S.No. Description. Unit.

Quantity

a) OUTGOING. 0
i) 5 No. ACB Panels each having following: 0

1600 A, 415/V, Motorised, Fully Drawout type (EDO), Four Pole, Air Circuit Breaker with
microprocessor based overload, short circuit , Instantaneous & Earth Fault trip including and 0
lockable trip push button. The ACB should have Icw=Ics=Icu=50 KA for 1 sec.

Indicating lamps with 6A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB 0

Push button to CLOSE the ACB 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
Digital energy metre with CT 0
0
ii) 6 No. ACB Panels each having following: 0

1250 A, 415/V, Motorised, Fully Drawout type (EDO), Four Pole, Air Circuit Breaker with
microprocessor based overload, short circuit , Instantaneous & Earth Fault trip including and 0
lockable trip push button. The ACB should have Icw=Ics=Icu=50 KA for 1 sec.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB 0

Push button to CLOSE the ACB 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
Digital energy metre with CT 0
0
iii) 2 No. ACB Panels each having following: 0

1000 A, 415/V, Motorised, Fully Drawout type (EDO), Four Pole, Air Circuit Breaker with
microprocessor based overload, short circuit , Instantaneous & Earth Fault trip including and 0
lockable trip push button. The ACB should have Icw=Ics=Icu=50 KA for 1 sec.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB 0

Push button to CLOSE the ACB 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
Digital energy metre with CT 0
iv) 2 No. ACB Panels each having following: 0

800 A, 415/V, Motorised, Fully Drawout type (EDO), Four Pole, Air Circuit Breaker with
microprocessor based overload, short circuit , Instantaneous & Earth Fault trip including and 0
lockable trip push button. The ACB should have Icw=Ics=Icu=50 KA for 1 sec.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB 0

Push button to CLOSE the ACB 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

Digital energy metre with CT 0


0
v) 7 Nos. MCCB FEEDER as per following details/ specifications: 0

630Amp 415 volts, 50 KA ( Ics) Four Pole, Microprocessor release based MCCB with variable
0
current settings and having O/L, S/C & inbuilt E/F protection.

Extended rotary operating mechanism with door interlock with defeat feature and padlock
0
facility. MCCB should be with spreader link and phase barriers.

Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP . 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

Digital Energy meter 0


0
vi) 1 Nos. MCCB FEEDER as per following details/ specifications: 0

500 Amp 415 volts, 50 KA ( Ics) Four Pole, Microprocessor release based MCCB with variable
0
current settings and having O/L, S/C & inbuilt E/F protection.

Extended rotary operating mechanism with door interlock with defeat feature and padlock
0
facility. MCCB should be with spreader link and phase barriers.

Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP . 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

Digital Energy meter 0


0
vii) 3 Nos. MCCB FEEDER as per following details/ specifications: 0

400Amp 415 volts, 50 KA ( Ics) Four Pole, Microprocessor release based MCCB with variable
0
current settings and having O/L, S/C & inbuilt E/F protection.

Extended rotary operating mechanism with door interlock with defeat feature and padlock
0
facility. MCCB should be with spreader link and phase barriers.

Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP . 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
Digital Energy meter 0
0
viii) 10 Nos. MCCB FEEDER as per following details/ specifications: 0

250 Amp 415 volts, 50 KA ( Ics) Four Pole, Microprocessor release based MCCB with variable
0
current settings and having O/L, S/C & inbuilt E/F protection.

Extended rotary operating mechanism with door interlock with defeat feature and padlock
0
facility. MCCB should be with spreader link and phase barriers.

Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP . 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

Digital Energy meter 0


0
ix) 13 Nos. MCCB FEEDER as per following details/ specifications: 0
160 Amp 415 volts, 50 KA ( Ics) Four Pole, Microprocessor release based MCCB with variable
0
current settings and having O/L, S/C & inbuilt E/F protection.

Extended rotary operating mechanism with door interlock with defeat feature and padlock
0
facility. MCCB should be with spreader link and phase barriers.

Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP . 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

Digital Energy meter 0


0

Main LT Panel ( For Cancer Hosptial , Medical & Nursing College) as mentioned above. Set 1

0
2.02
CAPACITOR PANEL ESS-1 (For Cancer Hosptial , Medical & Nursing College ) 800
0
kVAr

Supply, installation, testing and commissioning of MV cubicle type totally enclosed free
standing type, powder coated, dust, damp and vermin proof Capacitor Panel complete with
busbars, MV danger notice plate, ammeter, ammeter selector switch, indicating lamps, CTs,
heavy duty, MPP resin filled, type Capacitors suitable for non linear loads upto 15% with
Copper wound 14% D-tunned filters, total operating losses of capacitor shall not more than 0.5
W/ KVAR, Power contactors suitable for capacitor switching or Capacitor duty with current
limiting contactor circuit to suppress switching inrush current interconnections with suitable
capacity aluminium leads/ solid aluminium strips, rods, connection of incoming and outgoing
cables with thimbles, and having following incoming and outgoing switchgears complete as
per techinical Specifications as required.

a) INCOMER:

1250 A, 415 Volts, Fully Motorised, Fully Drawout type (EDO), 50 KA, Four Pole, Air Circuit
Breaker with microprocessor based overload, short circuit & Instantanious Earth fault trip
including lockable trip push button.
Indicating lamps with 6A protection MCBs to indicate OPEN, CLOSE, TRIP.
R, Y & B Phase indicating lamps (LED type) with 6A control SP MCBs.
Day & Night mode selector switch.
14 steps Intelligent microprocessor based Automatic Power factor Correction relay having
measurment sensitivity of 1 % or better.
Extension of incoming busbars for connection of multicore armoured aluminium cables.

b) METERING:
1 set of Digital Amp. Meter, Digital Power factor meter and Digital voltmeter.

c) BUSBARS:
1250 Amps TPN busbars of aluminium with temperture rise of 40 ° C over and above Ambient
temperture of 45 Degree Celsius.(Total 85 ° C)

d) OUTGOINGS:
i) 4 Nos. MCCB as per following details/ specification:
200 Amps, 415 volts, 50 KA TP MCCB with Thermal Magnetic release having variable current
settings.
Extended rotary operating mechanism with door interlock, defeat feature and padlock facility.
MCCB should be with spreader link and phase barriers.

415 volts, TP Power Contactor suitable for capacitive switching including current limiting
contactor circuit to supress switching inrush current.

ON/ OFF delay timers for switching capacitor circuit.


"ON" and "OFF" LED indicating lamp and 2A control SP MCBs.
Push button for CLOSE and TRIP. 0
100 KVAR heavy duty MPP type resin filled capacitors suitable for non linear loads upto 15%,
0
& total operating losses not more than 0.5 W per KVAR.

ii) 8 Nos. MCCB as per following details/ specification:

100 Amps, 415 volts, 50 KA TP MCCB with Thermal Magnetic release having variable current
settings.

Extended rotary operating mechanism with door interlock, defeat feature and padlock facility.
MCCB should be with spreader link and phase barriers.
415 volts, TP Power Contactor suitable for capacitive switching including current limiting
contactor circuit to supress switching inrush current.
ON/ OFF delay timers for switching capacitor circuit.
"ON" and "OFF" LED indicating lamp and 2A control SP MCBs.

50 KVAR heavy duty MPP type resin filled capacitors suitable for non linear loads upto 15% &
total operating losses not more than 0.5 W per KVAR.

CAPACITOR PANEL AS MENTIONED ABOVE Set 3


0
2.03 MAIN L.T. PANEL (NORMAL) (For Hostels & Dinning Blocks) Location -ESS-2 0

Supply, installation, testing and commissioning of LT Panel, cubicle type, totally enclosed, free
standing type, dust ,damp and vermin proof panel , powder coated, made up of CRCA sheet,
complete with aluminum busbars, danger notice plate, interconnections with suitable capacity
0
aluminum leads/solid aluminum strips/rods, necessary interlocking, and having incoming and
outgoing switchgears with cable alley in front as mentioned below and complete as per
technical specifications and as required.

Note : 0
1 All ACBs shall have spare contacts 0

HSCC_NEIGRIHMS_Shillong Est-E 1_R1


S.No. Description. Unit. Quantity

2 All relays to operate at 240Volts, Single phase, 50Hz., AC supply through UPS. UPS of
0
suitable Rating is also in the scope of Supply
3
Intellignet Panel Meter: Flush mounting, 96X96 mm size class 1 accuracy and LCD display.
Panel meter should be suitable for true RMS reading. Meter should measure line and phase
voltage, current of all 3 phasees and neutral, HZ, PF, KW, KWH, KVAR, KVARH, KVA, KVAH, 0
Voltage and current including one set of CT. Meter should be EMI/ EMC complaint. Meter
should be with RS 485 port for communication on Modbus protocol.

4 All ACBs shall have 50 KA for 1 second. 0


5 All ACBs should have Icw =Ics=Icu=100%
6 All MCCBs shall have Ics=Icu=100%
7 Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door for all
Microprocessor Based outgoing MCCB
0
A. INCOMER: 0
i) 2 No. ACB Panels each having following: 0

2000 A, 415/500V Motorised, Fully Drawout type (EDO), Four Pole, Air Circuit Breaker with
microprocessor based overload, short circuit , Instantaneous & Earth Fault trip including under 0
voltage release and lockable trip push button. ACB should have Icw=Ics=Icu=50 KA for 1 sec.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB 0
Push button to CLOSE the ACB. 0
R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs 0
Intellgent Panel Meter as mention above 0
One set of dual core dual ratio CT of 2000/1000/5/5A for capacitor panel. 0
0
B. BUSBARS : 0
2000 Amps 50 KA, TPN busbars of aluminium with temperture rise of 40 ° C over and above
0
Ambient temperture of 45 Degree Celsius.(Total 85 ° C)
0
C. BUS COUPLER : 0
i) 1No. ACB Panels each having following: 0

2000 A, 415/500V,415 V, Motorised, Fully Drawout type (EDO), Four Pole, Air Circuit Breaker
with microprocessor based overload, short circuit , Instantaneous & Earth Fault trip including 0
and lockable trip push button. The ACB should have Icw=Ics=Icu=50 KA for 1 sec.

1 set of indicating lamps to indicate OPEN, CLOSE, TRIP. 0


Push button to CLOSE the ACB. 0
1 Set of A meter with ASS and CTs. 0
0
D. OUTGOING. 0
0
i) 3 No. ACB Panels each having following: 0

1000 A, 415/500V, 415 V, Motorised, Fully Drawout type (EDO), Four Pole, Air Circuit Breaker
with microprocessor based overload, short circuit , Instantaneous & Earth Fault trip including 0
and lockable trip push button. The ACB should have Icw=Ics=Icu=50 KA for 1 sec.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB 0

Push button to CLOSE the ACB 0


R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

Digital energy metre with CT 0


0
ii) 9 Nos. MCCB FEEDER as per following details/ specifications: 0
400 Amp 415 volts, 50 KA ( Ics)Four Pole, Microprocessor release based MCCB with variable
0
current settings and having O/L, S/C & inbuilt E/F protection.

Extended rotary operating mechanism with door interlock with defeat feature and padlock
0
facility. MCCB should be with spreader link and phase barriers.

Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP . 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

Digital Energy meter 0


0
iii) 2 Nos. MCCB FEEDER as per following details/ specifications: 0
320 Amp 415 volts, 50 KA ( Ics)Four Pole, Microprocessor release based MCCB with variable
0
current settings and having O/L, S/C & inbuilt E/F protection.

Extended rotary operating mechanism with door interlock with defeat feature and padlock
0
facility. MCCB should be with spreader link and phase barriers.

Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP . 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

Digital Energy meter 0

iii) 3 Nos. MCCB FEEDER as per following details/ specifications: 0

250 Amp 415 volts, 50 KA ( Ics) Four Pole, Microprocessor release based MCCB with variable
0
current settings and having O/L, S/C & inbuilt E/F protection.

Extended rotary operating mechanism with door interlock with defeat feature and padlock
0
facility. MCCB should be with spreader link and phase barriers.

Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP . 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

Digital Energy meter 0


0
iv) 8 Nos. MCCB FEEDER as per following details/ specifications: 0
200Amp 415 volts, 50 KA (Isc), Four Pole, Microprocessor release based MCCB with variable
0
current settings and having O/L, S/C & inbuilt E/F protection.

Extended rotary operating mechanism with door interlock with defeat feature and padlock
0
facility. MCCB should be with spreader link and phase barriers.

Indicating lamps (LED Type) with 2A protection MCBs to indicate ON, OFF, TRIP . 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

Digital Energy meter 0


0
Main LT Panel (NORMAL) (For Hostels & Dinning Blocks) as mentioned above. Set 1
0
2.04
Main LT Panel (EMERGENCY) (For Hostels & Dinning Blocks) Loction -ESS-2 ) 0

A INCOMER: 0
i 2 Nos. MCCB as per following details / specifications: 0
630 A, 415/500V, 415/500V Motorised, Fully Drawout type (EDO), Four Pole, Air Circuit
Breaker with microprocessor based overload, short circuit , Instantaneous & Earth Fault trip
0
including under voltage release and lockable trip push button. ACB should have
Icw=Ics=Icu=50 KA for 1 sec.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB 0

Push button to CLOSE the ACB 0


R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs 0
Intellgent Panel Meter as mention above 0
DG should start automatically and will have automatic change over at LT panel through auto
0
change over arrangement of suitable capacity.
B BUSBARS: 0
630 Amp TPN busbars of aluminium with temperture rise of 40 ° C over and above Ambient
0
temperture of 45 Degree Celsius.(Total 85 ° C)
0
C BUS COUPLER : 0
i 1 Nos. MCCB as per following details / specifications: 0

630 A, 415/500V,415 V, Motorised, Fully Drawout type (EDO), Four Pole, Air Circuit Breaker
with microprocessor based overload, short circuit , Instantaneous & Earth Fault trip including 0
and lockable trip push button. The ACB should have Icw=Ics=Icu=50 KA for 1 sec.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB 0

Push button to CLOSE the ACB 0


R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs 0
1 Set of A meter with ASS and CTs. 0
0
D OUTGOING: 0
i 13 Nos. MCCB as per following details / specifications: 0
100 Amps,415 volts, FP, 35 KA Moulded Case Circuit Breaker with thermal magnetic release
0
having variable current settings .

R,Y&B phase indicating lamp (LED type) with 2A control SP MCB to indicate ON, OFF, TRIP . 0

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
0

Main LT Panel (EMERGENCY) (For Hostels & Dinning Blocks) as mentioned above. Set 1
0
2.05 CAPACITOR PANEL ESS-2 (For Hostels & Dinning Blocks) 500 KVAR 0

Supply, installation, testing and commissioning of MV cubicle type totally enclosed free
standing type, powder coated, dust, damp and vermin proof Capacitor Panel complete with
busbars, MV danger notice plate, ammeter, ammeter selector switch, indicating lamps, CTs,
heavy duty, MPP resin filled, type Capacitors suitable for non linear loads upto 15% with
Copper wound 14% D-tunned filters, total operating losses of capacitor shall not more than 0.5
W/ KVAR, Power contactors suitable for capacitor switching or Capacitor duty with current
limiting contactor circuit to suppress switching inrush current interconnections with suitable
capacity aluminium leads/ solid aluminium strips, rods, connection of incoming and outgoing
cables with thimbles, and having following incoming and outgoing switchgears complete as
per techinical Specifications as required.

0
A. INCOMER : 0

800 A, 415 Volts,415/500V,415 V, Motorised, Fully Drawout type (EDO), Four Pole, Air Circuit
Breaker with microprocessor based overload, short circuit , Instantaneous & Earth Fault trip 0
including and lockable trip push button. The ACB should have Icw=Ics=Icu=50 KA for 1 sec.

Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP. 0

R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs 0

Day & Night mode selector switch 0

14 steps Intelligent microprocessor based Automatic Power factor Correction relay having
0
measurment sensitivity of 1 % or better.

Extension of incoming busbars for connection of multicore armoured aluminium cables. 0

0
B. METERING : 0

1 set of digital Amp. Meter, digital Power factor meter and Digital voltmeter 0
0
C. BUSBARS : 0
800 Amps TPN busbars of aluminium with temperture rise of 40 ° C over and above Ambient
0
temperture of 45 Degree Celsius.(Total 85 ° C)
0
D. OUTGOINGS : 0
i) 2 Nos . MCCB as per following details/ specification: 0
200 Amps, 415 volts, 50 KA TP MCCB with Thermal Magnetic release having variable current
settings.
Extended rotary operating mechanism with door interlock, defeat feature and padlock facility.
MCCB should be with spreader link and phase barriers.

HSCC_NEIGRIHMS_Shillong Est-E 2_R1


S.No. Description. Unit. Quantity

415 volts, TP Power Contactor suitable for capacitive switching including current limiting
contactor circuit to supress switching inrush current.
ON/ OFF delay timers for switching capacitor circuit.
"ON" and "OFF" LED indicating lamp and 2A control SP MCBs.
Push button for CLOSE and TRIP. 0
100 KVAR heavy duty MPP type resin filled capacitors suitable for non linear loads upto 15%,
0
& total operating losses not more than 0.5 W per KVAR.
0
ii) 4 Nos . MCCB as per following details/ specification: 0
100 Amps, 415 volts, 50 KA TP MCCB with Thermal Magnetic release having variable current
settings.

Extended rotary operating mechanism with door interlock, defeat feature and padlock facility.
MCCB should be with spreader link and phase barriers.

415 volts, TP Power Contactor suitable for capacitive switching including current limiting
contactor circuit to supress switching inrush current.

ON/ OFF delay timers for switching capacitor circuit.

"ON" and "OFF" LED indicating lamp and 2A control SP MCBs.

Push button for CLOSE and TRIP. 0


50 KVAR heavy duty MPP type resin filled capacitors suitable for non linear loads upto 15%, &
0
total operating losses not more than 0.5 W per KVAR.
0
iii) 4 Nos . MCCB as per following details/ specification: 0
63 Amps, 415 volts, 50 KA TP MCCB with Thermal Magnetic release having variable current
settings.
Extended rotary operating mechanism with door interlock, defeat feature and padlock facility.
MCCB should be with spreader link and phase barriers.

415 volts, TP Power Contactor suitable for capacitive switching including current limiting
contactor circuit to supress switching inrush current.
ON/ OFF delay timers for switching capacitor circuit.
"ON" and "OFF" LED indicating lamp and 2A control SP MCBs.
Push button for CLOSE and TRIP. 0
25 KVAR heavy duty MPP type resin filled capacitors suitable for non linear loads upto 15%, &
0
total operating losses not more than 0.5 W per KVAR.
0
Capacitor panel (For Hostels & Dinning Blocks) as mentioned above. Set 2
0
Total SubHead 2: Main LT Panel as mentioned above. 0
0
4.00 SUBHEAD 4: RISING MAINS 0

Supply, installation, testing and commissioning of plug in type , indoor sandwich type with
high conductivity Aluminium Conductor , 415 V,3 phase, 4 wire, vertical Aluminium Rising
main Class B or better in following sizes including bends, flexible, provision of the tap off's as
per requirment , Adoptor boxes for cable connection if required are inclusive , 2 nos of 0
aluminium earthing strips 50 X 6mm through out the length of the rising mains, end cover,
including all types of support and necessary hardware for installation of the rising main etc.
complete as per specifications and as required. (Exact lengths to be measured at site).
4.01
i 1000 A , 415 volts Metre 40
ii 1250 A,415 volts Metre 80
0
Supply, fixing, testing and commissioning of Direct End Feed Unit of following ratings, wall
mounted, dust, damp and vermin proof complete with M.V. danger notice plate,
interconnections with suitable capacity aluminium strips / bars, connection of incoming cables 0
with thimbles, powder coat painted and having following incoming switchgears for rising main
4.02 complete as required.
i) 1 No. ACB Panels each having following 0
1000A 415V, 4P 50 kA EDO ACB with Microprocessor based release having Overload , Short
circuit and Earth fault Protection with overvoltage, undervoltage protection and ON /OFF/TRIP Set 1
Indications with MCB.
0
ii) 1 No. ACB Panels each having following 0
1250A 415V, 4P 50 kA EDO ACB with Microprocessor based release having Overload , Short
circuit and Earth fault Protection with overvoltage, undervoltage protection and ON /OFF/TRIP Set 2
Indications with MCB.
0
Supply, fixing, testing and commissioning of distribution tap off box of following Capacity on
the existing rising mains complete with Four Pole, Moulded Case Circuit Breaker, 0
4.03 interconnection, earthing etc. complete as required.
0
i 100 Amps with MCCB 35 KA Nos 18
ii 125 Amps with MCCB 35 KA Nos 4
iii 160 Amps with MCCB 35 KA Nos 11
iv 200 Amps with MCCB 35 KA Nos 5
vi 400 Amps with MCCB 35 KA Nos 5
0
TOTAL SUBHEAD - 4: RISING MAINS as mentioned above 0
0
5.00 SUB HEAD 5 :MV PANELS 0

Supply, installation, testing and commissioning of following M.V. cubicle type totally enclosed,
wall mounted/Free standing type, powder coated, dust, damp and vermin proof, indoor type
Distribution Board/Panel complete with busbars, M.V. danger notice plate, interconnections
0
with suitable capacity aluminium leads/solid aluminium strips/rods, connection of incoming and
outgoing cables with thimbles, and having following incoming and outgoing switchgears
complete as per techinical specification and as required.

NOTE
All MCCBs shall have Ics=Icu. 0

MCB Should be connected through terminal Strip of suitable rating

REGIONAL CANCER HOSPITAL 0


5.01 MV PANEL FOR{ LEVEL+1, +2, +4,+5,+6 FLOOR (SECTION -1)}
0
a) INCOMER: 0
400 Amp 415 volts, 35 KA FP MCCB with microprocessor based release having variable
0
current settings of O/L, S/C & inbuilt E/F protection release.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)
Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door. 0
1 No. 0 to 500 V Digital voltmeter with selector switch. 0

Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
630 Amp TPN Aluminium busbars 0
0
c) OUTGOING: 0
0
i) 8 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0
ii)
8 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

MV PANEL FOR{ LEVEL+1, +2, +4,+5,+6 FLOOR (SECTION -1)} : as mentioned above Set 5

0
5.02 MV PANEL FOR{ LEVEL+3, +7 FLOOR (SECTION -1) & LOWER GROUND FLOOR &
LEVEL +3 (SECTION -2)} 0

a) INCOMER: 0

125 Amp 415 volts, 35 KA FP MCCB with thermal magnetic release having variable current
0
settings of O/L, S/C protection and E/ F Module.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)
1 No. 0 to 500 V Digital voltmeter with selector switch. 0
Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
300 Amp FP Aluminium busbars 0
0
c) OUTGOING: 0
0
i)
5 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

ii)
5 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

MV PANEL FOR{ LEVEL+3, +7 FLOOR (SECTION -1) & LOWER GROUND FLOOR &
Set 4
LEVEL +3 Floor (SECTION -2)} : as mentioned above
0
5.03 MV PANEL FOR{ LEVEL+1, +2, +4,+5,+6 FLOOR (SECTION -2)}
0
a) INCOMER: 0

200 Amps,415 volts, FP 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal magnetic
0
release having variable current settings of O/L, S/C protection and E/ F Module.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

1 No. 0 to 500 V Digital voltmeter with selector switch. 0

Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
300 Amp TPN Aluminium busbars 0
0
c) OUTGOING: 0
i) 8 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0
ii)
8 no.40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

MV PANEL FOR{ LEVEL+1, +2, +4,+5,+6 FLOOR (SECTION -2)} : as mentioned above Set 5

0
5.04 MV PANEL FOR { ENTRY &+7 LEVEL FLOOR (SECTION -2)} 0
a) INCOMER: 0

160 Amps,415 volts, FP 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)
1 No. 0 to 500 V Digital voltmeter with selector switch. 0
Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
300 Amp TPN Aluminium busbars 0
0
c) OUTGOING: 0

HSCC_NEIGRIHMS_Shillong Est-E 3_R1


S.No. Description. Unit. Quantity

i) 6 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0


ii)
6 no.40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

MV PANEL FOR { ENTRY &+7 LEVEL FLOOR (SECTION -2)} : as mentioned above Set 2

0
5.05 OT / ICU PANEL 0
a) INCOMER: 0
2 Nos. MCCB as per following details/ specifications: 0

200 Amps,415 volts, FP 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

1 No. 0 to 500 V Digital voltmeter with selector switch. 0

Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
400 Amp TPN Aluminium busbars 0
0
c) OUTGOING: 0
i)
12 no.63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

OT / ICU PANEL as mentioned above Set 1

5.06 Main MV PANEL Computer Panel (LEVEL +1 (SECTION -1 ) 0


a) INCOMER: 0
2 Nos. MCCB as per following details/ specifications:

200 Amps,415 volts, FP 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

1 No. 0 to 500 V Digital voltmeter with selector switch. 0

Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
400 Amp TPN Aluminium busbars 0
0
c) OUTGOING: 0
i) 2 Nos. MCCB as per following details / specifications: 0

125 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

ON, OFF, TRIP indication (LED Type). 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
ii) 8 Nos. MCCB as per following details / specifications: 0

63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

ON, OFF, TRIP indication (LED Type). 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
iii) 6 no. 25 Amps , 240 volts, 9 KA ,Double Pole, Miniature Circuit Breaker. 0
0

MV PANEL Computer Panel (LEVEL +1 (SECTION -1 ) as mentioned above Set 1

5.07 MV PANEL Computer Panel (LEVEL +1 (SECTION -2 ) 0


a) INCOMER: 0

125 Amps,415 volts, FP 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/F module.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)
1 No. 0 to 500 V Digital voltmeter with selector switch. 0

Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
300 Amp TPN Aluminium busbars 0
0
c) OUTGOING: 0
i) 8 Nos. MCCB as per following details / specifications: 0

63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

ON, OFF, TRIP indication (LED Type). 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
ii) 6 no. 25 Amps , 240 volts, 9 KA ,Double Pole, Miniature Circuit Breaker. 0
0

MV PANEL Computer Panel (LEVEL +1 SECTION-2) as mentioned above Set 1

0
5.08
SUB COMPUTER/ UPS PANEL (SECTION -1 {Level+2,+3,+4,+5,+6,+7}& SECTION -2
0
{ Level+2,+3,+4,+5,+6,+7 & Entry Floor} )

a) INCOMER: 0
63 Amps,415 volts, FP 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal magnetic
0
release having variable current settings of O/L, S/C protection and E/F module.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

1 No. 0 to 500 V Digital voltmeter with selector switch. 0

Digital ammeter with selector switch with one set ofsuitable C.Ts. 0
0
b) BUSBARS: 0
300 Amp TPN Aluminium busbars 0
c) OUTGOING: 0
i)
6 no. 25 Amps , 240 volts, 9 KA ,Double Pole, Miniature Circuit Breaker. 0

SUB COMPUTER/ UPS PANEL (SECTION -1 {Level+2,+3,+4,+5,+6,+7}& SECTION -2


Set 13
{ Level+2,+3,+4,+5,+6,+7 & Entry Floor} ) as mentioned Above

5.09 LIFT PANEL (SECTION-1 & SECTION-2) 0


a) INCOMER: 0

160 Amps,415 volts, FP 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/F module.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

1 No. 0 to 500 V Digital voltmeter with selector switch. 0

Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
300 Amp TPN Aluminium busbars 0
0
c) OUTGOING: 0
i) 4 Nos. MCCB as per following details / specifications: 0

63 Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal magnetic
0
release having variable current settings of O/L, S/C protection.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

ON, OFF, TRIP indication (LED Type). 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

LIFT PANEL (SECTION-1 & SECTION-2) as mentioned above Set 2


0
5.10 EQUIPMENT PANEL : Regional Cancer Hospital 0
A) INCOMER: 0

800 Amp 415 volts, 35 KA FP MCCB with microprocessor based release having variable
0
current settings of O/L, S/C & inbuilt E/F protection release.

Extended rotary operating mechanism with door interlock with defeat feature and padlock
0
facility. MCCB should be with spreader link and phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

1 No. 0 to 500 V Digital voltmeter with selector switch. 0

0
B) BUSBARS : 0
1000 Amps Phase TPN busbars of aluminium. 0
0
C) OUTGOING: 0
i) 2 Nos. MCCB as per following details/ specifications: 0

HSCC_NEIGRIHMS_Shillong Est-E 4_R1


S.No. Description. Unit. Quantity

400 Amp 415 volts, 35 KA TP+NL MCCB with microprocessor based release having variable
0
current settings of O/L, S/C & inbuilt E/F protection release.

Extended rotary operating mechanism with door interlock with defeat feature and padlock
0
facility. MCCB should be with spreader link and phase barriers.

ON, OFF, TRIP indication (LED Type) 0


Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
ii) 3 Nos. MCCB as per following details/ specifications: 0

320 Amp 415 volts, 35 KA TP+NL MCCB with microprocessor based release having variable
0
current settings of O/L, S/C & inbuilt E/F protection release.

Extended rotary operating mechanism with door interlock with defeat feature and padlock
0
facility. MCCB should be with spreader link and phase barriers.
ON, OFF, TRIP indication (LED Type) 0
Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
0
iii) 2 Nos. MCCB as per following details/ specifications: 0

250 Amp 415 volts, 35 KA TP+NL MCCB with microprocessor based release having variable
0
current settings of O/L, S/C & inbuilt E/F protection release.

Extended rotary operating mechanism with door interlock with defeat feature and padlock
0
facility. MCCB should be with spreader link and phase barriers.

ON, OFF, TRIP indication (LED Type) 0


Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

0
iv) 4 Nos. MCCB as per following details/ specifications: 0

160 Amp 415 volts, 35 KA TP+NL MCCB with thermal magnetic release having variable
0
current settings of O/L, S/C protection.

Extended rotary operating mechanism with door interlock with defeat feature and padlock
0
facility. MCCB should be with spreader link and phase barriers.

ON, OFF, TRIP indication (LED Type) 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
0
EQUIPMENT PANEL as mentioned above : Set 1
0
NURSING COLLEGE 0
5.11 MV PANEL: NURSING COLLEGE (SECTION -1 (LOCATION : GROUND FLOOR ELEC.
0
ROOM)
a) INCOMER: 0
630 Amp 415 volts, 35 KA FP MCCB with microprocessor based release having variable
0
current settings of O/L, S/C & inbuilt E/F protection release.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door.
1 No. 0 to 500 V Digital voltmeter with selector switch. 0
Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
800 Amp TPN Aluminium busbars 0
0
c) OUTGOING: 0
i) 2 Nos. MCCB as per following details / specifications: 0
320 Amp 415 volts, 35 KA TP+NL MCCB with microprocessor based release having variable
0
current settings of O/L, S/C & inbuilt E/F protection release.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door.

ON, OFF, TRIP indication (LED Type) 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
0
ii) 2 Nos. MCCB as per following details / specifications: 0
250 Amp 415 volts, 35 KA TP+NL MCCB with microprocessor based release having variable
0
current settings of O/L, S/C & inbuilt E/F protection release.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door.

ON, OFF, TRIP indication (LED Type) 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
0
iii) 2 Nos. MCCB as per following details / specifications: 0
63 Amp 415 volts, 35 KA TP+NL MCCB with thermal magnetic release having variable current
0
settings of O/L, S/C protection.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

ON, OFF, TRIP indication (LED Type) 0


Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
0
iv) 11 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0
v)
8 no.40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

MV PANEL (NORMAL PANEL)Section -1 : as mentioned above Set 1


0
5.12 MV PANEL: NURSING COLLEGE (SECTION -2 LOCATION : GROUND FLOOR ELEC.
0
ROOM)
a) INCOMER: 0
320 Amp 415 volts, 35 KA (Ics= Icu), FP MCCB with variable current settings and having
0
microprocessor based O/L, S/C & inbuilt E/F protection release.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)
1 No. 0 to 500 V Digital voltmeter with selector switch. 0
Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
500 Amp FP Aluminium busbars 0
0
c) OUTGOING: 0
i) 2 Nos. MCCB as per following details / specifications: 0

63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu),Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C .

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

ON, OFF, TRIP indication (LED Type) 0


Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
0
ii)
11 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

iii)
8 no.40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breakr. 0

MV PANEL NURSING COLLEGE (SECTION -2 ): as mentioned above Set 1

0
5.13 MV PANEL: NURSING COLLEGE (EMERGENCY PANEL LOCATION : GROUND FLOOR
0
ELEC. ROOM)
a) INCOMER: 0

250 Amp 415 volts, 35 KA (Ics= Icu), FP MCCB with variable current settings and having
0
microprocessor based O/L, S/C & inbuilt E/F protection release.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door.
1 No. 0 to 500 V Digital voltmeter with selector switch. 0
Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
300 Amp TPN Aluminium busbars 0
0
c) OUTGOING: 0
i) 2 Nos. MCCB as per following details / specifications: 0
200Amps,415 volts, TP+NL, 35 KA (Ics= Icu),Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

ON, OFF, TRIP indication (LED Type) 0


Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
0
ii) 4 Nos. MCCB as per following details / specifications: 0

63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu),Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

ON, OFF, TRIP indication (LED Type) 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
0
iii)
4 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

iv)
8 no.40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

HSCC_NEIGRIHMS_Shillong Est-E 5_R1


S.No. Description. Unit. Quantity

MV PANEL (Emergency) : as mentioned above Set 1

5.14 MAIN COMPUTER/ UPS PANEL NURSING COLLEGE 0


a) INCOMER: 0
2 Nos. MCCB as per following details / specification
100 Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

0
b) BUSBARS: 0
300 Amp TPN Aluminium busbars 0
c) OUTGOING: 0
i) 2 Nos. MCCB as per following details / specifications: 0
63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

ON, OFF, TRIP indication (LED Type) 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

iii) 12 no. 32 Amps , 240 volts, 9 KA ,Double Pole, Miniature Circuit Breaker 0
0

MAIN COMPUTER/ UPS PANEL NURSING COLLEGE (SECTION -1) as mentioned above Set 1

5.15 SUB COMPUTER/ UPS PANEL NURSING COLLEGE-(SECTION -2) 0


a) INCOMER: 0
63 Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal magnetic
0
release having variable current settings of O/L, S/C protection and E/ F Module.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

0
b) BUSBARS: 0
300 Amp TPN Aluminium busbars 0
c) OUTGOING: 0
i) 12 no. 32 Amps , 240 volts, 9 KA ,Double Pole, Miniature Circuit Breaker. 0
0
SUB COMPUTER/ UPS PANEL NURSING COLLEGE-(SECTION -2) as mentioned above Set 1
0
MEDICAL COLLEGE 0
5.16 MV PANEL (NORMAL): MEDICAL COLLEGE (SECTION -1) (G. FLOOR LEVEL-1929.75) 0
a) INCOMER: 0

630 Amp 415 volts, 35 KA (Ics= Icu), FP MCCB with variable current settings and having
0
microprocessor based O/L, S/C & inbuilt E/F protection release.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door.

1 No. 0 to 500 V Digital voltmeter with selector switch. 0

Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
800 Amp FP Aluminium busbars 0
0
c) OUTGOING: 0
i) 2 Nos. MCCB as per following details / specifications: 0
320 Amp 415 volts, 35 KA (Ics= Icu), TP+NL MCCB with variable current settings and having
0
microprocessor based O/L, S/C & inbuilt E/F protection release.

ON, OFF, TRIP indication (LED Type) 0

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
ii) 2 Nos. MCCB as per following details / specifications: 0
160 Amps,415 volts, TP+NL 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

ON, OFF, TRIP indication (LED Type) 0

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
iii) 3 Nos. MCCB as per following details / specifications: 0

125 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

ON, OFF, TRIP indication (LED Type) 0

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
iv) 6 Nos. MCCB as per following details / specifications: 0
100 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection .
ON, OFF, TRIP indication (LED Type) 0
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.
Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
0
v) 2 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0
vi) 6 no.40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

MV PANEL (NORMAL): MEDICAL COLLEGE (SECTION -1) (G. FLOOR LEVEL-1929.75) :


Set 1
as mentioned above

0
5.17
MV PANEL (NORMAL): MEDICAL COLLEGE {(SECTION -1) (1st FLOOR LEVEL-
1933.50 & 2nd FLOOR LEVEL-1937.25)}{(SECTION -2) (1st FLOOR LEVEL-1933.50 & 0
4th FLOOR LEVEL-1944.75)}

a) INCOMER: 0
125 Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)
1 No. 0 to 500 V Digital voltmeter with selector switch. 0
Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
300 Amp TPN Aluminium busbars 0
0
c) OUTGOING: 0
i) 8 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0
0

MV PANEL (NORMAL): MEDICAL COLLEGE {(SECTION -1) (1st FLOOR LEVEL-


1933.50 & 2nd FLOOR LEVEL-1937.25)}{(SECTION -2) (1st FLOOR LEVEL-1933.50 & Set 4
4TH FLOOR LEVEL-1944.75)}as mentioned above

0
5.18
MV PANEL (NORMAL): MEDICAL COLLEGE {(SECTION -1) (LG FLOOR LEVEL - 1926,
4th FLOOR LEVEL -1944.75 & 5TH FLOOR LEVEL1948.50) & (SECTION -2) (3rd FLOOR 0
LEVEL -1941 & 5TH FLOOR LEVEL1948.50)}

a) INCOMER: 0

100 Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

1 No. 0 to 500 V Digital voltmeter with selector switch. 0


Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
300 Amp TPN Aluminium busbars 0
0
c) OUTGOING: 0
i) 4 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0
ii) 4 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0
0

MV PANEL (NORMAL): MEDICAL COLLEGE {(SECTION -1) (LG FLOOR LEVEL - 1926,
4th FLOOR LEVEL -1944.75 & 5TH FLOOR LEVEL1948.50) & (SECTION -2) (3rd FLOOR Set 5
LEVEL -1941 & 5TH FLOOR LEVEL1948.50)}:as mentioned above

0
5.19
MV PANEL (NORMAL): MEDICAL COLLEGE (SECTION -2) (G. FLOOR LEVEL-1929.75) 0

a) INCOMER: 0
320 Amp 415 volts, 35 KA (Ics= Icu),FP MCCB with variable current settings and having
0
microprocessor based O/L, S/C & inbuilt E/F protection release.
R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door.
1 No. 0 to 500 V Digital voltmeter with selector switch. 0
Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
500 Amp FP Aluminium busbars 0
0

HSCC_NEIGRIHMS_Shillong Est-E 6_R1


S.No. Description. Unit. Quantity

c) OUTGOING: 0
i) 1 Nos. MCCB as per following details / specifications: 0
200 Amps,415 volts, TP+NL, 35 KA (Ics= Icu),Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection .
ON, OFF, TRIP indication (LED Type) 0
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.
Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
ii) 4 Nos. MCCB as per following details / specifications: 0
125 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

ON, OFF, TRIP indication (LED Type) 0

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
iii) 3 Nos. MCCB as per following details / specifications: 0
100 Amps,415 volts, TP+NL, 35 KA Moulded Case Circuit Breaker with thermal magnetic
0
release having variable current settings of O/L, S/C protection .

ON, OFF, TRIP indication (LED Type) 0

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
0
iv) 6 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0
v) 2 no.40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0
MV PANEL (NORMAL): MEDICAL COLLEGE (SECTION -2) (G. FLOOR LEVEL-
Set 1
1929.75)) : as mentioned above
0
0
5.20
MV PANEL (NORMAL): MEDICAL COLLEGE (SECTION -1) (3rd FLOOR LEVEL -1941) &
0
(SECTION -2) (2nd FLOOR LEVEL -1937.25)

a) INCOMER: 0
200 Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.
R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

1 No. 0 to 500 V Digital voltmeter with selector switch. 0


Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
300 Amp TPN Aluminium busbars 0
0
c) OUTGOING: 0
i)
8 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

MV PANEL (NORMAL): MEDICAL COLLEGE (SECTION -1) (3rd FLOOR LEVEL -1941) &
Set 2
(SECTION -2) (2nd FLOOR LEVEL -1937.25) :as mentioned above

0
5.21 MV PANEL (EMERGENCY): MEDICAL COLLEGE (SECTION -1) (G. FLOOR LEVEL-
0
1929.75)
a) INCOMER: 0

630 Amp 415 volts, 35 KA (Ics= Icu), FP MCCB with variable current settings and having
0
microprocessor based O/L, S/C & inbuilt E/F protection release.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door.
1 No. 0 to 500 V Digital voltmeter with selector switch. 0
Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
800 Amp FP Aluminium busbars 0
0
c) OUTGOING: 0
i) 2 Nos. MCCB as per following details / specifications: 0

320 Amp 415 volts, 35 KA (Ics= Icu), FP MCCB with variable current settings and having
0
microprocessor based O/L, S/C & inbuilt E/F protection release.

ON, OFF, TRIP indication (LED Type) 0

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door.

Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
ii) 2 Nos. MCCB as per following details / specifications: 0
200 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.
ON, OFF, TRIP indication (LED Type) 0

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
iii) 9 Nos. MCCB as per following details / specifications: 0
100 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.
ON, OFF, TRIP indication (LED Type) 0
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.
Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
iv) 3 Nos. MCCB as per following details / specifications: 0
63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.
ON, OFF, TRIP indication (LED Type) 0
Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.
Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
0
v)
6 no.40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

MV PANEL (Emergency): MEDICAL COLLEGE (SECTION -1) (G. FLOOR LEVEL-


Set 1
1929.75)) : as mentioned above
0
5.22 MV PANEL (EMERGENCY): MEDICAL COLLEGE (SECTION -2) (G. FLOOR LEVEL-
0
1929.75)
a) INCOMER: 0
320 Amp 415 volts, 35 KA (Ics= Icu), FP MCCB with variable current settings and having
0
microprocessor based O/L, S/C & inbuilt E/F protection release.
R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)
Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

1 No. 0 to 500 V Digital voltmeter with selector switch. 0

Digital ammeter with selector switch with one set Suitable C.Ts. 0

0
b) BUSBARS: 0
500 Amp FP Aluminium busbars 0
0
c) OUTGOING: 0
0
i) 7 Nos. MCCB as per following details / specifications: 0

100 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

ON, OFF, TRIP indication (LED Type) 0

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
ii) 2 Nos. MCCB as per following details / specifications: 0

63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection .

ON, OFF, TRIP indication (LED Type) 0

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
0
iii) 8 no.40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0
0
MV PANEL (Emergency): MEDICAL COLLEGE (SECTION -2) (G. FLOOR LEVEL-
Set 1
1929.75)) : as mentioned above
0
5.23
MV PANEL(EMERGENCY): MEDICAL COLLEGE {SECTION -1 (LGF LEVEL - 1926),
(1ST.FLOOR LEVEL-1933.50) ,(2ND FLOOR LEVEL-1937.25)& (3rd FLOOR LEVEL
-1941),(4th FLOOR- 1944.75)& (5th FLOOR LEVEL-1948.50)} & {SECTION -2 0
1ST.FLOOR LEVEL-1933.50) ,(2ND FLOOR LEVEL-1937.25)& (3rd FLOOR LEVEL -1941),
(4th FLOOR- 1944.75)& (5th FLOOR LEVEL-1948.50)}

a) INCOMER: 0
100 Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

1 No. 0 to 500 V Digital voltmeter with selector switch. 0


Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
300 Amp TPN Aluminium busbars 0
0
c) OUTGOING: 0

HSCC_NEIGRIHMS_Shillong Est-E 7_R1


S.No. Description. Unit. Quantity

i) 6 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0


ii) 2 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0
0

MV PANEL(EMERGENCY): MEDICAL COLLEGE {SECTION -1 (LGF LEVEL - 1926),


(1ST.FLOOR LEVEL-1933.50) ,(2ND FLOOR LEVEL-1937.25)& (3rd FLOOR LEVEL
-1941),(4th FLOOR- 1944.75)& (5th FLOOR LEVEL-1948.50)} & {SECTION -2 Set 11
1ST.FLOOR LEVEL-1933.50) ,(2ND FLOOR LEVEL-1937.25)& (3rd FLOOR LEVEL -1941),
(4th FLOOR- 1944.75)& (5th FLOOR LEVEL-1948.50)} :as mentioned above

0
5.24 MAIN COMPUTER/ UPS PANEL MEDICAL COLLEGE-(SECTION -1) 0
a) INCOMER: 0
2 Nos. MCCB as per following details / specifications:
160 Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
0
b) BUSBARS: 0
300 Amp TPN Aluminium busbars 0
c) OUTGOING: 0
i) 2 Nos. MCCB as per following details / specifications: 0

100 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

ON, OFF, TRIP indication (LED Type) 0

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

ii) 9 Nos. MCCB as per following details / specifications: 0

63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

ON, OFF, TRIP indication (LED Type) 0

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
iii) 4 no. 32 Amps , 240 volts, 9 KA ,Double Pole, Miniature Circuit Breaker. 0
0

MAIN COMPUTER/ UPS PANEL MEDICAL COLLEGE-(SECTION -1) as mentioned above Set 1

0
5.25 MAIN COMPUTER/ UPS PANEL MEDICAL COLLEGE-(SECTION -2) 0
a) INCOMER: 0

100 Amps,415 volts, FP 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal magnetic
0
release having variable current settings of O/L, S/C protection and E/ F Module.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
0
b) BUSBARS: 0
300 Amp TPN Aluminium busbars 0
c)
OUTGOING: 0

i) 8 Nos. MCCB as per following details / specifications: 0


63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection .

ON, OFF, TRIP indication (LED Type) 0

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
iii) 4 no. 32 Amps , 240 volts, 9 KA ,Double Pole, Miniature Circuit Breaker. 0
0

MAIN COMPUTER/ UPS PANEL MEDICAL COLLEGE-(SECTION -2) as mentioned above Set 1

0
5.26
SUB COMPUTER/ UPS PANEL MEDICAL COLLEGE -(SECTION -1 &2) 0

0
a) INCOMER: 0

63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
0
b) BUSBARS: 0
300 Amp TPN Aluminium busbars 0
c) OUTGOING: 0
i 8 no. 32 Amps , 240 volts, 9 KA ,Double Pole, Miniature Circuit Breaker. 0
0
SUB COMPUTER/ UPS PANEL MEDICAL COLLEGE -(SECTION -1 &2) as mentioned
Set 11
above

UG -1 & UG -2 HOSTELS 0
5.27 NORMAL MAIN MV PANEL {UG HOSTEL-1& UG HOSTEL-2 SECTION- B (LOCATION :
0
ELECTRICAL ROOM GROUND FLOOR)}
a) INCOMER: 0
400 Amp 415 volts, 35 KA (Ics= Icu), FP MCCB with variable current settings and having
0
microprocessor based O/L, S/C & inbuiltE/F protection release.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)
Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.
1 No. 0 to 500 V Digital voltmeter with selector switch. 0
Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
500 Amp TPN Aluminium busbars 0
0
c) OUTGOING: 0
i) 2 Nos. MCCB as per following details / specifications: 0
200 Amps,415 volts, TP+NL, (Ics= Icu), Moulded Case Circuit Breaker with thermal magnetic
0
release having variable current settings of O/L, S/C protection.
ON, OFF, TRIP indication (LED Type) 0

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
0
ii) 2 Nos. MCCB as per following details / specifications: 0
63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection .

ON, OFF, TRIP indication (LED Type) 0

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.
Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
0
iii) 10 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0
iv) 6 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0
NORMAL MAIN MV PANEL {UG HOSTEL-1& UG HOSTEL-2 SECTION- B }: as mentioned
Set 2
above
0
5.28 NORMAL MAIN MV PANEL {UG HOSTEL-1& UG HOSTEL-2 SECTION- A (LOCATION :
0
ELECTRICAL ROOM GROUND FLOOR)}
a) INCOMER: 0
200 Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

1 No. 0 to 500 V Digital voltmeter with selector switch. 0

Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
300 Amp TPN Aluminium busbars 0
0
c) OUTGOING: 0
i)
10 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

ii)
6 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

NORMAL MV PANEL SECTION- A : as mentioned above Set 2


0
5.29 EMERGENCY MV PANEL {UG HOSTEL-1& UG HOSTEL-2 (LOCATION : ELECTRICAL
0
ROOM GROUND FLOOR)}
a) INCOMER: 0

100 Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)
1 No. 0 to 500 V Digital voltmeter with selector switch. 0
Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
300 Amp TPN Aluminium busbars 0
0
c) OUTGOING: 0
i) 3 Nos. MCCB as per following details / specifications: 0

HSCC_NEIGRIHMS_Shillong Est-E 8_R1


S.No. Description. Unit. Quantity

63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection .

ON, OFF, TRIP indication (LED Type) 0

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

ii)
4 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

EMERGENCY MV PANEL {UG HOSTEL-1& UG HOSTEL-2} : as mentioned above Set 2


0
INTERNEE HOSTEL , UG-3 , Nursing -1 Nursing -2 0
5.30 NORMAL MAIN MV PANEL (INTERNEE HOSTEL , UG-3 , Nursing -1& Nursing -2)
0
SECTION- B (LOCATION : ELECTRICAL ROOM GROUND FLOOR)
a) INCOMER: 0

320 Amp 415 volts, 35 KA (Ics= Icu), FP MCCB with variable current settings and having
0
microprocessor based O/L, S/C & inbuilt E/F protection release.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door.
1 No. 0 to 500 V Digital voltmeter with selector switch. 0
Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
500 Amp TPN Aluminium busbars 0
0
c) OUTGOING: 0
i) 2 Nos. MCCB as per following details / specifications: 0

160 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection .

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
0
ii) 2 Nos. MCCB as per following details / specifications: 0

63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection .

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

ON, OFF, TRIP indication (LED Type) 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
0
iii)
10 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

iv)
4 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

NORMAL MAIN MV PANEL (INTERNEE HOSTEL , UG-3 , Nursing -1& Nursing -2)
Set 3
SECTION- B : as mentioned above
0
5.31 NORMAL MAIN MV PANEL (INTERNEE HOSTEL , UG-3 , Nursing -1& Nursing -2)
0
SECTION- A (LOCATION : ELECTRICAL ROOM GROUND FLOOR)
a) INCOMER: 0

160 Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

1 No. 0 to 500 V Digital voltmeter with selector switch. 0


Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
300 Amp TPN Aluminium busbars 0
0
c)
OUTGOING: 0
i)
8 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0
ii) 6 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0
NORMAL MV PANEL (INTERNEE HOSTEL , UG-3 , Nursing -1& Nursing -2) SECTION- A
Set 3
: as mentioned above
0
5.32
EMERGENCY MV PANEL (INTERNEE HOSTEL , UG-3 , Nursing -1& Nursing -2)
0
(LOCATION : ELECTRICAL ROOM GROUND FLOOR)

a) INCOMER: 0
100Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal magnetic
0
release having variable current settings of O/L, S/C protection and E/ F Module.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

1 No. 0 to 500 V Digital voltmeter with selector switch. 0


Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
300 Amp TPN Aluminium busbars 0
0
c) OUTGOING: 0
i) 3 Nos. MCCB as per following details / specifications: 0

63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

ON, OFF, TRIP indication (LED Type) 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0

ii)
4 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

EMERGENCY MV PANEL (INTERNEE HOSTEL , UG-3 , Nursing -1& Nursing -2) : as


Set 3
mentioned above
0
5.33
NORMAL MV PANEL (UG DINING BLOCK & NURSING DINING BLOCK) 0

a) INCOMER: 0
200 Amps,415 volts, FP, 35 KA Moulded Case Circuit Breaker with thermal magnetic release
0
having variable current settings of O/L, S/C protection and E/ F Module.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)
1 No. 0 to 500 V Digital voltmeter with selector switch. 0
Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
300 Amp TPN Aluminium busbars 0
0
c) OUTGOING: 0
i) 4 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0
ii) 8 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0
NORMAL MV PANEL (UG DINING BLOCK & NURSING DINING BLOCK) : as mentioned
Set 2
above
0
5.34
EMERGENCY MV PANEL (UG DINING BLOCK & NURSING DINING BLOCK) 0
a) INCOMER: 0
100 Amps,415 volts, FP, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection and E/ F Module.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)
1 No. 0 to 500 V Digital voltmeter with selector switch. 0
Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
300 Amp TPN Aluminium busbars 0
0
c) OUTGOING: 0
i) 2 Nos. MCCB as per following details / specifications: 0
63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

ON, OFF, TRIP indication (LED Type) 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
ii) 2 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0
iii) 6 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0
NORMAL MV PANEL (UG DINING BLOCK & NURSING DINING BLOCK) : as mentioned
Set 2
above
0
5.35
MV PANEL GUEST HOUSE (LOCATION : ELECTRICAL ROOM GROUND FLOOR) 0

a) INCOMER: 0

250 Amp 415 volts, 35 KA (Ics= Icu), FP MCCB with variable current settings and having
0
microprocessor based O/L, S/C & inbuilt E/F protection release

HSCC_NEIGRIHMS_Shillong Est-E 9_R1


S.No. Description. Unit. Quantity

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

R,Y&B phase indicating lamp (LED type) with 6A control SP MCB & ON, OFF, TRIP
0
indication (LED Type)

Separate fault indication for O/L, S/C, & E/F to be provided on Panel Door.
1 No. 0 to 500 V Digital voltmeter with selector switch. 0
Digital ammeter with selector switch with one set Suitable C.Ts. 0
0
b) BUSBARS: 0
400 Amp TPN Aluminium busbars 0
0
c) OUTGOING: 0
i) 2 Nos. MCCB as per following details / specifications: 0

200 Amps,415 volts, TP+NL, 35 KA (Ics= Icu), Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection .

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
0
ii) 4 Nos. MCCB as per following details / specifications: 0
63 Amps,415 volts, TP+NL, 35 KA (Ics= Icu),Moulded Case Circuit Breaker with thermal
0
magnetic release having variable current settings of O/L, S/C protection.

Extended rotary operating mechanism with door interlocking with defeat feature and padlock
0
facility. MCCB should have spreader links & phase barriers.

ON, OFF, TRIP indication (LED Type) 0

Digital Ampere Metre of suitable range with suitable set of CT's and ASS. 0
0
iii)
6 no. 63 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

iv) 6 no. 40 Amps , 415 volts, 9 KA ,Four Pole, Miniature Circuit Breaker. 0

MV PANEL GUEST HOUSE (LOCATION : ELECTRICAL ROOM GROUND FLOOR) : as


Set 1
mentioned above
0
TOTAL SUB HEAD 5 : MV PANEL 0
0
6.00 SUBHEAD 6 : UPS SYSTEM 0
6.01 UPS 80 KVA. (REGIONAL CANCER CENTER OT'S AND ICU'S) 0

Supply, Installation, Testing and Commissioning of micro processor based 2 x 80 KVA at 0.8
power factor at out put. with over all efficiency of minimum 94% at full load, True Online
Double Conversion UPS using PWM IGBT technology. 3 Phase input 415 V +10% -15% and 0
input frequency 50 Hertz plus minus 5%, 3 phase input and 3 phase output. UPS operating in
parallel redundant load sharing mode (N+1) configration and each comprising of the following:

(a) 125% rated Rectifier cum charger unit + 100% rated inverter, integrated in UPS module 0

(b) IGBT Rectifier input for achieving THDi<5% and Input power factor of greater than 0.99 0

(c)100% rated external isolation transformer of H-class Delta/Star at the UPS output, after
0
static bypass including cabling between UPS and transformer
(d) 100% rated Inbuilt static switch 0
(f) 100% rated Inbuilt Maintenance Bypass 0

(g) 100% rated moulded case circuit breaker having I thermal, magnetic and automatic U/V
0
trip mechanics

(i) RS 485 port for BMS connectivity 0


(j) Supplying and installing Built-in suitable air-circulating fan . 0
Input phase reversal protection to be provided as standard, UPS should shift on battery and
0
provide alarm.
(k) Supply, Installation, Testing and Commissioning of 12 V sealed maintenance free, Valve
Regulated Lead Acid (VRLA) batteries for providing 30 minutes back up on each UPS at full 0
load at 0.8 power factor.

(l) Supply, Fixing of battery rack for each UPS system along with inteconnecting links, BCB
0
etc as required

(m) UPS Should be provided with of Static Bypass Module having High Switching Frequency
Microprocessor Based with builtin Technical Protections like Short Circuit, Overload, High/
Low Voltage cutoff protection of load from source inclusive of Bypass facility, SBM is
activated during malfunctioning conditions of Load like:-
-Short Circuit
0
-Overload
-Over temprature
-Bypassing of particular load if reqd.

UPS 80 KVA SYSTEM AS MENTIONED ABOVE. SET 1


0
6.02 UPS 80 KVA. (COMPUTER POINTS ) 0

Supply, Installation, Testing and Commissioning of micro processor based 80 KVA at 0.8
power factor at out put. with over all efficiency of minimum 94% at full load, True Online
Double Conversion UPS using PWM IGBT technology. 3 Phase input 415 V +10% -15% and 0
input frequency 50 Hertz plus minus 5%, 3 phase input and 3 phase output, each comprising
of the following:

(a) 125% rated Rectifier cum charger unit + 100% rated inverter, integrated in UPS module 0

(b) IGBT Rectifier input for achieving THDi<5% and Input power factor of greater than 0.99 0

(c)100% rated external isolation transformer of H-class Delta/Star at the UPS output, after
0
static bypass including cabling between UPS and transformer
(d) 100% rated Inbuilt static switch 0
(f) 100% rated Inbuilt Maintenance Bypass 0

(g) 100% rated moulded case circuit breaker having I thermal, magnetic and automatic U/V
0
trip mechanics

(i) RS 485 port for BMS connectivity 0


(j) Supplying and installing Built-in suitable air-circulating fan . 0
Input phase reversal protection to be provided as standard, UPS should shift on battery and
0
provide alarm.
(k) Supply, Installation, Testing and Commissioning of 12 V sealed maintenance free, Valve
Regulated Lead Acid (VRLA) batteries for providing 30 minutes back up on each UPS at full 0
load at 0.8 power factor.

(l) Supply, Fixing of battery rack for each UPS system along with inteconnecting links, BCB
0
etc as required

(m) UPS Should be provided with of Static Bypass Module having High Switching Frequency
Microprocessor Based with builtin Technical Protections like Short Circuit, Overload, High/
Low Voltage cutoff protection of load from source inclusive of Bypass facility, SBM is
activated during malfunctioning conditions of Load like:-
-Short Circuit
0
-Overload
-Over temprature
-Bypassing of particular load if reqd.

UPS 80 KVA SYSTEM AS MENTIONED ABOVE. SET 2

6.03 UPS 120 KVA. (COMPUTER POINTS ) 0


Supply, Installation, Testing and Commissioning of micro processor based 80 KVA at 0.8
power factor at out put. with over all efficiency of minimum 94% at full load, True Online
Double Conversion UPS using PWM IGBT technology. 3 Phase input 415 V +10% -15% and 0
input frequency 50 Hertz plus minus 5%, 3 phase input and 3 phase output, each comprising
of the following:

(a) 125% rated Rectifier cum charger unit + 100% rated inverter, integrated in UPS module 0

(b) IGBT Rectifier input for achieving THDi<5% and Input power factor of greater than 0.99 0

(c)100% rated external isolation transformer of H-class Delta/Star at the UPS output, after
0
static bypass including cabling between UPS and transformer
(d) 100% rated Inbuilt static switch 0
(f) 100% rated Inbuilt Maintenance Bypass 0

(g) 100% rated moulded case circuit breaker having I thermal, magnetic and automatic U/V
0
trip mechanics

(i) RS 485 port for BMS connectivity 0


(j) Supplying and installing Built-in suitable air-circulating fan . 0
Input phase reversal protection to be provided as standard, UPS should shift on battery and
0
provide alarm.
(k) Supply, Installation, Testing and Commissioning of 12 V sealed maintenance free, Valve
Regulated Lead Acid (VRLA) batteries for providing 30 minutes back up on each UPS at full 0
load at 0.8 power factor.
(l) Supply, Fixing of battery rack for each UPS system along with inteconnecting links, BCB
0
etc as required
(m) UPS Should be provided with of Static Bypass Module having High Switching Frequency
Microprocessor Based with builtin Technical Protections like Short Circuit, Overload, High/
Low Voltage cutoff protection of load from source inclusive of Bypass facility, SBM is
activated during malfunctioning conditions of Load like:-
-Short Circuit
0
-Overload
-Over temprature
-Bypassing of particular load if reqd.

UPS 120 KVA SYSTEM AS MENTIONED ABOVE. SET 1


0
TOTAL SUBHEAD 6 : UPS SYSTEMS 0
0
SUB HEAD- 7: MCB DISTRIBUTION BOARDS. 0
7.00 MCB DISTRIBUTION BOARD 0
7.01
Supplying & fixing following way, three pole and neutral sheet steel, MCB distribution board,
415 volts,on recess/surface complete with loose wire box, terminal blocks, tinned copper
busbar, neutral link, earth bar,din bar, detachable gland plate, interconnections, phosphatized 0
and powder coated including earthing connection bolt etc. as per technical specifications and
as required.(but without MCB & RCCB).

i 4 way (8+12), Double door Each 82


ii 6 way (8+12) Double door Each 169
iii 8 way (8+24), Double door Each 157
0
7.02
Supplying & fixing following way, single pole and neutral,sheet steel, MCB distribution board,
240 volts,on recess/surface complete with loose wire box, terminal blocks, tinned copper
busbar, neutral link, earth bar,din bar, detachable gland plate, interconnections, phosphatized
0
and powder painted including earthing etc.Before procurement of DB the contractor has to
take approval of DB schedule/ drawing of each DB from the Electrical Engineer, HSCC, as
per technical specifications and as required.(but without MCB & RCCB),

i 6 way Double door Each 27


ii 8 way Double door Each 70
iii 12 way Double door Each 25
0
7.03
Supplying & fixing 6 Amps to 32 Amps rating, 240 volts,'B' series, miniature circuit breaker
suitable for lighting & other loads of following poles in the existing MCB DB complete with 0
connections, testing & commissioning etc. as per technical specifications & as required.

i Single pole Each 8660

HSCC_NEIGRIHMS_Shillong Est-E 10_R1


S.No. Description. Unit. Quantity

ii Triple pole & neutral Each 20


0
7.04
Supplying & fixing following rating, four pole, 415 volts, Miniature Circuit Breaker (MCB),in the
existing MCB DB complete with connections, testing & commissioning etc. as per technical 0
specifications and as required.

i 25 Amps Each 47
i 40 Amps Each 131
ii 63 Amps Each 224
0
7.05
Supplying & fixing following rating, four pole, 415 volts, Residual Current Circuit Breaker
(RCCB) having a sensitivity current upto 300 mA in the existing MCB DB complete with 0
connections, testing & commissioning etc. as per technical specifications and as required.

i 25 Amps Each 33
iii 40 Amps Each 131
iv 63 Amps Each 224
0
7.06
Supplying and fixing following rating, double pole, 240 volts, MCB (B/C/D/ Curve) in the
0
existing MCB DB complete with connections, testing and commissioning etc. as required.

i 16 amps Each 87
ii 25 amp Each 31
0
7.07
Supplying and fixing Single pole Blanking plate in the existing MCB DB complete as required. Each 111

0
TOTAL SUB HEAD-7: MCB DISTRIBUTION BOARDS. 0