Product Specification

easYgen-2000 Series

Genset Control for


Multiple Unit Operation DRAFT
DESCRIPTION • Isolated & mains parallel
operation
I/Os
The easYgen-2000 Series provides the following I/Os: • Load transfer programs
• FlexRangeTM - Two separate sets of 3-phase true r.m.s.
voltage measuring inputs for the generator and mains: • Softload features
o 100 Vac rated (max. 150 Vac)
o 400 Vac rated (max. 600 Vac) • Open/closed transition
APPLICATIONS • 3-phase true r.m.s. generator current/power
• 1-phase true r.m.s. current input freely configurable either • Synchronization with
as mains current measurement or ground current mea-
The easYgen-2000 Series are versatile genset controllers, including
complete control, monitor and protection features. surement (ground fault protection) phase matching and slip
• 1 speed input (magnetic/switching) * frequency
FlexAppTM - This feature provides the tools to easily configure the • 10 configurable discrete alarm inputs *
easYgen-2000 Series. Different operating modes may be selected by
simple configuration:
• LogicsManagerTM - up to 11 programmable relay outputs * • AMF
• FlexInTM – up to 4 configurable analog inputs *
• Multiple unit island parallel operation up to 16 units (load sharing and • Flexible Outputs – up to 4 configurable analog outputs *
load dependent start/stop features) • FlexCANTM – up to 2 CAN bus communication networks *
• Up to 16 units for load
• Single unit mains parallel operation sharing and load-
• Different breaker control modes (including close/open/synch com-
mands):
Protection (ANSI #) dependent start/stop
Generator: Over-/undervoltage (59/27), over-
- None breaker control for application w/ external breaker control or
no breaker.
/underfrequency (81O/U), unbalanced voltage, dead bus • 100V-480V true r.m.s.
detection, overload (32), unbalanced load (46), rever-
- Generator breaker control for e.g. stand by application or mains se/reduced power (32R/F), definite overcurrent and time- voltage sensing with
parallel applications.
- Generator and mains breaker control for e.g. AMF, open/closed
overcurrent (50/51), inverse time-overcurrent (IEC255), FlexRangeTM
measured ground fault (50N/51N), phase rotation, breaker
transitions, parallel, interchange and soft loading programs failure monitoring
Engine: Over-/underspeed (12), battery over-
• True r.m.s. current sens-
The easYgen-2000 Series is able to control up to 16 gensets con-
nected in a island parallel network with automatic sequencing.
/undervoltage, auxiliary excitation, speed/frequency mis- ing
match
FlexInTM – The units provide three multitype analog inputs that can be Mains: Over-/undervoltage (59/27), over- • Generator kWh meter
freely configured for different type of sender either as a resisitive or as /underfrequency (81O/U), phase shift, rotation field
current input: • Counters for engine
Features
• Resistive input: 0-500 Ohm, for Pt100, linear 2-point, user-defined 9- • 128×64 dot graphical interactive LC display with soft keys starts, operating hours,
point and VDO: 0 to 180Ohm [0 to 5bar/0 to 10bar]; 0 to 380Ohm [40
to 120°C/50 to 150°C],
• Start/stop logic for Diesel/Gas engines maintenance call
• Engine pre-glow or purge control
• 0/4 to 20 mA: linear 2-point, user-defined 9-point
The senders can be isolated (2-pole) or can offer a ground return (1
• Warm-up control via timer or coolant temperature • Freely configurable
• Speed, frequency, voltage, power, reactive power, and
pole)
power factor set points (auto or remote controlled) discrete & analog I/Os
Flexible Outputs – Free configurable speed- and voltage bias outputs • Power and reactive power load sharing with up to 16 units
for many speed governors and voltage regulators. The outputs can including load-dependent start/stop • Multi-lingual capability
also be used as freely scalable outputs. • Generator kWh meter
• Operating hours/start/maintenance counters - Operating • CANopen / J1939 ECU
FlexCANTM – Flexible and isolated CAN bus providing different proto-
cols: CANopen protocols; coupling of IKD 1 expansion cards (up to
hours also available from a connected ECU via J1939/CAN Control
• Configurable trip levels/delays/alarm classes
16DIs/16DOs) as well as of 3rd party expansion cards (request more
detailed information from our sales department).
• PC and/or front panel configurable (ToolKit software)
• Multi-level password protection
• Modbus RTU Protocol
ECU monitoring and alarm management as well as remote start/stop
• Multi-lingual capability
and control commands with various ECUs via the J1939 protocol are
• Event recorder (300 events, FIFO) with real time clock
• CE marked
possible (supported ECUs: Scania S6, MTU ADEC, Volvo EMS2,
(battery backed; min. 5 years)
Deutz EMR2, Sisu, Cummins and standard messages).
• Remote control via interface / discrete inputs • UL/cUL Listing
LogicsManagerTM - The LogicsManager enables you to change the
internal operation sequences of the control. (pending)
The various measuring values, inputs and internal states or constant
values may be combined logically by Boolean operators and program- • GL/LR Marine Approval
mable timers. This enables you to create and/or modify monitoring and
control functions.
(pending)
* Depends on easYgen-2000 package. Check last page for details.
SPECIFICATIONS

Power supply .......................................................... 12/24 Vdc (8 to 40 Vdc) Relay outputs ............................................................................ potential free
Intrinsic consumption .................................... 2 PCB hardware max.~ 12 W Contact material ................................................................................... AgCdO
....................................................................... 1 PCB hardware max..~ 8 W Load (GP) .........................................................................2.00 Aac@250 Vac
Ambient temperature (operation) ....................... -20 to 70 °C / -4 to 158 °F 2.00 Adc@24 Vdc / 0.36 Adc@125 Vdc / 0.18 Adc@250 Vdc
Ambient temperature (storage) ........................ -40 to 85 °C / -22 to 185 °F Pilot duty (PD) ..................................................................................................
Ambient humidity...................................................... 95 %, non-condensing 1.00 Adc@24 Vdc / 0.22 Adc@125 Vdc / 0.10 Adc@250 Vdc
Voltage ...............................................................................................( /∆) Analog inputs (none isolated) .............................................freely scaleable
100 Vac [1] Rated (Vrated) ............................................69/120 Vac Type .............................................................0 to 500/2500Ohms / 0 to 20 mA
Max. value (Vmax)............................................86/150 Vac Resolution .............................................................................................. 11 Bit
Surge volt.(Vsurge) ....................................................2.5 kV Analog outputs (isolated) ....................................................freely scaleable
and 400 Vac [4] Rated (Vrated) ..........................................277/480 Vac Type ......................................................................... ± 10 V / ± 20 mA / PWM
Max. value (Vmax)..........................................346/600 Vac Insulation voltage ............................................................................... 500 Vac
Surge volt.(Vsurge) ....................................................4.0 kV Resolution ..................................................... 11/12 Bit (depending on output)
Accuracy .......................................................................................... Class 1 ± 10 V (scaleable).........................................internal resistance .~ 500 Ohms
Linear measuring range .............................................................. 1.25×Vrated ± 20 mA (scaleable)................................................maximum load 500 Ohms
Measuring frequency ................................................50/60 Hz (40 to 85 Hz) Housing Front panel flush mounting ............... Plastic housing
High Impedance Input; Resistance per path ....... [1] 0.498 MΩ, [4] 2.0 MΩ Dimensions WxHxD.............219 × 171 × 62 mm (easYgen-2200)
Max. power consumption per path ................................................ < 0.15 W WxHxD.............219 × 171 × 99 mm (easYgen-2500)
Current (Isolated) Rated (Irated) .............................. [1] ../1 A or [5] ../5 A Front cutout WxH ............................... 186 [+1.1] × 138 [+1.0] mm
Linear measuring range ........................................................ Igen = 3.0×Irated Connection ........................................................screw/plug terminals 2.5 mm²
Imains/ground = 1.5×Irated Front.....................................................................................insulating surface
Burden .......................................................................................... < 0.15 VA Sealing Front .............................. IP65 (with screw fastening)
Rated short-time current (1 s) .................................[1] 50×Irated, [5] 10×Irated Front .............................. IP54 (with clamp fastening)
Discrete inputs .............................................................................. isolated Back ................................................................... IP20
Input range ............................................................. 12/24 Vdc (8 to 40 Vdc) Weight ............................................................. approx. 800 g (easYgen-2200)
Input resistance .............................................................. approx. 20 kOhms ..................................................................... approx. 1,100 g (easYgen-2500)
Disturbance test (CE) .............tested according to applicable EN guidelines
Listings .............................................................................. UL/cUL (pending)
Marine Approvals .............................. GL/LR (pending), others upon request

DIMENSIONS

Plastic housing for front panel mounting (easYgen-2500 – P1)

17,53

171,00

219,00

10,00
97,30
87,30

183,94
TERMINAL DIAGRAM

59 58 57 56 55 54 53 52 51 50 49 48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32 31 30
Relay [R 1] (isolated)
- Fixed to Ready for operation

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
480 Vac
Mains voltage N
100 Vac Relay [R 2] (isolated)
- Preconfigured to Horn
480 Vac configurable via LogicsManager
Mains voltage L3
100 Vac Relay [R 3] (isolated)
- Preconfigured to Starter
480 Vac configurable via LogicsManager
Mains voltage L2
100 Vac Relay [R 4] (isolated)
- Preconfigured to Fuel solenoid
480 Vac configurable via LogicsManager
Mains voltage L1
100 Vac
Relay [R 5] (isolated)
480 Vac - Fixed to "Command: open MCB"
Generator voltage N if MCB Control is enabled
100 Vac otherwise configurable via LogicsManager

480 Vac Relay [R 6] (isolated)


Generator voltage L3 - Fixed to "Com.: close GCB" [GCB, GCB/MCB]
100 Vac - Fixed to "Com.: open GCB" [GCB open]
480 Vac Common (terminals 44 to 51)
Generator voltage L2
100 Vac Discrete input [DI 01] (isolated)
- Emergency stop (LogicsManager) [DI 01]
480 Vac Discrete input [DI 02] (isolated)
- Start in Auto (LogicsManager) [DI 02]
Generator voltage L1
100 Vac Discrete input [DI 03] (isolated)
- Low oil pressure (LogicsManager) [DI 03]
* if MCB Control is enabled

Discrete input [DI 04] (isolated)


+ [AI 03] - Coolant temp. (LogicsManager) [DI 04]
Discrete input [DI 05] (isolated)
+ [AI 02] Analog inputs - Alarm acknowledge(LogicsManager) [DI 05]
0 to 500 Ohms / 0 to 20 mA Discrete input [DI 06] (isolated)
+ [AI 01] - Enable MCB (LogicsManager) [DI 06]
Discrete input [DI 07] (isolated)
- Reply: MCB open * (LogicsManager) [DI 07]
s1 Discrete input [DI 08] (isolated) [DI 08]
Ground or mains current - Reply: GCB open
(isolated)
s2 Auxiliary excitation D+
easYgen-2500 P1

L3 12/24 Vdc
Power supply
L2 8 to 40 Vdc
Generator current 0 Vdc
(isolated)
L1 Function Earth
GND +
MPU input
PWM GND

VOut GND

GND

- Analog output [AO 01]


-
N/C

+/-10 Vdc / +/-20 mA / PWM CAN-L


(isolated) CAN bus 1
(isolated)
+ CAN-H
IA

Subject to technical modifications. 2009-01-27 | easYgen-2500 P1 Wiring Diagram draft17.skf

easYgen-2500 – P1
60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79

108 107 106 105 104 103 102 101 100 99 98 97 96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81 80

Relay [R7] (isolated)


- Preconfigured to "Command: "GCB open"
configurable via LogicsManager

[DI 10] Discrete input [DI 10] (isolated) Relay [R8] (isolated)
- Preconfigured to "Command: close MCB"
[DI 09] Discrete input [DI 09] (isolated) in [GCB/MCB] breaker mode
configurable via LogicsManager
Common (terminals 75 to 76)
Relay [R9] (isolated)
configurable via LogicsManager

Relay [R10] (isolated)


configurable via LogicsManager

Relay [R11] (isolated)


configurable via LogicsManager

+ Analog input [AI 04]


0 to 500 Ohms / 0 to 20 mA

IA Analog output [AO 04] CAN-L


0/4 to 20 mA
GND (isolated) CAN-H
CAN bus 2
(isolated)
IA Analog output [AO 03] GND
0/4 to 20 mA
GND (isolated) Shield
PWM GND

VOut GND

GND

- Analog output [AO 02]


N/C

+/-10 Vdc / +/-20 mA / PWM


(isolated)
+
IA

Function Earth
easYgen-2500 P1

RS-485-b

RS-485-a
RS-485 Interface
(isolated)
GND

Shield

Subject to technical modifications. 2008-11-24 | easYgen-2500 P1 Wiring Diagram draft16.skf

easYgen-2500 – P1
FEATURES OVERVIEW
International
Woodward easYgen-2000 Series
PO Box 1519
Fort Collins CO, USA Model 2200-P1 2200-P2 2500-P1
80522-1519 Measuring
1000 East Drake Road Generator voltage (3-phase/4-wire)   
Fort Collins CO 80525 Generator current (3x true r.m.s.)   
Ph: +1 (970) 482-5811 Mains voltage (3-phase/4-wire)   
Fax: +1 (970) 498-3058 Mains or ground current (1x true r.m.s.) #1   
Control
Europe
Different Breaker Operation modes FlexAppTM   
Woodward GmbH
Handwerkstrasse 29 Automatic, Manual, and Stop operating modes   
70565 Stuttgart, Germany Single unit mains parallel operation   
Ph: +49 (0) 711 789 54-0 Multiple-unit island parallel operation (up to 16 units)   
Fax: +49 (0) 711 789 54-100 AMF (auto mains failure operation)   
email: stgt-info@woodward.com Stand-by operation   
Critical mode operation   
Distributors & Service GCB and MCB synchronization (slip synchronization / phase matching)   
Woodward has an international Open (break-before-make) and closed (make-before-break) transition   
network of distributors and Interchange   
service facilities. For your Load-dependent start/stop   
nearest representative, call the n/f, V, P, Q, and PF remote control via analog input or interface   
Fort Collins plant or see the Load/var sharing for up to 16 gensets   
Worldwide Directory on our HMI
website.
Soft keys (advanced LC display)   
Start/stop logic for Diesel/Gas engines   
Generator kWh meter   
Operating hours/start/maintenance counter   
www.woodward.com/power Configuration via PC #2   
Event recorder entries with real time clock (battery backup) 300 300 300
Protection ANSI#
Generator: voltage/frequency 59/27/81O/81U   
Generator: overload, reverse/reduced power 32/32R/32F   
Generator: unbalanced load 46   
For more information contact:

Generator: instantaneous overcurrent 50   


Generator: time-overcurrent (IEC 255 compliant) 51   
Generator: ground fault #3 50G   
Generator: power factor 55   
Generator: rotation field   
via Speed input
via ECU
Engine: overspeed/underspeed 12/14 via Speed input or ECU
[CAN/J1939]
[CAN/J1939]
Genset: speed/frequency mismatch   
Engine: D+ auxiliary excitation failure   
Mains: voltage/frequency/phase shift 59/27/81O/81U/78   
Mains: rotation field   
I/Os
Speed input (magnetic/switching; Pickup)  - 
Discrete alarm and control inputs (configurable) #4 8 8 10
Discrete outputs (configurable) LogicsManagerTM 6 6 11
External discrete inputs / outputs via CANopen (maximum) 16 / 16 16 / 16 16 / 16
Subject to technical modifications. Analog inputs (configurable) FlexInTM 3 3 4
This document is distributed for
Analog outputs (+/- 10V, +/- 20mA, PWM; configurable) 1 1 4
informational purposes only. It is not CAN bus communication interfaces FlexCANTM 1 2 2
to be construed as creating or RS-485Modbus RTU Slave interface - - 1
becoming part of any Woodward Serial service interface for configuration   
Governor Company contractual or
Listings/Approvals
warranty obligation unless expressly
stated in a written sales contract. UL/cUL Listing (pending)   
LR Marine Approval (pending)   
We appreciate your comments about CE Marked   
the content of our publications.
Please send comments including the P/Ns 2200-P1 2200-P2 2500-P1
document number below to Plastic Housing
stgt-doc@woodward.com 1A CT inputs / front panel mounting with display #7 P/N 8440-1856 8440-1858 8440-1860
5A CT inputs / front panel mounting with display #7 P/N 8440-1855 8440-1857 8440-1884
© Woodward
#1 mains or ground current selectable
#2 via serial or CAN connection by ToolKit software
All Rights Reserved #3 measured ground current
#4 it is possible to connect up to two digital IO expansion boards (P/N 8440-1041), which provide 8 additional DIs and DOs each.
37xxx - 2009/1/Stuttgart #7 a screw and a clamp kit are delivered with the unit for fastening