Question details
800xA >
Operations (https://forum-
Comments (0) (javacript:void(0)) New comment (javacript:void(0))
controlsystems.abb.com/Topic/800xA/Ope
0 on the configuration wizard in the client --> on the system software user settings.
800xA >
System >
Backup, restore (https://forum-
check your system admin group name, system user group name are set properly and controlsystems.abb.com/Topic/800xA/Syst
(/Question/AnswerVote? restore/Documents/6046)
type the service account user name , password and apply the settings to start the
800xA (https://forum-
controlsystems.abb.com/Topic/800xA/Doc
services on the client. FO L LOW ( /ACCO U N T/ S U B S C R I B E ? C AT E G O
AKS experts
Comments (1) (javacript:void(0)) New comment (javacript:void(0))
If you retored a disk ... Ghost Backups are designed to restore the SAME node after a disk failure. This means that things
(/Question/AnswerVote?
like the Windows System ID (SID) etc remain unchanged. A restored computer should rejoin to the same domain with
relatively little trouble. You may need to run the AfwConfigWizard to set the Service Account names and passwords ( ie
answerId=56081&value=1)
the system settings) after a node is restored. That is what your AfwTrayIcon is telling you to do.
Flavio Mussolin (https://forum-
controlsystems.abb.com/Profile/Flavio
Mussolin/)
Rank: 4
If you actually "Copied" one computer to another using a Ghost image file, then there is a lot more work to do. A S K ( H T T P S : / / FO R U M - CO N T R O L SYST E M S
- The computer must be removed from then joined to the domain again.
( Sorry, I dont want to post on an open forum about how to mess with registry settings as this is potentially quite
dangerous. )
Ingo (https://forum-
controlsystems.abb.com/Profile/Ingo/)
A S K ( H T T P S : / / FO R U M - CO N T R O L SYST E M S
Rob Lyon (https://forum-controlsystems.abb.com/Profile/Rob Lyon/) Rank: 2 (https://forum-controlsystems.abb.com/Report/Submit/56081)
https://forum-controlsystems.abb.com/56000/operator-client-stopped
Answered 5 years ago 1/2
6/11/2019 operator client stopped (800xA Operations Display Operations System Administration & configuration Administration Backup, restore 800…
raudales (https://forum-
controlsystems.abb.com/Profile/raudales/
1 The domain controller is not reachable (possibly due to improper cloning) and/or System Software User Settings are
Rank: 20
stale need to be re-applied.
A S K ( H T T P S : / / FO R U M - CO N T R O L SYST E M S
(/Question/AnswerVote?
As already mentioned by others, there are a few mandatory measures required after cloning of one running computer
into another running computer:
answerId=56424&value=1)
- Change hostname Geof Ledin (https://forum-
controlsystems.abb.com/Profile/Geof
- Change IP-address Ledin/)
Rank: 42
- A duplicated SID is not critical to System 800xA, AFAIK.
A S K ( H T T P S : / / FO R U M - CO N T R O L SYST E M S
- Rejoin domain
*) The two latter ones is preferably done prior cloning. E.g. by "Disconnect" or "Remove" Client.
Titus (https://forum-
Cloning is not officially documented in any System 800xA User's Guide. controlsystems.abb.com/Profile/Titus/)
Rank: 6
/Stefan A S K ( H T T P S : / / FO R U M - CO N T R O L SYST E M S
https://forum-controlsystems.abb.com/56000/operator-client-stopped 2/2