO III

PLAN DE TENDIDO #5. CONDUCTOR TIPO FLINT


ACUMULADO
Numeración Plaqueta Torre PT-203 PT-204 PT-205 PT-206 PT-207 PT-208 PT-209 PT-210 PT-211 PT-212 EN METROS

Vano Horizontal (m) 436.01 461.70 415.25 441.89 493.17 416.12 401.67 419.31 423.90 3,909.02
Desnivel entre alturas TORRE 7.53 -11.55 0.68 4.16 0.89 -10.23 8.19 -5.12 1.89
Catenaria (m) - FLINT 10.00 438.26 464.15 417.33 444.12 495.64 418.33 403.76 421.44 426.02 10.00 3,949.04
Long. Acumulada (m) - FLINT 448.26 912.41 1,329.74 1,773.85 2,269.49 2,687.82 3,091.58 3,513.02 3,939.04

EMPALMES FLINT 56.6 360.7

969.0 2980.0
FASE: A
FASE: B
FASE: C

OBSTACULOS: CAMINO CAMINO CAMINO

FRENO HIDRAULICO PULLER HIDRAULICO

NUMERO DE TORRE: PT-203 PT-204 PT-205 PT-206 PT-207 PT-208 PT-209 PT-210 PT-211 PT-212
TIPO DE TORRE: 2a2 2s1 2s1 2s1 2s1 2s1 2a2 2s1 2s1 2a2

LONG TOTAL DE TENDIDO: 3909.02 [m] horizontal

DATOS DEL CONDUCTOR: SIMBOLOGÍA


BOBINA FLINT LANZADA Nº: 1 BOBINA FLINT LANZADA Nº: 2
TIPO: AAAC 740,8 MCM. 25,16mm PULLER HIDRAULICO
PESO UNITARIO: 1.0146 kg/m FASE LARGO. (m) APLIC (m) SOBRA (m) N° Bobina FASE LARGO. (m) APLIC (m) SOBRA (m) N° Bobina
SUP INTER 3,000.00 2,980.00 20.00 99 SUP INTER 3,000.00 969.00 2031.00 49 FRENO HIDRAULICO
SUP EXTER 3,000.00 2,980.00 20.00 43 SUP EXTER 3,000.00 969.00 2031.00 54
MEDIA INTER 3,000.00 2,980.00 20.00 154 MEDIA INTER 2,031.00 969.00 1062.00 49 GRAMPA TERMINAL
MEDIA EXTER 3,000.00 2,980.00 20.00 197 MEDIA EXTER 2,031.00 969.00 1062.00 54
INF INTER 3,000.00 2,980.00 20.00 63 INF INTER 1,062.00 969.00 93.00 49 EMPALME TIPO PREFORME
INF EXTER 3,000.00 2,980.00 20.00 100 INF EXTER 1,062.00 969.00 93.00 54 PARA FLINT
OBSERVACIONES:
SE INSTALARON 14 BOBINAS FLINT NUEVAS Y SE USARON 4 SOBRAS DE BOBINA DE CONDUCTOR FLINT.

Ing. Joaquín Castro O. Ing. Nelson Quispe


Residente de Obra Supervisor de Obra
Servicios ALAVI ENDE Servicios y Construcciones S.A.
PROYECTO: AMPLIACION SEGUNDA TERNA LINEA DE TRANSMISION LA BELGICA -
LOS TRONCOS 230kV, TRAMO III
PLAN DE TENDIDO #6. CONDUCTOR TIPO FLINT
ACUMULADO
Numeración Plaqueta Torre PT-212 PT-213 PT-214 PT-215 PT-216 EN METROS

Vano Horizontal (m) 419.85 398.56 404.48 348.47 1,571.36


Desnivel entre alturas TORRE

Catenaria (m) - FLINT 10.00 421.95 400.55 406.50 350.21 10.00 1,599.22
Long. Acumulada (m) - FLINT 431.95 832.50 1,239.00 1,589.22

EMPALMES FLINT

1,599.2
FASE: A
FASE: B
FASE: C

OBSTACULOS:

FRENO HIDRAULICO PULLER HIDRAULICO

NUMERO DE TORRE: PT-212 PT-213 PT-214 PT-215 PT-216 PORT TRON


TIPO DE TORRE: 2a2 2s1 2s1 2s1 2a2 PORT

LONG TOTAL DE TENDIDO: 1571.36 [m] horizontal

DATOS DEL CONDUCTOR: SIMBOLOGÍA


BOBINA FLINT LANZADA Nº: 1
TIPO: AAAC 740,8 MCM. 25,16mm PULLER HIDRAULICO
PESO UNITARIO: 1.0146 kg/m FASE LARGO. (m) APLIC (m) SOBRA (m) N° Bobina
SUP INTER 3,000.00 1,659.50 1340.50 FRENO HIDRAULICO
SUP EXTER 3,000.00 1,659.50 1340.50
MEDIA INTER 3,000.00 1,659.50 1340.50 GRAMPA TERMINAL
MEDIA EXTER 3,000.00 1,659.50 1340.50
INF INTER 3,000.00 1,659.50 1340.50 EMPALME TIPO PREFORME
INF EXTER 3,000.00 1,659.50 1340.50 PARA FLINT
OBSERVACIONES:
SE INSTALARON 6 BOBINAS FLINT NUEVAS.

Ing. Joaquín Castro O. Ing. Nelson Quispe


Residente de Obra Supervisor de Obra
Servicios ALAVI ENDE Servicios y Construcciones S.A.
PROYECTO: LINEA DE TRANSMISIÓN ELECTRICA ANILLO ENERGÉTICO DEL SUR 230 KV TORREHUAYCO - LITIO, TRAMO I - A
PLAN DE TENDIDO #4. CONDUCTOR TIPO FLINT E HILO DE GUARDA EHS

ACUMULADO
Numeración Plaqueta Torre PT-146 PT-147 PT-148 PT-149 PT-150 PT-151 PT-152 PT-153 PT-154 PT-155 PT-156 NH-350 port LIT EN METROS

Vano Horizontal (m) 552.03 586.97 438.25 235.70 715.37 275.28 457.15 479.43 327.61 348.35 319.48 75.00 4,810.62
Desnivel entre alturas TORRE 14.57 -43.76 -57.42 10.67 93.21 10.26 -1.21 -9.76 -3.83 0.32 -2.38 12.90 67.40

Catenaria (m) - FLINT 10.00 554.98 591.54 444.21 237.12 725.02 276.85 459.44 481.93 329.27 350.09 321.09 10.00 76.48 10.00 4,878.02
Long. Acumulada (m) - FLINT 564.98 1,156.53 1,600.73 1,837.85 2,562.88 2,839.72 3,299.16 3,781.09 4,110.36 4,460.45 4,781.54 4,868.02 4,878.02

EMPALMES FLINT 190.8 46.3

1791.5 3000.0 86.5


FASE: A
FASE: B
FASE: C

Catenaria (m) - EHS 10.00 554.98 591.54 444.21 237.12 725.02 276.85 459.44 481.93 329.27 350.09 321.09 10.00 76.48 10.00 4,878.02
Long. Acumulada (m) - EHS 564.98 1,156.53 1,600.73 1,837.85 2,562.88 2,839.72 3,299.16 3,781.09 4,110.36 4,460.45 4,781.54 4,858.02 4,868.02
EMPALMES EHS 226.6 364.9

791.6 4000.0 86.5


FASE: EHS

CARETERA
OBSTACULOS: PRINCIPAL -
LINEA
TRIFASICA

FRENO HIDRAULICO PULLER HIDRAULICO

NUMERO DE TORRE: NH-339 NH-340 NH-341 NH-342 NH-343 NH-344 NH-345 NH-346 NH-347 NH-348 NH-349 NH-350 port LIT
TIPO DE TORRE: DTF DTS DTT DTT DTT DTT DTT DTT DTF DTT DTT 2HAT port

LONG TOTAL DE TENDIDO: 4810.62 [m] horizontal

DATOS DEL CONDUCTOR: BOBINAS Nº 1 FLINT: BOBINAS Nº 2 FLINT: BOBINAS Nº 3 FLINT: (VANO FLOJO) SIMBOLOGÍA

TIPO: AAAC 740,8 MCM. 25,16mm FASE LARGO. (m) APLIC (m) SOBRA (m) N° Bobina FASE LARGO. (m) APLIC (m) SOBRA (m) N° Bobina FASE LARGO. (m) APLIC (m) SOBRA (m) N° Bobina

PESO UNITARIO: 1.0146 kg/m SUP INTER 3,000.00 3,000.00 0.00 443 / 690 SUP INTER 1,870.30 1,791.50 78.80 313 / 690 SUP INTER 543.10 86.50 456.60 278 / 690 PULLER HIDRAULICO
SUP EXTER 3,000.00 3,000.00 0.00 475 / 690 SUP EXTER 1,870.30 1,791.50 78.80 141 / 690 SUP EXTER 456.60 86.50 370.10 278 / 690
MEDIA INTER 3,000.00 3,000.00 0.00 461 / 690 MEDIA INTER 3,000.00 1,791.50 1208.50 535 / 690 MEDIA INTER 370.10 86.50 283.60 278 / 690 FRENO HIDRAULICO
MEDIA EXTER 3,000.00 3,000.00 0.00 572 / 690 MEDIA EXTER 3,000.00 1,791.50 1208.50 552 / 690 MEDIA EXTER 283.60 86.50 197.10 278 / 690
INF INTER 3,000.00 3,000.00 0.00 202 / 690 INF INTER 3,000.00 1,791.50 1208.50 290 / 690 INF INTER 197.10 86.50 110.60 278 / 690
INF EXTER 3,000.00 3,000.00 0.00 474 / 690 INF EXTER 3,000.00 1,791.50 1208.50 438 / 690 INF EXTER 110.60 86.50 24.10 278 / 690 GRAMPA TERMINAL
BOBINAS Nº 1 EHS : BOBINAS Nº 2 EHS : BOBINAS Nº 3 EHS : (VANO FLOJO)
FASE LARGO. (m) APLIC (m) SOBRA (m) N° Bobina FASE LARGO. (m) APLIC (m) SOBRA (m) N° Bobina FASE LARGO. (m) APLIC (m) SOBRA (m) N° Bobina EMPALME TIPO PREFORME
EHS 4,000.00 4,000.00 0.00 87 / 55 EHS 1,181.00 791.60 389.40 87 / 50 EHS 389.40 86.50 302.90 87 / 50 PARA FLINT O EHS
OBSERVACIONES:
SE INSTALARON 10 BOBINAS FLINT NUEVAS Y 2 SOBRAS DE BOBINAS FLINT, SE INSTALARON 1 BOBINA NUEVA EHS Y 2 SOBRAS DE BOBINAS EHS.

Ing. Eddy Fernandez Chambi Ing. Sergio Puñi Nina


Residente de Obra Supervisor de Obra
Servicios ALAVI ENDE Servicios y Construcciones S.A.

Vous aimerez peut-être aussi