Académique Documents
Professionnel Documents
Culture Documents
Distribution Feeders
Syllabus:
Distribution Feeders
Objectives:
Learning Outcomes:
1. Feeders
2. Distributors and
Service mains: A service mains is generally a small cable which connects the
distributor to the consumers’ terminals.
1. Nature of current.
2. Type of construction
3. Scheme of connection
(a) Feeders: A feeder is designed from the point of view of its current carrying
capacity while the voltage drop consideration is relatively unimportant. It is
because voltage drop in a feeder can be compensated by means of voltage
regulating equipment at the substation.
(b) Distributors: A distributor is designed from the point of view of the voltage
drop in it. It is because a distributor supplies power to the consumers and
there is a statutory limit of volt-age variations at the consumer’s terminals (±
6% of rated value). The size and length of the distributor should be such that
voltage at the consumer’s terminals is within the permissible limits.
The distribution system is classified into (i) primary distribution system and (ii)
secondary distribution system.
((ii) Secondary distribution system :It is that part of a.c. distribution system
which includes the range of voltages at which the ultimate consumer utilizes the
electrical energy delivered to him. The secondary distribution employs 400/230
V, 3-phase, 4-wire system. Electric power from the generating station is
transmitted at high voltage to the substation located in or near the city. At this
substation, voltage is stepped down to 11 kV with the help of step-down
transformer. Power is supplied to various substations for distribution or to big
consumers at this voltage. This forms the high voltage distribution or primary
distribution. The primary distribution circuit delivers power to various
substa-tions, called distribution sub-stations. The substations are situated
near the consumers’ localities and contain step-down transformers. At each
distribution substation, the voltage is stepped down to 400 V and power is
delivered by 3-phase, 4-wire a.c. system. The voltage between any two phases
is 400 V and between any phase and neutral is 230 V. The single phase
domestic loads are connected between any one phase and the neutral, whereas
3-phase 400 V motor loads are connected across 3-phase lines directly.
Fig. 2.3 shows a typical secondary distribution system
This is the simplest distribution circuit and has the lowest initial cost. However,
it suffers from the following drawbacks:
a. The end of the distributor nearest to the feeding point will be heavily
loaded.
b. The consumers are dependent on a single feeder and single distributor.
Therefore, any fault on the feeder or distributor cuts off supply to the
consumers who are on the side of the fault away from the substation.
c. The consumers at the distant end of the distributor would be subjected to
serious voltage fluctuations when the load on the distributor changes.
Due to these limitations, this system is used for short distances only.
The simplest and the lowest- cost and therefore the most common
form of primary feeder is the radial-type primary feeder as shown in F i g
2 . 6 The main primary feeder branches into various primary laterals
which in turn separates into several sub laterals to serve all the
distribution transformers. In general, the main feeder and sub feeders are
three-phase three- or four-wire circuits and the laterals are three-
phase or single-phase. The current magnitude is the greatest in the circuit
conductors that leave the substation. The current magnitude continually
lessens out towards the end of the feeder as laterals and sub laterals are
tapped off the feeder. Usually as the current lessens the size of the feeder
conductors is also reduced. However, the permissible voltage regulation may
restrict any feeder size reduction which is based only on the thermal
capability, i.e., current-carrying capacity, of the feeder..
Figure 2.7 shows a modified radial-type primary feeder with tie and
sectionalizing switches to provide fast restoration of service to customers
by switching non faulted sections of the feeder to an adjacent primary
feeder or feeders. The fault can be isolated by opening the associated
disconnecting devices on each side of the faulted section.
Fig 2.8 shows another type of radial primary feeder with express feeder
and back feeder. The section of the feeder between the substation low-
voltage bus and the load center of the service area is called an express feeder.
No sub feeders o r laterals a r e allowed to be tapped off the express feeder.
However, a sub feeder is allowed to provide a back feeder toward the
substation from the load center.
Fig. 2.7 Radial -Type Primary Feeder with tie and sectionalizing switches
Fig. 2.8 Radial-type primary feeder with express feeder and back feed
Fig. 2.9 Radial-type phase-area feeder
Fig 2.12 Illustration of the voltage-square rule and the feeder distance-
coverage principle as a functionof feeder voltage level and a single load
�
�
� ��
�
is times the original load and area. If the new feeder voltage level is
increased to three times the previous voltage level, the new load and area
that can be served with the same percent voltage drop is 4.32
Assume that there are many closely spaced loads and/or lateral lines
connected to the main but not shown in Figure. Since the load is
uniformly distributed along the main, as shown in Figure 2.18 the load
current in the main is a function of the distance. Therefore, in view of the
many closely spaced small loads, a differential tapped-off load current dI,
which corresponds to a dx differential distance, is to be used as an
idealization. Here, l is the total length of the feeder and x is the distance of
the point 1 on the feeder from the beginning end of the feeder. Therefore
the distance of point 2 on the feeder from the beginning end of the feeder is
x + d x . Is the sending-end current at the feeder breaker, and Ir is the
receiving-end current. Ix1 and Ix2 are the currents in the main at points 1
and 2, respectively. Assume that all loads connected to the feeder have the
same power factor.
The following equations are valid both in per unit or per phase (line-to-
neutral) dimensional variables. The circuit voltage is of either primary or
secondary, and therefore shunt capacitance currents may be neglected.
dI
This is a constant. Therefore k =
I x , that is, the current in the main of
dx
some x distance away from the circuit breaker, can be found as a
function of the sending-end current I s and the distance x. This can be
accomplished either by inspection or by writing a current equation
containing the integration of the d I . Therefore, for the dx distance
I x1 = I x 2 + d I
dx dI
I x 2 = I x1 - d I = I x1 - dx
dx dx
I x 2 = I x1 - kdx
dI
k=
dx
I r = I s - kl
When x = l
Is
Ir = 0 � k =
l
And since x = l
Therefore, substituting
� x�
Ir = Is �
1- �
� l�
I x = Ir
� x�
Ix = Is �
1- �
� l�
This gives the current in the main at some x distance away from the
circuit breaker
The differential series voltage drop dv and the differential power loss dPLS due
to I 2R losses can also be found as a function of the sending-end current Is
and the distance x in a similar manner.
dV = I x �zdx
x
dV = I s (1 - ) �zdx
l
dPLS = I x2 �rdx
2
� x �
dPLS = �
I s (1 - ) ��rdx
� l �
The series voltage drop VDx due to I x current at any point x on the feeder
is
x
VDx = �
dV
0
x
� x� � x�
VDx = � 1- �
Is � �zdx = I s �z �x �
1- �
0 � l � � 2l �
Therefore, the total series voltage drop �VDx on the main feeder when
x=l is
1
�VD x =
2
I s �z �l
The total copper loss per phase in the main due to I 2 R losses is
�P LS =�
dPLS
0
1
�P LS = I s2 �r �l
3
Therefore, from Equation, the distance x from the beginning of the
main feeder at which location the total load current Is may be
concentrated, i.e., lumped for the purpose of calculating the total
voltage drop, is
x=l/2
Fig 2.20 the sending-end current as a function of the distance along a feeder
l l
Is = �-dIx = �k �I
x =0 x=0
s �xdx
l2
I s = k �I s �
2
The k is the constant
dI x x
= - k �I s �x = -2 I s � 2
dx l
Therefore the current in the main at some x distance away from the circuit
breaker can be found
� x2 �
Ix = Is �
1- 2 �
� l �
� x2 �
dV = I x �zdx = I s �z �
1- 2 �dx
� l �
� x2 �
dPLS = I �rdx = I �r �
2
x 1 - 2 �dx
2
s
� l �
The series voltage drop due to I x current at any point x on the feeder is
x
VDx = �
dV
0
� x2 �
VDx = I s �z �x �
1- 2 �
� 3l �
Therefore the total series voltage drop on the main feeder when x=l is the
2
�VD x =
3
z ��
l Is
The total copper loss per phase in the main due to i 2 R losses is
l
8 2
�P LS =�
dPLS =
15
I s �r �l
0
APPLICATION OF THE A, B, C, D GENERAL CIRCUIT CONSTANTS TO
RADIAL FEEDERS
V r = Vr �00 ,V s = Vs �d
I r = I r �- q r
A = A1 + jA2
B = B1 + jB2
I r = I r ( cos q r - j sin q r )
V r = Vr �00
V s = Vs ( cos d + j sin d )
Let
Where
Similarly
Present Design Practice of Secondary distribution system
The part of the electric utility system that is between the primary system
and the consumer’s property is called the secondary system. Secondary
distribution systems include step-down distribution transformers, secondary
circuits (secondary mains), consumer services (or SDs), and meters to measure
consumer energy consumption.
Generally, the secondary distribution systems are designed in single
phase for areas of residential customers and in three phase for areas of
industrial or commercial customers with high-load densities.
Secondary Banking
The “banking” of the distribution transformers, that is, parallel
connection, or, in other words, interconnection, of the secondary sides of two or
more distribution transformers, which are supplied from the same primary
feeder, is sometimes practiced in residential and light-commercial areas where
the services are relatively close to each other, and therefore, the required
spacing between transformers is little. However, many utilities prefer to keep
the secondary of each distribution transformer separate from all others. In a
sense, secondary banking is a special form of network configuration on a radial
distribution system. The advantages of the banking of the distribution
transformers include the following:
1. Improved voltage regulation
2. Reduced voltage dip or light flicker due to motor starting, by providing
parallel supply paths for motor-starting currents
3. Improved service continuity or reliability
4. Improved flexibility in accommodating load growth, at low cost, that is,
possible increase in the average loading of transformers without corresponding
increase in the peak load
Banking the secondaries of the distribution transformers allows us to take
advantage of the load diversity existing among the greater number of
consumers, which, in turn, induces a savings in the required transformer
kilovolt-amperes. These savings can be as large as 35% , depending upon the
load types and the number of consumers.
Figure 2.23 shows two different methods of banking secondaries. The
method illustrated in Figure 2.24a is commonly used and is generally preferred
because it permits the use of a lower-rated fuse on the high-voltage side of the
transformer, and it prevents the occurrence of cascading the fuses. This
method also simplifies the coordination with primary-feeder sectionalizing
fuses by having a lower-rated fuse on the high side of the transformer.
Furthermore, it provides the most economical system.
Figure 2.24 gives two other methods of banking secondaries. The method
shown in Figure 2.24a is the oldest one and offers the least protection, whereas
the method shown in Figure 2.24b offers the greatest protection. Therefore, the
methods illustrated in Figures 2.23a and b and 2.24a have some definite
disadvantages, which include the following:
1. The requirement for careful policing of the secondary system of the banked
transformers to detect blown fuses.
2. The difficulty in coordination of secondary fuses.
3. Furthermore, the method illustrated in Figure 2.23b has the additional
disadvantage of being difficult to restore service after a number of fuses on
adjacent transformers have been blown.
Fig 2.23 Two different methods of banking secondaries: (a) type 1 and (b) type 2
Fig 2.24 Two additional methods of banking secondaries:
(a) type 3 and (b) type 4.
Today, due to the aforementioned difficulties, many utilities prefer the
method given in Figure 2.24b. The special distribution transformer known as
the completely self-protecting-bank (CSPB) transformer has, in its unit, a built-
in high-voltage protective link, secondary breakers, signal lights for overload
warnings, and lightning protection.
CSPB transformers are built in both single phase and three phase. They
have two identical secondary breakers that trip independently of each other
upon excessive current flows. In case of a transformer failure, the primary
protective links and the secondary breakers will both open. Therefore, the
service interruption will be minimum and restricted only to those consumers
who are supplied from the secondary section that is in fault.
However, all the methods of secondary banking have an inherent
disadvantage: the difficulty in performing TLM (Transformer Load Management)
to keep up with changing load conditions. The main concern when designing a
banked secondary system is the equitable load division among the
transformers. It is desirable that transformers whose secondaries are banked
in a straight line be within one size of each other.
For other types of banking, transformers may be within two sizes of each
other to prevent excessive overload in case the primary fuse of an adjacent
larger transformer should blow. Today, in general, the banking is applied to the
secondaries of single-phase transformers, and all transformers in a bank must
be supplied from the same phase of the primary feeder.