Vous êtes sur la page 1sur 30

Thursday, October 5

Freeze for less: energy cost reduction in industrial refrigeration 
Anatoli Naoumov, GreenQ Partners
Message to take home 
• 30% reduction of energy use  
is possible through a low/no capex  
whole plant optimization 

• No risk to operation, machines or  
relations with current refrigeration contractor 

• Scientifically solid and  
practically proven framework 

• $hort payback, incentives apply 

 
 GreenQ Partners © 2017  2 
What’s In It For Me if I do not own 
the plant? 
• Proven way to score praise, respect and recognition 
• Low risk to you: you stay in charge of changes 
• Professional satisfaction: gain more out of 
machines 
• Massive energy cost savings is a winning topic to 
brag about at a next conference or job interview 
 
 
GreenQ Partners © 2017  3 
Plan for the next 40 minutes 
WHAT: Plant optimization : Theory and example 
HOW: Project framework        
Results of completed project        
Q&A                
 

GreenQ Partners © 2017  4 
Component vs. whole plant 
optimization in refrigeration 
Component  Whole plant 
Analysis  Component consumption  Component and whole plant 
measurement  consumption measurement  
Whole plant consumption 
modelling 
Solution  Improve component  Improve whole plant performance 
focus  performance 
Reporting  Engineering calculation of  Savings are determined from 
assumed savings in assumed  measurement of actual whole 
conditions of separate  plant consumption with  
components  no engineering calculations 

Does your CFO understand engineering calculations? 

GreenQ Partners © 2017  5 
Plant optimization measures 
1. Reduce condensing pressure  Efficient operation is 
the key  
2. Optimize suction pressure  to savings 

3. Optimize hot gas defrosting schedule 
4. Add VFDs to motors where needed  
(and set them properly!) 

GreenQ Partners © 2017  6 
Science of industrial refrigeration 
efficiency 
“Lowering condensing pressure can provide up to 50% of total energy savings“.  
Russell U.K. 2005, “The Process of Optimizing and Fine Tuning Refrigeration Systems to 
Improve Efficiency and Lower Operating Costs”, IIAR Ammonia Refrigeration Conference 
Acapulco, Mexico, IIAR, Arlington 
 

“When suction pressure increases, parasitic (fan) load increases as well. There is 
point at which the additional parasitic power consumption exceeds the 
compressor power reduction”. 
Reindl, D.T., Jekel, T.B., Elleson, J.S., 2005, Industrial Refrigeration Energy Efficiency Guide 
book, Industrial Refrigeration Consortium – University of Wisconsin‐Madison. Madison, WI 

“Eliminating one unnecessary 20‐min defrosting per day will save 2% of energy use of the 
whole refrigeration plant.”  
Stoecker, W.F. 1998, Industrial Refrigeration Handbook, McGraw Hill publishers 

GreenQ Partners © 2017  7 
Papers by Sergei Khoudiachov 
Optimization of Refrigeration Plant Operation. Engineering Approach 

32nd Annual Meeting International Institute of Ammonia Refrigeration March 14–17, 2010 2010 Industrial 
Refrigeration Conference & Exhibition Manchester Grand Hyatt San Diego, California 
http://www.iiar.org/IIAR/WCM/IIAR_Publications/IIAR_Technical_Papers/2010_Technical_Pa
pers.aspx  

Operating Ammonia Refrigeration Systems At Peak Efficiency 

International institute of Refrigeration .Ammonia Refrigeration Technology. International Conference. 
Ohrid 2013 
http://toc.proceedings.com/18495webtoc.pdf  

GreenQ Partners © 2017  8 
1. Reduce condensing pressure:  
  massive opportunity 
3 psig reduction   1‐1.5% reduction  
      of the compressor energy use 
 
50 psig reduction at 400hp compressor  
       200MWh per year 
 
Reduction is part of floating  
Reduction saves 90‐95% of the floating savings 
 

GreenQ Partners © 2017  9 
1. Reduce condensing pressure:  
    barriers and solutions 
Barriers  Solutions 
Incomplete defrosting  Adjust valves, add pressure during defrosting 
Insufficient oil cooling of screw  Add small liquid pump or electronic valve 
compressors 
Insufficient liquid supply far from  Add ammonia pump or heat exchanger to sub‐
receiver  cool ammonia 
Increase regulating valve 
Oil carry over  Install oversized oil separator 

GreenQ Partners © 2017   10 
2. Optimize suction pressure 
1degF increase of  
suction pressure   Higher suction pressure  
   1‐2% decrease    more evaporators = more heat  
  at compressor use   compressor load increase  

Solution: accurate modelling to min total consumption 

GreenQ Partners © 2017  11 
3. Optimize defrosting schedule 
• Defrosting is routinely done on time schedule 

• An additional 20‐min defrosting per day  
= 2% of refrigeration plant energy use 

• Solution: To minimize energy use  
defrosting schedule should follow  
frost formation, not time. 

GreenQ Partners © 2017  12 
Economics of measures: example 
• Regional food 
distribution center  

• Compressors ‐ 800 hp 
evaporators  ‐ 112 hp 
condenser ‐ 25 hp 

• 3,000MWh per year 
($300K at $100/MWh)  

GreenQ Partners © 2017  13 
Example: energy savings 
Total Savings:     20% of use 
Energy savings (kWh/yr)  Low capex optimization  46% of total  
Add 
condenser 
Add VFD to  fan VFD 
screw  8% 
compressors  
15% 
Lower 
cond. 
Optimize  pressure 
suction  form 135 
pressure +  psig to 95 
evaporator  psig 
fans VFDs  31% 
31% 
Optimize 
hot gas 
defrosting 
15% 

GreenQ Partners © 2017  14 
Example: Economics at a glance 
Total Savings:     20% of use 
Energy savings (kWh/yr)  No capex optimization  46% of total  
Add 
condenser 
Add VFD to  fan VFD 
screw  8% 
compressors   Simple payback (years) 
15% 
Lower  Add VFD to screw compressors 9.1 
cond. 
Optimize  pressure  Optimize suction pressure +
suction  form 135  6.3 
evaporator fans VFDs
pressure +  psig to 95 
evaporator  psig  Optimize hot gas defrosting 0.5 
fans VFDs  31% 
31%  Lower cond. pressure form 135
0.5 
Optimize  psig to 95 psig
hot gas 
Add condenser fan VFD 3.1 
defrosting 
15% 

GreenQ Partners © 2017  15 
Example: Economics for CFO 
Energy  % of total  Simple 
SIR  
Description  savings  energy  payback  Investment 
(5 years) 
(kWh/yr)  use  (years) 
Add condenser fan VFD  48,900  2%  3.1  1.4   $         15,000  
Lower cond. pressure 
form 135 psig to 95 psig
185,000  6%  0.5  8.8   $           9,250  
Optimize hot gas 
defrosting 
90,000  3%  0.5  8.8 
 $           4,500  
Optimize suction 
pressure + evaporator  188,000  6%  6.3  0.7   $      118,000  
fans VFDs 
Add screw compressors 
87,700  3%  9.1  0.5 
VFDs   $         80,000  
Total  599,600  20% 

GreenQ Partners © 2017  16 
Framework steps 
1.  Assess opportunities through analysis of system 
setup and procedures, modeling and measurement 

2.  Create whole plant consumption baseline “before” 
through statistical analysis 

3.  Implement changes 

4.  Measure consumption “after” to document savings 
as cumulative sum of differences between predicted 
and actual consumption 

5. (Keep monitoring to ensure results stay) 

GreenQ Partners © 2017  17 
Measurement is the key to prove 
results 

GreenQ Partners © 2017  18 
Completed project 
Process cooling at industrial bakery 
Issues:  
 Process cooling is a bottleneck 
 Struggle to meet demand 
 Adding ice affects quality 
 

GreenQ Partners © 2017  19 
Baseline: 
actual and predicted ‘before’  
Predicted 
Actual 

GreenQ Partners © 2017  20 
Savings ‘after’ 
Implementation (partial) 
 180 psig  150 psig 
Results 
 Reduction 13% 
 Bottleneck removed 

Predicted 
Actual 

GreenQ Partners © 2017  21 
Cumulative sum of saving 
(CUSUM) 

Savings 
normalized to 
production and 
weather 

GreenQ Partners © 2017  22 
Summary 

• 30% energy use reduction is possible though optimization 

• Metering removes risks of hidden performance 

• Current refrigeration contractor stays 

• Incentives apply 

GreenQ Partners © 2017  23 
Contact 

Anatoli Naoumov, CMVP, MBA 
anaoumov@greenq.ca  
416‐728‐7239  
www.GreenQ.ca  

To receive a copy of this presentation with links to reports, financial details of example, and detailed 
explanations on how suggested measures work –  
 
Leave me your card marked ‘slides’  

GreenQ Partners © 2017  24 
Reduction of condensing pressure 
Overcoming barriers 
• Not enough pressure for complete hot gas defrosting 
Some operators report that hot gas defrosting cannot be completed when condensing pressure is low. This is only 
partially true: Often incomplete defrosting issue can be resolved through adjustment of defrosting valves. If incomplete 
defrosting still persists, condensing pressure can be slightly elevated for defrosting time and set back when defrosting is 
over through PLC.  
• Insufficient oil cooling of screw compressors 
This is likely the most common barrier to reduction of condensing pressure. Typically, at condensing pressure below 120 
psig flow of liquid into the compressor will be limited by the thermal expansion valve. An addition of a small liquid 
ammonia pump or of an electronic expansion valve will remove this barrier.  
• Insufficient liquid supply of ammonia far from receiver 
We sometimes hear from operators that at condensing pressure below 120 psig, pressure difference 80‐90 psig, plants 
experience an undersupply of liquid ammonia to evaporators that are far away from receiver. This happens because 
liquid ammonia starts to evaporate in the pipe and vapour blocks liquid supply. This issue can be resolved through 
additional cooling of liquid ammonia below saturation temperature or by increasing the size of the regulating valve. Sub 
cooling can be achieved through installation of heat exchanger or ammonia pump.  
• Oil carry over into ammonia through separator 
At low condensing pressure gas density decreases and velocity increases. High gas velocity can cause oil carry over into 
ammonia system. This barrier can be removed by installation of oversized oil separator or by reducing mass flow of the 
refrigerant. 

GreenQ Partners © 2017  25 
Reduction of condensing pressure 
Floating vs. reduced condensing pressure 
Floating condensing pressure consists of two steps:  
• lowering condensing pressure and  
• actual floating.  
Typically, lowering condensing pressure can provide 90‐95% of energy savings. Actual floating can give us just 5‐
10% of the savings. Why does it happen? Lower condensing pressure reduces energy use by compressors, while 
floating condensing pressure reduces energy use by condensers. Usually, nominal power of condensers is about 
10% of compressors’ power.  
Additionally, floating can be activated only during short periods of the year.  During summer, no floating is 
possible, because condensers typically run at full capacity to keep required condensing pressure. During winter, 
no floating is possible because refrigeration plants operate at minimum allowable condensing pressure. During 
fall and spring, floating can be activated, when condenser capacity exceeds optimum. However, floating will never 
be activated if a refrigeration plant has undersized condensers.   

GreenQ Partners © 2017  26 
Optimize suction pressure 
It is a common knowledge, that raising suction pressure, often measured as suction temperature, reduces energy 
consumption at compressor. Typically, reduction is 1‐2% per 1 degF increase in suction temperature. Increase of suction 
pressure does not come free; therefore, efficiency of the whole refrigeration plant should be considered to determine 
the optimum suction pressure. This is not a trivial decision. 
Higher suction pressure will reduce temperature difference between suction temperature and air temperature in the 
refrigerated room. To keep the required refrigeration capacity more evaporators will be running. Therefore, fans will use 
more energy and release more heat in refrigerated room. This will cause a need for additional compressor energy to 
compensate this parasitic refrigeration load.  
To estimate plant performance at a higher suction pressure, energy saved by compressors should be compared to energy 
used by additional evaporator fans. Sometimes, increase of energy use at evaporator fans exceeds saving at compressors. 
Power of evaporator fans determines optimum suction pressure.  
Optimal value of suction pressure should be determined for each plant through accurate modeling. 

GreenQ Partners © 2017  27 
Optimize Hot Gas Defrosting frequency  
Hot gas defrosting requires temporary heating parts of plant that are cold during the regular work cycle. In our experience, the 
procedure is routinely done on time schedule, while from energy use perspective it should be done on as‐needed basis: often in 
summer and rarely in winter. 

Defrosting is needed to eliminate frost from evaporator coils. Too much frost kills efficiency of evaporators. On the other hand, 
defrosting itself costs energy.  

Defrosting is a highly inefficient procedure in terms of energy: from every 100 units of heat provided by hot gas, less than 20 
units will melt frost, the remaining 80 units will warm up parts of the system. These 80 units must be removed by the 
refrigeration plant during the regular operation. After 35 minutes of hot gas defrosting, the evaporator coil, as well as part of 
refrigeration plant, will run for the next 1 hour in a cooling mode to remove the heat of defrosting. As a rule of thumb, 
eliminating one unnecessary defrosting per day saves 3% of whole refrigeration plant energy use. 

Frequency of defrosting should be set to minimize total energy losses from frost and hot gas defrosting procedure. We 
recommend accurate plant‐specific modeling to determine this frequency. 

GreenQ Partners © 2017  28 
Screw compressor VFD 
VFDs can be installed for refrigeration compressors. These compressors have constant torque loads. With constant torque 
loads, the torque loading is not a function of speed. As the speed changes, the load torque remains constant and energy 
use changes linearly with speed. This means that at 50% speed the compressor will use 50% energy. There is no energy 
saving benefits of using VFDs for reciprocated compressors, unless you want gradual change capacities of these 
compressors.  
Typically, screw compressors use slide valves to reduce capacity. Capacity can be changed gradually but energy efficiency 
will suffer. This energy efficiency will be reduced gradually (linearly) by unloading screw compressor from 100% to 50%. It 
will be reduced exponentially when compressor capacity is below 50%.  
How much energy can be saved by compressor VFD? 
This depends of average compressor load and operating compression ratio. Compressor VFD helps to recover losses related 
to part load operation of this compressor. The losses are greater when compressor operate at low capacity (below 50%) 
and at high compression ratio. It means that if compressor operate long time at low capacity and high compression ratio 
energy saved by VFD will be good. If compressor operate at high capacity and at low compression ratio energy saved by 
VFD will be minimal. Don’t forget that VFD itself use additional 3 – 3.5% of energy.     

GreenQ Partners © 2017  29 
Fan VFDs 
VFDs can be helpful to recover losses related to part load operation (compressors, condensers, evaporators). How great are 
the energy losses related to part load operation?  
If plant is poorly designed and/or poorly operated, energy losses will be great and a lot of energy can be recovered through 
the use of VFDs and they will have a relatively short payback. If plant has a good design and is operated well, energy losses will 
be minimal and little energy can be recovered. Payback for an investment in VFDs for this plant will be very long. Plant design 
and plant operation are two major factors to determine VFDs’ payback.  
Condenser fan VFDs can save up to 8% of a refrigeration plant’s energy use. But typically, the energy savings will be 
significantly lower because the operating time at favorable energy saving conditions will be short. During summer operation, 
the majority of refrigeration plants run condensers at full capacity. Very little energy can be saved during summer time. During 
winter operation, many condensers use little energy. This means that energy losses of part load operation are minimal and 
little energy can be recovered. During spring and fall some refrigeration plants can get good energy savings from condenser 
fan VFDs, especially plants with centrifugal condenser fans. To get maximum savings from condenser fan VFDs, condensers 
should not be undersized. 
Evaporator fan VFDs can be useful to save energy, especially for evaporator coils located in penthouses. Electrical motors of 
these evaporator fans, typically, are oversized. Many designers are over focused on air throw and little attention is paid to 
natural air convection. Typically, penthouses are located in the middle of a cold room and the warmest air located under the 
ceiling is pulled evenly from each side of the room. This factor helps prevent hot spots in a refrigerated room with penthouses 
and many evaporator fans can operate successfully at a low speed. Ceiling hung evaporator fans should have a good throw to 
push warm air from the opposite upper corner of a cold room. Modern cold rooms with penthouses are typically high‐rise 
construction. During the cooling mode, the room height will help to natural air convection and the warmest air will always 
enter the evaporators.  

GreenQ Partners © 2017  30 

Vous aimerez peut-être aussi