Frequency

Monitoring
Relay
SP 320
WIRING EXAMPLE
(requires optional S3-B base) Application Examples
Link for start-up delay • Frequency supervision on AC generator sets.
• Over-frequency/under-frequency detection.
5
6
7
• Protection of frequency-sensitive equipment.
• Detection of over frequency on generator sets to prevent
4 8
overheating.
3 9

2 10
1 11

~ PowerACSupply ~
SUPPLY RELAY
TYPE VOLTAGE AC/DC CONTACTS
ORDERING
CODE SP320 / 240 AC S
SLIMLINE Note: 50Hz standard (60Hz, 400Hz on special order)

Technical Specification
Power Supply: Response:
Start-up delay: approx. 10 seconds standard (1 to 15
Supply voltage: 12, 24, 110, 240 (ie. 220-240), 380, seconds available on special order)
400, 415, 525 VAC ±15% Time delay on trip: 1 second (approx).

Supply frequency: 50Hz nominal (ie. 42Hz-58Hz) Frequency Sensing:


60Hz & 400Hz versions available on Repetitive accuracy: 1%
special order. Hysteresis: 0.5Hz fixed

Description of Controls
P1: The Over-frequency Threshold is LED 1:The red LED marked “Over-
SLIMLINE SP-320 adjusted on P1. speed” illuminates whenever
Frequency Monitor
P2: The Under-frequency Threshold is the frequency exceeds the
54 56 adjusted on P2. set over-frequency threshold.
Over-
speed
S1: With the function Selector Switch LED 2:The green LED marked
P1 the unit can be programmed to: “Relay ON” illuminates
52 58
- respond to over-frequency only when the relay is energised,
44 46
Under-
speed (S1 set to “OS”). ie. under normal frequency
- respond to under-frequency only conditions.
P2
42 48 (S1 set to “US”). LED 3:The red LED marked
- respond to both over-frequency “Under-speed” illuminates
LED 1 Over speed
as well as under-frequency
LED 2 Relay
OS
OS+US
whenever the frequency
ON US (S1 set to “OS + US”). drops below the set under-
LED 3 Under speed S1
frequency threshold.

Operational Diagrams
SP320 Frequency Monitoring without start-up delay SP320 Frequency Monitoring with start-up delay
Power Supply Power Supply

Over-frequency Over-frequency
Setpoint Setpoint
Hysteresis Supply Hysteresis Supply
Frequency Frequency
Hysteresis Hysteresis

Under-frequency Under-frequency
Setpoint Setpoint

10 sec
Relay On Relay On