Instruction Manual
SF6 circuit--breaker
GL318
With spring operating mechanisms
FK3--4
This equipment contains Fluorinated Greenhouse Gas (SF6) covered by the Kyoto Protocol, which has
a Global Warming Potential (GWP) of 22200.
SF6 should be recovered and not released into the atmosphere.
For further information on the use and handling of SF6, please refer to IEC 62271: High-Voltage
Switchgear and Controlgear - Part 303: Use and Handling of Sulphur Hexafluoride (SF6).
03--2008 D1402EN/01
E AREVA 1/8
Content
Instruction Manual
03--2008 D1402EN/01
E AREVA 2/8
Content
Instruction Manual
Safety
Technical data
03--2008 D1402EN/01
E AREVA 3/8
Content
Instruction Manual
Installation
3,000 daN)
The installation procedure (advised), developed (minimum)
below, imposes a lifting equipment with the following
characteristics :
NOTE : If it is impossible to obtain the advoca- H+2m
ted lifting equipment, one “complementary instal-
lation procedure” is supplied in annexes.
H
H+1m
03--2008 D1402EN/01
E AREVA 4/8
Content
Instruction Manual
Installation, continued
Commissioning
03--2008 D1402EN/01
E AREVA 5/8
Content
Instruction Manual
Maintenance
Annexes
03--2008 D1402EN/01
E AREVA 6/8
Content
Instruction Manual
+ H
Installation, continued
03--2008 D1402EN/01
E AREVA 7/8
Content
Instruction Manual
03--2008 D1402EN/01
E AREVA 8/8
Technical data
Technical characteristics
Designation GL318
Standard IEC
Ur Rated voltage (r.m.s. value) kV 800
Ir Rated normal current A 4000
fr Rated frequency Hz 50
Ip Rated withstand current (peak value) kA 125
Ik Short--time withstand current (r.m.s. value) kA 50
Rated insulation level
(At sea level)
Rated short--duration power--frequency withstand
Ud
voltage (r.m.s. value)
D Phase--to--earth and phase--to--phase kV 830
D Across open contacts kV 1150
Rated lightning impulse withstand voltage (peak
Up
value)
D Phase--to--earth and phase--to--phase kV 2100
D Across open contacts kV 2100 (+455)
Rated breaking current in symmetrical short--
Isc kA 50
circuit
Rated making current (peak value) kA 125
Total break time ms 40 ±2
Rated operating sequence
O -- 0.3s -- CO -- 3min -- CO
Resistance of main contacts chamber without H.V. connectors
µΩ
(new contact) ≤ 80
The above characteristics are of a general nature, only those values given on
the circuit--breaker’s rating plates are contractually binding.
03--2006 L10--044EN/01
E AREVA 1/2
Technical data
Technical characteristics
Absolute pressures of The table below gives the absolute pressures of the SF6 gas mixture :
the SF6
gas mixture
SF6 The table below gives the masses of the SF6 gas :
gas masses
The above characteristics are of a general nature, only those values given on
the circuit--breaker’s rating plates are contractually binding.
Operating device The table below gives low voltage components characteristics of the FK3--4
operating device :
The above characteristics are of a general nature, only those values given on
the circuit--breaker’s rating plates are contractually binding.
03--2006 L10--044EN/01
E AREVA 2/2
Description and operation
General description of the circuit-- breaker
Description The circuit--breaker is made up of three poles. Each pole is made up of two
interrupting modules connected by an electric connection. Each interrupting
module is controled by an operating device.
Pole parts table The table below gives the main parts of the pole :
C E
03--2008 L12--055EN/01
E AREVA 1/8
Description and operation
General description of the circuit-- breaker
Interrupting module
Diagram
1
6
5 1
4
7
5 4
03--2008 L12--055EN/01
E AREVA 2/8
Description and operation
General description of the circuit-- breaker
Column
Support column Consisting of two, three or four ceramic insulators, the support column (2)
allows the circuit--breaker to be ground--insulated and it also encloses the
operating tie--rod which is attached to the interrupting chamber’s moving con-
tacts.
The support column can also be equipped with a corona ring (13).
Housing of the A housing (3) -- situated at the base of the column -- contains the lever and
mechanism crank assembly and which operates the moving contact.
Diagram
13
03--2008 L12--055EN/01
E AREVA 3/8
Description and operation
General description of the circuit-- breaker
Bearing structure
Description The support--frame (10) -- made up with four supports fastened to the housing
(3) -- supports all the circuit--breaker components.
The support--frame may be supplied by either AREVA or the customers.
Diagram
3
10
03--2008 L12--055EN/01
E AREVA 4/8
Description and operation
General description of the circuit-- breaker
Operating device
Description The operating device (11) is a spring operating mechanism of the FK3--4 type.
The door of the operating device (11) is equipped with two windows. These
windows permit to display the optical signalization of the circuit--breaker state
and closing spring state.
Diagram
11
03--2008 L12--055EN/01
E AREVA 5/8
Description and operation
General description of the circuit-- breaker
Marshalling cubicle
Description The marshalling cubicle (D) is fastened on the ground near the central
pole. Included with :
S The relays required to operate the circuit--breaker.
S The interconnection terminals boards.
S The terminals boards.
Diagram
03--2008 L12--055EN/01
E AREVA 6/8
Description and operation
General description of the circuit-- breaker
Electrical connection
Diagram
12
03--2008 L12--055EN/01
E AREVA 7/8
Description and operation
General description of the circuit-- breaker
03--2008 L12--055EN/01
E AREVA 8/8
Description and operation
Description of the interrupting chambers
Presentation
Diagram
Parts table The table below gives the main parts of the interrupting chambers :
06--2004 L12--105EN/02
E AREVA 1/4
Description and operation
Description of the interrupting chambers
Interrupting chamber
Quenching medium The quenching medium is pressurized SF6 gas or -- in particular instances --
pressurized SF6+CF4 gas mixture.
Interrupting principle The interrupting chamber is of thermal blasting type, using the energy from
the arc, with an auxiliary autopneumatic effect.
Diagram
1 2 4
Description The interrupting chamber has been designed in such a way as to increase the
mechanical resistance of the working part and take advantage of the low wear
rate of the contacts subjected to the arc in SF6. The working part is enclosed
in a leak tight ceramic envelope, providing insulation between the circuit--
breaker input and output.
The chamber is made up of the following elements :
06--2004 L12--105EN/02
E AREVA 2/4
Description and operation
Description of the interrupting chambers
Upper housing
Description The upper housing encloses the movement transfer mechanism (15) from the
operating tie--rod (8) to the moving contact (4) of the two chambers.
Diagram
4
4
15
Parts table The table below gives the housing internal and peripheral components :
06--2004 L12--105EN/02
E AREVA 3/4
Description and operation
Description of the interrupting chambers
06--2004 L12--105EN/02
E AREVA 4/4
Description and operation
Pole operation
(Interrupting principle)
Presentation
1 6 1
2 3 5
1 4
In this module This module contains the stages of the pole operation :
Stage Page
Opening 2
Closing 5
06--2004 L13--005EN/02
E AREVA 1/6
Description and operation
Pole operation
(Interrupting principle)
Opening
Opening When an electrical or manual opening order is given, the energy accumulated
in the opening spring (7) is released.
The insulating tie--rod (8), directly activated by the opening spring (7), trans-
mits the movement to the transfer mechanism (9) inside the housing which
causes the contacts to separate simultaneously in both chambers.
06--2004 L13--005EN/02
E AREVA 2/6
Description and operation
Pole operation
(Interrupting principle)
Opening, continued
Stage Description
Start of opening When the moving contact (4) separates from the main
contacts (3), the current is switched onto the arc con-
tacts (10). The compression of the (Vp) volume cau-
ses the first rise of pressure.
3 10 4 Vp
Thermal effect When the contacts (10) separate, the arc appears and
its energy causes the pressure to rise in the thermal
expansion volume (Vt), closed by the fixed contact rod
(11) and the insulating nozzle (12).
11 12 10 Vt
Interrupting and When the rod (11) comes out of the nozzle (12), the
assistance thermal overpressure in the volume (Vt) is released
at opening causing an energy blast to occur, just before the cur-
rent zero passage, ensuring final quenching of the arc.
The (Vp) volume pressure decreases to the ambient
pressure by means of the valve (13) to allow the end
of the opening.
11 12 Vt Vp 13
06--2004 L13--005EN/02
E AREVA 3/6
Description and operation
Pole operation
(Interrupting principle)
Opening, continued
Special case For small currents (example : operating no--load lines, transformers or ca-
of small currents pacitor banks), the thermal energy of the arc is too low to provide enough ex-
cess pressure.
Consequently, the conventional autopneumatic effect developing in the vol-
ume (Vp) is used mainly, to blast the arc.
Vp
06--2004 L13--005EN/02
E AREVA 4/6
Description and operation
Pole operation
(Interrupting principle)
Closing
Description When an electrical or manual closing order is given, the energy accumulated
in the closing spring (15) -- situated inside the operating device -- is released.
This energy is transmitted directly to the pole operating shaft (16), to ensure
closing.
The release of the energy stored up in the closing spring (15) causes displace-
ment of the moving parts -- and so the closing of the interrupting chambers
-- and also reloads the opening spring (7).
15
16
06--2004 L13--005EN/02
E AREVA 5/6
Description and operation
Pole operation
(Interrupting principle)
This page is intentionally blank.
06--2004 L13--005EN/02
E AREVA 6/6
Description and operation
Operating device of circuit--breaker
Presentation
Topic Page
Description of the mechanism 2
Auxiliary fittings 3
Operating principle 5
05--2003 L14--005EN/03
E AREVA 1/6
Description and operation
Operating device of circuit--breaker
Drive shaft D The main shaft (1) is linked up to the the circuit--breaker pole by means
of a cylinder (2).
D A damper (4) is linked up to the lever (32).
D In the “CLOSED” position, the main shaft (1) rests on the opening latch
(6) by means of the lever (5).
D In the “OPEN” position, the lever with roller (11) rests on the closing
cam (10).
D The opening spring (3) activates the lever (33) by means of the chain
(34). This spring is a pressure helical type.
NOTE : The levers (5)--(11)--(32) (33) form one piece only.
9
Diagram
15
17 34 3
33
30
2
8 1
32
11
12 4
10 6
7 31
11
16 14 26 5
32
5
33
34
11 33 17 12
05--2003 L14--005EN/03
E AREVA 2/6
Description and operation
Operating device of circuit--breaker
Auxiliary fittings
Reloading the closing The closing spring (9) is loaded by means of the reducing gears (13) and the
spring motor (12).
Auxiliary electric D The auxiliary contacts (30) are activated by a rod and a lever (31), the
fittings latter is activated by the main shaft (1).
D The limit switch of the motor (17) is activated by the cam (26)
The cam (26) is installed on the closing shaft (7).
D The closing latch (14) and the opening latch (6) are electrically activated
by coils (22) “Closing” and (27) “Opening”.
Auxiliary mechanical D The operating mechanism can be activated by the manual levers (24)
fittings “Closing” and (28) “Opening”.
WARNING : Operating the mechanism by the manual levers (24) “Closing”
and (28) “Opening” overrides electrical interlocks. Ensure it is electrically safe
to operate the equipment when using these levers to defeat electrical inter-
locks and lockouts.
D The indicator (29) gives the “OPEN” or “CLOSED” positions of the circuit--
breaker. An operation counter (36) gives the number of realized operations.
D The indicator (23) gives the “CHARGED” or “DISCHARGED” states of the
closing spring.
D If the auxiliary current supply fails, the hand--held crank (21) permits the
closing spring to be fully charged.
Diagram
9
30
17
34
1
23 6
29
12 27
7
26
31 28
14 22
21 13 24
05--2003 L14--005EN/03
E AREVA 3/6
Description and operation
Operating device of circuit--breaker
Operating principle
Closing D When the closing coil is energized or the manual closing lever is operated,
the closing latch (14) releases the inertia flywheel (8).
D The closing shaft (7) effects a 180° rotation generated by the loaded clos-
ing spring (9).
D The cam (10) rotates the main shaft (1) by means of the lever with roller
(11). After a 60° rotation, the lever (5) rests on the opening latch (6).
D Simultaneously, the opening spring (3) is loaded by means of the chain (34)
activated by the rotation of the lever (33).
D A freewheel, installed on the gear wheel (19), avoids the reducing gears
(13) and the motor (12) being driven by the gear wheel of the inertia flywheel
(8).
NOTE : A mechanical device (not shown) prevents all closing opera-
tions if the circuit--breaker is already in the “CLOSED” position.
Diagram
34
3
33
1
5
12 11 27
7
10
22
24 28
13 19 14
05--2003 L14--005EN/03
E AREVA 4/6
Description and operation
Operating device of circuit--breaker
Reloading the closing D When the motor (12) is supplied with current, it immediately starts to load
spring the closing spring (9) by means of the reducing gears (13) of the inertia fly-
wheel (8) and the chain (15).
D At the full stroke, the gear (19) is at the no tooth sector of the inertia flywheel
(8) and the reducing gears (13) can decelerate without causing strain on the
closing latch (14).
NOTE : During the loading of the closing spring, the supplying circuit
of the closing coil is cut to avoid an untimely closing operation.
Diagram
9
15
8
14
19
12 13 19
05--2003 L14--005EN/03
E AREVA 5/6
Description and operation
Operating device of circuit--breaker
Opening D When the opening coil (27) is energized or the manual opening lever (28)
is operated, the opening latch (6) releases the lever (5).
D The main shaft (1) effects a 60° clockwise rotation -- generated by the
loaded opening spring (3) -- before reaching the circuit--breaker “OPEN” posi-
tion.
D A damper (4) dampens the excess energy to smoothly finish travel.
Diagram
3
60°
1
6
4
5
27
28
05--2003 L14--005EN/03
E AREVA 6/6
Description and operation
SF6 gas monitoring
Presentation
Introduction The circuit--breaker uses pressurized SF6 gas as electric arc quenching gas.
The SF6 gas pressure monitoring is essential to assure the circuit--breaker
performances.
Symbol Designation
pre Filling rated pressure for the insulation
pae Alarm pressure for the insulation
pme Minimal pressure for the insulation
Topic Page
Gas pressure and density 2
Pressure measurement 3
Measuring density 4
Densimeter 5
09--2004 L20--001EN/06
E AREVA 1/6
Description and operation
SF6 gas monitoring
Introduction The electrical characteristics of switchgear depend on the density of SF6 gas
i.e. the mass of gas pumped into a compartment of a given volume.
Constant density At constant density, with an fixed compartment volume, the pressure
changes in the same way as the temperature. Since the gas density re-
mains invariable owing to the fact that no modification occurs in the quanti-
ty of gas or the volume of the relevant compartment, the electrical charac-
teristics of the switchgear will remain unchanged.
09--2004 L20--001EN/06
E AREVA 2/6
Description and operation
SF6 gas monitoring
Pressure measurement
Atmospheric pressure
09--2004 L20--001EN/06
E AREVA 3/6
Description and operation
SF6 gas monitoring
Measuring density
Measuring density When it is not possible to directly measure density, this may be checked
using an industrial pressure gauge capable of measuring the effective
pressure.
An effective pressure value corresponds to the rated density, determined
for normal atmospheric pressure (101.3 kPa) and an ambient temperature
of 20°C (68°F).
For each pressure reading (filling, inspection of densimeter thresholds...), the
rated effective pressure should be corrected according to the ambient tem-
perature and atmospheric pressure of the site at the time the reading is taken.
See the module “Calculation of the SF6 gas filling pressure to using the
pressure gauge (tool)”.
09--2004 L20--001EN/06
E AREVA 4/6
Description and operation
SF6 gas monitoring
Densimeter
Localization The densimeter is situated onto the bottom of the pole of the circuit--breaker,
and joined to the gas volume of the circuit--breaker.
Working The densimeter is fitted with internal contacts. These contacts close succes-
sively if the gas’s density diminishes and determine 2 distinct thresholds.
These contacts are wired to the terminal block inside the cubicle and are usu-
ally left at the user’s disposal for the following use :
D Alarm pressure ”pae” acts as a warning (topping up necessary).
D Minimum functional pressure for insulation ”pme” must be used either to
lock the circuit--breaker in position or to cause automatic opening. The option
is chosen by the client in keeping with operating requirements.
09--2004 L20--001EN/06
E AREVA 5/6
Description and operation
SF6 gas monitoring
Densimeter, continued
Reading the dial The dial is divided into three colored areas : Green, Yellow and Red. The posi-
tion of the needle indicates the SF6 gas absolute pressure value.
-1
GREEN None
Perform a topping--up
YELLOW
operation.
09--2004 L20--001EN/06
E AREVA 6/6
Packaging -- Shipping and storage
Packaging - Identification - Storage
Presentation
Information The different parts of the poles (chambers and column) are filled with nitrogen
(N2) for transport purposes to an effective pressure of 0.03 MPa at 20°C
(68°F) and 101.3 kPa.
Topic Page
Packaging 2
Identifying sub--assemblies and their packaging 3
Storage 4
05--2006 L22--007EN/03
E AREVA 1/6
Packaging -- Shipping and storage
Packaging - Identification - Storage
Packaging
Introduction For transport, the different parts of the apparatus are divided--up between
several cases :
S Interrupting chambers.
S Columns + (corona rings, electrical connections ...).
S Operating devices : each operating device is vacuum--wrapped in a pro-
tective bag containing desiccants.
S Frames if the latter is supplied by AREVA.
S The SF6 bottle(s) or -- in particular instances -- SF6 bottle(s) and CF4
bottle(s).
S Marshalling cubicle.
S Assembly products (grease, oil, etc.) used for installation.
S Capacitors (if the apparatus is equipped with these).
Characteristics of The table below gives the characteristics of the circuit--breaker components
packaging cases packaging cases depending on the apparatus :
Packaging case Length Width Height Gross weight
Qty
type cm cm cm kg
Interrupting cham-
bers 2 513 181 136
x 3
Columns
2 627 191 105
(4 insulators)
Frame
2 546 96 96
(H = 4877 mm)
Operating device 2 318 103 144
SF6 gas *
(SF6+CF SF gas *
6
4)
gas
CF4 gas *
mixture
Marshalling cubicle 1 131 76 172 284
Necessities (prod-
ucts) 1 60 60 70 37
for assembly
Capacitors * 2 266 141 124
05--2006 L22--007EN/03
E AREVA 2/6
Packaging -- Shipping and storage
Packaging - Identification - Storage
2 MANUFACTURER
REFERENCE No.
1
POSITION IN
CASE No.
THE SAME
PHASE
CIRCUIT--BREAKER PHASE
IDENTIFICATION No. NUMBER
Place of the plates Choose and install the components identified by the plate (1).
01/1-- 1
01/2-- 2
01/2-- 1 01/3-- 2
01/3-- 1
OUTSIDE PLATE
INSIDE PLATE
05--2006 L22--007EN/03
E AREVA 3/6
Packaging -- Shipping and storage
Packaging - Identification - Storage
Storage
Introduction The storage procedures defined below are for storage times of less than 2
years. For longer periods, special packaging must be designed and appropri-
ate procedures devised.
Short--term storage The apparatus must be stored in its transport packaging and placed on beams
(6 months) in a flood--proof place.
Medium--term storage The table below indicate how to stock the main components of the circuit---
(less than 2 years) breaker for a medium--term storage :
Component Storage
The apparatus must be stored with its
Components transport packaging open whilst
of the circuit--breaker pole placed on beams in a closed (indoor),
but ventilated, flood--proof place.
The operating device should be
stored in the same place as the cir-
cuit--breaker, these two sub--assem-
blies being inseparable. Check that
the vacuum packaging is leak--tight.
If this has been damaged, proceed as
follows :
Operating device S The operating device should be
placed so that air can enter through
the vents of the rear plate and side
panels.
S In order to prevent corrosion dam-
age due to formation of condensation,
it is mandatory that the heating circuit
be switched on.
05--2006 L22--007EN/03
E AREVA 4/6
Packaging -- Shipping and storage
Packaging - Identification - Storage
Storage
05--2006 L22--007EN/03
E AREVA 5/6
Packaging -- Shipping and storage
Packaging - Identification - Storage
05--2006 L22--007EN/03
E AREVA 6/6
Installation
Erection general instructions
Instructions The table below gives the instructions of environment to respect for the erec-
of environment tion :
Instruction Comment
Verify the Civil engineering work : dimensions,
levels of concrete pads (structure fixation), in
A accordance with the tolerances given by Civil
work standards (refer to circuit--breaker out-
line).
Erection The table below gives the instructions to respect for proper erection of the cir-
instructions cuit--breaker :
Instruction Comment
Read all the “Installation” modules completely
before beginning erection works.
1 The erection instructions describe all the proce-
dures to be carried out as well as their chrono-
logical order.
Warning No responsibility is taken over by AREVA T&D S.A. for damages and dis-
turbances resulting out of non--adherence to the “Installation” modules.
06--2004 L30--002EN/01
E AREVA 1/2
Installation
Erection general instructions
06--2004 L30--002EN/01
E AREVA 2/2
Installation
Tightening torques
Presentation
Introduction In the assembling with screws, all the fastening screws must be “greased” be-
fore torque tightening.
Products used The table below gives the list of the used products for the screws before tight-
ening :
Topic Page
Screw greasing before tightening 2
Tightening torques values 3
06--2004 L31--001EN/01
E AREVA 1/4
Installation
Tightening torques
Choice of the The table below gives the product to use for the screws before tightening de-
product to use pending on the assembling type :
Can be
Product ...
dismantled ?
with seals
YES MOLYKOTE 111
NO LOCTITE 225
Where to apply The table below indicates the part of the screws to treat with the appropriate
the product ? product before tightening depending on the assembling type :
usual
electrical connections
Tapping or threading
with seals
Tapping or threading
06--2004 L31--001EN/01
E AREVA 2/4
Installation
Tightening torques
Values table The tool and the tightening method must be such that the torque actually ap-
plied to the screw head corresponds with the reference torque shown in the
table below, to within a tolerance of ± 20%.
TIGHTENING TORQUES
in daN.m
daN m
STEEL SCREWS
CLASS 6.8
or
CLASS 8.8
88
STAINLESS A2--70, A4--70
STAINLESS A2--80, A4--80
06--2004 L31--001EN/01
E AREVA 3/4
Installation
Tightening torques
06--2004 L31--001EN/01
E AREVA 4/4
Installation
Erection general procedures
Presentation
Introduction During the erection of the circuit--breaker, some particular mounting or check-
ing operations will be realized.
Topic Page
Preparing and installing static seals 2
Screw sealing 3
Using a water pressure gauge 5
06--2004 L31--003EN/01
E AREVA 1/6
Installation
Erection general procedures
Necessary products List of the AREVA products necessary for the installing :
AREVA
Diagram Designation
reference
Process The table below gives the steps of installing static seals :
Step Action Comment
1 Clean bearing grooves and sur-
faces using ISOPROPANOL.
2 Rid the seal of all foreign bodies Check the condition of the seal
such as paintbrush bristles or fil- which should present no
ings... scratches or deformation (it
Remove (where applicable) the should be neither flattened,
color identification point with fin- stretched, nor broken).
gernail, never with a sharp instru-
ment.
3 Lightly lubricate the seal by hand Do not use a brush to do this.
using MOLYKOTE 111 grease. Eliminate excess grease by
squeezing the seal between
fingers, leaving only a thin layer
on the entire surface.
4 Put the seal(s) in place.
5 Lubricate both bearing surfaces Do not put grease on the inside
with MOLYKOTE 111. surface.
Fill the residual volume of the
seal’s outside groove with grease.
06--2004 L31--003EN/01
E AREVA 2/6
Installation
Erection general procedures
Screw sealing
Introduction To prevent humidity from penetrating SF6 gaskets, the outer mounting screws
should be sealed by applying an appropriate product.
NOTE : This procedure should be applied to all assemblages of parts
submitted to SF6 pressure and electrical connection assembling.
Necessary products List of the AREVA products and accessories necessary for the screw seal-
ing :
AREVA
Diagram Designation
reference
Choice of the The table below gives the product to use for the screw sealing depending on
product to use the assembling type :
Can be
Product ...
dismantled ?
with seals
YES MOLYKOTE 111
NO LOCTITE 225
06--2004 L31--003EN/01
E AREVA 3/6
Installation
Erection general procedures
Where to apply The table below indicates the part of the screws to treat with the appropriate
the product ? product before tightening depending on the assembling type :
Tapping or threading
Tapping or threading
06--2004 L31--003EN/01
E AREVA 4/6
Installation
Erection general procedures
Introduction In each assemblage performed using a double seal (1) and (2), the volume
(3) communicates with the outside by a channel (4), blocked--off by a plug (5)
or (6), so that leak--tightness can be checked.
4
6
5
Process The table below gives the steps of the leak--tightness checking using a
water pressure gauge :
2...3 turns 6
8
9
06--2004 L31--003EN/01
E AREVA 5/6
Installation
Erection general procedures
06--2004 L31--003EN/01
E AREVA 6/6
Installation
Checking for presence of nitrogen (N2)
in pole parts
Presentation
Introduction The pole parts (chambers and columns) are filled with nitrogen (N2) for trans-
port purposes to an effective pressure of 0.03 MPa at 20°C and 101.3 kPa.
Necessary tools List of the necessary AREVA tools for the checking for presence of N2 gas in
poles :
Topic Page
Checking for presence of N2 gas in columns 2
Checking for presence of N2 gas in interrupting chambers 4
03--2008 L31--074EN/01
E AREVA 1/4
Installation
Checking for presence of nitrogen (N2)
in pole parts
Visual inspection Begin visual inspection to check the condition of ceramic envelopes. Make
of the column sure that their enamel has not been chipped or in any way damaged during
transportation.
03--2008 L31--074EN/01
E AREVA 2/4
Installation
Checking for presence of nitrogen (N2)
in pole parts
Process The table below gives the steps of manual checking for presence of N2 gas
in columns :
1 3
3
4
03--2008 L31--074EN/01
E AREVA 3/4
Installation
Checking for presence of nitrogen (N2)
in pole parts
Comment A transport cover (5) is installed on the housing (6) common to both interrup-
tion chambers. This cover is equipped with a test valve, in turn protected by
a plug (8). The case is fitted with a outside trap--door to have access to the
transport cover.
Process The table below gives the steps of checking for presence of N2 gas in the inter-
rupting chambers (case trap--door removed) :
Step Action Diagram
1 Remove the plug (8) by undoing
the screws (9) and briefly press on 7
the valve clapper (7) : some gas
should escape. 8
x 2
H M6--20
0,7 daN.m
03--2008 L31--074EN/01
E AREVA 4/4
Installation
Support-- frame assembly
Presentation
Topic Page
Components necessary for the operation 2
Support--frame components (per pole) 3
Preparing the column 5
Frame--support assembly 6
Installing the lifting tools 10
10--2006 L31--137EN/02
E AREVA 1/10
Installation
Support-- frame assembly
Lifting strap
(1) 2
(3 m)
10--2006 L31--137EN/02
E AREVA 2/10
Installation
Support-- frame assembly
(2) Support 2
(3) Support 2
Screws
(5) 1
H M16-45
Screws
(7) 16
H M16-35
Washer
(9) 16
NORDLOCK NL16 SS
10--2006 L31--137EN/02
E AREVA 3/10
Installation
Support-- frame assembly
Screws
(20) 16
H M16-45
10--2006 L31--137EN/02
E AREVA 4/10
Installation
Support-- frame assembly
Preparing the pole D Sling the “A” column with the aid of two flexible lifting straps (1).
D Extract the column from the case and put it down on the case wood cover
laying :
-- first, the end of the column,
-- second, the support of the operating mechanism (4) on a wedge to ensure
the correct installing of the frame supports.
X minimum = 260 mm
10--2006 L31--137EN/02
E AREVA 5/10
Installation
Support-- frame assembly
Process The table below gives the steps of installing the supports of the frame :
Step Action
1 With the aid of two flexible lifting straps, position the frame--support
(3) onto the housing (10) and fasten it with the use of the screws (7)
and NORDLOCK washers (9). Do not tighten the screws (7).
-- Install the screw (5) only on this support.
10
x1 3
5
2x2
9 H M16--45
7
H M16--35
2 With the aid of two flexible lifting straps, position the frame--support
(2) onto the housing (10) and fasten it with the use of the screws (7)
and NORDLOCK washers (9). Do not tighten the screws (7).
2
10
2x2
9
7
H M16--35
10--2006 L31--137EN/02
E AREVA 6/10
Installation
Support-- frame assembly
Process, continued The table below gives the steps of installing the supports of the frame :
Step Action
3 Install the strengthening pieces (21)--(25) inside the frame--support
(2) with the use of the screws (20). Adjust the distance between the
supports and fasten the strengthening pieces (21)--(25) on the
frame--support (3). Do not tighten the screws (20).
x4
20
3
25
21 H M16--45
4 With the aid of two flexible lifting straps, position the frame--support
(2) onto the housing (10) and fasten it with the use of the screws (7)
and NORDLOCK washers (9). Do not tighten the screws (7).
10
2x2
9
7
2
H M16--35
5 With the aid of two flexible lifting straps, position the frame--support
(3) onto the housing (10) and fasten it with the use of the screws (7)
and NORDLOCK washers (9). Do not tighten the screws (7).
10
2x2
9
7
H M16--35
Continued on next page.
10--2006 L31--137EN/02
E AREVA 7/10
Installation
Support-- frame assembly
Process, continued The table below gives the steps of installing the supports of the frame :
Step Action
6 Install the strengthening pieces (21)--(25) inside the frame--support
(3) with the use of the screws (20). Adjust the distance between the
supports and fasten the strengthening pieces (21)--(25) on the
frame--support (2). Do not tighten the screws (20).
21
3
2x2
20
25
21
H M16--45
2 25
x2
20
24
24
H M16--45
x2
20
24
24
H M16--45
10--2006 L31--137EN/02
E AREVA 8/10
Installation
Support-- frame assembly
Process, continued The table below gives the steps of installing the supports of the frame :
Step Action
8 Tighten all the screws to the recommended torques.
18 daN.m
10--2006 L31--137EN/02
E AREVA 9/10
Installation
Support-- frame assembly
(16) Washer 8
Process The table below gives the steps of installing the lifting tools on the support---
frame :
Step Action
1 Install the lifting shackle (14) in the holes of the frame.
2 Install the ring bolts (15) on the base of the frame, inserting the thick
washers (16).
14
x4 16
15
10--2006 L31--137EN/02
E AREVA 10/10
Installation
Column -- chambers coupling
Presentation
Identification Before the chambers -- column coupling, check that interrupting chambers
and column reference numbers are the right ones.
Coupling duration The final chambers -- column coupling operations must be realized in dura-
tion no longer than 40 min.
NOTE : The coupling operations should be performed by at least two
persons.
T(max) ≤ 40 min
H
H+1m
Coupling steps The chambers -- column coupling must be done in several steps :
Step Topic Page
A Positioning the case of the chambers 2
B Preparing the interrupting chambers 3
C Preparing the column stress--shields 4
D Preparing the necessary components for the coupling 5
E Lifting and preparing the column 7
F Final coupling 8
04--2005 L31--715EN/01
E AREVA 1/14
Installation
Column -- chambers coupling
Introduction To facilitate the lifting of the poles, and to work in complete safety, it is essen-
tial that the cases be positioned correctly in relation to the lifting equip-
ment.
Positioning of the Using the lifting equipment, position the first case in such a way that :
case S the axis chambers is perpendicular with the lifting plane.
S the space between the case and the lifting equipment is superior of the col-
umn fitted with the frame “L” + 2 m.
NOTE : The cradle of the first chamber will be use for the column--
chambers coupling of the three poles.
Diagram
L+2m
04--2005 L31--715EN/01
E AREVA 2/14
Installation
Column -- chambers coupling
Dismantling the case Remove the cover and the side panels of the case.
of the chambers
Rotation With two flexible lifting straps, revolve the chambers of 180° and make the
of the chambers transport cover level.
NOTE : Orient the housing (2) in such a way the bosse is situated
on the lifting equipment side.
04--2005 L31--715EN/01
E AREVA 3/14
Installation
Column -- chambers coupling
Necessary AREVA List of the AREVA components necessary for the assembling (per pole) :
components
(32) Bracket 4
Screws
(34) 4
H M10-30
Assembling Install the brackets (32) on the stress--shields ring (33) using screws (34)
do not tighten.
32
33
x 4
34 H M10--30
Positioning Install temporarily the stress--shields ring (33) -- brackets (32) to chambers
side -- around the housing (2).
32 33
04--2005 L31--715EN/01
E AREVA 4/14
Installation
Column -- chambers coupling
Necessary AREVA List of the AREVA components necessary for the coupling :
components
(12) Seal 1
Screw
(14) H M16--60 (19 mm) 8
H M16--70 (30 mm)
Washer
(15) 16
M16
(16) Nut 8
04--2005 L31--715EN/01
E AREVA 5/14
Installation
Column -- chambers coupling
Necessary AREVA List of the AREVA tools necessary for the coupling :
tools
(7) Stop 1
(8) Lever 1
04--2005 L31--715EN/01
E AREVA 6/14
Installation
Column -- chambers coupling
Lifting strap
(45) 4
(3 m)
Process The table below gives the steps of lifting the column :
Step Action Diagram
1 Install the strands of the lifting
strap (45) on the lifting tool at 45
the end of the supports.
x4
04--2005 L31--715EN/01
E AREVA 7/14
Installation
Column -- chambers coupling
Final coupling
Column orientation Orient the column (1) in such a way the support (3) of the operating mech-
anism is situated on the same side as the boss of the housing (2).
Assembling the Assemble sections A, B and C of the spindles (17) and (18), without over--
centering spindles tightening, so that these can be removed later without difficulty.
NOTE : Spindle (18) is longer than spindle (17).
17
C
18
B
A
Deflating the S Remove the plug (5) from the transport cover (4) and press valve (6) to
chambers bring the volume of chambers back to ambient pressure.
REMINDER : transport gas pressure : nitrogen (N2) at 0.03 MPa at 20°C
(101.3 kPa).
S Install the plug (5).
6 5
04--2005 L31--715EN/01
E AREVA 8/14
Installation
Column -- chambers coupling
Removing the The table below gives the steps of removing the transport cover of the
transport cover of the interrupting chambers :
interrupting
chambers
H M16--55
11
10
Installing the Install the centering spindles (17) and (18) so that these come to rest against
centering spindles the sphere of housing (2), tighten the nuts (30) a little.
Install the screws (39) on the centering spindles (17) and (18).
Place the protection tool (19).
17 18
39 19
39
30
2
30
Removing the cover The table below gives the steps of removing the cover of the column :
of the column
22
x 8
23
H M16--55
22
Installing the seal The table below gives the steps of installing the seal :
12
12 21
04--2005 L31--715EN/01
E AREVA 11/14
Installation
Column -- chambers coupling
Mounting The table below gives the steps of mounting the chambers -- column cou-
coupling pin pling pin :
Step Action Diagram
1 Move down slowly the column
(1) introducing the centring
spindles (17) and (18) into the 1
holes of the flange.
26 18
17
2 Move down slowly the column 10
to align the hole of the cylinder
(10) with the hole of the tie--rod
(26).
20
4 Remove the tool (20).
11
20
10
19
04--2005 L31--715EN/01
E AREVA 12/14
Installation
Column -- chambers coupling
B
A
28
12
28
04--2005 L31--715EN/01
E AREVA 13/14
Installation
Column -- chambers coupling
30
04--2005 L31--715EN/01
E AREVA 14/14
Installation
Tipping down the pole of the circuit-- breaker
and vacuum operation
Presentation
Introduction The column--chambers coupling is now finished -- the pole is yet maintained
by the lifting equipment. In order to continue the pole installation, it is neces-
sary now to lay it on the ground.
Topic Page
Tipping down the pole of the circuit--breaker 2
Vacuum operation 3
Protection of the interrupting chambers 4
06--2004 L31--721EN/02
E AREVA 1/4
Installation
Tipping down the pole of the circuit-- breaker
and vacuum operation
Process The table below gives the steps of tipping down the pole of the circuit--
breaker :
Step Action
1 Using the lifting device, slowly tip down the pole around the axis of
the interrupting chambers until the ground.
14 x4
11
13
15
12
06--2004 L31--721EN/02
E AREVA 2/4
Installation
Tipping down the pole of the circuit-- breaker
and vacuum operation
Vacuum operation
Principle The procedure of the vacuum operation depends on the duration of cham-
bers/column coupling.
06--2004 L31--721EN/02
E AREVA 3/4
Installation
Tipping down the pole of the circuit-- breaker
and vacuum operation
Introduction It is important to protect the insulators of the interrupting chambers during the
next operations (installing the terminals, installing the capacitors ...)
06--2004 L31--721EN/02
E AREVA 4/4
Installation
Installing terminals
with preparation of contact surfaces
Presentation
Diagram
01/1-- 1
01/2-- 1
01/3-- 1
01/1-- 2
01/2-- 2
01/3-- 2
01/1-- 2
01/1-- 1
01/2-- 2
01/2-- 1 01/3-- 2
01/3-- 1
Topic Page
Components, products and accessories 2
Preparing the contact surfaces 3
Installing terminal 4
08--2004 L31--734EN/01
E AREVA 1/4
Installation
Installing terminals
with preparation of contact surfaces
Necessary List of the AREVA components necessary for the assembling (per pole) :
components
Mark Diagram Designation Number
(1) Terminal 1
Screws
(3) 4
H M12--45
Necessary products List of the AREVA products and accessories necessary for the installing :
and accessories
AREVA
Diagram Designation
reference
--02212334 Rag
08--2004 L31--734EN/01
E AREVA 2/4
Installation
Installing terminals
with preparation of contact surfaces
Preparing the The contact grease is a mixture composed of Vaseline and Contactal grease.
contact grease CONTACT GREASE = 50% Vaseline + 50% Contactal grease
Preparing the The table below gives the steps of preparing the contact surfaces :
contact surfaces
01/3-- 2
Remove the temporary screws
1 from the terminal pads X1 or X1
X2. 01/1-- 1
01/2-- 1
01/3-- 1
08--2004 L31--734EN/01
E AREVA 3/4
Installation
Installing terminals
with preparation of contact surfaces
Installing terminal
Process Assemble immediately the terminal (1) on one interrupting chamber (2) after
preparation of contact surfaces. Fasten the terminal using screws (3); use
CONTACT GREASE to seal the screws.
01/1-- 1
2 01/2-- 1
2 01/3-- 1
2
01/1-- 2
01/2-- 2
01/3-- 2
x 4
3
H M12--45
5 daN.m 1
08--2004 L31--734EN/01
E AREVA 4/4
Installation
Installing the capacitors
Presentation
Diagram
Lifting strap
(12) 2
(3 m)
12--2004 L31--741EN/03
E AREVA 1/4
Installation
Installing the capacitors
Necessary List of the AREVA components necessary for the assembling (per pole) :
components
(1) Capacitor 2
(3) Support 2
Support
(4) 2
or (depending on the apparatus)
Screws
(5) 8
H M12-30
Screws
(8) 4
H M12-45
Screws
(9) 4
H M12-25
(1) Spacer 4
12--2004 L31--741EN/03
E AREVA 2/4
Installation
Installing the capacitors
Installing S Install the support (3) on the capacitor (1) using the screws (5).
the supports
S Install the support (4) on the capacitor (1) using the screws (5).
x 2
5
4
4
x 2 H M12--30
5 5 daN.m
3 H M12--30
5 daN.m
12--2004 L31--741EN/03
E AREVA 3/4
Installation
Installing the capacitors
Process Install the capacitors (1) on the interrupting chambers (6) and (7) using the
screws (8) and (9).
NOTE : Use the two spacers (10) to install the capacitors -- capacitor
support (4) side.
x 2
9
x 2 H M12--25
9 5 daN.m
1
1
H M12--25
5 daN.m
x 2 4
8
4 10 10
H M12--45
5 daN.m
12--2004 L31--741EN/03
E AREVA 4/4
Installation
Installing stress--shields on the interrupting chambers
Presentation
Diagram
Topic Page
Preparing the stress--shields 2
Installing the stress--shields 3
12--2004 L31--750EN/04
E AREVA 1/4
Installation
Installing stress--shields on the interrupting chambers
Necessary AREVA List of the AREVA components necessary for the assembling (per pole) :
components
(2) Bracket 8
Screws
(3) 8
H M10-30
Assembling Install the brackets (2) on the stress--shields ring (1) using screws (3) do not
tighten.
x 4
H M10--30
12--2004 L31--750EN/04
E AREVA 2/4
Installation
Installing stress--shields on the interrupting chambers
Necessary AREVA List of the AREVA components necessary for the assembling (per pole) :
components
Screws
(5) 8
H M12-30
Process Install the stress--shields (1) at each end of the interrupting chambers (4)
using the screws (5).
1
4
x 4
5
H M12--30
5 daN.m
12--2004 L31--750EN/04
E AREVA 3/4
Installation
Installing stress--shields on the interrupting chambers
12--2004 L31--750EN/04
E AREVA 4/4
Installation
Lifting and positionning the pole
Presentation
Necessary tools List of the necessary AREVA tools for the lifting and positionning of the pole :
LIFTING STRAP
(1) 4
(3 m -- 1000 kg)
LIFTING STRAP
(2) 4
(6 m-- 1000 kg)
Topic Page
Positioning the lifting straps 2
Lifting the pole 3
Positioning the pole 4
04--2007 L31--766EN/04
E AREVA 1/4
Installation
Lifting and positionning the pole
Process The table below gives the steps of positioning the lifting straps :
Step Action
1 D For poles of circuit--breakers fitted with a column made up with
three insulators, four 6 m lifting straps are sufficient.
D For columns made up with four insulators, prepare four wholes :
one 3 m lifting strap (1) knotted with one 6 m lifting strap (2).
2 Pass the lifting straps like the picture below.
-- The lifting straps “a” pass over the housing (7).
-- The lifting straps “b” pass under the housing (7).
3 Cross the lifting straps “a” and “b” and place them onto the frame
using the four lifting shackles (8).
8
b
a
7 b
a
1
2
8
04--2007 L31--766EN/04
E AREVA 2/4
Installation
Lifting and positionning the pole
Process By means of a lifting device hoist the pole up whilst allowing it to rest on the
base of the frame.
Place the trip ropes (10) on the support legs of the chassis frame (9) to ensure
guidance of the pole at the time of lifting.
Lift the pole with precaution.
10
04--2007 L31--766EN/04
E AREVA 3/4
Installation
Lifting and positionning the pole
Process The table below gives the steps of positioning the pole :
Step Action
1 Use a lifting device to position the chassis frame onto its ground
attachment points but do not secure it, whilst respecting the orienta-
tion of the pole indicated on the sketch of the device.
2 If necessary, place shims under the supports of the frame so that the
upper plate is level.
3 Install the washers (12) and clamp the whole to the ground using nut.
4 Remove the lifting straps.
5 Check the tightening torques of all frame screws.
18 daN.m
6 Tighten the fixings on the two floor seatings in accordance with the
module entitled ’Tightening Torques’ and in accordance with the
diameters of the anchoring points.
12
04--2007 L31--766EN/04
E AREVA 4/4
Installation
Installing electric connection
with preparation of contact surfaces
Presentation
Diagram
Topic Page
Components, products and accessories 2
Preparing the connection 3
Installing the connection 5
08--2004 L31--770EN/02
E AREVA 1/8
Installation
Installing electric connection
with preparation of contact surfaces
Necessary List of the AREVA components necessary for the assembling (per pole) :
components
(1) Terminal 2
(5) Connection 2
(6) Flange 2
(7) Stud 2
Washer
(9) 2
M20
Nut
(10) 2
H M20
Screws
(11) 8
CHc M16--55
08--2004 L31--770EN/02
E AREVA 2/8
Installation
Installing electric connection
with preparation of contact surfaces
Necessary products List of the AREVA products and accessories necessary for the installing :
and accessories
AREVA
Diagram Designation
reference
--02212334 Rag
08--2004 L31--770EN/02
E AREVA 3/8
Installation
Installing electric connection
with preparation of contact surfaces
Preparing the The contact grease is a mixture composed of Vaseline and Contactal grease.
contact grease CONTACT GREASE = 50% Vaseline + 50% Contactal grease
Preparing the The table below gives the steps of preparing the contact surfaces :
contact surfaces
x2
3 Coat with CONTACT
GREASE.
x2
4 Wipe with a clean rag, leav-
ing just a thin layer of
grease.
08--2004 L31--770EN/02
E AREVA 4/8
Installation
Installing electric connection
with preparation of contact surfaces
Assembling the The table below gives the steps of assembling the connection :
connection
x4
11
1
CHc M16--55
x2 13,5 daN.m
5
5
08--2004 L31--770EN/02
E AREVA 5/8
Installation
Installing electric connection
with preparation of contact surfaces
Assembling the The table below gives the steps of assembling the connection :
connection, continued
4
9
10
08--2004 L31--770EN/02
E AREVA 6/8
Installation
Installing electric connection
with preparation of contact surfaces
Preparing the The table below gives the steps of preparing the contact surfaces :
contact surfaces
X1 X2
4 Coat with CONTACT
GREASE.
08--2004 L31--770EN/02
E AREVA 7/8
Installation
Installing electric connection
with preparation of contact surfaces
Fastening the The table below gives the steps of fastening the connection :
connection
Step Action
1 Sling the connection with the aid of one flexible lifting strap (12).
2 Insert the connection between the interrupting chambers (2). Move
the terminal (1) inside to make the operation easier.
3 Fasten the first terminal to the interrupting chamber using screws (3);
use CONTACT GREASE to seal the screws.
4 Move the terminal (1) to the other interrupting chamber and fasten it
using screws (3); use CONTACT GREASE to seal the screws.
5 Tighten -- to recommended torques -- the nuts (10) of the connection
flange (4).
6 Make sure that there is no contact between stress--shields (13)
and connection. Correct -- if necessary -- by acting on the fixa-
tion of the stress--shields (13).
12 13
1
x 4
3
2 2
H M12--45
5 daN.m
4
= =
23 daN.m
1
10
x 4
3
H M12--45
5 daN.m
08--2004 L31--770EN/02
E AREVA 8/8
Installation
Installing the operating device
Presentation
Necessary AREVA List of the AREVA tools necessary for the installing :
tools
Mark Diagram Designation Number
(6) Lever 1
Process The table below gives the steps of installing the operating device on the
pole--support :
03--2008 L31--7801EN/01
E AREVA 1/12
Installation
Installing the operating device
Unpacking Remove packaging protection and check that operating device and pole
reference numbers are the right ones.
Closing spring
Circuit--breaker Released
Open
(11) Seal 1
(22) Spacer 4
Installing the -- Install the spacers (22) on the screws (9) outside the operating device.
necessary
components -- Install the seal (11) on the operating shaft (13).
-- Check the presence of grease (ASEOL 0--365.2) on the operating shaft
(13).
13
11
22
x4
9
03--2008 L31--7801EN/01
E AREVA 2/12
Installation
Installing the operating device
Introduction The pole is equipped -- for transport purposes -- with a blocking tool (4) and
a safety sheet metal (5) fixed temporarily at the end of the sleeve (12).
To realize the installing of the operating mechanism, it is necessary to :
a -- remove the blocking tool (4) and the safety sheet metal (5)
b -- proceed to manual opening the pole
c -- install the blocking tool (4) (”open” position)
4
12
Grease Check the presence of grease (ASEOL 0--365.2) on the pole operating shaft.
03--2008 L31--7801EN/01
E AREVA 3/12
Installation
Installing the operating device
“Manual opening” The table below gives the steps of “manual opening” operation :
operation
12
12 4
03--2008 L31--7801EN/01
E AREVA 4/12
Installation
Installing the operating device
Washer
(10) 4
M20
(22) Spacer 1
(26) Spacer 1
Nut
(14) 4
H M20
03--2008 L31--7801EN/01
E AREVA 5/12
Installation
Installing the operating device
Coupling The table below gives the steps of the operating device coupling :
Step Action
1 Sling the operating device using a lifting strap (1) like diagram.
NOTE : Do not remove the roof (17) of the operating device
before slinging.
2 Lift the operating device and make this level.
Approximate weight 300 kg.
3 Approach the operating device in assembly position, the jib of the
lifting equipment must be under the stress--shields ring (to avoid that
the cables touch the stress--shields ring).
4 Introduce the operating mechanism shaft (13) into the cylinder (12)
of the pole operating shaft (7).
5 As soon as the lower fastening screw (9) “A” emerge from the hole
of the operating mechanism support (8), install the spacer (26),
washer (10) and the nut (14).
NOTE : Do not tighten the nut (14).
26
14
9
10
8
12
1
17
”A”
13
03--2008 L31--7801EN/01
E AREVA 6/12
Installation
Installing the operating device
Installing The table below gives the steps of installing the operating device fastening
the fastening nuts nuts :
Step Action
1 Install the spacer (22), washer (10) and the nut (14) on the lower
fastening screw “B”.
NOTE : Do not tighten the nut (14).
2 Install the eccentric spacers (23), washers (10) and the nuts (14) on
the upper fastening screws “C” and “D”.
NOTE : Do not tighten the nuts (14).
3 Rotate the eccentric spacers (23) to do the contact with the lower
edge of the pole--support oblong holes.
4 Tighten -- temporarily at the indicated tightening torque -- the
fastening screws (9).
23
10 5 daN.m
14
23
x 2
”C”
”D” 9
”B”
14
10
22
x1
Wedging The table below gives the wedging procedure for the fastening screws
and tightening depending to the X play :
X
24
22 25
Important
20
35 daN.m
If the X play is ... Action
Tighten to the indicated tightening
X <1 mm
torque.
D Wedge between the spacer (22)
and the operating device (20) with the
X ≥1 mm provided wedges (24)--(25).
D Tighten the screw to the
indicated tightening torque.
03--2008 L31--7801EN/01
E AREVA 8/12
Installation
Installing the operating device
03--2008 L31--7801EN/01
E AREVA 9/12
Installation
Installing the operating device
Process Connect up the operating device’s wires refer to the wiring diagram of the
circuit--breaker.
Connect up the operating device’s wires.
NOTE : Use the holes provided on the supports of the frame to fix
the cables.
Connecting up the Connect the wires from the electrical contact SF6 densimeter (18) cable (19)
contact densimeter to the operating mechanism terminal block, in accordance with the relative
cable diagram.
18
19
03--2008 L31--7801EN/01
E AREVA 10/12
Installation
Installing the operating device
Process Switch on the permanent heating system of the operating device (in both
summer and winter) to avoid condensation, and the corrosion which might
result from this.
03--2008 L31--7801EN/01
E AREVA 11/12
Installation
Installing the operating device
03--2008 L31--7801EN/01
E AREVA 12/12
Installation
Fitting the SF6 filler unit
with its pipe work
Presentation
Introduction Each circuit breaker pole is fitted with an SF6 filler and test unit, which is
used to monitor the SF6 gas. To fit the unit and its pipe work, follow the
procedure explained below :
Subject Page
Fitting the filler unit to the chassis 2
Fitting the SF6 pipe work to the pole’s casing 3
Fixing the pipe work 4
Connecting the densimeter cable 5
03--2008 L31--982EN/01
E AREVA 1/6
Installation
Fitting the SF6 filler unit
with its pipe work
Procedure The following table gives the various stages to be followed when fitting to the
filler unit to the chassis :
H M16--45
x 2
3
H M12--30
5 daN.m
x 3
21
H M12--30
5 daN.m
03--2008 L31--982EN/01
E AREVA 2/6
Installation
Fitting the SF6 filler unit
with its pipe work
Preparation The following table lists the various preparatory steps to be followed when
fitting the SF6 pipe work to the pole’s casing :
Connecting the After having checked for the presence of the two new seals (15 and 16),
SF6 pipe work attach the SF6 pipe end piece (17) using the fixings (13).
x 3
16 13
17 15
H M6--20
0,7 daN.m
03--2008 L31--982EN/01
E AREVA 3/6
Installation
Fitting the SF6 filler unit
with its pipe work
Procedure Attach the pipe work (27) using collars (23), bolts (24), washers (25) and nuts
(26).
x 10 H M6--30
0,7 daN.m
26
25
24
25
23
27
03--2008 L31--982EN/01
E AREVA 4/6
Installation
Fitting the SF6 filler unit
with its pipe work
Procedure Connect the wires (29) from the SF6 densimeter cable (30) to the terminal on
the actuating device as shown on the contract--specific diagrams .
30
29
03--2008 L31--982EN/01
E AREVA 5/6
Installation
Fitting the SF6 filler unit
with its pipe work
This page is intentionally blank.
03--2008 L31--982EN/01
E AREVA 6/6
Installation
Connection the vacuum pump
Presentation
Necessary AREVA List of the AREVA tools necessary for the installing :
tools
UNIVERSAL CONNECTION
(2) 1
1/2” GAZ ET 1/2” NPT
Topic Page
Installing the universal connection 2
Connection the tube of the customer supply vacuum pump 3
Connection the AREVA supply vacuum pump 4
03--2008 L31--858EN/01
E AREVA 1/4
Installation
Connection the vacuum pump
Process The table below gives the steps of installing the universal connection :
3
2 Install the universal
connection (2)) (hand
tightening of nut is sufficient).
03--2008 L31--858EN/01
E AREVA 2/4
Installation
Connection the vacuum pump
(8) Collar 1
Connection The table below gives the connection procedure of the vacuum depending of
the used tube union :
03--2008 L31--858EN/01
E AREVA 3/4
Installation
Connection the vacuum pump
Vacuum pump The table below describes the accessory (9) main components of the
equipment vacuum pump (1) :
SUCKING UP
PNEUROP DN25
11
14 SUCKING BACK
DN25
12 1
9
CLOSED
10
13
Process The table below gives the steps of the vacuum pump connection :
03--2008 L31--858EN/01
E AREVA 4/4
Installation
Installing and commissioning
the synchronous device RPH2
Presentation
Introduction The synchronous device RPH2 is delivered with the C.B. and is to be installed
in the relay room. Delivering the RPH2 with a C.B. includes :
D The RPH2 itself,
D The programming and the testing of the RPH2 device in association with
the C.B., in accordance with the programming document and the checking
document delivered with the C.B.,
D If necessary, a temperature sensor is supplied (in accordance with the pro-
gramming document).
The RPH2 installation in the relay room to be made by people in charge of
installing the protection and control equipment in the substation.
The RPH2 installation instructions to people in charge of installing the protec-
tion and control equipment in the substation are detailed below.
Topic Page
Installing the RPH2 2
Installation at site of the RPH2 associated with a C.B. 3
Programming document and checking document delivered 4
with the C.B.
Adding a RPH2 device on an existing C.B. 5
Replacing a RPH2 device 6
07--2004 L31--871EN/01
E AREVA 1/6
Installation
Installing and commissioning
the synchronous device RPH2
Installing the RPH2 The RPH2 device must be installed in the relay room. Cables must be wired :
device in the relay D between the circuit breaker and the RPH2 device,
room
D between the High Voltage Transformer (and Current Transformer if appli-
cable) and the RPH2 device.
Installing the ambient In some application, a temperature sensor to measure the ambient tempera-
temperature sensor ture is needed to be connected to the RPH2 device, and to correct the varia-
(option) tion of the C.B. operating times.
When this temperature sensor is needed, it is delivered with the RPH2 device.
This temperature sensor must be fitted at site, near the relay room, to mea-
sure the site ambient temperature.
The temperature sensor must be connected to the RPH2 device using a cable
(twisted pair).
In addition the correct operation of the synchronous device RPH2 needs that
the reference voltage is measured respecting the previous phase in the C.B.
low voltage diagram.
See the module “Correspondence between C.B. poles and the network
phases and the phase measuring the reference voltage”.
07--2004 L31--871EN/01
E AREVA 2/6
Installation
Installing and commissioning
the synchronous device RPH2
Process The RPH2 device is programmed in factory and tested with the associated
C.B. during the factory tests.
After installing the RPH2 , people in charge of installing the protection and
control equipment in the substation commission the RPH2 with the associat-
ed C.B. They can check the correct operation of the assembly RPH2 + C.B.
using a time recorder tool (type Hathaway CTB400) and referring with the pro-
gramming document and the checking document delivered with the C.B.
07--2004 L31--871EN/01
E AREVA 3/6
Installation
Installing and commissioning
the synchronous device RPH2
Introduction The RPH2 device is delivered with the C.B., and programmed and check
with its associated C.B.
Programming Programming the RPH2 consists to enter in the RPH2 internal memory all the
document parameters in relation with the application and also with the type of the associ-
ated C.B. (see the RPH2 service manual 58.020.034). All these parameters
are noted on the document called “Programming document” delivered with
the C.B.
Checking document Once programmed, the RPH2 is factory checked with the associated C.B. to
test the correct operation of this assembly. This checking tests that the se-
quence of operating times is in accordance with the previous application. The
sequence of these operating times is written in a document called “Checking
document” delivered with the C.B.
07--2004 L31--871EN/01
E AREVA 4/6
Installation
Installing and commissioning
the synchronous device RPH2
Process Contact the after--sale service in order to check if the C.B. is capable of syn-
chronous operation.
Also using the RPH2 device needs to modify the C.B. low voltage diagram :
D The operation impulses needs to cross the RPH2 device,
D Depending on option and application, some information delivered by the
C.B. needs to be wired to the RPH2 device.
07--2004 L31--871EN/01
E AREVA 5/6
Installation
Installing and commissioning
the synchronous device RPH2
Type of RPH2 The RPH2 device must be the same type of the replaced one.
Programming The RPH2 device must be programmed in accordance with the programming
document associated with the C.B. (see the RPH2 service manual
58.020.034). All these parameters are noted on the document called “Pro-
gramming document” delivered with the C.B.
Checking Check tests that the sequence of operating times is in accordance with the
previous application. The sequence of these operating times is written in a
document called “Checking document” delivered with the C.B.
07--2004 L31--871EN/01
E AREVA 6/6
Installation
RPH2--Assignment of the circuit breaker poles to the net-
work phases and reference voltage measurement phase
Presentation
Introduction The electrical diagram supplied with the circuit breaker illustrates the connec-
tions between the RPH2 and the circuit breaker poles, making the assumption
that :
-- The reference voltage is measured on phase 1.
-- Circuit breaker pole 1 is installed on phase 1 of the network.
-- Circuit breaker pole 2 is installed on phase 2 of the network (phase lag of
120° relative to phase 1 of the network).
-- Circuit breaker pole 3 is installed on phase 3 of the network (phase lag of
240° relative to phase 1 of the network).
07--2004 L31--872EN/01
E AREVA 1/6
Installation
RPH2--Assignment of the circuit breaker poles to the net-
work phases and reference voltage measurement phase
In all cases
Changeover of the Change over in the RPH2 the programming of the operating times and offset
operating times and times of the channel 1 auxiliary switches :
offset times of the D Modify the operating time and aux. offset time programmed in the RPH2
auxiliary switches for phase L1 in order to have the times of the circuit breaker pole correspond-
programmed in the ing to the same phase as the phase on which the reference voltage is mea-
RPH2 for channel 1 sured.
D Modify the operating time and aux. offset time programmed in the RPH2
for phase L2 in order to have the times of the circuit breaker pole correspond-
ing to the phase with the 120° lag relative to the phase on which the reference
voltage is measured (caution: do not change over the flash and pre--flash
times)
D Modify the operating time and aux. offset time programmed in the RPH2
for phase L3 in order to have the times of the circuit breaker pole correspond-
ing to the phase with the 240° lag relative to the phase on which the reference
voltage is measured (caution: do not change over the flash and pre--flash
times)
The table below gives the changeover of the operating times and offset
times of the auxiliary switches programmed in the RPH2 for channel 1 :
Reference phase Phase with 120° lag Phase with 240° lag
in relation to the in relation to the
reference phase reference phase
RPH2
Phase L1 Phase L2 Phase L3
item
Data to Time of pole corre- Time of the phase Time of pole corre-
be input sponding to the ref- corresponding to the sponding to the
erence phase phase with 120° lag phase with 240° lag
relative to the refer- relative to the refer-
ence phase ence phase
Changeover of the Change over terminals X8 :8, X8 :9 and X8 :10 in order to have :
impulse circuits D X8 :8 linked to the impulse circuit of the circuit breaker pole correspond-
corresponding to ing to the same phase as the phase on which the reference voltage is
channel 2 of the measured.
RPH2 D X8 :9 linked to the impulse circuit of the circuit breaker pole correspond-
ing to the phase with the 120° lag relative to the phase on which the refer-
ence voltage is measured.
D X8 :10 linked to the impulse circuit of the circuit breaker pole corre-
sponding to the phase with the 240° lag relative to the phase on which the
reference voltage is measured.
The table below gives the changeover of the impulse circuits corre-
sponding to channel 2 :
Reference phase Phase with 120° lag Phase with 240° lag
in relation to the in relation to the
reference phase reference phase
From RPH2 terminal X8 :8 RPH2 terminal X8 :9 RPH2 terminal X8 :10
To Impulse circuit of the Impulse circuit of the Impulse circuit of the
pole corresponding to pole corresponding to pole corresponding to
the reference phase the phase with a 120° the phase with a 240°
lag relative to the ref- lag relative to the ref-
erence phase erence phase
Changeover of the Change over in the RPH2 the programming of the operating times and offset
operating times and times of the channel 2 auxiliary switches :
offset times of the D Modify the operating time and aux. offset time programmed in the RPH2
auxiliary switches for phase L1 in order to have the times of the circuit breaker pole correspond-
programmed in the ing to the same phase as the phase on which the reference voltage is mea-
RPH2 for channel 2 : sured.
D Modify the operating time and aux. offset time programmed in the RPH2
for phase L2 in order to have the times of the circuit breaker pole correspond-
ing to the phase with the 120° lag relative to the phase on which the reference
voltage is measured.
D Modify the operating time and aux. offset time programmed in the RPH2
for phase L3 in order to have the times of the circuit breaker pole correspond-
ing to the phase with the 240° lag relative to the phase on which the reference
voltage is measured.
The table below gives the changeover of the operating times and offset
times of the auxiliary switches programmed in the RPH2 for channel 2 :
Reference phase Phase with 120° lag Phase with 240° lag
in relation to the in relation to the
reference phase reference phase
RPH2
Phase L1 Phase L2 Phase L3
item
Data to Time of pole corre- Time of the phase Time of pole corre-
be input- sponding to the ref- corresponding to the sponding to the
Datos a erence phase phase with 120° lag phase with 240° lag
entrar relative to the refer- relative to the refer-
ence phase ence phase
07--2004 L31--872EN/01
E AREVA 3/6
Installation
RPH2--Assignment of the circuit breaker poles to the net-
work phases and reference voltage measurement phase
Changeover of the Change over terminals X8 :13, X8 :14 and X8 :15 in order to have :
connections of the D X8 :13 linked to the auxiliary switch of the circuit breaker pole correspond-
auxiliary switches ing to the same phase as the phase on which the reference voltage is mea-
sured.
D X8 :14 linked to the auxiliary switch of the circuit breaker pole correspond-
ing to the phase with the 120° lag relative to the phase on which the reference
voltage is measured.
D X8 :15 linked to the auxiliary switch of the circuit breaker pole correspond-
ing to the phase with the 240° lag relative to the phase on which the reference
voltage is measured.
The table below gives the changeover of the connections of the auxilia-
ry switches :
Reference phase Phase with 120° lag Phase with 240° lag
in relation to the in relation to the
reference phase reference phase
From RPH2 terminal X8 :13 RPH2 terminal X8 :14 RPH2 terminal X8 :15
To Auxiliary switch of the Auxiliary switch of the Auxiliary switch of the
pole corresponding to pole corresponding to pole corresponding to
the reference phase the phase with a 120° the phase with a 240°
lag relative to the ref- lag relative to the ref-
erence phase erence phase
07--2004 L31--872EN/01
E AREVA 4/6
Installation
RPH2--Assignment of the circuit breaker poles to the net-
work phases and reference voltage measurement phase
Changeover of the Change over the terminals of terminal block X9 in order to have :
current measurement D X9 :1 and X9 :2 (or X9 :3) linked to the current measurement circuit corre-
circuits sponding to the same phase as the phase on which the reference voltage is
measured.
D X9 :4 and X9 :5 (or X9 :6) linked to the current measurement circuit corre-
sponding to the phase with the 120° lag relative to the reference phase.
D X9 :7 and X9 :8 (or X9 :9) linked to the current measurement circuit corre-
sponding to the phase with the 240° lag relative to the phase on which the ref-
erence voltage is measured.
The table below gives the changeover of the current measurement cir-
cuits :
Reference phase Phase with 120° lag Phase with 240° lag
in relation to the in relation to the
reference phase reference phase
From RPH2 terminals RPH2 terminals RPH2 terminals
X9 :1 and X9 :2 X9 :4 and X9 :5 X9 :7 and X9 :8
(or X9 :3) (or X9 :6) (or X9 :9)
To Current measure- Current measure- Current measure-
ment circuit corre- ment circuit corre- ment circuit corre-
sponding to the refer- sponding to the phase sponding to the phase
ence phase with a 120° lag rela- with a 240° lag rela-
tive to the reference tive to the reference
phase phase
07--2004 L31--872EN/01
E AREVA 5/6
Installation
RPH2--Assignment of the circuit breaker poles to the net-
work phases and reference voltage measurement phase
This page is intentionally blank.
07--2004 L31--872EN/01
E AREVA 6/6
Installation
Vacuum operation
Presentation
Decision table The table below gives the vacuum operation procedure depending on the
duration of chambers/column coupling :
03--2008 L31--886EN01
E AREVA 1/6
Installation
Vacuum operation
Process The table below gives the steps of the simple vacuum operation :
Open
Closed
1
END OF PROCEDURE
03--2008 L31--886EN01
E AREVA 2/6
Installation
Vacuum operation
Preparing the The table below gives the steps of preparing the nitrogen bottle (N2) :
nitrogen bottle (N2)
N2
2 Fit the pressure reducer (10) on
the nitrogen (N2) bottle (8). 8
N2 10
3 Briefly open the nitrogen (N2)
bottle tap (9) and the cock (11) of 9 Open
the pressure reducer to eliminate
any air inside the piping (approx.
20 s at low flow--rate).
N2 11 Closed
N2 11 Closed
END OF PROCEDURE
03--2008 L31--886EN01
E AREVA 3/6
Installation
Vacuum operation
Vacuum operation The table below gives the steps of the vacuum operation with nitrogen purging
(N2) :
5
3 S Open the nitrogen (N2) bottle
tap (9). 9 12
S Open and close the cock (11)
of the pressure reducer to
eliminate any air inside the tube Open
(12) (approx. 3 s at low
flow--rate).
S Close the nitrogen (N2) bottle
tap (9). N2 11 Closed
12
03--2008 L31--886EN01
E AREVA 4/6
Installation
Vacuum operation
Vacuum operation, The table below gives the continuation of the steps of the vacuum operation
continued with nitrogen purging (N2) :
12
7 Remove the filling tool (4) with the
valve cap.
4
8 Connect the vacuum pump and
open the tap (1) to bring the
volume of pole back to ambient
pressure (filled with nitrogen at
0.03 MPa).
Open
Closed
1
03--2008 L31--886EN01
E AREVA 5/6
Installation
Vacuum operation
03--2008 L31--886EN01
E AREVA 6/6
Installation
Calculation of the SF6 gas filling pressure
for using the pressure gauge (tool)
Presentation
Introduction SF6 pressure values, for the filling, must obligatorily be read on the pressure
gauge 0--1 MPa (tooling). Pay no attention to indications given by the dial
densimeter (MPa -- psi), it is not accurate enough for the filling.
Symbol Designation
pre Filling rated pressure for the insulation
pae Alarm pressure for the insulation
pme Minimal pressure for the insulation
Topic Page
Example of the filling pressure calculation 2
Calculation of the filling pressure at site 3
Values of the SF6 gas pressures in accordance 4
with the temperature
06--2004 L31--901EN/03
E AREVA 1/6
Installation
Calculation of the SF6 gas filling pressure
for using the pressure gauge (tool)
Parameters Values
pre
0,65 MPa
SF6 gas rated filling effective
(94.3 psi)
pressure for the insulation
Ambient temperature 5°C
Local atmospheric pressure 93,2 kPa
SF6 gas filling The table below gives the calculation steps of the pure SF6 filling pressure :
06--2004 L31--901EN/03
E AREVA 2/6
Installation
Calculation of the SF6 gas filling pressure
for using the pressure gauge (tool)
Measurement Write down the result measurement into the corresponding box :
Calculation of the Transfer the values into the corresponding box and write down the result :
pure SF6 gas filling
pressure
With the help of the table (page 5) “Values of the SF6 gas pre
effective pressures in accordance with the temperature”,
determine the value “pre“ in accordance with
the ambient temperature (B) " C ,
Value of the reference atmospheric pressure in MPa D 0 , 1 0 1
Transfer the value of the local atmospheric pressure
(A) " A - ,
Calculate the difference of the atmospheric pressure
(D -- A) " E ,
Transfer the value (C) "
C+ ,
Calculate the rated effective pressure
(E + C) " F ,
The filling with SF6 gas is carried out
to the calculated pressure, plus 0.01 MPa, + 0 , 0 1
(F + 0.01) " G ,
06--2004 L31--901EN/03
E AREVA 3/6
Installation
Calculation of the SF6 gas filling pressure
for using the pressure gauge (tool)
Values of the SF6 gas effective pressures in accordance with the temperature
Rated effective pres- Values of the SF6 gas effective pressures (MPa) corrected in accordance with
sure 0.75 MPa temperature for an atmospheric pressure of 101.3 kPa :
t_C pre pae pme t_C pre pae pme
--25 0,584 0,500 0,477 18 0,743 0,634 0,604
--24 0,588 0,503 0,480 19 0,746 0,637 0,607
--23 0,591 0,506 0,483 20 0,75 0,64 0,61
--22 0,595 0,509 0,486 21 0,754 0,643 0,613
--21 0,599 0,512 0,489 22 0,757 0,646 0,616
--20 0,602 0,516 0,492 23 0,761 0,649 0,619
--19 0,606 0,519 0,495 24 0,765 0,652 0,622
--18 0,610 0,522 0,498 25 0,768 0,656 0,625
--17 0,613 0,525 0,501 26 0,772 0,659 0,628
--16 0,617 0,528 0,504 27 0,776 0,662 0,631
--15 0,621 0,531 0,507 28 0,780 0,665 0,634
--14 0,625 0,534 0,509 29 0,783 0,668 0,637
--13 0,628 0,537 0,512 30 0,787 0,671 0,640
--12 0,632 0,540 0,515 31 0,791 0,674 0,643
--11 0,636 0,544 0,518 32 0,794 0,677 0,645
--10 0,639 0,547 0,521 33 0,798 0,680 0,648
--9 0,643 0,550 0,524 34 0,802 0,684 0,651
--8 0,647 0,553 0,527 35 0,805 0,687 0,654
--7 0,650 0,556 0,530 36 0,809 0,690 0,657
--6 0,654 0,559 0,533 37 0,813 0,693 0,660
--5 0,658 0,562 0,536 38 0,816 0,696 0,663
--4 0,661 0,565 0,539 39 0,820 0,699 0,666
--3 0,665 0,568 0,542 40 0,824 0,702 0,669
--2 0,669 0,572 0,545 41 0,827 0,705 0,672
--1 0,673 0,575 0,548 42 0,831 0,708 0,675
0 0,676 0,578 0,551 43 0,835 0,712 0,678
1 0,680 0,581 0,554 44 0,839 0,715 0,681
2 0,684 0,584 0,557 45 0,842 0,718 0,684
3 0,687 0,587 0,560 46 0,846 0,721 0,687
4 0,691 0,590 0,563 47 0,850 0,724 0,690
5 0,695 0,593 0,566 48 0,853 0,727 0,693
6 0,698 0,596 0,569 49 0,857 0,730 0,696
7 0,702 0,600 0,572 50 0,861 0,733 0,699
8 0,706 0,603 0,575 51 0,864 0,736 0,702
9 0,709 0,606 0,577 52 0,868 0,740 0,705
10 0,713 0,609 0,580 53 0,872 0,743 0,708
11 0,717 0,612 0,583 54 0,875 0,746 0,711
12 0,720 0,615 0,586 55 0,879 0,749 0,713
13 0,724 0,618 0,589 56 0,883 0,752 0,716
14 0,728 0,621 0,592 57 0,887 0,755 0,719
15 0,732 0,624 0,595 58 0,890 0,758 0,722
16 0,735 0,628 0,598 59 0,894 0,761 0,725
17 0,739 0,631 0,601 60 0,898 0,764 0,728
06--2004 L31--901EN/03
E AREVA 4/6
Installation
Calculation of the SF6 gas filling pressure
for using the pressure gauge (tool)
Values of the SF6 gas effective pressures in accordance with the temperature,
continued
Rated effective pres- Values of the SF6 gas effective pressures (MPa) corrected in accordance with
sure 0.65 MPa temperature for an atmospheric pressure of 101.3 kPa :
t_C pre pae pme t_C pre pae pme
--30 0,492 0,409 0,387 16 0,637 0,530 0,500
--29 0,495 0,412 0,389 17 0,641 0,532 0,503
--28 0,498 0,415 0,391 18 0,644 0,535 0,505
--27 0,501 0,417 0,394 19 0,647 0,537 0,508
--26 0,505 0,420 0,396 20 0,65 0,54 0,51
--25 0,508 0,422 0,399 21 0,653 0,543 0,512
--24 0,511 0,425 0,401 22 0,656 0,545 0,515
--23 0,514 0,428 0,404 23 0,659 0,548 0,517
--22 0,517 0,430 0,406 24 0,663 0,550 0,520
--21 0,520 0,433 0,409 25 0,666 0,553 0,522
--20 0,524 0,435 0,411 26 0,669 0,556 0,525
--19 0,527 0,438 0,414 27 0,672 0,558 0,527
--18 0,530 0,441 0,416 28 0,675 0,561 0,530
--17 0,533 0,443 0,419 29 0,678 0,564 0,532
--16 0,536 0,446 0,421 30 0,682 0,566 0,535
--15 0,539 0,449 0,424 31 0,685 0,569 0,537
--14 0,543 0,451 0,426 32 0,688 0,571 0,540
--13 0,546 0,454 0,429 33 0,691 0,574 0,542
--12 0,549 0,456 0,431 34 0,694 0,577 0,545
--11 0,552 0,459 0,433 35 0,697 0,579 0,547
--10 0,555 0,462 0,436 36 0,701 0,582 0,550
--9 0,558 0,464 0,438 37 0,704 0,584 0,552
--8 0,562 0,467 0,441 38 0,707 0,587 0,554
--7 0,565 0,469 0,443 39 0,710 0,590 0,557
--6 0,568 0,472 0,446 40 0,713 0,592 0,559
--5 0,571 0,475 0,448 41 0,716 0,595 0,562
--4 0,574 0,477 0,451 42 0,720 0,597 0,564
--3 0,577 0,480 0,453 43 0,723 0,600 0,567
--2 0,580 0,483 0,456 44 0,726 0,603 0,569
--1 0,584 0,485 0,458 45 0,729 0,605 0,572
0 0,587 0,488 0,461 46 0,732 0,608 0,574
1 0,590 0,490 0,463 47 0,735 0,611 0,577
2 0,593 0,493 0,466 48 0,738 0,613 0,579
3 0,596 0,496 0,468 49 0,742 0,616 0,582
4 0,599 0,498 0,470 50 0,745 0,618 0,584
5 0,603 0,501 0,473 51 0,748 0,621 0,587
6 0,606 0,503 0,475 52 0,751 0,624 0,589
7 0,609 0,506 0,478 53 0,754 0,626 0,591
8 0,612 0,509 0,480 54 0,757 0,629 0,594
9 0,615 0,511 0,483 55 0,761 0,631 0,596
10 0,618 0,514 0,485 56 0,764 0,634 0,599
11 0,622 0,516 0,488 57 0,767 0,637 0,601
12 0,625 0,519 0,490 58 0,770 0,639 0,604
13 0,628 0,522 0,493 59 0,773 0,642 0,606
14 0,631 0,524 0,495 60 0,776 0,645 0,609
15 0,634 0,527 0,498
06--2004 L31--901EN/03
E AREVA 5/6
Installation
Calculation of the SF6 gas filling pressure
for using the pressure gauge (tool)
This page is intentionally blank.
06--2004 L31--901EN/03
E AREVA 6/6
Installation
Pre-- filling with SF6 gas at 0.05 MPa
Presentation
Principle The pre--filling of the pole with SF6 gas at 0.05 MPa must be done after the
vacuum operation.
Necessary equipment List of the necessary AREVA equipment and tools for the pre--filling with
and tools SF6 gas :
Topic Page
Preparing the SF6 gas bottle 2
Pre--filling with SF6 gas 3
Tightness inspection 4
03--2008 L31--956EN/01
E AREVA 1/4
Installation
Pre-- filling with SF6 gas at 0.05 MPa
Process The table below gives the steps of preparing the SF6 gas bottle :
SF6
2 Fit the pressure reducer (10) on
the SF6 gas bottle (8). 8
SF6 10
3 Briefly open the SF6 gas bottle tap
(9) and the cock (11) of the 9 Open
pressure reducer to eliminate any
air inside the piping (approx. 20 s
at low flow--rate).
SF6 11 Closed
END OF PROCEDURE
03--2008 L31--956EN/01
E AREVA 2/4
Installation
Pre-- filling with SF6 gas at 0.05 MPa
Process The table below gives the steps of the pre--filling with SF6 gas operation :
5
2 D Open the SF6 gas bottle tap (9).
9 12
D Open and close the cock (11) of
the pressure reducer to eliminate
any air inside the tube (12)
(approx. 3 s at low flow--rate). Open
D Close the SF6 gas bottle tap (9).
SF6 11 Closed
12
4 Open the SF6 gas bottle tap (9)
and adjust gas output by acting on 9 Open
the cock (11) of the pressure
reducer (reduced flow rate). 13
D Close the tap (9) from time to
time to check pressure on the
gauge (13).
D Start filling again until the
required pressure about 0.05 MPa
is reached. SF6 Closed
11
D Close in this order : the tap (9),
then the cock (11).
END OF PROCEDURE
03--2008 L31--956EN/01
E AREVA 3/4
Installation
Pre-- filling with SF6 gas at 0.05 MPa
Tightness inspection
Necessary AREVA List of the AREVA tools necessary for the tightness inspection :
tools
Chambers -- column The table below gives the steps of the chambers -- column tightness
coupling inspection operation :
18
16
17
18
14
03--2008 L31--956EN/01
E AREVA 4/4
Installation
Filling with SF6 gas
Presentation
Necessary equipment List of the necessary AREVA equipment and tools for the filling with SF6
and tools gas :
2 Filling tool 1
8 Pressure reducer 1
Gauge
14 1
0...1 MPa
Topic Page
Filling with SF6 gas 2
Confirm the pressure 3
Checking pressure 4
Checking gas--tightness 6
Moisture content of SF6 gas in circuit--breaker 7
03--2008 L32--017EN/01
E AREVA 1/8
Installation
Filling with SF6 gas
Filling pressure Calculate the SF6 gas filling pressure in accordance with the temperature and
calculation the local atmospheric pressure.
Filling is carried out to calculated pressure plus 0.01 MPa.
See the module “SF6 gas monitoring” (Calculation of the filling pressure at
site).
Ambient
temperature
0°C
Process The table below gives the steps of the filling with SF6 gas operation :
11
Open
SF6
9 Closed
03--2008 L32--017EN/01
E AREVA 2/8
Installation
Filling with SF6 gas
Process The table below gives the confirmation operation steps of the filling pressure
with SF6 gas :
15
14
17
03--2008 L32--017EN/01
E AREVA 3/8
Installation
Filling with SF6 gas
Checking pressure
Principle Having allowed the temperature to remain steady for at least 12 hours after
filling, it is necessary to check and definitively adjust the pressure to its
corrected value -- defined according to both ambient temperature and
atmospheric pressure.
Preparation The table below gives the preparation steps before checking pressure :
3
17
15
14
03--2008 L32--017EN/01
E AREVA 4/8
Installation
Filling with SF6 gas
Decision table The table below gives the process depending the pressure measured :
14
16
End of control The table below gives the end steps of the checking pressure :
Step Action Diagram
1 Disconnect the gauge (14)
0--1 MPa.
14
03--2008 L32--017EN/01
E AREVA 5/8
Installation
Filling with SF6 gas
Necessary AREVA List of the AREVA tools necessary for the tightness inspection :
tools
Process Make sure that the plug (17) is perfectly leak--tight using the leak detector
(12).
12
17
03--2008 L32--017EN/01
E AREVA 6/8
Installation
Filling with SF6 gas
Principle This measurement is not required, the equipment being provided with
molecular sieves in sufficient quantity to give a dew point of ≤ 0°C (32°F) for
an ambient temperature of 20°C (68°F), this applies for a unit filled to its
nominal pressure for 2 or 3 months.
03--2008 L32--017EN/01
E AREVA 7/8
Installation
Filling with SF6 gas
03--2008 L32--017EN/01
E AREVA 8/8
Commissioning
Pre-- commissioning inspections
Presentation
Introduction After installation of the bay, completion of all earth circuit and electrical con-
nections, it is necessary to perform certain pre--commissioning inspections.
These inspections should be performed with the apparatus ready to be com-
missioned (energized), in other words
S LV electrical circuits conforming, in voltage and type, with the low--voltage
diagrams and rating plate of the apparatus.
S Envelopes at rated SF6 ou SF6+CF4 gas mixture pressure.
NOTE : Rated pressure, pressure of equipment after SF6 ou SF6+CF4
gas mixture filling.
S Flexible connections linking circuit--breaker to busbar installed.
Inspections Page
Pole/operating device coupling sleeve 2
Orientation and identification of interrupting chambers 3
SF6 or SF6+CF4 gas 4
Operating device 5
Finish and test operations 6
06--2006 L34--011EN/02
E AREVA 1/6
Commissioning
Pre-- commissioning inspections
Checking Check that the blocking tool is not on the flange of the sleeve. Otherwise
remove it imperatively.
06--2006 L34--011EN/02
E AREVA 2/6
Commissioning
Pre-- commissioning inspections
Inspection Check that the interruption chambers are disposed correctly, the bosses
(B1) and (B2) must be situated on the same side as the operating mecha-
nism (3).
Diagram
B1
B2
06--2006 L34--011EN/02
E AREVA 3/6
Commissioning
Pre-- commissioning inspections
Reminder SF6 or SF6+CF4 envelopes are at rated pressure following the SF6 or
SF6+CF4 gas filling operation.
Checking SF6 or SF6 or SF6+CF4 pressure values must obligatorily be read on the pressure
SF6+CF4 gas inspection gauge (tooling). Pay no attention to indications given by the dial
densimeter on the filling control block (where applicable) ; it is not accurate
enough for this inspection.
See the module “Calculation of the SF6 or SF6+CF4 gas filling pressure
to using the pressure gauge (tool)”.
SF6 or SF6+CF4 gas The SF6 or SF6+CF4 humidity level need not be known as the equipment is
humidity level fitted with molecular sieves in sufficient numbers to give a dew point lower
than, or equal to, 0°C at an ambient temperature of 20°C, for an apparatus
filled to its rated pressure for 2 or 3 months.
Checking tightness Each on site assemblage of parts subjected to SF6 or SF6+CF4 gas requires
of assemblages seals. The quality of these assemblages must be checked.
under SF6 or SF6+CF4 This inspection should be undertaken once all the filling and pressure control
pressure operations are finished.
06--2006 L34--011EN/02
E AREVA 4/6
Commissioning
Pre-- commissioning inspections
Operating device
Measurements Note the supply voltage of motors on the operating mechanism terminals.
06--2006 L34--011EN/02
E AREVA 5/6
Commissioning
Pre-- commissioning inspections
Finish Check the general appearance of the apparatus and touch up paint if neces-
sary before commissioning.
Test operations S The connection of auxiliary circuits is sufficiently advanced to allow remote
controls to be used.
S Perform 5 CLOSING -- OPENING cycles electrically, by remote control.
06--2006 L34--011EN/02
E AREVA 6/6
Maintenance
Maintenance plan
Presentation
Introduction GL circuit--breakers use pure SF6 gas as an arc quenching medium (or a
SF6+CF4 gas mixture) and require only a reduced amount of maintenance.
Topic Page
Maintenance plan 2
Maintenance operations 3
Detail of maintenance operations 4
07--2006 L51--004EN/04
E AREVA 1/6
Maintenance
Maintenance plan
Maintenance plan
Maintenance Under normal operating conditions, the maintenance plan may be defined as
frequency follows :
Type of
Frequency Comment
examination
It is advisable to perform
at least 2 CO duty cycles
per year, when apparatus
Maintenance are scarcely used, in order
Once or twice a year
visits to check that the circuit--
breaker and associated
control circuits are work-
ing properly.
This necessitates circuit--
breaker shutdown. It is not
necessary, however to dis-
Inspections Every five years
mantle interrupting cham-
bers and other sub--assem-
blies.
Perform when one of the fol- However, it is recommended
lowing criteria is reached : to proceed with inspection of
D operating life time the pole or circuit--breaker
≥ 20 years used the most, then to adapt
Overhaul
D number of mechanical the maintenance pro-
cycles ≥ 3,000 gramme for the other brea-
kers depending on the
D electric wear limit results observed.
07--2006 L51--004EN/04
E AREVA 2/6
Maintenance
Maintenance plan
Maintenance operations
Guide The table below is a guide of the operations to be carried out at each mainte-
nance stage :
07--2006 L51--004EN/04
E AREVA 3/6
Maintenance
Maintenance plan
General condition The apparatus should be subjected to visual inspection. If patches of corro-
of the apparatus sion are found begin reconditioning of the affected parts.
The table below gives the process respecting surface finish and protection :
Products used :
D RUMCOAT EEVA primer by DERIVERY ref. 333103.
D Polyurethane lacquer 780 by DERIVERY, ref. depending on color of equip-
ment.
07--2006 L51--004EN/04
E AREVA 4/6
Maintenance
Maintenance plan
SF6 pressure gas For a circuit--breaker equipped with a ”dial--type” SF6 gas densimeter, check
the position of the needle.
GREEN None
Perform a topping--up
YELLOW
operation.
Operating device Air--vents should be clean, free of dust and unobstructed. If necessary clean
using a solvent.
Make sure that the permanent resistors are working properly by checking that
these give off heat and that there are no overheating marks (a zone notorious
for this).
For thermally controlled resistors, check that energizing and de--energizing
takes place correctly at voltage supply terminals by means of a thermostat
(recommended thermostat temperature : +5°C).
If necessary, change resistors found to be defective.
For the opening damper, if any leak is observed, please contact
AREVA T&D S.A., After--Sales Department, to proceed with any changes.
Operation counter Read indications given by the counter(s) and note these on the inspection
sheet ”Maintenance visits”.
The number of circuit--breaker operations recorded influences future mainte-
nance operations.
07--2006 L51--004EN/04
E AREVA 5/6
Maintenance
Maintenance plan
Tightening of Check and adjust, with a torque wrench, the tightening torques of screws on
mountings sub--assemblies not subjected to gas pressure. The tightening torques are
given in paragraph ”Tightening torques”.
Relay operation Check relay operation by executing the following circuit--breaker sequences :
-- closing lock--out,
-- automatic opening (where applicable),
-- anti--pumping.
Tightening With the electric cubicle out of service, check that the connectors and tips of
LV terminals conductors are tightened correctly and check the torque of connection mount-
ings.
Tool used : 4 mm diameter screw driver , for terminals of the ”Entrelec” type
(for example).
Insulating envelopes Check the condition of insulating envelopes, these should be free from impact
marks, splintering, cracks, dust deposits, pollution etc...
If necessary, clean these using a dry rag.
If anomalies are found contact :
AREVA T&D SA, After--sales Service in order to change the defective parts.
07--2006 L51--004EN/04
E AREVA 6/6
Maintenance
Electrical wear limits
Estimation Electrical wear can be determined by means of the curve below. This
curve corresponds with the formula :
I (kA)
Diagram
50
20
10
Number of interruptions
06--2004 L51--052EN/03
E AREVA 1/2
Maintenance
Electrical wear limits
06--2004 L51--052EN/03
E AREVA 2/2
Maintenance
Control of contact densimeter thresholds
Presentation
02--2008 L51--113EN/01
E AREVA 1/8
Maintenance
Control of contact densimeter thresholds
Procedure The following table defines the procedure for preparing the densimeter :
Step Action Illustration
1 Remove the fixings (8) and
the valve cover (2) then
remove the seals (16). 16
x4
8
H M6--20
2 Remove the valve (5) cap
(4).
5
4
02--2008 L51--113EN/01
E AREVA 2/8
Maintenance
Control of contact densimeter thresholds
Procedure The following table defines the procedure for connecting the densimeter to
the test tool :
12
22
SF6
02--2008 L51--113EN/01
E AREVA 3/8
Maintenance
Control of contact densimeter thresholds
Adjusting the pres- The following table defines the steps for adjusting SF6 pressure in the
sure of the SF6 gas connection valve unit (5) :
Step Action Remark
1 Open the tap (21) on the SF6
cylinder and adjust the gas outlet
using the reducing valve (22 (low
rate of flow). See the ”Calculating the SF6
From time to time, close the tap gas filling pressure for use
(21) to read the pressure on the of the pressure gauge
pressure gauge (11). (tools)” module.
2 Resume filling until the desired
pressure is reached.
3 Close the tap (21) and the valve
(22) in that order.
21
11
Open
SF6 Closed
22
02--2008 L51--113EN/01
E AREVA 4/8
Maintenance
Control of contact densimeter thresholds
Check The following table defines the steps for checking the densimeter :
20
02--2008 L51--113EN/01
E AREVA 5/8
Maintenance
Control of contact densimeter thresholds
Procedure The following table defines the procedure for re--installing the filler unit :
Step Action Illustration
1 Disconnect pipe (12) from
the block’s valve (5).
Screw the cap (4) onto the 4 5
valve (5).
12
x4
8
H M6--20
0,7 daN.m
02--2008 L51--113EN/01
E AREVA 6/8
Maintenance
Control of contact densimeter thresholds
Procedure The following table defines the steps for storing the checking tools :
Step Action Illustration
1 Disconnect the pipe (23),
between theSF6 gass bot- 11
tle and the valve (10) on
the pressure gauge (11).
10
23
SF6
02--2008 L51--113EN/01
E AREVA 7/8
Maintenance
Control of contact densimeter thresholds
02--2008 L51--113EN/01
E AREVA 8/8
Maintenance
Intervention on the FK3-- 4 operating device
Presentation
Topic Page
Positions of optical signalization 2
Safety measures 3
Preparing the operating device 4
Replacing an opening or closing electro--magnet 5
Resumption of service 6
Lubrication 8
Cleaning the windows 9
06--2004 L51--303EN/03
E AREVA 1/10
Maintenance
Intervention on the FK3-- 4 operating device
“A” position
“B” position
“C” position
“D” position
06--2004 L51--303EN/03
E AREVA 2/10
Maintenance
Intervention on the FK3-- 4 operating device
Safety measures
Circuit--breaker The table below gives the steps to prepare the circuit--breaker to work safely :
general preparing
Release the springs The table below gives the procedure to release the closing spring and the
opening spring depending the circuit--breaker state :
If the circuit--breaker
Action
position is ...
In the operating device, activate the
opening handle and the closing han-
dle like below :
Closed 1 -- Open
2 -- Close
3 -- Open
Check the optical Check that the operating mechanism’s optical signalization shows the sym-
signalization bols below :
06--2004 L51--303EN/03
E AREVA 3/10
Maintenance
Intervention on the FK3-- 4 operating device
Introduction In order to perform certain maintenance operations inside the operating de-
vice it is necessary to remove some cabinet parts.
Removing The table below gives the steps of side panels removing :
side panels
2
x2
M8 3
2 Take hold of the left side
panel (3) from underneath, 3
pull slightly towards the out-
side, then downwards to re-
move it.
06--2004 L51--303EN/03
E AREVA 4/10
Maintenance
Intervention on the FK3-- 4 operating device
Process The table below gives the steps of replacing an opening or closing electro--
magnet :
9
5 Reinstall the core (11).
06--2004 L51--303EN/03
E AREVA 5/10
Maintenance
Intervention on the FK3-- 4 operating device
Resumption of service
Installing the side Insert the side panel (3) under the edge of the roof plate (4). Press it down to
panels insert the mounting screws and fasten using nuts (2).
4
x2
2
M8
06--2004 L51--303EN/03
E AREVA 6/10
Maintenance
Intervention on the FK3-- 4 operating device
Energizing The table below gives the resumption of service steps of the circuit--breaker
pole :
Check the optical Check that the operating mechanism’s optical signalization shows the sym-
signalization bols below :
06--2004 L51--303EN/03
E AREVA 7/10
Maintenance
Intervention on the FK3-- 4 operating device
Lubrication
Principle No future lubrication will be necessary. The bearings and rollers have been
lubricated in our workshops with special grease :
ASEOL SYLITEA 4--018
This grease can easily endure very low temperatures and has an excellent
resistance to ageing. So that its qualities are not modified during use, it is pro-
hibited to :
Mixture with other lubricants can cause the layer of grease to become too
hard.
06--2004 L51--303EN/03
E AREVA 8/10
Maintenance
Intervention on the FK3-- 4 operating device
06--2004 L51--303EN/03
E AREVA 9/10
Maintenance
Intervention on the FK3-- 4 operating device
06--2004 L51--303EN/03
E AREVA 10/10
Annexes
Tooling and accessories
Presentation
Topic Page
Special tools 2
Accessories 6
03--2008 L60--025EN/01
E AREVA 1/8
Annexes
Tooling and accessories
Special tools
Table of special The table below gives the AREVA special tools (SF6 case) :
tools
NUMBER DESIGNATION USE
Transport of SF6 gas
EMPTY filling tools and
VLD001875.. TRANSPORT control tools.
★✩ CASE Inspection of
(OPTIONAL) densimeter
thresholds.
VL--02842117P
PRESSURE
+
GAUGE SF6 filling,
V0005499001P
0...0,765 MPa topping--up.
★✩
Inspection of
VL--02842118P densimeter
PRESSURE
+ thresholds.
GAUGE
V0005499001P
0...1 MPa
★✩
WATER
VL465059004P PRESSURE
Checking for leaks
✩ GAUGE
(OPTIONAL) ✩
VL--02557208P
PRESSURE
+
REDUCER SF6 filling,
VLN55161601P
0...0,765 MPa topping--up.
★✩
Inspection of
VL--02557392P densimeter
PRESSURE
+ thresholds.
REDUCER
VLN55161601P
0...1 MPa
★✩
Inspection of
V0000270121P
SET OF SEALS densimeter
✩
thresholds.
03--2008 L60--025EN/01
E AREVA 2/8
Annexes
Tooling and accessories
Table of special The table below gives the continuation of AREVA special tools :
tools, continued
NUMBER DESIGNATION USE
V0001652002P
LIFTING STRAP
★✩ Handling of the pole.
(3m)
(x4/station)
V0001652001P
LIFTING STRAP
★✩ Handling of the pole.
(6m)
(x4/station)
VL--02236071P
LIFTING
★ Handling of the pole.
SHACKLE
(x4/station)
VLD00786901
Handling
★ WASHER
of the column.
(x8/station)
VLN55069303P
Handling
★ RING BOLT
of the column.
(x4/station)
V0004570001P
Blocking tool of the
★
pole operating shaft
(x1/pole BLOCKING TOOL
for replacing the
installed in
operating device.
factory)
V0000482002P
CENTRING Chambers/column
★✩
SPINDLES coupling.
(x1/station)
03--2008 L60--025EN/01
E AREVA 3/8
Annexes
Tooling and accessories
Table of special The table below gives the continuation of AREVA special tools :
tools, continued
NUMBER DESIGNATION USE
V0005025001P
Chambers/column
★✩ STOP
coupling.
(x1/station)
V0000508001P
Chambers/column
★✩ SCREWING TOOL
coupling.
(x1/station)
V0000571001P
Installing the
★✩ LEVER
operating device.
(x1/station)
V0000504001P
Chambers/column
★✩ PROTECTION
coupling.
(x1/station)
V0000486001P
Chambers/column
★✩ COUPLING PIN
coupling.
(x1/station)
VACUUM PUMP
VLN55001903P
110/220V
★
50 Hz (4,5 m3/h)
Vacuum operation
in pole.
VACUUM PUMP
VLN55001904P
115/230V
★
60 Hz (4,5 m3/h)
03--2008 L60--025EN/01
E AREVA 4/8
Annexes
Tooling and accessories
Table of special The table below gives the continuation of AREVA special tools :
tools, continued
NUMBER DESIGNATION USE
UNIVERSAL
CONNECTION
VLN55000406P Vacuum operation
1/2” GAZ
★ in pole.
AND
1/2” NPT
Checking
VLD00001901P gas--tightness of SF6
LEAK DETECTOR
★✩ filling plug. SF6 leak
detection.
Inspection of
densimeter
VL--02861501P thresholds.
TEST LAMP
✩ Inspection of
interruption contact
wear.
VLD00818001
CRANK HANDLE Spring reloading.
✩
03--2008 L60--025EN/01
E AREVA 5/8
Annexes
Tooling and accessories
Accessories
20 kg
VL--01861435P
★✩ SF6 BOTTLE SF6 filling topping--up.
10 kg
VL--01861434P
★✩ SF6 BOTTLE SF6 filling topping--up.
5 kg
VL--01861433P
★✩ SF6 BOTTLE SF6 filling topping--up.
12 kg
VL--01861451P
★✩ CF4 BOTTLE CF4 filling topping--up.
LOCTITE 262
VL--01818336P Screw locking.
(50 ml)
LOCTITE 225
VL--01818327P Screw sealing.
(250 ml)
GREASE Preparation
VL--01835265P
MOLYKOTE 111 of SF6 seals.
GREASE
VL--01835208P
MOBILPLEX 47 Lubricating screws
or before tightening to
VL--01835203P GREASE torques.
MOBILUX EP3
03--2008 L60--025EN/01
E AREVA 6/8
Annexes
Tooling and accessories
Accessories, continued
Table of accessories, The table below gives the continuation of AREVA accessories :
continued
Preparation of
VASELINE
VL--01835106P electrical contact
204--9
surfaces.
Preparation of
CONTACTAL
VL--01835118P electrical contact
GREASE
surfaces.
GREASE
VL--01835251P General lubrication.
ASEOL 0--365.2
Preparation of
SCOTCH BRITE
VL--02212337P electrical contact
A -- VF
surfaces.
ABRASIVE Preparation of
VL--01831320P PAPER electrical contact
A 400 surfaces.
Preparation of
VL--02212334P RAG electrical contact
surfaces.
Preparation of
ROUND BRUSH
VL--02211842P electrical contact
br. 4
surfaces.
Preparation of
BRUSH
VL--02211831P electrical contact
br. 16
surfaces.
CAN OF
Preparation of SF6
VL--01861262P IZOPROPANOLA
seals.
(1 l)
03--2008 L60--025EN/01
E AREVA 7/8
Annexes
Tooling and accessories
03--2008 L60--025EN/01
E AREVA 8/8
TRANSMISSION & DISTRIBUTION
High voltage switchgear
SUMMARY
Summary PS 0000/A 03
Chemicals PS 0005/A 02
Machinery PS 0007/A 03
Operation PS 0008/A 03
Maintenance PS 0009/A 03
SAFETY SHEET
WORKING
ENVIRONMENT
WORK REQUIREMENTS.
All remedial action, for all life-cycles of the equipment, must be carried out in a safe working environment.
SAFETY INSTRUCTIONS.
MAINTENANCE
INSTALLATION
SCRAPPING &
TRANSPORT
OPERATION
RECYCLING
START-UP
PACKING
SAFETY INSTRUCTIONS
1 Personnel :
- Appropriate clothing, gloves, helmet, safety boots,
harness, etc..
X X X X X X X
- The personnel concerned must be familiar with the
basic working regulations governing a given work
station: mechanical, dielectric, pressure hazards, etc..
2 Handling Equipment :
- This must be in good working order, regularly X X X X X X X
maintained, properly adjusted and compliant with the
standards in force in the country of use.
3 Tools in General :
- Only use tools appropriate to the type of work to be X X X X X
carried out.
4 Working Area :
- Make sure the floor is safe (free from oil, blunt
X X X X X
objects, etc.).
- The site must be properly demarcated and kept clear.
SAFETY SHEET
HANDLING OPERATIONS
WORK REQUIREMENTS.
As a general rule, handling operations must be carried out by personnel familiar with the basic handling
regulations, using equipment in good working order, and wearing the appropriate protective clothing or
equipment.
Ensure that the condition of the cases is such that they can be safely handled (state of the wood, shock-
resistance, etc.).
SAFETY INSTRUCTIONS.
MAINTENANCE
INSTALLATION
SCRAPPING &
TRANSPORT
OPERATION
RECYCLING
START-UP
PACKING
SAFETY INSTRUCTIONS
Operator Safety :
- use of gloves, helmets, safety boots, etc., X X X X X X X
- loads not to be carried with personnel underneath.
MAINTENANCE
INSTALLATION
SCRAPPING &
TRANSPORT
OPERATION
RECYCLING
START-UP
PACKING
SAFETY INSTRUCTIONS
SAFETY SHEET
PRESSURIZED EQUIPMENT
Our equipment includes gas pressure assemblies (SF6, nitrogen, air, etc.) or fluids (oil).
WORK REQUIREMENTS.
· Comply with the storage, transport and operating instructions supplied with our equipment.
· Before initial filling and pressurizing, check the overall condition of the shielding concerned :
- no signs of impact, splitting or chipping on the porcelain components, etc.,
- no visible damage to hoses and/or rigid pipes (cuts, folds, corrosion, etc.) or to fittings and metal
protection (accumulators, tank, etc.).
SAFETY INSTRUCTIONS.
As a general rule, all work on pressurized equipment must be carried out by qualified personnel.
MAINTENANCE
INSTALLATION
SCRAPPING &
TRANSPORT
OPERATION
RECYCLING
START-UP
PACKING
SAFETY INSTRUCTIONS
MAINTENANCE
INSTALLATION
SCRAPPING &
TRANSPORT
OPERATION
RECYCLING
START-UP
PACKING
SAFETY INSTRUCTIONS
3 Hydraulic Equipment.
SAFETY SHEET
SF6
Use and Handling
Sulphur hexafluoride (SF6) is a gas which in its basic state is colourless, odourless and tasteless. It is not toxic,
but it cannot sustain life. It is a heavy gas that is dispersed slowly into the atmosphere.
In its natural state, SF6 is delivered and stored in pressurized tanks (bottles or spheres) at a pressure of
approximately 20 bar at 20°C (in its liquid form) and complies with IEC standard 376.
However, under the effect of the electric arc, the SF6 molecules break up and the elements mostly recombine
during cooling either due to extinction of the arc or by regeneration caused by the presence of active
absorbent charges within the circuit breaker.
Various chemical reactions, associated with the volatilization of the materials in contact with the electric arc,
create either fluoridized or sulphurous secondary gas products or solid products in the form of metallic fluoride
powder ; or again, in the presence of traces of water or moisture, hydrofluoric acid or sulphur dioxide.
In the life-cycle of the equipment, SF6 can be observed not only in its pure state, but also in its contaminated
state :
WORK REQUIREMENTS.
The storage of these containers is governed by the same storage regulations as compressed gas bottles :
- keep away from any source of heat and in a cool, dry and well-ventilated area,
- always fit a pressure reducing valve.
Whilst SF6 in its pure state is not toxic, the decomposition products have varying degrees of toxicity. They may
irritate the skin, the eyes and the mucous membranes; and in massive amounts may cause serious lesions
(oedema, heart failure, circulatory disorders and unconsciousness).
However, very rapidly and before there is any real danger, signs such as a pungent smell, irritation of the
mucous of the nose, the eyes and the mouth will give a warning and the personnel concerned will have
sufficient time to take the necessary safety actions.
Where the gas is used or handled within enclosed premises, ensure adequate ventilation, especially low down.
If the gas is inhaled, the area concerned must be evacuated immediately.
Under normal operating conditions, leaks are exceptionally minor and not critical, even when the gas contains
impurities (due to the regenerating filters in the circuit breaker).
Filling and where necessary topping up operations must be carried out using the appropriate tools.
During maintenance operations, or at the end of the life-cycle, dust inside the equipment must be removed by
a vacuum extractor and the operator should wear a mask. Gas recovery must be carried out using the
appropriate gas recovery equipment.
Gases and decomposition products must be treated and/or disposed of by specialist organizations.
Under extremely abnormal conditions (e.g. break in the shielding) in an enclosed space, individual protective
equipment is recommended.
Lastly, it is forbidden to smoke, drink, eat or keep food in the vicinity of open SF6 equipment, whether indoors
or outside (harmful dust).
SAFETY INSTRUCTIONS.
It is essential that both the fitter and the user read IEC Technical Report 1634 regarding the use and
handling of sulphur hexafluoride gas.
MAINTENANCE
INSTALLATION
SCRAPPING &
TRANSPORT
OPERATION
RECYCLING
START-UP
PACKING
SAFETY INSTRUCTIONS
Transport of SF6 X X
Pure SF6 X X X X X
Contaminated SF6 X X X
SAFETY SHEET
CHEMICALS
Generally speaking, the products used for installation and commissioning are bought chemical products,
namely :
These must be kept in their original packing and the tops replaced after use.
Some packing products require careful handling as they may contain preservatives.
WORK REQUIREMENTS.
As a general rule, chemical products must be used and stored away from any source of heat. Smoking is to be
avoided.
Avoid contact with the skin and any splashes to the eyes.
Products and packing must be destroyed in accordance with local environmental regulations.
SAFETY INSTRUCTIONS.
MAINTENANCE
INSTALLATION
SCRAPPING &
TRANSPORT
OPERATION
RECYCLING
START-UP
PACKING
SAFETY INSTRUCTIONS
Drying Agents X X X X X
Hydraulic Oil X X X X X X X
Loctite X X
SAFETY SHEET
ELECTRICAL EQUIPMENT
Our equipment is subjected to high and low tension loads that could expose the personnel to the risk of
electrocution.
WORK REQUIREMENTS.
The operating company is responsible for ensuring compliance with the safety instructions governing high
tension.
The basic regulations in respect of low tension installations must also be complied with.
SAFETY INSTRUCTIONS.
All work on high-tension networks and low-tension installations must be performed by qualified operators
wearing personal protective clothing and using the appropriate tools and equipment.
MAINTENANCE
INSTALLATION
SCRAPPING &
TRANSPORT
OPERATION
RECYCLING
START-UP
PACKING
SAFETY INSTRUCTIONS
1 High Tension.
2 Low Tension.
SAFETY SHEET
MACHINERY
Our equipment contains moving parts (linkage, levers, etc.), reserve power (springs, accumulators, etc.)
and pressurized sheathing ; the associated hazards are dealt with in safety sheet "Pressurized Equipment"
PS 0003/A.
WORK REQUIREMENTS.
Prior to any work on the control equipment and the motion transfer mechanism, disable the springs on
mechanically operated units and bring pressure back to zero for hydraulically operated units.
SAFETY INSTRUCTIONS.
As a general rule, work on the control equipment and transmissions must be performed by qualified operators
wearing personal protective clothing and using the appropriate tools and equipment.
MAINTENANCE
INSTALLATION
SCRAPPING &
TRANSPORT
OPERATION
RECYCLING
START-UP
PACKING
SAFETY INSTRUCTIONS
1 Moving Parts.
2 Spring-operated Mechanism.
2.1 Before any work is carried out, cut off all power to the
X X X X X
reset motor.
2.3 Make sure that all safety rules are complied with while
X X X X X
the work is being carried out.
3 Hydraulic Mechanism.
3.1 Before any work is carried out, cut off power to the
X X X X X
motor pump.
SAFETY SHEET
OPERATION
If the unit shows any sign of an unwanted condition, it must be examined by the user.
WORK REQUIREMENTS.
The operators concerned must be suitably qualified and must comply with the normal operating and
maintenance instructions issued by AREVA.
Depending on the severity of the fault observed, the necessary corrective measures must be taken, e.g :
- replenish the SF6 gas in the event of a leak,
- isolate the system in the event of a major malfunction.
SAFETY INSTRUCTIONS.
MAINTENANCE
INSTALLATION
SCRAPPING &
TRANSPORT
OPERATION
RECYCLING
START-UP
PACKING
SAFETY INSTRUCTIONS
Opening malfunction :
COMPLY WITH THE SPECIFIC INSTRUCTION PROVIDED IN THE FOLLOWING CASES :
Cut-off failure. X
Abnormal noise. X X
SAFETY SHEET
MAINTENANCE
· To ensure safe and unimpaired operation of the equipment, regular maintenance is essential.
Neglected maintenance can create hazards.
WORK REQUIREMENTS.
· Comply with the maintenance programme and service intervals shown in the AREVA manuals.
· In addition, every maintenance operation must comply with the following requirements :
- it must be carried out by suitably qualified personnel,
- both the work involved and the associated hazards must be clearly identified beforehand,
- the tools and equipment used (standard or specific to AREVA) must be appropriate and in proper
working order,
- any replacement parts must be AREVA parts.
SAFETY INSTRUCTIONS.
· The safety instructions below are general and not exhaustive. They should therefore be modified and/or
supplemented for all specific maintenance operations to be carried out.
MAINTENANCE
INSTALLATION
SCRAPPING &
TRANSPORT
OPERATION
RECYCLING
START-UP
PACKING
SAFETY INSTRUCTIONS
OBJET - TITLE :
DISJONCTEUR GL318 (D) A COMMANDE MECANIQUE FK3.4 - MONTAGE SITE
CIRCUIT BREAKER GL318 WITH SPRING MECHANISM – SITE ERECTION
- DESTINATAIRES - EXEMPLARIES :
GIL Veronique
VALLA Jean-yves
ATTENCIA Bernard
THION René
LABADIE Jean-Claude
VENARD Pierre LICENCIES
Pas de poste OPM en diffusion
HIGH VOLTAGE PRODUCTS - 130, rue Léon Blum 69611- Villeurbanne Cedex - France
Tél : +33 (0)4 72 68 34 34 - Fax : +33 (0)4 72 68 39 22
VALIDITÉ
VALIDITY
DURÉE D'OUVERTURE : Intervalle de temps OPENING TIME : Interval of time between the
entre l'instant de mise sous tension du instant of energizing the opening release and the
déclencheur et l'instant de la séparation des instant when the arcing contacts have separated in
contacts d'arc sur tous les pôles (ou des contacts all poles (or simulator contacts controled by the
du simulateur commandés par la charge fictive). dummy load).
MANOEUVRE Maximum
OPERATION
Fermeture - Closing 2
Ouverture - Opening 2
MANOEUVRE Maximum
OPERATION
Fermeture - Closing 4
Ouverture - Opening 2,8
Tension Moteur en V
Maximum
Motor Voltage in V
toutes 10
all
Type de chambre
Maximum par tête
Type of chamber
Maximum by head
105/4 90
105/5 95
105/11 95
105/13 95
58.020.034 E
This page is intentionally blank.
RPH2 Service Manual
CONTENTS
1. IN GENERAL 6
1.2. Unpacking 6
1.3. Storage 6
1.4. Installation 6
2. INTRODUCTION 8
3. APPLICATION NOTES 16
Page 1/73
AREVA T&D Austria AG Issue 3 58.020.034 E
2004-02-12
Page 2
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
5 RPH2 MENUE SYSTEM 39
5.2 CB Data 44
5.2.1 Operating Time CH1 44
5.2.2 Operating Time CH2 44
5.2.3 Arcing Time CH1 44
5.2.4 Arcing Time CH2 45
5.2.5 Auxiliary Timeshift CH1 45
5.2.6 Auxiliary Timeshift CH2 45
5.2.7 Adaptive Control 45
5.2.7.1 Weighting Factor 46
5.2.7.2 Adaptive Times CH1 46
5.2.7.3 Adaptive Times CH2 46
5.2.7.4 Reset Adaptive Times 46
5.2.8 Compensation 46
5.2.9 kU1 Voltage CH1 46
5.2.10 kP1 Pressure CH1 47
5.2.11 Temperature Compensation CH1 47
5.2.12 Table Temp. CH1 47
5.2.12.1 Delta_t xx°C 47
5.2.13 kU2 Voltage CH2 48
5.2.14 kP2 Pressure CH2 48
5.2.15 Temperature Compensation CH2 48
5.2.16 Table Temp. CH1 48
5.2.16.1 Delta_t xx°C 48
Page 3
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
5.3.6 Pressure 53
5.3.6.1 Value at 4 mA 53
5.3.6.2 Value at 20 mA 54
5.4 Alarms 54
5.4.1 Reset Obligatory 54
5.4.2 Lock-Out 55
5.4.3 Alarm List 55
5.4.3.1 Lock-out 56
5.4.3.2 Frequency min 56
5.4.3.3 Frequency max. 56
5.4.3.4 Current max. (peak) 57
5.4.3.5 Reference Voltage Failure 57
5.4.3.6 RTC Impulse Failure 57
5.4.3.7 Neutral intermediate 57
5.4.3.8 Neutral grounded 57
5.4.3.9 Neutral isolated 57
5.4.3.10 Selftest ERROR 57
5.4.3.11 Selftest CH1 ERROR 57
5.4.3.12 Selftest CH2 ERROR 58
5.4.3.13 Command Time CH1 min 58
5.4.3.14 Command Time CH2 min 58
5.4.3.15 Operating Time min 58
5.4.3.16 Operating Time max. 58
5.4.3.17 Drive mech. Failure 59
5.4.3.18 Archive Full 59
5.4.3.19 Archive Failure 59
5.4.3.20 Control Voltage min 59
5.4.3.21 Control Voltage max. 59
5.4.3.22 Temperature min 59
5.4.3.23 Temperature max. 60
5.4.3.24 Temp. Transducer Fault 60
5.4.3.25 Pressure min 60
5.4.3.26 Pressure max. 60
5.4.3.27 Press. Transducer Fault 60
5.5 Measurement 60
5.5.1 Current Graphs 60
5.5.2 Measured Times 61
5.5.2.1 Command OUT 61
5.5.2.2 CB Signal received 61
5.5.2.3 Calculated Operating Time 62
5.5.2.4 Measured Operating Time 62
5.5.3 Frequency 62
5.5.4 Current (RMS) 63
5.5.5 Control Voltage 63
5.5.6 Actual Temperature 63
5.5.7 Temperature for Compensation 64
5.5.8 Additional Operating Times 64
5.5.8.1 Voltage CH1 64
5.5.8.2 Voltage CH2 64
5.5.8.3 Temperature CH1 65
5.5.8.4 Temperature CH2 65
5.5.8.5 Pressure CH1 65
5.5.8.6 Pressure CH2 65
Page 4
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
5.5.9 Pressure (L1/L2/L3) 66
5.5.10 Pressure (L1) 66
6 COMMISSIONING 68
Page 5
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
1. IN GENERAL
The electronic switching circuit of the RPH2 Point-on-Wave Controller from AREVA
T&D Austria AG, Leonding meets all the requirements concerning electromagnetic
compatibility in accordance with the EN 50 081-1/1992 and EN 50 082-2/1995.
Care is necessary only if the plug-in unit is pulled out of the casing. Take care not to
touch the plug contact on the back! For storing and transporting loose plug-in units, we
recommend a conductive fail packaging.
As soon as the plug-in unit is properly installed in the casing, no safety measures are
necessary at all.
1.2. Unpacking
Despite the general robust construction of the Point-on-Wave Controller, it must be
handled with care before installation. Before accepting the Point-on-Wave Controller it
should be checked for damage which could have originated during transportation. If
you have cause for complaint, please refer to the transport company and notify a
person responsible at AREVA.
1.3. Storage
If the Point-on-Wave Controller is not to be installed immediately upon receipt, it
should be stored in a place which is free of dust and moisture, in its original packaging.
If a moisture-absorption bag is in the packaging, leave it as it is. The effectiveness of
the drying agent is impaired if the non-protected bag is subjected to the surrounding
conditions.
Before the Point-on-Wave Controller is placed in the box again, warm the drying bag
slightly in order to regenerate the drying agent.
1.4. Installation
The RPH2 Point-on-Wave Controller can either be installed in a switchboard or a
suitable frame with the provided material (panel cut-out see diagram 58.001.115), or a
special fitting is available for wall mounting (see diagram 58.001.116).
Page 6
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
We suggest the control room or the relays room as the most favourable installation
site. Installation in a heated outdoor control cubicle is also possible. Installation directly
in the operating mechanism of a circuit breaker is not provided for (please contact
AREVA regarding this).
The position should be well lit in order to make inspections easier.
Wiring is carried out according to the wiring diagram which is enclosed with every
Point-on-Wave Controller. Take care to earth the housing appropriately.
Page 7
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
2. INTRODUCTION
The 7 alarm LED's are active, however there is only one alarm contact (Alarm 1)
available. In addition, there is an alarm contact "Device not ready".
The casing is a standard 19 inch sub-rack, with half width for one device or
alternatively with full width for 2 devices. After removing the 4 external screws of the
front panel, the plug-in unit on the grip rail can be removed from the housing. Safety
notes see 1.1.
Page 8
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
2.3.2. Current measurement module: Option I
With this the phase currents during the switching process can be recorded and
graphically displayed. Data from the last 4 switching operations (curves, amplitudes) are
stored in a non volatile memory and can be analysed on the display. Primary values are
shown after feeding in the current transformer ratios.
With reduced control voltage at the circuit breaker coil there is less energy available to
change the electrical control commands into a mechanical action. The operating time
extends itself. (Valid for all types of operations.)
By altering the hydraulic pressure on hydraulic drives, the energy available to carry out
the switching movement changes.
The ambient temperature is the most complex parameter of influence. The electrical
resistance of the trip coils, the oil viscosity and the pressure of the SF6 gas are
dependent on the temperature. In addition, changes of length in the driving linkage and
the porcelains occur. All these parameters influence the operating time in different ways.
In the extreme, each of these 3 parameters can alter the operating time by some
milliseconds. The RPH2 with option A is in the position to compensate these operating
time alterations.
There are inputs available for the measurements acquired when measuring the control
voltage, pressure and temperature for the compensation of pole operating times.
The control voltage is measured directly in the RPH2 at the input terminals for the
auxiliary voltage. There are no external measuring devices necessary.
For measuring pressure and temperature, external sensors with integrated transducer
banks (2 conductor constructions, auxiliary voltage 24 VDC) and standard output signal
(4...20 mA) are necessary. The supply for the transducer bank is effected by the RPH2.
Up to 8 RPH2's can be switched in parallel on one temperature sensor. When
measuring pressure, an individual transducer is necessary for each circuit breaker
(option A1) or each circuit breaker pole (option A3). The measuring range of the
measuring instruments depends on the requirements and can be simply parameterized
in the RPH2.
2.3.3.1. Option A0
Measuring and compensation of control voltage and temperature (for springloaded
drives)
Page 9
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
2.3.3.2. Option A1
Same design as 2.3.3.1, however with additional measurement and compensation for
hydraulic pressure (for hydraulic drives which have a mutual pressure generation for all
three poles).
2.3.3.3. Option A3
Like 2.3.3.2, however for circuit breakers which have pressure generation per pole.
Sys t em Da t a
> Pa s swo r d
Sy s t em F r e q u e n c y
Co n t r o l Vo l t a g e
Ra t ed Pr essu r e
00 0 0
12345 6 78
L1 L2 L 3
Page 10
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
Note: The whole contrast-range of the display is adjustable. Therefore the display
becomes nearly transparent or dark respectively for a moment. The selected contrast is
stored in a non-volatile memory.
2.4.3.2.LED 1 to 7 (red)
To show the parameterized alarms. The LED's are assigned to the alarm relays 1 to 7.
Next to the LED's is a window in which the user's message texts can be placed. For a
withdrawn cassette, the input tag with the texts is inserted from the top behind the front.
As insert use a sheet of paper 41 mm x 90 mm.
Status Function
Steady light An alarm has occurred. The LED remains alight until
the alarm is active (regardless of whether the "Quitt"
button has been pressed). As long as the LED is
alight, the affiliated output relay is also activated.
Page 11
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
Status Function
Blinking An alarm has occurred which is marked as „Rest
obligatory“
After pressing the "Quitt" button two possibilities arise:
1) The LED extinguishes, i.e. the alarm was no
longer active when reseted, the output relay is released.
2) The indicator switches over to permanent light, i.e.
the alarm is still active, the output relay remains
energized.
As long as the LED is alight or blinks, the affiliated output relay is energized.
2.4.4. Keys
[Enter] Menu point open / confirm
[+] Cursor up / increase value
[-] Cursor down / decrease value
[Esc] Leave menu point / break-off action
[Quitt] Acknowledge alarm / alter current scale (together with [+] or [-])
PC Serial Port RPH2 Serial Port PC Serial Port RPH2 Serial Port
1 1 1 1
Changes are only possible after the password has been activated.
After feeding the auxiliary voltage, the first four lines of the master menu (1st plane)
appear on the display. Move the menu cursor (black triangle on the left side of the
Page 12
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
display) up and down using the [+] an[-] keys. The first four lines of the 2nd plane are
shown after pressing [Enter]. Analogues are also valid for the 3rd plane. The menu
cursor is moved again using [+] or [-]. The contents of the cells are shown in the status
line. If a value is to be altered, move the menu cursor to the desired plane and line.
After pressing [Enter], a blinking cursor appears under the first status line position.
Change this position using [+] or [-]. [Enter] moves the cursor right to the next position.
With [Esc] the input mode can be left at any time without storing the changes made.
The input is confirmed with [Enter]. The new value is stored and the menu cursor
appears. [Esc] enables the input procedure to be repeated.
After completing the input, turn the key-operated switch to "OFF" and then to
"OPERATION" or start the selftest via the menu. After the selftest the data in the
system is accepted.
The following pages show a list of all the available menu points. The cross-references
to the chapter with the detailed function description are in the column "Chapt.".
The column "Module" shows with which model variation this menu is available.
The following coding system applies:
-1 RPH2 with one switching function
-2 RPH2 with two switching functions
Ax Analogue module in all models with module A
A1 Analogue module, e.g. Option 1
I Current measuring module Option I
S Signal module Option S
Page 13
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
2.5.1. Menu structure
5.2 CB Data
5.2.1 Operating Time CH1
5.2.2 Operating Time CH2
5.2.3 Arcing Time CH1
5.2.4 Arcing Time CH2
5.2.5 S Aux.Timeshift CH1
5.2.6 S Aux.Timeshift CH2
5.2.7 SAx Adaptive Control ->
5.2.7.1 SAx Weighting Factor
5.2.7.2 SAx Adaptive Times CH1
5.2.7.3 SAx Adaptive Times CH2
5.2.7.4 SAx Reset Adaptive Times
5.2.8 Ax Compensation
5.2.9 Ax kU1 Voltage CH1
5.2.10 A1,A3 kP1 Pressure CH1
5.2.11 Ax Temp. Comp. CH1
5.2.12 Ax Table Temp. CH1 ->
5.2.12.1 Ax Delta_t xx°C
5.2.13 Ax kU2 Voltage CH2
5.2.14 A1,A3 kP2 Pressure CH2
5.2.15 Ax Temp. Comp. CH2
5.2.16 Ax Table Temp. CH2 ->
5.2.16.1 Ax Delta_t xx°C
5.3 Analogue Data
5.3.1 Thresholds
5.3.1.1 I Current max (peak)
5.3.1.2 Ax Control Voltage max
5.3.1.3 Ax Control Voltage min
5.3.1.4 Ax Temperature max
5.3.1.5 Ax Temperature min
5.3.1.6 A1,A3 Pressure max
5.3.1.7 A1,A3 Pressure min
5.3.2 I Rated Curr. prim
5.3.3 I Rated Curr. sec
Page 14
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
Chapter Module Level 1 Level 2 Level 3
Analogue Data (contin.)
5.3.4 Ax Actual Contr. Voltage
5.3.5 Ax Temperature
5.3.5.1 Ax Value at 4 mA
5.3.5.2 Ax Value at 20 mA
5.3.6 A1,A3 Pressure
5.3.6.1 A1,A3 Value at 4 mA
5.3.6.2 A1,A3 Value at 20 mA
5.4 Alarms
5.4.1 Reset obligatory
5.4.2 Lock-out
5.4.3 Alarm List
5.4.3.1 Lock-out
5.4.3.2 Frequency min
5.4.3.3 Frequency max
5.4.3.4 I Current max (peak)
5.4.3.5 Ref. Voltage Failure
5.4.3.6 S RTC Impulse Failure
5.4.3.7 Neutral intermediate
5.4.3.8 Neutral grounded
5.4.3.9 Neutral isolated
5.4.3.10 Selftest ERROR
5.4.3.11 Selftest CH1 ERROR
5.4.3.12 -2 Selftest CH2 ERROR
5.4.3.13 Command Time CH1 min
5.4.3.14 -2 Command Time CH2 min
5.4.3.15 S Operating Time min
5.4.3.16 S Operating Time max
5.4.3.17 S Drive Mech. Failure
5.4.3.18 Archive Full
5.4.3.19 Archive Failure
5.4.3.20 Ax Control Voltage min
5.4.3.21 Ax Control Voltage max
5.4.3.22 Ax Temperature min
5.4.3.23 Ax Temperature max
5.4.3.24 Ax Temp. Transd. Fault
5.4.3.25 A1,A3 Pressure min
5.4.2.26 A1,A3 Pressure max
5.4.3.27 A1,A3 Pressure Transd. Fault
5.5 Measurement
5.5.1 I Current Graphs
5.5.2 Measured Times
5.5.2.1 Command OUT
5.5.2.2 S CB Signal received
5.5.2.3 Ax Calculated Op. Time
5.5.2.4 S Measured Op. Time
5.5.3 Frequency
5.5.4 I Current (RMS)
5.5.5 Ax Control Voltage
Page 15
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
Chapter Module Level 1 Level 2 Level 3
Measurement (contin.)
5.5.6 Ax Temperature
5.5.7 Ax Temperature f. Comp
5.5.8 Ax Additional Op. Times
5.5.8.1 Ax Voltage CH1
5.5.8.2 Ax Voltage CH 2
5.5.8.3 Ax Temperature CH1
5.5.8.4 Ax Temperature CH2
5.5.8.5 A1,A3 Pressure CH1
5.5.8.6 A1,A3 Pressure CH2
5.5.9 A3 Pressure (L1/L2/L3)
5.5.10 A1 Pressure (L1)
5.6 Aux. Functions
5.6.1 S Alarm Output
5.6.2 S Alarm Input
5.6.3 Error Type
5.7 Switching Archive
3. APPLICATION NOTES
3.1.1.1. Closing
Energizing of transformers, reactors and capacitors is normally effected three-pole - for
all 3 phases simultaneously. In doing this the point on wave is left up to chance. If
closing is carried out in this manner, high inrush currents with high DC components are
unavoidable. When energizing capacitors additional high switching surges can occur.
The results are unwanted operation of protection devices and repercussions on
machines and network.
The inrush currents and switching surges can be reduced to an acceptable rate by
installing closing resistors at the circuit breaker. The costs for such closing resistors are
very high, due to the mechanical expenditure. Besides, the necessarily high energetic
absorbtivity of the resistor material sets relatively restricted limits of practicability.
By selecting a suitable switching time the physical causes of these high inrush currents
can be counteracted. This possibility is effected through synchronized switching with the
RPH2. This enables the three poles of a circuit breaker to be controlled independently.
Page 16
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
3.1.1.2. Opening
The de-energizing of shunt reactors is a critical process liable to generate re-ignitions
between circuit breaker contacts. This means very high stress for the insulation of both
the shunt reactor and the circuit breaker.
If the contact separation takes place a sufficient amount of time before the current zero
crossing through suitable circuit breaker control, to ensure a gap capable of
withstanding the transient recovery voltage at interruption.
On the other hand, the opening time is the time between the electrical command and the
separation of the main contacts. The operating times of circuit breakers, independent of
the breaking system and the type of operating mechanism, changes in dependence on
certain service parameters:
· With reduced control voltage at the operating coil there is less energy available to
change the electrical control commands into a mechanical action. The operating
time extends itself. (Valid for all types of operating drives.)
· By altering the hydraulic pressure on hydraulic drives, the energy available to carry
out the switching movement changes.
· The ambient temperature is the most complex parameter of influence. The electrical
resistance of the operating coils, the oil viscosity and the pressure of the SF6 gas
are all dependent on the temperature. Moreover, there is expansion of operating
rods and porcelains. All these parameters influence the operating time in different
ways.
In the extreme, each of these 3 parameters can alter the operating time by some
milliseconds. The RPH2 is in the position to compensate these operating time variations.
· Large graphic display to show the adjusted and measured values ( in German,
English and French or user defined language)
· Analogue module for measuring control voltage, pressure and temperature, for the
compensation of changes in operating time.
Page 17
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
· Current measuring function for the graphic display of the line currents during
switching.
· Two switching functions (CLOSING and OPENING) with one device are possible.
· Switching programs with fixed switching times for the most frequent applications.
· Extensive archive function. The most important data for the last 1000 operations are
stored in a non-volatile memory and are available for diagnostic purposes.
· Comfortable PC software for setting and read-out archive data. All data can be
stored and printed out. If the user cannot find sufficiency with the three languages
mentioned previously, then the display can be translated into the user's national
language using PC software.
Page 18
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
Figure 1
2
System
voltage
3
Current
t_arc
1
CB-ON
command
t d CB operating time
to RPH2
Command
by RPH2
4
CB main
contact
Figure 2
2
System
voltage
3
4
Current
t_arc
1
CB-OFF
command
t_d CB operating time
to RPH2
Command
by RPH2
CB main
contact
time
t_arc...arcing time of CB
t_d ...delay time of RPH2
Page 19
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
Whether the system neutral is grounded or isolated, the RPH2 registers the signal
contacts of the neutral earthingswitch and automatically selects the correct switching
time.
For transformers with primary windings in delta connection the program for isolated
neutral must be used (short circuit the terminals -X6:8 with -X8:11 of the RPH2).
Page 20
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
3.2.1. Closing
3.2.2. Opening
For switching off transformers and three leg reactors with the RPH2, please read point
3.3.2 "Switching off Reactor Groups".
The mechanical closing and/or opening operating time of the three circuit breaker poles
(see 3.1.2 for definition). Accuracy about ±0,1 ms.
3.2.3.1. Closing
For closing at the correct time, the pre-arcing time of the breaker at the closing voltage
(see table 2) according to the phases and the treatment of the system neutral.
If the exact value cannot be obtained from the breaker manufacturer, the optimum
closing time can be determined through switching tests with oscillographical
measurements of the inrush currents. For RPH2 with option I, the inrush currents are
directly shown by the device (curve course and peak value). For the tests it is advisable
Page 21
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
to begin with an assumed pre-arcing time of 3 ms at Ö(2/3)*Un, 2.5 ms at ½*Ö2*Un and
4.5 ms at 1.5*Ö(2/3)*Un.
3.2.3.2. Opening
Data of the optimum arcing time in order to guarantee a sure current breaking in the
next zero crossing.
See 3.3.3 for further information
3.3.1. Closing
3.3.2. Opening
Breaking of small inductive currents, as is with reactors, can lead to high switching
surges if current chopping or restriking in the circuit breaker occurs.
Contact separation should take place a sufficient time before current zero crossing so
that after current breaking the contact gap is great enough to withstand the recovery
voltage. The switching times given in table 1, indicate the moment of current breaking.
The necessary arcing window is taken into account by the RPH2 through the arcing
time.
Page 22
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
The mechanical closing and/or opening operating time of the three circuit breaker poles
(see 3.1.2 for definition). Accuracy about ±0,1 ms.
3.3.3.1. Closing
The pre-arcing times of the circuit breaker must be known.
· Pre-arcing time of the breaker in the voltage peak: equal value for all three phases
with grounded neutral or for phase L1 with isolated neutral.
· Pre-arcing time with partial voltage: for phases L2 and L3 with isolated neutral (see
table 2)
3.3.3.2. Opening
The optimum arcing time input determines the arcing window for a secure current
breaking, free from restrikes, in the next zero crossing. The value is given by the
breaker manufacturer.
In order not to come into conflict with unavoidable operating time tolerances, contact
separation should begin 1,5 ms after zero crossing at the earliest, i.e. do not select an
arcing time of longer than 8,5 ms (6,8 ms at 60 Hz). About a quarter period as arcing
time is regarded as standard time.
For circuit breaker opening, the breaker should achieve an operating time accuracy
of ±1,5 ms.
3.4.1. Closing
High inrush currents and high voltage surges can occur with the random switching of
capacitors, especially if switching takes place in the voltage peak. The effects of parallel
switching of capacitors is particularly serious. Particularly high voltage surges can occur,
due to reflections at the end of radial networks.
Page 23
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
3.4.2. Opening
In general, breaking of capacitive currents represents no problem for modern circuit
breakers. If the RPH2 is used for the synchronized switching of capacitor banks, then
the same applies as in 3.3.2, i.e. contact separation in sufficient time before voltage zero
crossing.
The mechanical closing and/or opening operating time of the three poles (see 3.1.2 for
definition). Accuracy about ±0,1 ms.
In order to achieve the necessary accuracy when closing in the voltage zero crossing,
the rate of fall of the withstand voltage (dUd/dt) of the breaker should be greater than
the rate of change of the gap voltage at voltage zero (dU/dt). Figure 3 shows three
possible cases.
1 The rate of fall of the breakers withstand voltage (dUd/dt) is less than the rate of
fall of the system voltage (dU/dt). dUd/dt < dU/dt, k<1.
The breaker can be used for this application if dUd/dt > 0.8*dU/dt. In this case
please contact the manufacturer of the breaker for calculation of the pre-arcing
times.
2 The rate of fall of the breakers withstand voltage (dUd/dt) is equal to the rate of
fall of the system voltage (dU/dt). dUd/dt = dU/dt, k=1.
3 The rate of fall of the breakers withstand voltage (dUd/dt) is greater than the rate
of fall of the system voltage (dU/dt). dUd/dt > dU/dt, k>1.
Figure 3
1 2 3
u
Page 24
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
However, some pre-arcing may be inevitable due to variations in the closing time and
the spread in dielectric withstand. To minimise energizing transients, the closing should
aim at an instant, td, after the voltage zero (the RPH2 takes this into account through a
given arcing time). If data is not available from the breaker manufacturer, the pre-
arcing time can be approximated. Modern breakers have closing contact speeds of
typical 5 m/s and a dielectric strength of more than 20 kV/mm. That results in a fall rate
(dUd/dt) of more than 100 kV/ms.
Figure 4 shows the voltage across the open contact gap and the withstand voltage fall
with varying closing times. The arcing time ta is calculated so that the withstand
voltage is approx. the same value as the upper and lower operating time tolerance.
Figure 4
Ud
Up
ta
t
T T
T1
The RPH2 arcing time setting can be calculated according to the following formulas.
Take note of the differing arcing times with isolated neutrals. The calculations must be
verified by switching tests.
Page 25
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
Note: The system voltage in the following formulas is related to one interrupting
chamber of the circuit breaker, take care in case of breakers with multiple interrupting
chambers!
The voltage across one interrupting chamber is calculated as follows where "m" is the
number of interrupting chambers of one pole:
1.05 m-1
Un = U system × Un... Voltage for one interrupting chamber
m
The following example demonstrates the calculation for the pre-arcing time for each
pole with various system neutral treatments.
Page 26
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
Example:
For closing, the switch should reach a operating time accuracy of ± 1,5 ms.
Page 27
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
3.5 Switching (closing) of uncharged Lines
Uncharged high voltage lines are to be fundamentally treated like capacitors. Due to
the inter-phase coupling the switching moments are not the same as for capacitor
banks. The RPH2 can also be used for auto-reclosing of uncompensated lines
equipped with inductive potential transformers. During the auto-reclose dead-time the
trapped charges on the line must be fully discharged by the inductive potential
transformers!
Whether the system neutral is earthed or isolated does not effect the switching
moments.
The RPH2 must be set to the [User Program] with the following settings (see also
5.1.5.1).
For [T_C1 Neutral isolated] and for [T_C1 Neutral grounded] the same values must be
set:
50 Hz:
L1 = 0 ms
L2 = 7.3 ms
L3 = 13.3 ms
60 Hz:
L1 = 0 ms
L2 = 6.1 ms
L3 = 11.1 ms
Page 28
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
4 FUNCTIONS OF THE ADDITIONAL MODULES
Figure 5
CB main closing
contact
CB aux. -Dt
contact
CB main opening
contact
CB aux. Dt
contact
time
To compensate the time shift between the main contacts and the auxiliary contacts of
the breaker poles, the possibility exists to feed in a compensation time in order to
maintain the operating time as real value on the display and in the archives. Figure 5
shows the correlation as an example. If the auxiliary contact closes after the main
contact then the compensation time value. Dt is negative, if the auxiliary contact opens
before the main contact then a positive value results. If no possibility exists to measure
the time shift of the auxiliary contacts, this value can also be determined via the RPH2
within the time release limits.
Conditions:
· The pole operating times given by the manufacturer are correctly fed in (see 5.1
and 5.2)
Page 29
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
· The environmental conditions correspond approx. to the conditions when measuring
the pole operating times in the factory. With strong deviations in the environmental
conditions, the pole operating times must be measured again on site.
· The RPH2 compensating function is deactivated (see 5.6).
· The circuit breaker can be operated repeatedly without load (with opened busbar
disconnector.
Figure 6
Me a s u r d T i me s
Pole operating times:
C o mm a n d OUT
CB S i g na l Re c e i v ed
Ca l c u l at e d Op . T i me s L1 = 139.3 ms
> Me a s u r ed Op . T i me L2 = 138.7 ms
146 . 5 1 45 . 6 14 6 . 1ms L3 = 139.6 ms
12345 678
L1 L2 L 3
The value for "H-contact SK1 Diff" for every pole is calculated with:
The input values in figure 7 are calculated with the values form figure 6 and .the values
of the pole operating times.
Figure 7
CB D a t a - >
A r c i n g T i me CH 1
A r c i n g T i me CH 2
> A u x . T i me s h i f t CH 1
A u x . T i me s h i f t CH 2
- 7 . 2 - 6 . 9 - 6 . 5ms
12345678
L1 L2 L3
Because the operating times are measured with a resolution of 0,5 ms, it is possibly
necessary to constitute the average value from several switching operations. Feed in
the determined values under [CB Data] / [Aux. Timeshift CH1] (figure 7) and check the
measured operating times as described above. A further compensation is possibly
necessary.
Page 30
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
Check in all cases that the measured operating time corresponds with actual operating
times of the circuit breaker. This is essential for using the function of the adaptive
control !
For devices with two switching functions (RPH2-2), repeat the procedure for the
second switching channel too.
Figure 8
ambient temperature
Page 31
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
In the menu [Measured value/Compensation] each of the actual additional times are
shown. After the key-operated switch is turned form "OFF" to "OPERATION", the
RPH2 carries out an automatic check and all analogue measured values for
compensation are set at the actual measured value.
Figure 9
32
Function calculated by RPH2
31
30
Value 2
Operating Time [ms]
(U2/t2)
29
28
27
Value 1
(U1/t1)
26
140 160 180 200 220 240
Operating Voltage [V]
Page 32
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
The compensation parameter kU can be calculated using the following formula:
Value 1:
U1 [V] rated control voltage
t1 [ms] CB operating time at nominal conditions
Value 2:
U2 [V] reduced control voltage
t2 [ms] CB operating time with U2
With RPH2's with two switching functions, the calculation for kU1 and kU2 is to be
carried out separately for both switching channels and the values stored in the RPH2.
The RPH2 calculates the additional times for operating time compensation according
to a piecewise linear function with one control point every 10 °C in the range of -50 °C
and +50 °C. So all kinds of temperature functions of the circuit breaker (from linear to
exponential) can be set to the RPH2. The measured values can be entered in the table
in figure 10. The line Delta_t = 0 ms defines the nominal operating time of the circuit
breaker under normal conditions. The values of Delta_t at different ambient
temperatures are the differences of the measured operating times to the nominal
operating time. The 11 values of Delta_t(T) (T = -50 °C to +50 °C) must be set to the
RPH2.
In the example in figure 11 the procedure is shown. The measured values are marked
by squares. Connect the points by lines end eventually extend the lines to the
extremes (dotted line in the example). Evaluate the values of Delta_t(T) at the control
points (-50 °C to +50 °C) so to get the 11 values for Delta_t(T) shown in the table in
figure 11.
By using the PC software "RPH2- Tool" also an exponential function with one open
parameter can be calculated. Especially for circuit breakers with spring drive
mechanism this option will be useful.
Page 33
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
Figure 10
Delta_t [ms]
Page 34
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
Figure 11
Delta_t [ms]
Temperature Delta_t
-50 °C 13.0 ms
-40 °C 9.0 ms
-30 °C 5.0 ms
-20 °C 2.5 ms
-10 °C 1.6 ms
0 °C 0.8 ms
+10 °C 0.4 ms
+20 °C 0.0 ms
+30 °C -0.2 ms
+40 °C -0.4 ms
+50 °C -1.0 ms
measured values
With RPH2's with two switching functions, the evaluation of Delta_t(T) has to be
carried out separately for both switching channels and the values stored in the RPH2.
One (Option A1) or three (Option A3) external sensors with integrated transducer (2
conductors, auxiliary voltage 24 VDC) and standard output signal (4 ... 20 mA) are
necessary for measuring hydraulic pressure. The transducer supply is effected through
the RPH2.
Page 35
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
The RPH2 calculates the additional times for operating time compensation according
to a function with one open parameter. By fixing this parameter, the compensation
function can be suited to the character of the circuit breaker. Calculation for opening
and closing takes place separately. The parameter kP1 works for switching channel 1,
kP2 for switching channel 2 (only for devices with 2 switching functions). For the model
with option A3 with pressure measuring per pole only a compensation parameter for
each of the three poles is fed in. If a zero value is fed in for a parameter, then no
additional times are calculated and the compensation function concerned is blocked.
Fixing the compensation parameters takes place through calculation or with the
assistance of the accompanying PC Software.
Two measuring points of the switching characteristic analogue for 4.2.1 are required to
calculate the equalising curve:
· One point with rated conditions (value 1): measured pole operating time (of one
pole) with rated voltage, rated pressure and rated temperature. In general that is the
manufacturer value for pole operating time.
· A second point with deviation conditions (value 2): measured pole operating time of
the same pole with rated control voltage, rated temperature and reduced hydraulic
pressure.
Example:
Value 1 (with nominal conditions):
P1 = 265 bar Rated pressure
t1 = 110.5 ms Pole operating time with nominal conditions
Value 2:
P2 = 200 bar Reduced pressure
t2 = 127.7 ms Pole operating time with pressure P2
Value 1:
P1 [V] rated hydraulic pressure
t1 [ms] CB operating time at nominal conditions
Value 2:
P2 [V] reduced hydraulic pressure
t2 [ms] CB operating time with P2
With RPH2's with two switching functions, the calculation for kP1 and kP2 is to be
carried out separately for both switching channels and the values stored in the RPH2.
Page 36
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
4.2.4 Specifications for the external sensors
For measuring pressure and temperature, external sensors with integrated transducer
are necessary which are not part of the delivery.
Such transducers can be obtained from many manufacturers. The measuring range of
the sensors adjust itself to the respective requirements.
However, unnecessarily large measuring ranges reduce the measuring accuracy of the
RPH2. The RPH2 measuring input is adapted to the measuring range of the sensor
through parameterisation.
The compensation of the time shift between the main contacts and the auxiliary contacts
of the breaker poles must be done very exactly to avoid errors in measuring of the
actual operating times.
· Time deviations of the measured values greater than 10 ms are not considered. (no
operation of the CB or incorrect measurement of operating times).
· Additional adaptive time is limited to 1 ms from one operation to the next.
· If the operating time corrected by adaptive control has drifted away from the pre-set
operating times for more than
±5 ms for opening
±10 ms for closing
the alarm "Drive mech. Failure" is generated.
The value of the weighting factor depends on the type of drive mechanism. We propose
a value of 0.25 to 0.30 for all types of mechanism.
Page 37
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
4.3 Current Module Option I
A current measuring module is available to make the switching of large transformers
and reactors easy when putting the RPH2 Point-on-Wave Controller into operation.
With this the inrush current can be recorded and graphically displayed during the
switching process. Data for the last 4 switching operations are stored in a non-volatile
memory and can be analysed on the display. Primary values are shown after feeding in
the current transformer current ratio.
For every phase there is an input for each 1 A and 5 A available. Because the current
inputs have a short time withstand of 100 xln, current measurement can be carried out
over a measuring core as well as a protection core of the current transformer.
Page 38
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
5 RPH2 MENUE SYSTEM
12345678
L1 L2 L3
Enter + - Esc
5.1.1 Password
The factory-setting of the-password is "0000". To activate the password you must
change to the submenu [System Data/Password]. The actual status (‘active’ or ‘off’) is
shown in the bottom-left corner of the display. Type in the correct password and confirm
the assumption by pressing the ‘Enter’-button (see chapter 2.5). The display shows
‘active’ and the green LED ‘ready’ starts blinking if the password is correct (see chapter
2.4.3.1).
The password will be deactivated automatically if no button is pressed for more than 90
seconds.
Sy s t em D a t a
> P a s swo r d
S y s t em F r equ e n c y
C o n t r o l Vo l t a g e
R a t ed P r e s s u r e
0 0 0 0
1234 5 6 78
L1 L2 L 3
Page 39
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
Sy s t em D a t a
P a s swo r d
> S y s t em F r equen c y
C o n t r o l Vo l t age
R a t ed P r e s s u r e
50 H z
12345678
L1 L2 L3
Sy s t em D a t a
P a s swo r d
S y s t em F r equ e n c y
> C o n t r o l Vo l t a g e
R a t ed P r e s s u r e
2 3 0 , 0 V
1234 5 6 78
L1 L2 L 3
Sy s t em D a t a
Sy s t em F rn eque c y
Co n t r o l Vg o l t a e
> Ra t ed P r ee s s u r
Sw i t c h i n gg P r o r am
1 0ba r
123456 78
L1 L2 L3
· transformer
· shunt reactor
· capacitor bank
· user program
Page 40
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
Sy s t em D a t a
Co n t r o l V o l t age
Ra t ed P r e s s u r e
> Sw i t c h i ng P r o g r am
La n guage
T r a n s f o rme r
1 2345678
L1 L2 L3
You can define your own switching moments for each phase by selecting the ‘User
Program’.
Note: If you select ‘user program’ you have to select the rated frequency first (see
chapter 5.2).
Us e r P r o g r am
> T _C 1 N e u t r . i so l a t e d
T _C 1 N e u t r . g ro u nde d
T _C 2 N e u t r . i so l a t e d
T _C 2 N e u t r . g ro u nde d
0 , 0 0 , 0 0 , 0ms
1 234 56 7 8
L1 L2 L3
The following two submenus are available only for module RPH2-2xx (module with two
switching channels):
Page 41
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
5.1.6 Function Channel 1
For the module RPH2-1xxx you have to select whether if you use the RPH2 for closing
or opening of the CB.
5.1.7 Language
Select your preferred language.
Available languages:
· German
· English
· French
· User language
S y s t em D a t a
Ra t ed P r e s s u r e
Sw i t c h i n g P r o g r am
> Languag e
T i me / Da t e
Eng l i s h
12345678
L1 L2 L3
Note: You can load the menutext in any language with the RPH-Tool (PC-based
software). If there any problems with the loaded language file you can return to the
English menus: Turn the key-operated switch to "OFF", press the "Quitt" button and
meanwhile return the key-operated switch back to "OPERATION".
S y s t em D a t a
Sw i t c h i ng P r o g r am
Languag e
> T i me / Da t e
New Pa s swo r d
1996 - 12 - 0 6 17 : 51
12 345678
L1 L2 L3
Page 42
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
Sy s t em D a t a
L anguag e
T i me / Da t e
> N ew Pa s swo r d
S e l f t e s t S t a r t
0 0 00
1234 5 678
L1 L2 L 3
Note: If you have forgotten the selected password, you can ask for a temporary
password (call your local AREVA representative)
The selftest-facility checks the internal function of the module and the switching outputs.
S y s t em D a t a
T i me / Da t e
New Pa s swo r d
> Se l f t e s t S t a r t
Se l f t e s t I n t e r v a l
YES
12345678
L1 L2 L3
Note: You can activate the selftest with the key-operated-switch too (see chapter 2.4.2).
The possible range is from 0,0 hours (shortest interval is 0,1 hour = 6 minutes) to 500
hours. Choosing a value of 0,0 hours deactivates the automatic selftest-facility.
Sy s t em D a t a
T i me / Da t e
N ew Pa s swo r d
S e l f t e s t S t a r t
> S e l f t e s t I n t e r v a l
2 4 , 0 Hr
12345 678
L1 L2 L 3
In the menu [Aux. Functions][Error Type] the type errors are displayed (see 5.6.3).
Page 43
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
5.2 CB Data
The permissible range is from 0,0 ms (minimum value is 0,1 ms) to 200 ms.
The switching function (closing or opening) for module RPH2-1xx depends on the
selection made in the submenu ‘Function Channel 1’. (see chapter 5.1.6).
CB D a t a
> Op e r a t i n g T i me CH 1
Op e r a t i n g T i me CH 2
A r c i n g T i me CH 1
A r c i n g T i me CH 2
0 , 0 0 , 0 0 , 0ms
12345678
L1 L2 L3
Note 1: The value of the operating time for each phase of the CB depends on the type
and manufacturer of the CB. This value is part of the CB-documentation delivered with
your CB.
Note 2: The difference between 2 phases should be less than one period (20 ms for
50 Hz).
Note 3: For single-phase-CBs the values for all three phases must be the same.
The permissible range is from 0,0 ms (minimum value is 0,1 ms) to 200 ms.
The permissible range is from 0,0 ms (minimum value is 0,1 ms) to 50 ms.
Closing: Pre-arcing time of the CB. The closing of the main-contact happens after the
chosen switching moment.
Page 44
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
Opening: Arcing time of the CB. The opening of the main-contact happens before the
zero-crossing of the current.
CB D a t a
Op e r a t i n g T i me CH 1
Op e r a t i n g T i me CH 2
> A r c i n g T i me CH 1
A r c i n g T i me CH 2
0 , 0 0 , 0 0 , 0ms
12345678
L1 L2 L3
CB D a t a
A r c i n g T i me CH 1
A r c i n g T i me CH 2
> A u x . T i mes h i f t CH 1
A u x . T i mes h i f t CH 2
+ 0 , 0 +0, 0 + 0 , 0ms
12345678
L1 L2 L3
CB Da t a
Au x . T i me s h i f t CH 2
> Adap t i v C o n t r o l - >
C omp e n s a t i on
kU1 V o l t a g e CH 1
12345678
L1 L2 L3
Page 45
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
This submenu and the following menus are available only with module RPH2-xSAx.
A d a p t i v Con t r o l
> W e i g h t i ng Fa c t o r
A d a p t i v e T i me s CH 1
A d a p t i v e T i me s CH 2
R e s e t Adap t i v e T i me
0 . 25
12345 678
L 1 L2 L 3
5.2.8 Compensation
If you select ‘NO’ all compensation functions are blocked.
If you select ‘YES’ compensation is active (for description see chapter 4.2)
CB Da t a
Au x . T i me s h i f t CH 1
Au x . T i me s h i f t CH 2
> C omp e n s a t i on
kU1 V o l t a g e CH 1
YES
12345678
L1 L2 L3
Page 46
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
CB Da t a
Au x . T i me s h
i f t CH 2
C omp e n s a ton i
> kU1 V o l t a g
e CH 1
kP1 P r e s s u
r e CH 1
30 , 3
12345678
L1 L2 L3
CB Da t a
k U 1 V o l t a g e CH 1
k P 1 P r e s u r e CH 1
> T emp . C omp . CH 1
T a b l e T emp . CH 1 - >
ON
12345678
L1 L2 L3
Ta b l e T emp 1. CH - >
D e l t a _ t -
°C 50
> D e l t a _ t -
°C 40
D e l t a _ t -
°C 30
D e l t a _ t -
°C 20
+5 . 3 ms
12345678
L1 L2 L3
Page 47
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
5.2.13 kU2 Voltage CH2
same as 5.2.9, but for control voltage compensation for channel 2.
5.3.1 Thresholds
The following submenus are depending on the configuration of the RPH 2 obtained.
Exceeding of limit-settings cause an alarm, if set (see chapter 5.4).
Ana l og D a t a
> T r e s ho l d s - >
CT Ra t e d Cu r r . p r im
CT Ra t e d Cu r r . s e c
Ac t ua l C on t r . Vo l t age
12345678
L1 L2 L3
Type in the allowed maximum value (peak-value) of the current during the switching
operation. If the current during a switching operation exceeds this limit an alarm is
generated.
Page 48
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
T r e s h o l d s - >
> Cu r r e n t ma
( p x eak )
Op . V o l t ag
ma e x
Op . V o l t ag
m i e n
T emp e r a t u r
ma e x
50 0 A
123456 78
L1 L2 L3
T r e s h o l d s - >
C u r r e n t ma x ( p eak )
> C on t r o l Vo l t ag e ma x
C on t r o l Vo l t ag e m i n
T emp e r a t u r e ma x
242 , 0 V
123456 78
L1 L2 L3
This submenu is available only with modules RPH2-xxA0, RPH2-xxA1, RPH2-xxA3.
T r e s h o l d s - >
Cu r r e n t ma
( p x eak )
Op . V o l t ag
ma e x
> Op . V o l t ag
m i e n
T emp e r a t u r
ma e x
200 , 0 V
123456 78
L1 L2 L3
Page 49
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
T r e s h o l d s - >
Op . V o l t a
e ma g x
Op . V o l t a
e m i g n
> T emp e r a t u
e ma r x
T emp e r a t u
e m i r n
+50 , 0 C
123456 78
L1 L2 L3
T r e s h o l ds - >
Op . V o lt age m i n
T emp e r at u r e ma x
> T emp e r at u r e m i n
P r e s s u re ma x
- 50 . 0 C
123456 78
L1 L2 L3
This submenu is available only for module RPH2-xxA0, RPH2-xxA1, RPH2-xxA3.
T r e s h o l ds - >
T emp e r at u r e ma x
T emp e r at u r e m i n
> P r e s s u re ma x
P r e s s u re m i n
35 0ba r
123456 78
L1 L2 L3
Page 50
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
T r e s h o l ds - >
T emp e r at u r e ma x
T emp e r at u r e m i n
P r e s s u re ma x
> P r e s s u re m i n
18 0ba r
123456 78
L1 L2 L3
Ana l og D a t a
T r e s ho l d s - >
> CT Ra t e d Cu r r . p r im
CT Ra t e d Cu r r . s e c
Ac t ua l C on t r . Vo l t age
50 0 A
1234567 8
L1 L2 L3
Ana l og D a t a
T r e s ho l d s - >
CT Ra t e d Cu r r . p r im
> CT Ra t e d Cu r r . s e c
Ac t ua l C on t r . Vo l t age
5 A
12345678
L1 L2 L3
Note: The current transformer has to be connected to the correct terminal of the RPH2
(1 A or 5 A, see wiring diagram).
Page 51
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
5.3.4 Actual Control Voltage
Type in the measured value of the actual control voltage. This input calibrates the
internal voltage measurement. This value acts as base for the calculation of
compensation of the switching moment.
Ana l o g Da t a
CT R a t ed Cu r r . p r im
CT R a t ed Cu r r . s e c
> Ac t u a l Con t r . Vo l t age
T emp e r at u r e - >
1 12 , 2 V
1234 5678
L1 L2 L3
Note:This input calibrates the voltage measurement function. The correct input of this
value is absolutely necessary. You cannot calibrate the RPH2 with the PC-software
‘RPH-Tool’.
In the Normal-Mode (Ready-LED is steady-light) the measured voltage is displayed.
After calibrating the voltage measurement check the correct function by monitoring the
display.
5.3.5 Temperature
The following submenus are available only with modules RPH2-xxA0, RPH2-xxA1,
RPH2-xxA3.
In this submenu the temperature transducer is calibrated.
Ana l o g D a t a
CT R a t e d Cu r r . s e c
Ac t u a l C on t r . Vo l t age
> T emp e r a t u r e - >
P r e s s u r e - >
12345678
L1 L2 L3
5.3.5.1 Value at 4 mA
Type in the rated value of the temperature transducer at an output current of 4 mA. This
information is part of the documentation of the temperature transducer.
Page 52
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
T emp e r a t u r e - >
> V a l u e a t 4 mA
V a l u e a t 2 0 mA
- 40 , 0 C
12345678
L1 L2 L3
5.3.5.2 Value at 20 mA
Type in the rated value of the temperature transducer at an output current of 20 mA.
This information is part of the documentation of the temperature transducer.
T emp e r a t u r e - >
V a l u e a t 4 mA
> V a l u e a t 2 0 mA
+100 , 0 C
12345678
L1 L2 L3
5.3.6 Pressure
These submenus are available only with modules RPH2-xxA1, RPH2-xxA3.
In the following submenus the pressure transducer can be calibrated.
Ana l o g D a t a
CT R a t e d Cu r r . s e c
Ac t u a l C on t r . Vo l t age
T emp e r a t u r e - >
> P r e s s u r e - >
12345678
L1 L2 L3
5.3.6.1 Value at 4 mA
Type in the rated value of the pressure transducer at an output current of 4 mA. This
information is part of the documentation of the pressure transducer.
P r e s s u r e - >
> Va l ue a t 4 mA
Va l ue a t 2 0 mA
0ba r
12345678
L1 L2 L3
Page 53
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
5.3.6.2 Value at 20 mA
Type in the rated value of the pressure transducer at an output current of 20 mA. This
information is part of the documentation of the pressure transducer.
P r e s s u r e - >
Va l ue a t 4 mA
> Va l ue a t 2 0 mA
500ba r
12345678
L1 L2 L3
5.4 Alarms
A l a rms
> R e s e t ob l i ga t o r y
L o c k - ou t
A l a rm L i s t - >
10100000
12345678
L1 L2 L3
In the example mentioned above the alarms 1 and 3 are marked with the function
"Reset obligatory" (must be acknowledged).
Page 54
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
Note: With the function "reset obligatory" you can change an alarm-message from the
type pulse type to a steady alarm type (see 5.4.3).
5.4.2 Lock-Out
Here you can mark each of the 7 alarm outputs to produce a blocking of the device in case
of the corresponding alarm occurs.
That means:
No switching operation is possible, the green LED is dark and the contact "Device not ready"
(-X6:12/13) is closed.
Some actions or alarms cause a lock out in any case ,also without activating the responding
alarm (LED dark, contact -X6:12-13 is closed):
· Keyswitch is "OFF"
· Relay starting up
· Reference voltage is missing
· Frequency not in permitted range
· Neutral earthing switch in intermediate position
Example:
A l a rms
R e s e t ob l i ga t o r y
> L o c k - ou t
A l a rm L i s t - >
00100000
12345678
L1 L2 L3
In the example mentioned above the activating of alarm 3 blocks the RPH2. No
operation is possible, until the "Quit" button is pressed. The output contact "Device not
ready" (-X6:12/13) is closed.
Example:
A l a rm L is t - >
F r equ e nc y m i n
F r equ e nc y ma x
> C u r r e n t ma x ( p e a k )
*R e f . V o lt age F a i l u r e
0010 0 1 0 0
1234 5 6 7 8
L1 L2 L 3
Page 55
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
In the example mentioned above the alarm-message ‘Current max. (peak)’ is assigned
to alarm-output 3 and alarm-output 6.
The asterisk (‘*’) at the position ‘Ref. Voltage Failure’ in the picture above indicates that
the fault ‘Ref. Voltage Failure’ is pending, that means the reference voltage is missing.
Pulse-alarm:
If an alarm-message is a pulse, this alarm-message is active only for a period of 0,5
seconds. If this alarm-message is assigned to an alarm-output which is marked as ‘reset
obligatory’, the alarm-output remains active until this alarm is acknowledged.
5.4.3.1 Lock-out
This is only a summary alarm. It is generated by other alarms which cause a blocking of the
relay. It is active when the device is blocked (see 5.4.2). The alarm itself causes no blocking
of the device!
Limits:
Rated Frequency Lower Limit
50 Hz 45 Hz
60 Hz 54 Hz
16 2/3 Hz 15 Hz
Note: The monitoring of the frequency is active only if the reference voltage is
connected to the device. If the reference voltage is missing, no alarm ‘Frequency min.’ is
generated.
Limits:
Rated Frequency Upper Limit
50 Hz 55 Hz
60 Hz 66 Hz
16 2/3 Hz 18,26 Hz
Note: The monitoring of the frequency is active only, if the reference voltage is
connected to the device. If the reference voltage is missing, no alarm ‘Frequency min.’ is
generated.
Page 56
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
5.4.3.4 Current max. (peak)
This alarm-message is generated if the setting of the current maximum (peak value) is
reached or exceeded during a switching operation in one or more phases (thresholds
see 5.3.1.1)
Note: This alarm-message blocks the RPH2 in any case, regardless whether the alarm
is set for blocking or not (see chapter 5.4.2).
Note: This alarm-message blocks the RPH2 in any case, regardless whether the alarm
is set for blocking or not (see chapter 5.4.2).
Note: This message is not an alarm-message but may be helpful for supervising
Note: This alarm-message blocks the RPH2 in any case, regardless whether the alarm
is set for blocking or not (see chapter 5.4.2).
Page 57
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
This alarm-message is a pulse (see chapter 5.4.3. Pulse-alarm).
The alarm is generated if the duration of the command impulse is less than 100 ms.
The alarm is generated if the duration of the command impulse is less than 100 ms.
Page 58
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
5.4.3.17 Drive mech. Failure
This alarm-message is generated when:
· The monitoring of the CB-position is undefined.
· The operating time corrected by adaptive control has drifted away for more than 5 ms
for opening and 10 ms for closing from the pre-set operating times (only with adaptive
control, see 4.2.5).
Note: The archive is capable to store 1000 switching operations. When the 900th
switching operation is stored in the archive the alarm-message is generated. Each
switching operation following generates an alarm-message until the archive is read by
the PC-Software RPH-Tool,
Page 59
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
5.4.3.23 Temperature max.
This alarm-message indicates that the upper limit of the ambient temperature is reached
(see chapter 5.3.1.4 ‘Temperature max.).
5.5 Measurement
Me a s u r eme n t
> Cu r r e n t Gr aph s - >
Me a s u r e d T i me s - >
F r e q u en c y
Cu r r e n t ( RMS )
YES
12345678
L1 L2 L3
Page 60
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
Pressing the ‘Enter’-button activates the Graph-mode. Repeatedly pressing the ‘Enter’-
button allows to go through the last 4 switching operations. Pressing the ‘+’- or ‘-’-button
changes from phase L1 to phase L2 to phase L3 to the peak values of the current of
each phase. When a graph is displayed, the amplification factor of the graph can be
changed. Pressing the [Quitt] and [+] button at the same time increases the
amplification, [Quitt] and [-] button decreases the amplification.
Me a s u r eme n t
Cu r r e n t Gr aph s - >
> Me a s u r e d T i me s - >
F r e q u en c y
Cu r r e n t ( RMS )
12345678
L1 L2 L3
Me a s u r e d T i me s - >
> C o mm a n d OU T
CB S i g na l r e c e i v ed
Ca l c u l a t e d Op . T i me
Me a s u r e d Op . T i me
4 . 5 9 . 5 9 . 5ms
12345 6 78
L1 L2 L 3
Me a s u r e d T i me s - >
C o mm a n d OU T
> CB S i g na l r e c e i v ed
Ca l c u l at e d Op . T i me
Me a s u r ed Op . T i me
123 . 3 1 24 . 1 12 3 . 7ms
12345 6 78
L1 L2 L 3
Page 61
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
This submenu is available only with module RPH2-xxxS.
Me a s u r e d T i me s - >
C o mm a n d OU T
CB S i g na l r e c e i v ed
> Ca l c u l at e d Op . T i me
Me a s u r ed Op . T i me
128 . 7 1 29 . 0 12 9 . 0ms
12345 6 78
L1 L2 L 3
Me a s u r e d T i me s - >
C o mm a n d OU T
CB S i g na l r e c e i v ed
Ca l c u l at e d Op . T i me
> Me a s u r ed Op . T i me
128 . 9 1 29 . 3 12 8 . 9ms
12345 6 78
L1 L2 L 3
5.5.3 Frequency
This submenu shows the actual frequency of the reference voltage.
Me a s u r eme n t
Cu r r e n t Gr aph s - >
Me a s u r e d T i me s - >
> F r e q u en c y
Cu r r e n t ( RMS )
50 , 00Hz
12345 678
L1 L2 L 3
Page 62
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
The switching moments (switching programs) are permanently corrected according to
the measured frequency.
Note: The measurement of the frequency works only when the reference voltage is
connected. If the reference voltage is missing the rated frequency is displayed instead.
Me a s u r eme n t
Me a s u r e d T i me s - >
F r e q u en c y
> Cu r r e n t ( RMS )
Co n t r o l Vo l t a ge
0 0 0 A
12345 678
L1 L2 L 3
Me a s u r eme n t
F r e q u en c y
C u r r e n t ( RMS )
> C o n t r o l Vo l t ag e
A c t u a l T emp e r a t u r e
61 , 2 V
123456 78
L1 L2 L3
Me a s u r e me n t
C u r r e n t ( RMS )
Co n t r o l Vo l t a g e
> A c t u a l T e mp e r a t u r e
T e mp e r a t u r e f . C o mp
61 , 2 V
12345678
L1 L2 L3
Page 63
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
5.5.7 Temperature for Compensation
This submenu shows the averaged environmental temperature (see chapter 4.2)
Me a s u r eme n t
C on t r o l Vo l t age
A c t u a l T emp e r a t u r e
> T emp e r a t u r e f . C omp
A dd i t i on . Op . T i me s - >
+0 , 0 C
12345678
L1 L2 L3
Ad d i t i o n. Op . T i me s - >
> V o l t a g e CH 1
V o l t a g e CH 2
T emp e r at u r e CH 1
T emp e r at u r e CH 2
- 0 , 1 -0 , 1 - 0 , 2ms
12345678
L1 L2 L3
Ad d i t i o n. Op . T i me s - >
V o l t a g e CH 1
> V o l t a g e CH 2
T emp e r at u r e CH 1
T emp e r at u r e CH 2
- 0 , 1 -0 , 1 - 0 , 2ms
12345678
L1 L2 L3
Page 64
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
5.5.8.3 Temperature CH1
This submenu shows the compensation value for the environmental temperature
measured for channel 1 per phase.
Ad d i t i o n. Op . T i me s - >
V o l t a g e CH 1
V o l t a g e CH 2
> T emp e r at u r e CH 1
T emp e r at u r e CH 2
- 0 , 1 -0 , 1 - 0 , 1ms
12345678
L1 L2 L3
Ad d i t i o n. Op . T i me s - >
V o l t a g e CH 2
T emp e r at u r e CH 1
> T emp e r at u r e CH 2
P r e s s u re CH 1
- 0 , 1 -0 , 1 - 0 , 2ms
12345678
L1 L2 L3
Ad d i t i o n. Op . T i me s - >
T emp e r at u r e CH 1
T emp e r at u r e CH 2
> P r e s s u re CH 1
P r e s s u re CH 2
- 0 , 1 -0 , 1 - 0 , 1ms
12345678
L1 L2 L3
Page 65
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
Ad d i t i o n. Op . T i me s - >
T emp e r at u r e CH 1
T emp e r at u r e CH 2
P r e s s u re CH 1
> P r e s s u re CH 2
- 0 , 1 -0 , 1 - 0 , 2ms
12345678
L1 L2 L3
Me a s u r eme n t
T emp e r a t u r e f . C omp
A dd i t i on . Op . T i me s - >
> P r e s s u r e ( L 1 / L2 / L3 )
P r e s s u r e ( L 1 )
310 3 01 307 ba r
123 45678
L1 L2 L3
Me a s u r eme n t
T emp e r a t u r e f . C omp
A dd i t i o n . Op . T i me s - >
P r e s s u r e ( L1 / L2 / L3 )
> P r e s s u r e ( L1 )
3 10ba r
12345 678
L1 L2 L 3
Page 66
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
5.6.2 Alarm Output
This submenu is for testing only. You can set the alarm-outputs individually by typing a
‘1’ at the according position of the pattern shown on the display (only available for
module RPH2-xxS).
Error type 1: the switching command on input -x8:1 or -x8:6 is still bending
Error type 2-4: CH1 phase L1 is defective
Error type 5-7: CH1 phase L2 is defective
Error type 8-10 CH1 phase L3 is defective
Error type 11-13: CH2 phase L1 is defective
Error type 14-16: CH2 phase L2 is defective
Error type 17-19: CH2 phase L3 is defective
List of messages:
· Switching OK
· NOT Switched (no operation of the breaker)
· Command Time min (command impulse to short (<100 ms))
In the statusline the date and the time of the operation is displayed.
Page 67
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
6 COMMISSIONING
NOTE: After the RPH2 is connected to the supply voltage the first time, or after a self
test, it will last about 20 seconds until the green LED is illuminated and the relay is
ready for operation (see also 2.4.2.2). If the green LED stays dark, please check at
first the proper connection of the reference voltage and the neutral earthing switch
6.1.1 Settings
System Frequency: 50 Hz
Control Voltage: 125 V
Switching Program: Transformer
Function Cannel 1: CB closing
Selftest Interval: 24 h
CT Rated Current
primary: 1A
secondary: 1A
Alarms:
Ref. Voltage Failure -> Alarm1
Neutral intermediate -> Alarm2
All other alarm functions are inactive.
Page 68
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
All other parameters are not essential for operation.
To evaluate the necessary data, use the configuration checklist shown on the last
pages of this service manual.
6.1.2 Inspection
Check whether the external wiring corresponds to the relevant RPH2 wiring diagram.
Particularly whether the reference voltage and the neutral earthing switch position
signals are wired. If a switching of the neutral is not intended, then it is necessary to
short circuit the relevant input terminals of the RPH2 (-X6:8 with -X8:11 for neutral
isolated or -X6:8 with -X8:12 for neutral grounded).
Make sure that the case is properly earthed. If external sensors are necessary, they
are to be installed according to the manufacturer's information. Check whether the
plug-in unit is sitting firmly and the fixing screws are tightened.
Measure the actual RPH2 control voltage with a multimeter. This value (depending on
the model) is required for parameterization (5.3.4).
Check the 48 V field voltage between the terminals -X6:8 and-X6:11 (ground).
Measure the voltage at the inputs of the external transducers (approx. 24 VDC).
Compare the displayed values on the RPH2 for control voltage, hydraulic pressure and
ambient temperature (only models RPH2-xxA) with the externally measured ones.
Verify the connections of the voltage and current transformer circuits (current only for
model RPH2-xI) to the correct terminals (100/Ö3V or 220/Ö3V, 1A or 5A) of the RPH2.
The two functions of the menu [Aux. Functions] maybe helpful by testing the external
connections:
The proper connection of the CB’s auxiliary contacts to the RPH2 (only model
RPH2-Sxx) can easily be checked by the function [Aux. Functions][Alarm Input]. When
the circuit breaker is in the closed position you must see three ‘1’ at the first positions
in the status line.
Au x . Fun c t i on s
> A l a rm I n pu t
A l a rm Ou t pu t
Se l f t e s t E RROR
RPH2 V 3 . 04 16 - 03 - 99
11100001
12345678
L1 L2 L3
When the breaker is in the open position, three ‘0’ will be displayed.
If the remote reset input is activated, at the fourth position a ‘1’ must be displayed.
Page 69
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
By using the function [Aux. Functions][Alarm Output] you can activate individually each
alarm relay by typing a ‘1’ at the according position of the pattern. So the external
wiring of the alarm circuits can be checked on correct function.
For the first load switchings, we recommend using an oscillograph to measure the
currents of the three phases together with the reference voltage, in order to verify that
the unit is working correctly. It is helpful if the three relayed drive commands can also
be recorded on additional oscillograph traces.
By using a RPH2 with the option I the currents during switching can be displayed and
analysed (see 5.5.1).
If the results are not satisfactory you must adapt the pole operating times and/ or the
arcing times to achieve the optimal function.
Page 70
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
Configuration Checklist RPH2
System Data
O User Program
Point on Wave L1 L2 L3
T_C1 Neutral isolated ms
T_C1 Neutral grounded ms
T_C2 Neutral isolated ms
T_C2 Neutral grounded ms
CB Data:
CB Data L1 L2 L3
Operating Time CH1 ms
Operating Time CH2 ms
Arcing Time CH1 ms
Arcing Time CH2 ms
Aux.Timeshift CH1 ms
Aux.Timeshift CH2 ms
Compensation O Yes O No
Page 71
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
Configuration Checklist RPH2
Temperature Compensation:
Switching Channel 1 Switching Channel 2
Temperature Delta_t Temperature Delta_t
+50 °C ms +50 °C ms
+40 °C ms +40 °C ms
+30 °C ms +30 °C ms
+20 °C ms +20 °C ms
+10 °C ms +10 °C ms
0 °C ms 0 °C ms
-10 °C ms -10 °C ms
-20 °C ms -20 °C ms
-30 °C ms -30 °C ms
-40 °C ms -40 °C ms
-50 °C ms -50 °C ms
Analogue Data:
Thresholds:
Temperature:
Value at 4 mA ..................... °C
Value at 20 mA ..................... °C
Pressure:
Value at 4 mA ...................... bar
Page 72
Issue 3 58.020.034 E AREVA T&D Austria AG, Leonding
2004-02
Configuration Checklist RPH2
Alarms:
Alarmtext 1 2 3 4 5 6 7
Alarm Functions
Reset Obligatory
Lock-out
Alarm List
Lock-out
Frequency min
Frequency max
Current max
Ref.Voltage Failure
RTC Impulse Failure
Neutral Intermediate
Neutral Grounded
Neutral Isolated
Selftest ERROR
Selftest CH1 ERROR
Selftest CH2 ERROR
Command Time CH1 min
Command Time CH2 min
Operating Time min
Operating Time max
Drive Mech.Failure
Archive Full
Archive Failure
Control Voltage min
Control Voltage max
Temperature min
Temperature max
Temp. Transducer Fault
Pressure min
Pressure max
Press. Transducer Fault
Page 73
AREVA T&D Austria AG, Leonding Issue 3 58.020.034 E
2004-02
Installation
Support-- frame assembly
Presentation
Topic Page
Components necessary for the operation 2
Support--frame components (per pole) 3
Preparing the column 5
Frame--support assembly 6
10--2006 L31--138EN/02
E AREVA 1/10
Installation
Support-- frame assembly
Lifting strap
(1) 2
(3 m)
10--2006 L31--138EN/02
E AREVA 2/10
Installation
Support-- frame assembly
(2) Support 2
(3) Support 2
Screws
(5) 1
H M16-45
Screws
(7) 16
H M16-35
Washer
(9) 16
NORDLOCK NL16 SS
10--2006 L31--138EN/02
E AREVA 3/10
Installation
Support-- frame assembly
Screws
(20) 16
H M16-45
10--2006 L31--138EN/02
E AREVA 4/10
Installation
Support-- frame assembly
Preparing the pole D Sling the “A” column with the aid of two flexible lifting straps (1).
D Extract the column from the case and put it down on the case wood cover
laying :
-- first, the end of the column,
-- second, the support of the operating mechanism (4) on a wedge to ensure
the correct installing of the frame supports.
X minimum = 260 mm
10--2006 L31--138EN/02
E AREVA 5/10
Installation
Support-- frame assembly
Process The table below gives the steps of installing the supports of the frame :
Step Action
1 With the aid of two flexible lifting straps, position the frame--support
(3) onto the housing (10) and fasten it with the use of the screws (7)
and NORDLOCK washers (9). Do not tighten the screws (7).
-- Install the screw (5) only on this support.
10
x1 3
5
2x2
9 H M16--45
7
H M16--35
2 With the aid of two flexible lifting straps, position the frame--support
(2) onto the housing (10) and fasten it with the use of the screws (7)
and NORDLOCK washers (9). Do not tighten the screws (7).
2
10
2x2
9
7
H M16--35
10--2006 L31--138EN/02
E AREVA 6/10
Installation
Support-- frame assembly
Process, continued The table below gives the steps of installing the supports of the frame :
Step Action
3 Install the strengthening pieces (21)--(25) inside the frame--support
(2) with the use of the screws (20). Adjust the distance between the
supports and fasten the strengthening pieces (21)--(25) on the
frame--support (3). Do not tighten the screws (20).
x4
20
3
25
21 H M16--45
4 With the aid of two flexible lifting straps, position the frame--support
(2) onto the housing (10) and fasten it with the use of the screws (7)
and NORDLOCK washers (9). Do not tighten the screws (7).
10
2x2
9
7
2
H M16--35
5 With the aid of two flexible lifting straps, position the frame--support
(3) onto the housing (10) and fasten it with the use of the screws (7)
and NORDLOCK washers (9). Do not tighten the screws (7).
10
2x2
9
7
H M16--35
10--2006 L31--138EN/02
E AREVA 7/10
Installation
Support-- frame assembly
Process, continued The table below gives the steps of installing the supports of the frame :
Step Action
6 Install the strengthening pieces (21)--(25) inside the frame--support
(2) with the use of the screws (20). Adjust the distance between the
supports and fasten the strengthening pieces (21)--(25) on the
frame--support (3). Do not tighten the screws (20).
21
3
2x2
20
25
21
H M16--45
2 25
x2
20
24
24
H M16--45
x2
20
24
24
H M16--45
10--2006 L31--138EN/02
E AREVA 8/10
Installation
Support-- frame assembly
Process, continued The table below gives the steps of installing the supports of the frame :
Step Action
8 Tighten all the screws to the recommended torques.
18 daN.m
10--2006 L31--138EN/02
E AREVA 9/10
Installation
Support-- frame assembly
10--2006 L31--138EN/02
E AREVA 10/10
Installation
Lifting and positionning the pole
Presentation
Necessary tools List of the necessary AREVA tools for the lifting and positionning of the pole :
LIFTING STRAP
(1) 2
”SPANSET” (3 m -- 1000 kg)
Topic Page
Lifting the pole 2
Positioning the pole 3
06--2004 L31--200EN/04
E AREVA 1/4
Installation
Lifting and positionning the pole
Process Install the two flexible lifting straps (1), placing these at the end of the column.
By means of a lifting device hoist the pole up whilst allowing it to rest on the
base of the frame.
Place the trip ropes (10) on the support legs of the chassis frame (9) to ensure
guidance of the pole at the time of lifting.
Lift the pole with precaution.
10
06--2004 L31--200EN/04
E AREVA 2/4
Installation
Lifting and positionning the pole
Process The table below gives the steps of positioning the pole :
Step Action
1 Use a lifting device to position the chassis frame onto its ground
attachment points but do not secure it, whilst respecting the
orientation of the pole indicated on the sketch of the device.
2 If necessary, place shims under the supports of the frame so that the
upper plate is level.
3 Install the washers (12) and clamp the whole to the ground using nut.
4 Remove the lifting straps.
5 Check the tightening torques of all frame screws.
18 daN.m
6 Tighten the fixings on the two floor seatings in accordance with the
module entitled ’Tightening Torques’ and in accordance with the
diameters of the anchoring points.
12
06--2004 L31--200EN/04
E AREVA 3/4
Installation
Lifting and positionning the pole
06--2004 L31--200EN/04
E AREVA 4/4
Installation
Installing terminals
with preparation of contact surfaces
Presentation
Diagram
01/1-- 1
01/2-- 1
01/3-- 1
01/1-- 2
01/2-- 2
01/3-- 2
01/1-- 2
01/1-- 1
01/2-- 2
01/2-- 1 01/3-- 2
01/3-- 1
Topic Page
Components, products and accessories 2
Preparing the contact surfaces 3
Installing terminal 4
08--2004 L31--505EN/01
E AREVA 1/4
Installation
Installing terminals
with preparation of contact surfaces
Necessary List of the AREVA components necessary for the assembling (per pole) :
components
(1) Terminal 1
Screws
(3) 4
H M12--45
Necessary products List of the AREVA products and accessories necessary for the installing :
and accessories
AREVA
Diagram Designation
reference
--02212334 Rag
08--2004 L31--505EN/01
E AREVA 2/4
Installation
Installing terminals
with preparation of contact surfaces
Preparing the The contact grease is a mixture composed of Vaseline and Contactal grease.
contact grease CONTACT GREASE = 50% Vaseline + 50% Contactal grease
Preparing the The table below gives the steps of preparing the contact surfaces :
contact surfaces
X1
X2
Remove the temporary screws
1 from the terminal pads X1 or 01/1-- 1
X2. 01/2-- 1
01/1-- 2
01/2-- 2 01/3-- 1
01/3-- 2
08--2004 L31--505EN/01
E AREVA 3/4
Installation
Installing terminals
with preparation of contact surfaces
Installing terminal
Process Assemble immediately the terminal (1) on one interrupting chamber (2) after
preparation of contact surfaces. Fasten the terminal using screws (3); use
CONTACT GREASE to seal the screws.
01/1-- 1
2 01/2-- 1
2 01/3-- 1
01/1-- 2 2
01/2-- 2
1
01/3-- 2
x 4
3
H M12--45
5 daN.m
08--2004 L31--505EN/01
E AREVA 4/4
Installation
Installing the capacitors
Presentation
Diagram
Lifting strap
(12) 2
(3 m)
12--2004 L31--600EN/03
E AREVA 1/4
Installation
Installing the capacitors
Necessary List of the AREVA components necessary for the assembling (per pole) :
components
(1) Capacitor 2
(3) Support 2
Support
(4) 2
or (depending on the apparatus)
Screws
(5) 8
H M12-30
Screws
(8) 4
H M12-45
Screws
(9) 4
H M12-25
(1) Spacer 4
12--2004 L31--600EN/03
E AREVA 2/4
Installation
Installing the capacitors
Installing S Install the support (3) on the capacitor (1) using the screws (5).
the supports
S Install the support (4) on the capacitor (1) using the screws (5).
x 2
5
4
4
x 2 H M12--30
5 5 daN.m
3 H M12--30
5 daN.m
12--2004 L31--600EN/03
E AREVA 3/4
Installation
Installing the capacitors
Process Install the capacitors (1) on the interrupting chambers (6) and (7) -- on the
opposite side as the bosse of the housing (13) -- using the screws (8)
and (9).
NOTE : Use the two spacers (10) to install the capacitors -- capacitor
support (4) side.
9
x 2
3 -- 4
H M12--25
5 daN.m
13 7
13
1
6
9
x 2 4
10
H M12--25
5 daN.m
4
10
x 2
8
H M12--45
5 daN.m
12--2004 L31--600EN/03
E AREVA 4/4
Installation
Installing stress-- shields on the interrupting chambers
Presentation
Diagram
Topic Page
Preparing the stress--shields 2
Installing the stress--shields 3
12--2004 L31--650EN/04
E AREVA 1/4
Installation
Installing stress-- shields on the interrupting chambers
Necessary AREVA List of the AREVA components necessary for the assembling (per pole) :
com
nents
(2) Bracket 8
Screws
(3) 8
H M10-30
Assembling Install the brackets (2) on the stress--shields ring (1) using screws (3) do not
tighten.
x 4
H M10--30
12--2004 L31--650EN/04
E AREVA 2/4
Installation
Installing stress-- shields on the interrupting chambers
Necessary AREVA List of the AREVA components necessary for the assembling (per pole) :
components
Screws
(5) 8
H M12-30
Process Install the stress--shields (1) at each end of the interrupting chambers (4)
using the screws (5).
1
4
x 4
5
1 H M10--30
3,2 daN.m
x 4
5
H M12--30
5 daN.m
12--2004 L31--650EN/04
E AREVA 3/4
Installation
Installing stress-- shields on the interrupting chambers
12--2004 L31--650EN/04
E AREVA 4/4
Installation
Column -- chambers coupling
Presentation
Identification Before the chambers -- column coupling, check that interrupting chambers
and column reference numbers are the right ones.
Coupling duration The final chambers -- column coupling operations must be realized in dura-
tion no longer than 40 min.
NOTE : The coupling operations should be performed by at least two
persons.
T(max) ≤ 40 min
Coupling steps The chambers -- column coupling must be done in several steps :
Step Topic Page
A Preparing the column stress--shields 2
B Preparing the necessary components for the coupling 3
C Lifting and preparing the interrupting chambers 5
D Final coupling 6
04--2005 L31--716EN/01
E AREVA 1/12
Installation
Column -- chambers coupling
Necessary AREVA List of the AREVA components necessary for the assembling (per pole) :
components
(32) Bracket 4
Screws
(34) 4
H M10-30
Assembling Install the brackets (32) on the stress--shields ring (33) using screws (34)
do not tighten.
32
33
x 4
34 H M10--30
Positioning Install temporarily the stress--shields ring (33) around the first insulator
base (1).
33
04--2005 L31--716EN/01
E AREVA 2/12
Installation
Column -- chambers coupling
Necessary AREVA List of the AREVA components necessary for the coupling :
components
(12) Seal 1
Screw
(14) H M16--60 (19 mm) 8
H M16--70 (30 mm)
Washer
(15) 16
M16
(16) Nut 8
04--2005 L31--716EN/01
E AREVA 3/12
Installation
Column -- chambers coupling
Necessary AREVA List of the AREVA tools necessary for the coupling :
tools
(7) Stop 1
(8) Lever 1
04--2005 L31--716EN/01
E AREVA 4/12
Installation
Column -- chambers coupling
Lifting the interrupt- Using the two straps provided, lift the chambers and MAKE THESE LEVEL
ing chambers with the housing (2) still at man--height (approximate weight : 700 kg).
Assembling the Assemble sections A, B and C of the spindles (17) and (18), without over--
centering spindles tightening, so that these can be removed later without difficulty.
NOTE : Spindle (18) is longer than spindle (17).
17
C
18
B
A
Deflating the S Remove the plug (5) from the transport cover (4) and press valve (6) to
chambers bring the volume of chambers back to ambient pressure.
REMINDER : transport gas pressure : nitrogen (N2) at 0.03 MPa at 20°C
(101.3 kPa).
S Install the plug (5).
6 5
04--2005 L31--716EN/01
E AREVA 5/12
Installation
Column -- chambers coupling
Final coupling
Orientation of For future identification of interrupting chambers, the right orientation must be
chambers respected during coupling.
The housing (2) possesses two bosses, (B1) and (B2).
Present the chambers directly above the column (1) in such a way that bosses
(B1) and (B2) of the housing (2) are situated on the same side as the support
(3) of the operating mechanism.
B1
1
B2
2
3
04--2005 L31--716EN/01
E AREVA 6/12
Installation
Column -- chambers coupling
Removing the The table below gives the steps of removing the transport cover of the
transport cover of the interrupting chambers :
interrupting
chambers
H M16--55
9
8
11
10
4 25
7
20
11
Installing the Install the centering spindles (17) and (18) so that these come to rest against
centering spindles the sphere of housing (2), tighten the nuts (30) a little.
Install the screws (39) on the centering spindles (17) and (18).
2
30
30
39
17
39 18
Removing the cover The table below gives the steps of removing the cover of the column :
of the column
x 8
23
H M16--55
22
04--2005 L31--716EN/01
E AREVA 8/12
Installation
Column -- chambers coupling
Installing the seal The table below gives the steps of installing the seal :
19
04--2005 L31--716EN/01
E AREVA 9/12
Installation
Column -- chambers coupling
Mounting The table below gives the steps of mounting the chambers -- column cou-
coupling pin pling pin :
Step Action Diagram
1 Move down slowly the inter-
rupting chambers (2) introduc-
ing the centring spindles (17)
and (18) into the holes of the 10
column flange (1). 2
18
26
2 Move down slowly the inter-
1 17
rupting chambers (2) to align
the hole of the cylinder (10)
with the hole of the tie--rod (26).
20
4 Remove the tool (20).
11
10
19
28
28
04--2005 L31--716EN/01
E AREVA 11/12
Installation
Column -- chambers coupling
04--2005 L31--716EN/01
E AREVA 12/12
Installation
Installing the operating device
Presentation
Necessary AREVA List of the AREVA tools necessary for the installing :
tools
Mark Diagram Designation Number
(6) Lever 1
Process The table below gives the steps of installing the operating device on the
pole--support :
03--2008 L31--7801EN/01
E AREVA 1/12
Installation
Installing the operating device
Unpacking Remove packaging protection and check that operating device and pole
reference numbers are the right ones.
Closing spring
Circuit--breaker Released
Open
(11) Seal 1
(22) Spacer 4
Installing the -- Install the spacers (22) on the screws (9) outside the operating device.
necessary
components -- Install the seal (11) on the operating shaft (13).
-- Check the presence of grease (ASEOL 0--365.2) on the operating shaft
(13).
13
11
22
x4
9
03--2008 L31--7801EN/01
E AREVA 2/12
Installation
Installing the operating device
Introduction The pole is equipped -- for transport purposes -- with a blocking tool (4) and
a safety sheet metal (5) fixed temporarily at the end of the sleeve (12).
To realize the installing of the operating mechanism, it is necessary to :
a -- remove the blocking tool (4) and the safety sheet metal (5)
b -- proceed to manual opening the pole
c -- install the blocking tool (4) (”open” position)
4
12
Grease Check the presence of grease (ASEOL 0--365.2) on the pole operating shaft.
03--2008 L31--7801EN/01
E AREVA 3/12
Installation
Installing the operating device
“Manual opening” The table below gives the steps of “manual opening” operation :
operation
12
12 4
03--2008 L31--7801EN/01
E AREVA 4/12
Installation
Installing the operating device
Washer
(10) 4
M20
(22) Spacer 1
(26) Spacer 1
Nut
(14) 4
H M20
03--2008 L31--7801EN/01
E AREVA 5/12
Installation
Installing the operating device
Coupling The table below gives the steps of the operating device coupling :
Step Action
1 Sling the operating device using a lifting strap (1) like diagram.
NOTE : Do not remove the roof (17) of the operating device
before slinging.
2 Lift the operating device and make this level.
Approximate weight 300 kg.
3 Approach the operating device in assembly position, the jib of the
lifting equipment must be under the stress--shields ring (to avoid that
the cables touch the stress--shields ring).
4 Introduce the operating mechanism shaft (13) into the cylinder (12)
of the pole operating shaft (7).
5 As soon as the lower fastening screw (9) “A” emerge from the hole
of the operating mechanism support (8), install the spacer (26),
washer (10) and the nut (14).
NOTE : Do not tighten the nut (14).
26
14
9
10
8
12
1
17
”A”
13
03--2008 L31--7801EN/01
E AREVA 6/12
Installation
Installing the operating device
Installing The table below gives the steps of installing the operating device fastening
the fastening nuts nuts :
Step Action
1 Install the spacer (22), washer (10) and the nut (14) on the lower
fastening screw “B”.
NOTE : Do not tighten the nut (14).
2 Install the eccentric spacers (23), washers (10) and the nuts (14) on
the upper fastening screws “C” and “D”.
NOTE : Do not tighten the nuts (14).
3 Rotate the eccentric spacers (23) to do the contact with the lower
edge of the pole--support oblong holes.
4 Tighten -- temporarily at the indicated tightening torque -- the
fastening screws (9).
23
10 5 daN.m
14
23
x 2
”C”
”D” 9
”B”
14
10
22
x1
Wedging The table below gives the wedging procedure for the fastening screws
and tightening depending to the X play :
X
24
22 25
Important
20
35 daN.m
If the X play is ... Action
Tighten to the indicated tightening
X <1 mm
torque.
D Wedge between the spacer (22)
and the operating device (20) with the
X ≥1 mm provided wedges (24)--(25).
D Tighten the screw to the
indicated tightening torque.
03--2008 L31--7801EN/01
E AREVA 8/12
Installation
Installing the operating device
03--2008 L31--7801EN/01
E AREVA 9/12
Installation
Installing the operating device
Process Connect up the operating device’s wires refer to the wiring diagram of the
circuit--breaker.
Connect up the operating device’s wires.
NOTE : Use the holes provided on the supports of the frame to fix
the cables.
Connecting up the Connect the wires from the electrical contact SF6 densimeter (18) cable (19)
contact densimeter to the operating mechanism terminal block, in accordance with the relative
cable diagram.
18
19
03--2008 L31--7801EN/01
E AREVA 10/12
Installation
Installing the operating device
Process Switch on the permanent heating system of the operating device (in both
summer and winter) to avoid condensation, and the corrosion which might
result from this.
03--2008 L31--7801EN/01
E AREVA 11/12
Installation
Installing the operating device
03--2008 L31--7801EN/01
E AREVA 12/12
This page is intentionally blank.