Wind load study as per IS 875 Part 3

Roof Height 12 customer input


Basic Wind Speed , Vb 180kmph 50 m/s - Vizag
k1 0.9 25 years life clause 5.3.1
k2 0.97 Terrain cat 2; Building category C clause 5.3.2.2
k3 1 topography factor 5.3.3.1
k4 1 cyclone factor 5.3.4

Vz = Vb x k1 x k2 x k3 x k4 43.65 m/s

Wind Pressure, Pz = Vz x Vz x .6 = 1143.1935 N/m2

Net Wind pressure, Pn = Kd x Ka x Kc x Pz


Kd 0.9 wind directionality factor 5.4
Ka 1 area averaging factor 5.4.2 table 4
Kc 1 combination factor 6.2.3.13 table 19

Pn = 1028.87415 N/m2
Roof Tilt, α = 5 deg
h/W = 0.5 as per roof dimension
Pressure Coeffient, Cp = External Coeff, Cpe + Internal Coeff, Cpi
0 & 180 degree internal suction = -0.4 low permeability
EF = -0.9
GH = -0.4
Wind pressure on EF Side = -1337.536395 N/m2
Wind pressure on GH Side = -823.09932 N/m2 Wind, θ -->

90 & 270 degree internal Pressure = -0.4


EF = -0.8
GH = -0.4
Wind pressure on EF Side = -1234.64898 N/m2
Wind pressure on GH Side = -823.09932 N/m2
Max Wind pressure = -1337.536395 N/m2

Design Wind pressure = 1.4kN/m2


Panel Dimensions = 1.97 x .992m assumed
Wind Load per panel = 2.735936 kN
Wind Load on Mid Clamp = 1.367968 kN 1368N
139.4462793 kgf 140kgf
Bracket and Clamp have been simulated for higher wind pressure per bracket.