Vous êtes sur la page 1sur 1

1 2 3 4 5 6 7 8 9 10 11 12

2-Ø7/8" ANCHOR BOLT(TYPE-2A)


REF.TO STD.DWG.NO.
DR-920-013-039-A3
EQUIPMENT BASE PLATE (TYP.)
(BY OTHERS)

PROJECTION=131
25 THK.GROUT
CHAMFER (25X25)
A T.O.G. +0.250 (TYP.) A
Ø7/8" ANCHOR BOLT(TYPE-2A)
2D13-75 REF.TO STD.DWG.NO.
75

16-D13
(STIRRUPS) DR-920-013-039-A3

(STIRRUPS)
(TYP.)

Ø10-100
(TYP.)
G.L. ±0.000 225

131

T.O.C. -0.200 T.O.G. +0.250

25 THK.GROUT

542

411
CONCRETE
THIS DRAWING
1-D13
B (TYP.) LEGEND B
B.O.F. -0.650 NOTES:
1. ALL DIMENSIONS IN THIS DRAWING ARE IN
100 50CL 50 THK. MILIMETERS, UNLESS NOTED OTHERWISE.
(TYP.) (TYP.) LEAN CONC.
D13-150 2. GRADE LEVEL ± 0.0000
D13-600
CROSS TIES (TOP&BOTTOM)
3. CONCRETE GRADE WHERE THE STRENGTH
(TYP.) (TYP.)
REACH 300 kg/cm² AT 28 DAYS
1-Ø10 COMPACTED SOIL
(STIRRUPS) 95% MAX. DRY DENSITY 4. IN CLAY SOIL WHERE DRYING SHRINKAGE OF
(TYP.) SOIL MAY OCCUR, FOUNDATIONS TO BE
SOIL-SUPPORTED SHALL BE POURED WITHIN 36
HOURS AFTER EXCAVATION IS COMPLETED. IF A
DELAY BEYOND THIS TIME IN POURING
C FOUNDATION SHOULD BE NECESSARY, A C
CONCRETE SEAL SLAB OF 50 MM THICKNESS
SHALL BE POURED IN THE BOTTOM OF THE
EXCAVATION IMMEDIATELY AFTER EXCAVATION
IS COMPLETED.
5. HIGH STRENGTH BARS (> DIA. 12) SHALL HAVE
YIELD STRENGTH 345 MPa AND SHALL CONFORM
TO BJTS 40.
6. MILD STEEL BARS (<=DIA. 10) SHALL HAVE YIELD
STRENGTH 235 MPa AND SHALL CONFORM TO
BJTP 24.
1-DIA. 450 mm,DEPTH 14 M
D (BORE PILE)
REF. TO STD DWG NO.
A 7. FOUNDATION ANCHOR BOLT SHALL CONFORM TO
ASTM A307 WITH YIELD STRENGTH 235 MPA AND D
DR-920-016-004 SHT.01 TENSILE STRENGTH 345 MPa.
8. NON SHRINK PRECISION GROUT HAVE
COMPRESSIVE STRENGHT OF GROUTING AT 7
DAYS NOT LESS THAN 800 KG/CM2, FLEXTURAL
STRENGHT AT 7 DAYS NOT LESS THAN 150
EQUIPMENT BASE PLATE KG/CM2, LINEAR SHRINKAGE LESS THAN 0.1%,
(BY OTHERS) 25 THK.GROUT 12 THK. COEFFICIENT OF LINEAR EXPANSION LESS THAN
BASE PLATE CHAMFER (25X25)
35 x 10-6 °C, WATER ABSORPTION LESS THAN
T.O.G. +0.250 (1000X150) (TYP.)
0.5%
16-D13 Ø7/8" ANCHOR BOLT(TYPE-2A)
2D13-75 75

(TYP.) REF.TO STD.DWG.NO.


(STIRRUPS)
(STIRRUPS)

DR-920-013-039-A3
E E
Ø10-100

(TYP.)
G.L. ±0.000 225

T.O.C. -0.100

1-D13
(TYP.)

B.O.F. -0.650

100 50CL 0 ISSUED FOR APPROVAL 28/11/18 DNA ISA UAN


50 THK.
F (TYP.) (TYP.)
LEAN CONC.
REV DESCRIPTION DATE DRAWN CHECKED APPROVED
F
1-Ø10 D13-150 D13-600
(STIRRUPS) (TOP&BOTTOM) CROSS TIES ALL RIGHT RESERVED
(TYP.) (TYP.) THIS DOCUMENT AND ANY DATA AND INFORMATION CONTAINED THERE IN ARE CONFIDENTIAL AND THE PROPERTY OF PT.
ENVIROMATE TECHNOLOGY INTERNATIONAL. AND THE COPYRIGHT THERE IS VESTED IN PT. ENVIROMATE TECHNOLOGY
COMPACTED SOIL INTERNATIONAL. NO PART OF THIS DOCUMENT, DATA, OR INFORMATION SHALL BE DISCLOSED TO OTHERS OR REPRODUCED IN
ANY MANNER OR USED FOR ANY PURPOSE WHATSOEVER. EXCEPT WITH THE PERIOD WRITTEN PERMISSION OF PT. ENVIROMATE
95% MAX. DRY DENSITY TECHNOLOGY INTERNATIONAL.
(TYP.)

PEMBANGUNAN 1 (SATU) UNIT


FASILITAS GAS EXTERNAL KAPASITAS
57 MMSCFD C/W ACCESSORIES DI KILANG
PERTAMINA RU II DUMAI
OWNER
G G

CONTRACTOR

1-DIA. 450 mm,DEPTH 14 M


(BORE PILE) DRAWING TITLE
REF. TO STD DWG NO.
DR-920-016-004

H H
DRAWING NUMBER REVISION
SCALE NTS

DR-920-016-018-A3
B JOB. NO

SHT.01 E20200-15-09
DRAWING SHEET:
0
2 OF 2

1 2 3 4 5 6 7 8 9 10 11 12