Académique Documents
Professionnel Documents
Culture Documents
SERVICE MANUAL
3.5KW-7.5KW
(with relay controller)
KOHLER -
GENERATORS,.’
Table of Contents
Page Page
A WARNING muffler
excessive
or with faulty exhaust system - exposure to
noise is not only tiring but can lead to impair-
HIGH VOLTAGE! Remember that the function of a genera- ment of hearing.
tor set is to produce electricity and that wherever electric-
ity is present, there is the potential danger of electrocu- A WARNING
tion. Take the same precautions with electrical appliances
HOT PIPING! An engine gets hot while running and
in your coach that you would observe in your home. Keep
exhaust system components get extremely hot. Do not
away from electrical circuits and wiring while the set is
work on generator set until unit is allowed to cool.
running and have electrical service performed only by
qualified electricians. Make sure unqualified persons,
especially children, cannot gain access to your set - keep A WARNING
the compartment door locked or securely latched at all
DANGEROUS FUELS! Use extreme caution when hand-
times. Be sure that generator is properly grounded. Never
ling, storing, and using fuels - all fuels are highly
touch electrical leads or appliances with wet hands, when
explosive in a vapor state. Store fuel in a well-ventilated
standing in water, or on wet ground as the chance of
area away from spark producing equipment and out of the
electrocution is especially prevalent under such con-
reach of children. Never add fuel to the tank while the
ditions.
A WARNING
engine is running to prevent spilled fuel from igniting on
contact with hot parts or from ignition spark. Keep fuel
UNIT STARTS WITHOUT NOTICE! To prevent accidental lines and connections tight and in good condition - don’t
starting on units with a remote start/stop switch, always replace flexible fuel lines with rigid lines. Flexiblesections
disconnect battery (remove negative lead first and recon- are used to avoid breakage due to vibration. Should any
nect it last) to disable generator set before working on any fuel leakage, fuel accumulation, or electrical sparks be
equipment connected to generator. noted, DO NOT OPERATE GENERATOR SET. Have sys-
terns repaired by qualified specialists before resuming A WARNING
generator operation. Additional precautions should be
BACKFIRE! A sudden backfire can cause serious burns.
taken when using the following fuels:
Keep hands and face away from the carburetor when the
Gasoline-Store gasoline only in approved red containers air cleaner is removed.
clearly marked GASOLINE. Don’t store gasoline in .any
occupied building. A WARNING
Propane (LP)-Adequate ventilation is mandatory. Pro- FIRE HAZARD! Keep the compartment and generator set
pane is heavier than air; install gas detectors low in room. clean and free of debris to minimize chances of fire. Also
Inspect detectors often. remember that hot exhaust gases and exhaust system
parts could start grass fires. Keep away from hot engine
A WARNING and generator parts’to avoid burning yourself.
UNINTENTIONAL STARTING!
starting when checking choke
To prevent
operation,
accidental
remove spark
A WARNING
plug lead(s) at spark plug(s). MOVING PARTS! Do not open generator set compartment
door when unit is running, except for servicing by quali-
A WARNING fied specialists. Replace guards, covers, and screens (if
used) before operating generator set.
FLASH FIRE! A sudden flash fire can cause serious burns.
To avoid the possibility of a flash fire, do not smoke or
permit flame or spark to occur near carburetor, fuel line,
A WARNING
fuel filter, fuel pump, or other potential sources of spilled HIGH VOLTAGE! When the power cord is plugged in
fuel or fuel vapors. during voltage regulator test, the AC pins become “hot”
and there is danger of electrocution.
A WARNING A WARNING
ELECTROCUTION! Your RV generator set must not be EXPLOSION! Use generator sets specified for RV use in RV
used to “backfeed” by connecting it to building/camp- installations only.
ground electrical circuits. Doing so can cause serious
injury or death to utility personnel working on utility
transmission lines and may also seriously injure persons in
your household. Unauthorized connection may be unlawful
in some states and/or localities. A transfer switch must be
installed in the RV to prevent interconnection of generator
and outside source of power.
Section 1.
Introduction and Specifications
l-l. INTRODUCTION 120 volt, 37.5 amp alternating current. It has a rotor with
four magnetic poles and operates at 1800 R.P.M., produc-
This manual covers operation, scheduled maintenance ing 60 hertz. A 40 amp line circuit breaker protects
troubleshooting and corrective maintenance for Kohler gen- generator against damage due to overload. See Figure l-2
erator sets designed and built for recreational vehicles. The for major components.
six standard models are the 3.5CM21 -RV, 4.5CM21-RV, 1-4. MODEL 4.5CKM21-RV
4.5CKM21 -RV, 5.5CM21 -RV, 7CM21 -RV and 7.5C21 -RV.
These models are referred to by their kilowatt output, The 4500 watt generator set is powered by a two cylinder
3.5kW, 4.5kW (single), 4.5kW (twin), 5.5kW, 7kW and Kohler Model KT17 engine. The set produces 120 volts,
7.5kW. Differences between models are noted throughout 37.5 amp alternating current. It has a rotor with four mag-
the manual. All models feature Kohler designed and built netic poles and operates at 1800 R.P.M., producing 60
4-cycle gasoline engines, rotating field generators and relay hertz. Two 20 amp circuit breakers protect against damage
controllers. See Table l-l for specifications and model vari- due to overload. See Figure l-3 for major components.
ations, Table 1-2 for dimensions and weight, and Table l-3
for engine specifications. Refer to the wiring diagrams in 1-5. MODEL 5.5CM21-RV
the back of the manual. The 5500 watt generator set is powered by a two cylinder
Kohler Model K582QS engine. The set produces 120 volt,
I-2. MODEL 3.5CM21-RV
46 amp alternating current. It has a rotor with four magne-
The 3500 watt generator set is powered by a single tic poles and operates at 1800 R.P.M., producing 60 hertz.
cylinder model K181 QS engine. The set produces 120 volt, A 50 amp circuit breaker (on most models) protects against
29 amp alternating current. It has a rotor with two damage due to overload. See Figure I-4for major compon-
magnetic poles and operates at 3600 R.P.M., producing 60 ents.
hertz or 3000 R.P.M., producing 50 hertz, 13 amp current.
1-6. MODEL 7CM21-RV
A 30 amp circuit breaker protects the set from overload
damage. Due to its compact size and lightweight, it is The 7000 watt generator set is powdered by a two cylinder
installed in RV’s with limited suspension support and Kohler Model K582QS engine. The’set produces 120 volt,
compartment space. See Figure l-l for major components. 58 amp alternating current. It has a rotor with four magne-
1-3. MODEL 4.5CM21-RV tic poles and operates at 1800 R.P.M., producing 60 hertz.
A 60amp circuit breaker (on most models) protects against
The 4500 watt generator set is powered by a single damage due to overload. See Figure I-4for major compon-
cylinder Kohler Model K341QS engine. The set produces ents.
Amps Per ..
Model Volts Term in al Watts Freq. (HZ) RPM Wires, I Phase
l-l
1-7. MODEL 7.5CZl-RV
The 7500 watt generator set is powered by a four cylinder torfrom overload. On the 7.X21 model-s, the set produces
Kohler Model L654 liquid-cooled engine. Two 30 Amp 120 volt, 62.5 amp alternating current. On the 7.5661
circuit breakers protect the rotating field 60 Hertz genera- models, 120/240 volt, 31.3 Amp alternating current is
produced. See Figure 1-5 for major components.
,
Specification 3.5 Model 4.5 Model 4.5 Model 5.5 Model 7.0 Model 7.5 Model
(Single) KT17 Series II
4
Weight (approximate) 150 lb. 235 lb.* 230 lb.** 315 lb. 334 lb. 470 lb.
(68.0 kg) (106.6 kg) (104.3 kg) (142.9 kg) (151.5 kg) (213.2 kg)
Length - Overall 22” 23- 13/26” 28-5/l 6” 26” 27-l/2” 43-l /4”
(55.9cm) (60.5cm) (71.9 cm) (66.Ocm) (69.8cm) (109.8cm)
Width - Overall 13-3/4” 18-3/l 6” 1 20-3/4” 21-l/2”
(34.9cm) (46.2cm) 1 (52.7 cm) (54.6cm)
.
4.5 Model 4.5 Model
Specifications 3.5 Model 5.5 Model 7.0 Model 7.5 Model
(Single) (Twin)
Fuel Inlet Connection l/4” I.D. l/4” I.D. 7/l 6-20 l/4” I.D. l/4” I.D. 7/l 6-20
Size U.N.F. U.N.F.
Frequency Regulation 5% 5% 5% 5% 5% 5%
25% Load 0.35 gal/hr 0.52 gal/hr 0.40 gal/hr 0.55 gal/hr 0.56 gal/hr 0.7 gal/hr
(1.3 lts/hr) (2.0 lts/hr) (1.5lts/hr) (2.1 lts/hr) (2.1 lts/hr) (2.6 lts/hr)
._g
‘; 50% Load 0.46 gal/hr 0.60 gal/hr 0.50 gal/hr 0.61 gal/hr 0.66 gal/hr 0.8 gal/hr
5v) (1.7lts/hr) (2.3 lts/hr) (1 .9lts/hr) (2.3 lts/hr) (2.5 lts/hr) (3.0 lts/hr)
c
s 75% Load 0.57 gal/hr 0.73 gal/hr 0.60 gal/hr 0.73 gal/hr 0.84 gal/hr 1.1 gal/hr
z (2.2 lts/hr) (2.8 lts/hr) (2.3lts/hr) (2.8 lts/hr) (3.2 Its/h r) (4.2 Its/hr)
l? .
100% Load 0.74 gal/hr 0.92 gal/hr 0.80 gal/hr 0.88 gal/hr 1.08 gal/hr 1.4 gal/hr
1-2
AIR COOLING SPARK
SHROUD
AIR
REMOTE CIRCUIT CL EANER
CONTROL PROTECTOR
BATTERY
CHARGING
CONTROLLER
RECTIFIER
REGULATOR
(HIDDEN) I
INTAKE
TIMING
SIGHT
INTAKE HOLE
BATTERY -+@ /
POSITIVE
CONNECTION
GROUND STRAP
Figure 1-1. Service Side View of a Kohler 3500 Watt RV Generator Set
DRY ELEMENT
AIR CLEANER
CIRCUIT _ GOVERNOR
PROTECTORS\ REGULAT(
REMOTE FUEL
CONTROL PUMP
EC EPTAC L HARNESS PLUG
BREAKER POINT
TIMING
SIGHT
HOLE
START-STOP
SWITCH
AIR DISCHARGE
0lL DRAIN (UNDER UNIT)
Figure l-2. Service Side View of a Kohler 4500 Watt Single Cylinder RV Generator Set
BREATHER_ AIR DUCT
/ IGNITION
thtMtNT
EXHAUST .d ~.
..”
TUBE
FUEL
LINE
i OIL FILL
CIRCUIT
?OTECTOR
VOLTAGE / FINS
c
EGULATOR
&j \ FUEL
PUMP
COOLING SLOTS /
$p”
:i:::::
,;:z> r..
“’
.:’
,:*.
:
,::. : ,, :.:::::,A~
./:
..,,,,,.
>::: ;,..1’
’ CONTROLLER
EQUIPMENT
GROUND
Figure 1-3. Service Side View of a Kohler 4500 Watt Twin Cylinder RV Generator Set
AIR CLEANER
. CARBURETOR
BATTERY
CHARGING VOLTAGE
REGULATOR EGULATOR
GOVERNOR
FULL-FLOW
CONTROLLER
OIL FILTER
GROUNDING
AIR I
MOUNTI “ISCHARGE
Y
BATTERY POSITIVE
CONNECTION
OIL DRAIN LOCATED
UNDER UNIT
Figure I-4. Service Side View of a Kohler 5500 or 7000 Watt RV Generator Set
I-4
l-8 OIL SPECIFICATIONS
MODEL CAPACITY
Use high quality detergent oil of API (American Petroleum
Institute) service class SF. Select viscosity based on the 35kW 1 Quart (0.95 Iitres)
air temperature at the time of operation as shown below: 4.5kW (Single) 2 Quarts (1.89 litres)
I
5.5kW 4 Quarts (3.78 litres) (Additional
I
I 1 I
I
l/2 quart (0.47 litres) when filter
I
T 1 r I I
'F-50 6 20 32 40 60 80 100 is replaced)
t I I T I I I I
c-30 -20 -10 0 10 20 30 40
7kW 4 Quarts (3.78 litres) (Additional
TEMPERATURE RANGE EXPECTED BEFORE NEXT OIL CHANGE
l l/2 quart (0.47 litres) when filter
\ /I\\ (HIDDEN)
I
CIjRBURETOR
VALVE
TAPPET,
COVER
REMO’ TE
CONTR OL
BELTTENSION
C:ONNEC TOR
ADJUSTMENT
GOVERNOR
ADJUSTMEN
OIL PRE
GAUGE / OIL PRESSURE \
OIL CONTROLLER
ADJUSTMENT \
/ FILL/CHECK \ GROUN
I /
OIL
MOUNTING FUEL FUEL STRAF
DRAIN
TRAY SOLENOID PUMP
Figure 1-5. Service Side View of Kohler 7500 Watt RV Generator Set c
l-5
Section 2
Operation
2-l. GENERAL
CHECK REQUIREMENT
2-3. OPERATION
NOTE
Figure 2-I. Controller
If the generator set shuts itself down due to
high engine temperature or low oil pressure,
the cause must be located and eliminated
before the set can be restarted. Also, make
sure the circuit breaker(s) is in the “on” posi-
tion so generator output is transferred to the ‘I. Move the START-STOP switch on the controller to
load. START position and hold until the engine is running but
not more than 10 seconds. Normally the engine will start
CAUTION within five seconds. If the engine does not start in 10 sec-
onds, release the switch and wait a few seconds before mov-
In the event of a “false start”, that is, the en- ing back to START position. This allows the choke to reset
gine gets up sufficient speed to disengage the in the full choke position.
starter but fails to continue running, allow the
engine to come to a complete halt before
making a restart attempt. If the flywheel is 2. Whenever possible allow a brief cooling period by run-
still rotating when the starter is engaged, the ning the set at low or no load for a few minutes just prior
starter pinion and ring gear will clash which to shutdown. To stop, move the switch to STOP position
may damage the ring gear teeth. and hold until the set comes to a complete halt.
2-I
Section 3
Scheduled Maintenance
3-l. GENERAL 3-2. SCHEDULED MAINTENANCE
Scheduled maintenance is “preventive” maintenance. Refer to Table 3-1 for scheduled maintenance requirements.
Major repair can be avoided by correcting problems when Perform each function at the indicated time interval. For
they are small. When performing maintenance, always each function, refer to the applicable paragraph for instruc-
look for signs of potential trouble, such as loose connec- tions.
tions or dirty components. When running the set, listen for
any unusual noises.
NOTE
NOTE - Oil Change
On a new engine change the oil after the first For maintenance work on engine components,
five hours of operation, and thereafter on refer to the Kohler engine service manual
K181QS and K341QS change oil every 25 which covers the engine model.
hours. On KT17, K582QS & L654 change oil
every 50 hours.
1
3-1
Section 4
Troubleshooting
4-l. GENERAL CAUTION
When troubleshooting a generator set, always consider the Do not push the V.B.U. button after the “GEN
simplest causes first. Narrow the problem down to a func- ON” lamp is on. Voltage regulator damage may
tional system, such as fuel or ignition. To operate efficient- resu It.
ly, an engine must have sufficient fuel, a good ignition
spark and good compression. All adjustments must be
correct. For a generator to produce the required electricity,
CAUTION
all parts must be clean, all connections tight, and all com-
ponents in working order. See Table 4-l for Engine Trou-
bleshooting and Table 4-2 for Generator Troubleshooting. Do not use the RV Systems Check as a replace-
ment for the controller. The hi-temp and low
4-2. RV SYSTEMS CHECK oil pressure switches will not shut the machine
down in the event of a malfunction. Generator
The “RV Systems Check” is designed to check the electri- damage will result.
cal status of an RV generator set prior to connecting and
testing with the controller. If the generator does not check
out in each step, correct the malfunction before proceeding 1. Make sure the battery is properly connected and oil is
to the next step. at proper level.
CAUTION
Do not push the CRANK button after the en- 2. Check the three fuses in the RV Systems Check tester
gine is running. Starter damage will result. (Figure 4-l). Replace any blown fuses.
RV
Note: May be actuated with ignition switch on
‘II I or off.
SYSTEMS CHECK “Choke” - Supplies battery voltage to choke plate
solenoid. Note: May only be actuated during
GEN cranking.
POL. CRANK ON’ SAFETY “V.B.U.” - Voltage Build Up, supplies battery vol-
tage to excite field.
VISUAL INDICATORS
“Pol” - Green - Indicates battery polarity correct.
IGNITION “GEN. ON” -. DOES NOT FUNCTION ON SETS
EQUIPPED WITH RELAY CONTROLLERS.
ON OFF
“Crank” - Amber -’ Indicates battery voltage signal
present during cranking.
“Safety Switch” - Amber - Indicates safety circuit
CRANK CHOKE V. B.U. wiring correct. Operator must manually short
temperature switch to ground to obtain this
indication.
FUSES
15 AMP - IGN/CRK 3 AMP - V.B.U.
1 AMP -CHOKE
4-1
3. Remove the 12 pin connector from the controller and NOTE
plug it into the tester.
On 5.5kW, 7kW and 7.5kW sets, the SAFETY
4. Observe the POL (polarity) lamp. Green light indicates lamp will go off after the engine has reached
battery polarity is correct. If lamp does not light, check for sufficient operating oil pressure.
correct battery connection to the generator set. IO. To check the high temperature cutout, low oil pressure
cutout and/or the oil level cutout for proper operation,
NOTE start the generator set and connect a jumper wire from the
cutout device to ground. The “amber” safety lamp should
On 5.5kW, 7kW and 7.5kW sets the SAFETY light, indicating the protective circuit is functioning prop-
lamp will also be on. This indicates the low oil erly.
pressure switch is functioning properly.
11. If all checks are OK, connect the 12 pin connector to
5. With the IGNITION switch in OFF position, press the the generator set controller.
CRANK button. The CRANK lamp should light and the
engine should crank. If the lamp does not light, no voltage If the 15 amp fuse blows, check for defective cranking
from the battery is present. solenoid, fuel pump or fuel solenoid, ignition coil, choke
heater, fuel shutdown control or shorted wiring.
6. Remove the air cleaner cover to observe the choke plate
during the next step. If the 1 amp fuse blows, check for defective choke sol-
enoid or wiring.
7. Again, with the IGNITION switch in OFF position press
the crank button. While the engine is cranking, press the If the 3 amp fuse blows, check for shorted or grounded
CHOKE button to supply battery voltage to the choke generator rotor or defective voltage regulator.
plate solenoid. Make sure the choke plate is functioning
properly. If not, see Section 7. Release the CRANK and
CHOKE buttons.
4-3. TROUBLESHOOTING
8. With the IGNITION switch ON, start the engine, using
CRANK and CHOKE buttons as needed. If engine does not
Refer to Table 4-l for engine troubleshooting. To make
start, see Engine Troubleshooting, Table 4-l. With engine
engine repairs, refer to the Kohler engine service manual
at operating speed, press V.B.U. (voltage build-up) button
which covers the engine model. A troubleshooting chart
momentarily. Check for generator output voltage. If no
cannot cover every possible cause of malfunction. Always
output voltage is available, see Troubleshooting Gen-
consider every possible cause of malfunction. Knowledge
erator., Table 4-2.
of four cycle engines and battery ignition systems can
be applied. Refer to Table 4-2 to troubleshoot the genera-
9. Turn the IGNITION switch to OFF position to stop the tor. The table refers to applicable paragraphs in the manual.
engine.
4-2
CONDITION POSSIBLE CAUSE
1. Engine will not crank. 1. Battery cable connections reversed. (Must be negative ground.)
2. 10 amp fuse in controller blown (5-3).
3. Defective start switch or “C” relay (5-2).
4. Open circuit in wiring harness or connector.
5. Faulty starter motor.
6. Open circuit in REI diode (5-4).
7. Normally closed 3CR contacts, open (5-5).
8. Busted or loose ground strap.
2. Engine cranks but will not start. 1. Choke not operating or out of adjustment (7-1, 7-2).
2. Check fuel supply to carburetor.
3. Faulty fuel shut-down control (7-3).
4. Faulty fuel pump.
5. Dirty or stuck ignition points.
6. Faulty condenser.
7. Faulty spark plug.
8. 2CR relay not functioning. Must have battery voltage on positive
connection of ignition coil (5-5).
9. Fuel mixture. Replace.
6. High AC voltage (above 125 volts AC). 1. Faulty exciter voltage regulator.
2. Stator reconnected improperly.
8. Unit will not operate with remote I. Incorrect wiring of remote switch to remote plug assembly. Center
switch - OK at controller. pole of remote switch must connect to terminal 4 of remote harness
plug, Figure 5-2.
2. Open connection in wiring.
12 VOLT
GENERATOR
“ON” LIGHT
12 VOLT
HOURMETER
1 Red 18
2 White 22
3 Brown 22
4 Black 18
5
6 Blue 22
5-l
llO AMP
lN.LINE
FUSE
I
CHOKE HTR.
d
\;/-
.
2CR
8 /
ZCR I I
52
5 II
-STARTER 1
REuOTE SW.
+
YLL
2CR EINTS
2 + ICN -
OIL e II
LIITLUI I
BREAKER
STD. ON 7kW
OPTION 5.5kW
. :
Q%. Qb +O-.
. I, 1 .
.
5-3
2. Energizing the 2CR relay will allow current to flow
I2 VOLT
through the 10 Amp in-line fuse to the ignition coil, choke
heater, carburetor shut-down solenoid and electric fuel
pump (if equipped).
3CRT 5. The
. . normally CLOSED contacts in the V.B.U. (voltage
bui,ld-up) circuit will then open and disconnect the battery
supply from the generator voltage regulator.
FUEL ‘PUMP
7. The normally closed 3CR contacts in series with the
“C” cranking contactor will open deenergizing the “C”
contactor. This offers protection from engaging the starter
motor while the unit is operating.
.
8. The 3CR contacts in series with the 2CR relay coil will
close, maintaining current flow to the 2CR relay coil.
The 2CR relay controls current flow to the engine ignition
circuit.
Y
i
L2 LI
r
t
CEN:: ATOR
LO
5-3. FUSES
5-5
THE SCHEMATIC BELOW SERVES AS
A GUIDE TO LOCATING PROPER
TERMINAL CONNECTIONS.
0 0
- COVER
TERMINAL CONNECTIONS AS
SHOWN ON WIRING DIAGRAM
0 0
START
I STOP
SWITCH
CONTROLLER
CONNECTORS SHOWN
FROM PIN INSERTION
SIDE -lr
---
r l
1
I
I
I
c
I I
I I I
I IOAMPFUSE I I
I I I
I ! I
I I I I
I I
I I
I I
I I
I I
I .I
I I
-m----- ~~~~~~--~~-----~
I
I
I
I
I
I
.I
~~~~,~~~ w-&-w------ --e,u#
I
- - - - - LOCAL CONTROL
801 A-241939 WUCR
&W@J fROu RUR)
277932
A WARNING
2. Disconnect the generator ground strap at the tray (Fig-
HIGH VOLTAGE! Remember that the function of a gen-
gure 6-3 or 6-4). On the 3.5kW and 4.5kW (single), remove
erator set is to produce electricity and that wherever
the battery positive lead from the generator positive stud
electricity is present, there is the potential danger of
and remove stud remove stud from the generator mounting.
electrocution. Take the same precautions with electrical
appliances in your coach that you would observe in your
home. Keep away from electrical circuits and wiring while 3. Remove the center panel (4.5, 5.5, 7, 7.5kW), see Fig-
the set is running and have electrical service performed ure 6-5; or remove the end panel (3.5kW), see Figure 6-6.
only by qualified electricians. Make sure unqualified
persons, especially children, cannot gain access to your
set-keep the compartment door locked or securely 4. Remove the plug from the voltage sensing relay Figure
latched at all times. Be sure that generator is properly 6-7). The relay can now be removed.
‘j 12b
1. End Bracket 7. Panel, Center 12b. Voltage Regulator (7.5KW) 18. Ball Bearing
2. Stator 8. Circuit Breaker(s) 13. Voltage Sensing Relay (VSR) 19. Washer
3. Rotor 9. Junction Panel 14. Thru Bolt 20. Tolerance Ring
4. Adapter IO. Generator Fan 15. Over Bolt 21. Brush
5. Guard, Fan 11. Bearing Cap 16. End Bracket 22. Brush Holder
6. Junction Panel 12a. Voltage Regulator (3.5kW-7kW) 17. Slip Ring
6-1
3 13
1 2I \ --.- /
,:::;
GROUND STRAF
6-2
Figure 6-9. Exhaust Tube
10. Tilt the generator end up and place blocks under the
generator adapter.
6-3
Figure 6-14. Exciter / Voltage Regulator
11. Lift the brushes by the leads and lock in this position
by inserting a retainer wire as shown in Figure 6-12.
6-4
inch gap between bolt and rotor. Bump the thru bolt with
a lead mallet to break the rotor loose (4.5, 5.5, 7, 7.5kW
only) for removal (Figure 6-l 7). If the bearing turns freely
and has no sign of damage do not remove, the fan will be
removed with rotor (Figure 6-18).
NOTE
On 7.5kW, if the rotor seems loose but can not
be removed, see Section 6-3.2.
CAUTION
6-5
Insulator
Sleeve
YL-J
Notch Must Be
On Bottom
NOTE
Cut one wire from switch so that it reaches
screw shown in Figure 6-23, strip 250 in.
(6.4mm) of insulation and crimp-on l/4” eye-
let term inal. Place terminal between lockwasher
and cover.
CAUTION
Figure 6-21. Oil Tank Removed
Any air leak in the ventilation line system could
cause the engine oil to be drawn from the reser-
voir into the crankcase, resulting in engine blow-
6-3.1. Removal of Oil Tank 4.5kW (KT17 Series I only)
by and a low oil level shutdown.
1. Drain oil from oil tank assembly. f. Cut the other wire from switch so that it reaches #I2
(purple) lead, strip .250 in. (6.4mm) of insulation and
2. Detach nut from eyebolt. Remove the bolt attaching the connect together using an insulink.
oil tank to engine leg. Detach ventilation line (Figure 6-20).
6-6
5. When installing the oil tank, make sure O-rings are not 5. The flywheel and adapter can now be removed (Figure
damaged. Apply grease to the O-rings, fitting and the oil 6-26).
tank bore. Push tank on squarely.
6. Strike downward on corner of stub shaft with a lead
6-3.2 On the 7.5kW generator set, if the rotor seems loose mallet as shown in Figure 6-27.
but cannot be removed, the flywheel has become free of
the crankshaft taper. To separate rotor from flywheel, 7. The stub shaft can now be removed.
adapter, and stub shaft proceed as follows.
Stub
Flywheel
This circuit magnetizes the rotor during cranking. When
Figure 6-25. Separating Stub Shaft and Flywheel the switch on the controller is moved to the start position,
6-7
DC current flows from the battery to brushes and sl ip rings
on the rotor. See Figure 6-28.
6-5. BRUSHES
6-5.2. Maintenance.
CAUTION
STARTER
12 VOLT
GENERATOR BATTERY
ROTOR
/
BRUSHES &
SLIP RINGS
4CR
GENERATOR
REGULATOR
6-8
6-6. SLIP RINGS
NOTE
Although the physical appearance of your Figure 6-31. Exciter / Voltage Regulator
voltage regulator may differ from the one pic-
tured, its fu tiction is identical.
A’ WARNING
HIGH VOLTAGE! Remember that the function of a gen-
erator set is to produce electricity and that wherever
electricity is present, there is the potential danger of
electrocution. Take the same precautions with electrical OR AC +
appliances in your coach that you would observe in your 0
home. Keep away from electrical circuits and wiring while
AC
the set is running and have electrical service performed
only by qualified electricians. Make sure unqualified
persons, especially children, cannot gain access to your
set-keep the compartment door Iock,ed or securely
latched at all times. Be sure that generator is properly
grounded. Never touch electrical leads or appliances with Figure 6-32. Terminal Identification
wet hands, when standing in water, or on wet ground as
the chance of electrocution is especially prevalent under
such conditions.
6-9
1. Connect two 100 watt light bulbs across “+” and ‘I-” NOTE
terminals of regulator. See Figure 6-33.
If bulbs flash momentarily and extinguish,
2. Set multimeter range to 100 Volts DC. Connect meter flicker dimly or glow steadily the regulator is
across light bulbs. Check for correct polarity (refer to functioning properly. These conditions are
Figure 6-33). caused by the amplitude of the “AC” supply
Fl
2A
110/120 AC B +
VAC OR
VARIABLE
TRANSFORMER’+
6-10
Figure 6-35. Two Pole Rotor
.:
6-8. STAT0 R
5. Start generator set and run at NO load. 1. On the 3.5kW, apply antiseize compound to the rotor
threads (Figure 6-39). Thread the rotor onto the drive
6. Observe ammeter with unit running. If current increases shaft, and tighten by hand.
considerably, a running short in the rotor has been detected.
2. On the 4SkW, 55kW, 7kW or 7.5kW, apply antiseize
EXCITER / compound to the crankshaft stub (Figure 6-40). Install the
VOLTAGE r 1 rotor onto the crankshaft with the thru bolt. See Table 6-2
REGULATOR ,-‘&I; DC for torque value.
I SIZE I TORQUE I
5116 100 to 125 in. Ibs. (11.3-14.1Nm)
BATTERY
Table 6-2. Generator Thru Bolt Torque
6-l 1. VOLTAGE SENSING RELAY 5. Position the brush holder and install the two brush
holder screws. To install the brush holder, it will be
The voltage sensing relay (Figure 6-38) is located in the necessary to retain the brushes with a wire (Figure 6-42).
end bracket assembly. Its function is to sense AC gen- Remove the wire when the brushes are installed.
TO PIN “4” OF ’
PI CONNECTOR
6-12
Figure 6-41. Stator and Rotor
).A:::‘; ::,..:, :,<4y:.:
THREADS
,. ..::
6-13
.A.. .: ,...
BREAKER :
6-14
Section 7
Choke, Shutdown Control and Governor
7-1. CHOKE TESTING AND ADJUSTMENTS (3.5kW,
A WARNING
BACKFIRE! A sudden backfire can cause serious burns.
4.5kW SINGLE)
Keep hands and face away from the carburetor when the
air cleaner is removed.
7-1.1 General. When the engine start switch is activated,
battery current activates the rotary solenoid in the electric A WARNING
choke unit (Figure 7-l). The choke lever pushes the choke FLASH FIRE! Asudden flash fire can cause serious burns.
plate into the full choke position. The solenoid deenergizes To avoid the possibility of a flash fire, do not smoke or
immediately after the switch is released from the start posi- permit flame or spark to occur near carburetor, fuel line,
tion. When the solenoid deenergizes, the choke plate opens fuel filter, fuel pump, or other potential sources of spilled
to a position determined by a thermostatic spring and the fuel or fuel vapors.
ambient temperature. As the engine warms and less choking
7-1.2. Inspection.
is needed, the thermistor circuit allows the choke plate to
1. Disconnect the high tension lead from the spark plug
gradually move to full open position.
sothe
A
engine will not start.
WARNING
2. Remove the air cleaner cover, element and base plate.
UNINTENTIONAL STARTING! To prevent accidental
3. Push the start-stop switch on the controller to the start
starting when checking choke operation, remove spark
position and hold for five seconds. The choke plate should
plug lead(s) at spark plug(s).
CHOKE
SHAFT
ONE LEAD TO
/
STARTER RELAY
THE OTHER LEAD
TO CONTROLLER
HEATER
(THERMISTOR)
TERMINAL
LOCKWASHER
IDLE FUEL
ADJUSTMENT
SOLENOID
TABS
SPRING
AUTOMATIC
ELECTRI-CHOKE UNIT I
LEVER
l/2 TURN TENSION
7-l
close a minimum of 45’ at an ambient temperature of 7-1.5. Replacement and Adiustment.
about 75’F (24’C). The plate will close more at lower tem- NOTE
peratures. The choke plate should open when the switch is
released. When installing the choke, make sure the choke
plate arm goes under the choke lever.
, , 4; During cranking the choke will remain closed as long as
t the start-stop switch is held in the start position.
1. Position the choke with the two mounting screws
5. If the choke does not function properly, refer to Choke slightly loose.
Troubleshooting, Table 7-l.
2. Push the choke unit all the way down, then, keeping
7-l .3. Testing - Choke Solenoid (3.5,4.5kW Single) slight pressure on it, move the chokeplate (in carburetor)
into the full open position allowing the choke unit to rise.
1. Disconnect leads from the solenoid tabs (Figure 7-l).
2. Check heater resistance. Connect one lead of an ohm- 5. Check choke function by removing the spark plug lead
meter or multimeter to the heater terminal. Connect the and cranking the engine. The choke plate should close
other lead to the carburetor body (ground). a minimum of 45’ at a temperature of about 75’F (24’C).
The plate will close more at lower temperatures. The choke
3. The resistance should read at least three ohms. If not, will remain closed as long as the start-stop switch is held in
replace the choke. the start position.
Choke won’t close when 1. Faulty lead wires or terminals. 1. Change lead wires or replace choke.
cranking. 2. Air cleaner gasket interference with 2. Reposition flat of gasket to provide
choke shaft lever. (4.5kW only.) clearance for choke shaft lever.
3. Faulty solenoid. 3. Test solenoid.
4. Faulty controller or ground 4. Replace lead to controller with
in controller. a jumper wire to ground. If choke
functions properly check con-
troller.
5. Choke lever lacks sufficient travel 5. Manually move the choke lever until
or smooth movement. the choke plate is fully closed. Re-
place the choke unit if it does not
move freely.
Choke will not fully open. 1. Choke spring not properly 1. Remove spring retainer and with
adjusted. choke wide open wind up spring l/2
turn, replace spring retainer.
2. Choke shaft fails to move freely. 2. Replace choke shaft.
3. Faulty choke adjustment. 3. Adjust choke.
4. Faulty heater. 4. Test heater resistance.
7-2
7-2, CHOKE TESTING AND ADJUSTMENTS (4.5 TWIN,
5.5, 7, 7.5kW)
7-2.2. Inspection.
7-3.1. General. If an engine has been working under load, 3. Check for defective solenoid with an ohmmeter or multi-
it tends to continue running or “diesel” after the switch is meter. Solenoid resistance is approximately 20 ohms.
moved to the stop position. This is prevented on these
generator sets by a solenoid and plunger which positively 7-3.3. Temporary Field Fix.
stops all flow of fuel when the switch is moved to the stop
position. See Figure 7-I or Figure 7-3. The solenoid is 1. Turn the main fuel adjusting needle out then shift the
mounted on the carburetor. When the switch is in the solenoid retaining bracket.
Choke won’t close during Faulty lead to choke. 1. Check for secure lead connections
cranking. 2. Make continuity check on lead. Re-
place if no continuity.
7-3
BREATHER PLATE
VALVE COVER
COVER GASKET
BREATHER
HOSE
Figure 7-5. Crankcase Breather Assembly (4.5kW Single)
GASKET -
STUD
FILTER GASKET \ ,
7-4
7-5.2. Adjustments. The governor maintains engine speed
when changing loads and limits the engine speed. Initial
adjustment is made at the factory and should not be re-
quired in the field unless the linkage works loose or becom-
es disconnected. Speed adjustment should be made if the
engine surges when changing loads or if speed drops consid-
erably when a normal load is applied.
Figure 7-8.
Governor Components and Adjustment Points
(4.5kW Single)
7-5
GOVERNOR
LINKAGE
\ CARBURETOR
DAMPENING BODY
IDLE STOP
SCRE
NOTE
7-8. GOVERNOR (5.5kW, 7kW).
When placing the base plate on the carburetor,
be sure to install the air intake tube into the 7-8.1. General. These models are equipped with centrifu-
blower housing as shown in Figure 7-10 (long gal flyweight type mechanical governors which are exter-
side down). nally mounted. See Figure l-4 for location. The governor
drive gear is driven by the camshaft gear.
7-7. GOVERNOR (4.5kW TWIN)
7-8.2. Speed Adjustment. The throttle shaft is fixed at a
7-7.1. General. This model is equipped with a centrifugal definite length to establish a load speed of 1800 RPM
flyweight mechanical governor. The governor gear/fly- (1500 RPM, 50 H z models). Any variation in speed fre-
weight mechanism is mounted within the crankcase and quency changes the output of the generator. For this rea-
driven off a gear on the camshaft. son only slight readjustment of speed is possible. Proceed as
follows:
7-7.2. Speed Adjustment. The throttle shaft is fixed at a
NOTE
definite length to establish a load speed of 1800 RPM. Any
variation in speed frequency changes the output of the gen- Due to variances in generator output wave-
erator. For this reason only slight re-adjustment of speed is shape, not all pointer type frequency meters are
possible. Proceed as follows: compatible.
7-6
Figure 7-11. Governor Sensitivity Adjustment (4.5kW Twin)
1. To increase speed, loosen the inside speed adjusting 2. To make the governor less sensitive, loosen the lower
nut (Figure 7-12) and tighten the outside nut to draw the nut and tighten the upper nut to draw the eyebolt upward.
eyebolt closer to the bracket which is mounted on the
governor. This will pull the throttle open. 3. Retighten the nut that was loosened to lock the eyebolt
at the new setting.
2. To decrease speed, ~Ioosen the outside nut and tighten
the inside nut tovforce the eyebolt away from the bracket. 7-8.4. Anti-Dieseling Control Adjustment. Used with car-
buretor assembly 48 053 29. See Figure 7-13 for dimen-
.3. When speed is correct, tighten the nut that was loosened
sions.
to lock the eyebolt at the new setting.
1. With anti-dieseling control dimensions correct, hold
SPEED ADJUSTING governor arm in fully closed position. See Figure 7-13 (bot-
EYE BOLT tom view).
UPPER NUT
CRANKCASE 2. With solenoid plunger fully in solenoid, adjust solenoid
BREATHER INCREASE SPEED coil so chain is taut. Tighten solenoid hold-down clamp.
\
3. With governor arm fully closed, adjust carburetor idle
stop screw one-turn in after screw makes contact with stop
spring.
DE NUT
THROTTLE /I-VI NOTE
LINKAGE
Solenoid is energized only when stop button is
~-??5lll held in stop position.
SENSITIVITY
7-7
-50 in_ -88 in.
(12.7mm) (22.4mm)
TO PIN 5 OF
A-241 939 CONTROLLER
.I25 in. \
(3.2mm) 3.38 in.
(85.9mm) IDLE STOP SCREW
NOTE
____-
Dimensions are approximate.
GOVERNOR
ARM
v
SOLENOID
I
tive, speed surging will occur with change in load. If the
governor is not sensitive enough, a big drop in speed will oc- SENSITIVITY
cur when normal load is applied. ADJUSTMENT
7-8
-a---LB-
.----.--.a
Fm
3CR ICR
2CR
CONNECTORS SHOWN
PIN INSCRTION SIDE
ICR
Tzrw 3CR Hi-TLMC
-YEmW Ill11 I I
r
ZCR
iw
l10 AMP
IN-LINE
FUSE
Ii i
4CR I
I 9
- .*. i> 3 A Rfl
it-
I
III I
I2 -- I
1
1-b I It
L •( HRS. )- - - / I
I I ‘I STARr
\/ I
r’ I l.r-- I
ZCR I
ae I
I
I
I
43% Ii ’ i
/
\ /
\ /
\ /
\ i
\ /
\ /
--- //’
‘EARLIER fvlODELS ONLY 238744
-.- _..-
IO AUP
. Pusc
i-
IN CINF
FUSE
-\ /
\ ./
/
‘\ ,J
‘. .0’
-- ---
t 1
BROWN-
PINK- .
HAZARD GREEN.
CfWJUND4 II I CONNCCTORS
fROM
SHOWN
PIN IN’SCRTlON
‘10 AMP SIDf . . *
IN-LINE
FUSE
PINK
I-” Rtl
d
i $4&+-r---t-+----y
I . ..I
R
II 1
i I
_~~~__~_-------~---~---
l&CM CUNTWL BOX A-241752
BLUE -
-.
T
AMP
IRCUIT
MAKER
l
1
I
I
I
I
I
I
VOLT. REG.
I
‘I
-~--c~---~-----
--AC Qt3 +0 JL -----I
I
I L ‘!. LOCAL CONTFiVL BOX A-24175>
(u(Ob’%it:M REAR)
\ \’ /-
-- -- AH 4.5 KW KT17 R.V
LI 120 VOLT
‘EARLIER MODELS ONLY 277947
REMOTE SW.
CONDENSER
y ’ I’I WII I
I 3cn ICR
IIII I II
CSXINECTMS SHOWN
PIN INSERTION SIDE
I
I _, i
.- chc -o-
VOLT. REG.
1
I
\ I
.---_-----_ _____ --me- J _~~R-
!_ _
278058
KTI 7 SERIES It
____P
4.5 KW RV
I20 VOLT / C.SA
278055
p-c------B-----~
B
(
-----
+ TO POINTS
REMOTE SW.
T\‘%:P OR VALVE
-BLACK
HhZh!! GWEN
GRDUSD + I
-- -_--I
li--
I
‘I I
‘I I
11 I
I
‘I
I I
-I II
-&I-_!L_S~!~S-K
4.5 KW RV
120/240 V/CSA
278056
Wiring Diagram - 5.5CM21, 7CM21 120-volt
BATT.
.jVZ
‘+.CHARGING
REG. AC
4CR
4
.-B
if-
ZCR
--It- .
‘IO AUP
HAZARD GREEN CoNNE&ORS SHOWN
GROUSD 4 1 II I
m LINE
FUSE r ! ! I
I
STD. ON 7KW
OPT. ON 5.5KW
I
1 VYAGE REG.,
ICR
I
II I‘
‘I -- START
l
ZCR
--WHITE - 1
flj- I 1
&
-II STbF- AI I
IL
d I
_-_-,,,,---------~L,---,~
h. ‘1
1 -;; - -- - - E&AL CONTROL BOX A-241939 C#VCR
mom fROY REAR]
‘\ /
\
/
/
/
/
/
FUEL PUMP
(PI)
._ I I
I : I I I D-d \I
L I GRAY-----7 RED -. i
I I - I
o- 0
...
LQp’ . .
0
..
1
241764
k-
-
-
#- -
8-15
12 VOLT
KOHLER REMOTE
--_--_ PANEL
FUEL PUMP
-GREEN
BLUE
WHITE
BLACK
RED
CONNECTORS SHOWN FROM
PIN .lNSERTION SIDE
TO
PINK LI
AC LOAD
L2
I
I
I
I
‘IIz I
kl I
2CR qpl) lK
-II ” I* I
70% I I
I I
I I
I I
I
I
I I
I
I I
CIR. BRKR. I I
/
I /
%+fj~jTRANSFORM ER I
I
I
I
L_--------- _----mm J L--I
-LOCAL CONTROL 80X A-241 752 COVER
- RED
(SHOWN FROM BACK) --,,--+
RED -
GENERATOR
241875
r
-B-M-----------
2_
--
-\_
3
PU Iri1r-1-1
I
2
EJ
-3ldtlnd
8-l 7
APPENDIX
Radio Frequent nterference Kit
A-2: 366
This kit can be installed to filter out electrical noise emit- 8. Remount regulator mounting plate to generator end
ted at radio frequencies. bracket.
A WARNING
ELECTRICAL SHOCK! Battery can cause electrical burns
and shocks. Exercise reasonable care when working near
the battery to avoid electrical connections through tools.
Remove wristwatch, rings, and any other jewelry.
6. Connect one AC lead to gray lead on capacitor as- Assemble As Shown When Using
sem bly. Omnetics Regulator
7. Connect the other AC lead to lead on capacitor as- Figure 2. To Mount Capacitor Assembly
sembly with pink terminal.
A-l
KOHLER
GENERATORS
TP-5024 g/89 KOHlER CO.KOHLER,WISCONSIN 53044
PRINTED IN U.S.A.