Vous êtes sur la page 1sur 3

Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

14 Accommodation

Design and construction of plant and


manifold rooms Note
It is permissible to accommodate medical compressed
Location of manifold rooms air plant, vacuum plant and AGS disposal system
14.1 Cylinder gas/liquid supply systems should not pumps in general plant areas accommodating such
be located in the same room as medical air equipment as air handling units, water service systems
compressors, PSA systems or vacuum plants. etc. They should not, however, be located with heating
or hot water service equipment or equipment likely to
14.2 Manifold rooms, emergency/reserve manifold produce any fumes or odour.
rooms for PSA systems, VIE installations and
medical compressed air systems should be located
Access
to take account of the risk assessment, but should
also take account of the location of the medical gas 14.7 Access to manifold rooms should be from the open
cylinder storage area. air, not from corridors or other rooms.
14.3 All manifolds, including the emergency reserve 14.8 Normal commercial lorry access is suitable for gas
manifolds, may be located within the same room. cylinder delivery vehicles, but consideration should
Manifold rooms should be located on an external be given to the provision of a raised level loading
wall(s) to facilitate ventilation, which will be bay to reduce cylinder handling hazards.
required at high and low level. Internally sited 14.9 Two doors should preferably be provided in a
manifold room and cylinder stores may require manifold room. One should be large enough to
mechanical ventilation. facilitate cylinder handling and must be in an
14.4 The emergency/reserve manifold for liquid oxygen outside wall. Exits must be free of all obstructions.
systems has traditionally been located within the Doors must open outwards. All doors must
VIE compound, but it is preferable to site the normally be locked to prevent unauthorised access,
manifold separately. For new installations, these but should be provided with means of entry and
emergency/reserve manifolds should be located exit in an emergency (for example by a push-bar
separately. arrangement on the inside).
14.5 In the case of surgical air the volume of gas used 14.10 Internal walls and ceilings, including any internal
is relatively small even though the instantaneous doors of the manifold room, should be of a suitable
flow rates are high. Therefore, it may be more non-combustible two-hour fire-resistant material as
convenient to include the manifold within the defined in BS 476-4:1970 and BS 476 Parts 20–23
operating department. (1987). Internal doors should be avoided where
practicable. Smoke detectors should be provided.
14.6 The surgical air 700 kPa manifold room may be
Automatic fire suppression should be considered.
used as the ready-use store for a small number of
Manifold rooms should not be located near high-
spare cylinders to be used on anaesthetic machines.
dependency wards.

114
14 Accommodation

Construction and layout of manifold rooms plantroom is deep-plan, mechanical ventilation


should be provided. The ambient temperature
14.11 The manifold room will contain the manifolds
of manifold rooms and plantrooms should be
as well as cylinder racks holding sufficient spare
maintained within the range of 10–40°C. The
cylinders to replace one bank of each manifold
ventilation rates should ensure that the plantroom
and the emergency/reserve manifold. (For nitrous
temperature does not exceed ambient temperature
oxide/oxygen manifolds, sufficient spare capacity
by more than 10°C.
for two banks of cylinders should be provided.)
Further replacement cylinders should be supplied 14.18 Manifold rooms may be used to store small
from the medical gas cylinder store. The size of the numbers of nitrous oxide/oxygen cylinders
manifold room should therefore be determined by intended for portable use; these are taken from the
the risk assessment. Adequate space should also be main cylinder store for the purpose of temperature
allowed for cylinder handling. equilibration, before being delivered to wards etc.
14.12 A typical automatic manifold with two duty and 14.19 To achieve temperature equilibration, additional
two stand-by cylinders is 1.8 m long and 0.6 m heating may be required; the natural ventilation
deep. One extra cylinder on each bank adds must not be reduced. Where such heating is
approximately 0.5 m to the overall length, so that provided, it should be by indirect means, for
a 2 x 6 manifold is approximately 4 m long. example steam, hot water or warm air. Naked
flames and exposed electric elements should not be
14.13 All medical gas manifolds may be installed in
used, and excessive surface temperature should be
the same room. Additional floor area should be
avoided. If necessary, cylinders should be protected
provided to accommodate separate storage racks
from excessive heat. Any primary heat source
for each gas. The racks should be designed along
should be located in a safe position, preferably
the lines of those on the manifolds, but the stored
remote from the manifold room.
cylinders may be closer together. Racks should
conform to ISO 32:1977. With the exception of 14.20 Cylinder recognition charts, supplied by the
small cylinders of N2O/O2 mixtures, under no medical gas supplier, should be prominently
circumstances should rooms contain gas cylinders displayed as appropriate.
other than those appropriate to their manifolds.
Lighting
Heating and ventilation
14.21 Manifold rooms should be provided with lighting
14.14 Ventilation louvres should be provided at both to an illumination level of 150 lux by means of
high and low level for all manifold rooms, to allow bulkhead lighting fittings to BS EN 60529:1992.
circulation of air. As a guide, separated openings Plantrooms other than manifold rooms should be
equivalent to at least 1.5% of the total area of the provided with a lighting level of 200 lux.
walls and floor should be provided. For example,
given a manifold room 5.0 x 4.0 x 2.4 m with a Noise control
total area of the walls and ceiling of 63.2 m2, the 14.22 Plantrooms should be designed and constructed to
total free open area for ventilation required is ensure the satisfactory control of noise emission.
1 m2. The effect of two vacuum pumps or compressors
14.15 Air intakes for compressor inlets should, if running together, in the case of duplex
possible, be located externally. However, they installations, and three or more in the case of
should not be installed as an alternative to the multiplex installations, will be to increase the free-
provision of adequate ventilation for cooling field noise level outside the plantroom by 5 dBA
purposes. for each additional pump or compressor operation
over and above the specified limits. Consideration
14.16 All ventilation louvres should be vermin/bird-
should be given to providing acoustic enclosures to
proof.
reduce the free-field noise levels in noise-sensitive
14.17 PSA and medical air compressors liberate, under areas adjacent to plantrooms.
maximum flow conditions, considerable heat.
14.23 Acoustic enclosure and/or plantroom design
Moreover, these plants aspirate air for breathing
must not inhibit normal cooling functions or
purposes. Generous natural ventilation should be
maintenance activities.
provided, and where this is not possible if the

115
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

14.24 Free-field noise levels should be given to the where necessary to prevent the transmission of
architect to assist in acoustic design of the noise and vibration along the pipelines and
plantrooms. conduits. Electrical bonding will be required.
14.25 The discharge from some vacuum pumps may
Labelling/signage
require silencing.
14.28 Labelling for medical gas systems, equipment and
14.26 Compressors and pumps should be mounted on
accommodation should be in accordance with
properly-selected anti-vibration mounting, where
Appendix K.
necessary, to minimise transfer of noise and
vibration to the structure of the building.
14.27 All pipework and electrical conduits connected to
the plant should be fitted with flexible connectors

116

Vous aimerez peut-être aussi