Vous êtes sur la page 1sur 7

To find Discharge 'Q' for ORDINARY HAZARD LPM

Q= K x Sqrt of P Discharge
K= 80 K - Factor Deponds on the bulb which you are selecting
P= 0.35 Kg/CM2 Pressure
Q= 47.3286382648 LPM For one sprinkler

We have to cosider for max water demand i.e, 16/18


sprinkler

Actual discharge for 16 sprinkler


16 x Q

Q= 2727.55 LPM For 12 sprinklers

To find diametre of the pipe the Q" sall be in M3

Q= LPM /( 60 *1000) M3 /sec

45.459228297
Q= 0.0454592283 M3 /s
Q= AxV
A= 3.14 x D2 / 4 M2 Area
V= 2.5 M/Sec Medium velocity

Q (3.14/D)2/4 x V
D Sqrt ((4 x Q ) / (3.14 x V M Diametre

To convert M to MM D x 1000 MM

0.1818369132
7.85
0.023163938
0.1521970367 M
D= 152.197036718 MM

To find a Pressure Loss P"

6.05 X 105
X L X
Q1.85

p= C1.85 X d4.87 Bar

p = loss of pressure per meter length of pipe (bar)


Q = flow rate through the pipe (in LPM) 2727.554
d = mean bore of the pipe (in MM) 152.197
C = a constant for the type and condition of pipe 120
L = equivalent length of pipe and fittings (in M) 600 AS per the Drawing

The following values shall be used for ‘C’ in sprinkler installations for
calculation purpose:
cast iron = 100
mild steel = 120
galvanized steel = 120

605000
7022.3958231677
42493076812.2586
298403205119950
0.000000002
1.21647486947764E-06
2270809.08119068
2.7623821807 Bar Pressure

To find a Pump Head MWC

Pressure loss through pipes + minimum pressure at sprinkler + static head


Mininum pressure at
sprinkler 0.35 Kg/CM2 For Ordinary Hazard
Static head 3.5 Height of the Building
Total Head 6.6123821807 Bar 10 m = 1 Kg/CM2
66.1238218065 MWC `
55 - 100 hydrants
To find Discharge 'Q' for ORDINARY HAZARD LPM
Pressure required at
remotest point 3.59 Kg/CM2 Pressure
Q= 273 M /HR
3
Discharge
273000
60 Min
Q= 4550 LPM

To find a Pressure Loss P"

6.05 X 105
X L X
Q1.85

p= C1.85 X d4.87 Bar

p = loss of pressure per meter length of pipe (bar)


Q = flow rate through the pipe (in LPM) 4550
d = mean bore of the pipe (in MM) 200 To Find Reff Sprinkler
C = a constant for the type and condition of pipe 120
L = equivalent length of pipe and fittings (in M) 600 AS per the Drawing

The following values shall be used for ‘C’ in sprinkler installations for
calculation purpose:
cast iron = 100
mild steel = 120
galvanized steel = 120

605000
7022.3958231677
160700074789.647
1128499533985554
5.36110101759018E-10
3.21666061055411E-07
5852225.92653312
1.8824624622 Bar Pressure

To find a Pump Head MWC

head shall be 3.5 bar + pressure loss through the pipes / fittings / valves etc.
+ Static head
Pressure required at
remotest point 3.59 Kg/CM2 For Ordinary Hazard
Static head 5 Kg/CM3 Height of the Building
Total Head 10.4724624622 Bar 10 m = 1 Kg/CM2
104.7246246219 MWC
20 - 55 hydrants
To find Discharge 'Q' for ORDINARY HAZARD LPM
Pressure required at
remotest point 3.5 Kg/CM2 Pressure
Q= 171 M /HR
3
Discharge
171000
60 Min
Q= 2850 LPM

To find a Pressure Loss P"

6.05 X 105
X L X
Q1.85

p= C1.85 X d4.87 Bar

p = loss of pressure per meter length of pipe (bar)


Q = flow rate through the pipe (in LPM) 2850
d = mean bore of the pipe (in MM) 200 To Find Reff Sprinkler
C = a constant for the type and condition of pipe 120
L = equivalent length of pipe and fittings (in M) 600 AS per the Drawing

The following values shall be used for ‘C’ in sprinkler installations for
calculation purpose:
cast iron = 100
mild steel = 120
galvanized steel = 120

605000
7022.3958231677
160700074789.647
1128499533985554
5.36110101759018E-10
3.21666061055411E-07
2462991.94214443
0.7922609164 Bar Pressure

To find a Pump Head MWC

head shall be 3.5 bar + pressure loss through the pipes / fittings / valves etc.
Pressure required at
remotest point 3.5 Kg/CM2 For Ordinary Hazard
Static head 5 Kg/CM3 Height of the Building
Total Head 9.2922609164 Bar 10 m = 1 Kg/CM2
92.9226091644 MWC
Up to 100 hydrants
To find Discharge 'Q' for ORDINARY HAZARD LPM
Pressure required at
remotest point 3.5 Kg/CM2 Pressure
Q= 137 M /HR 3
Discharge
137000
60 Min
Q= 2283.3333333333 LPM

To find a Pressure Loss P"

6.05 X 105
X L X
Q1.85

p= C1.85 X d4.87 Bar

p = loss of pressure per meter length of pipe (bar)


Q = flow rate through the pipe (in LPM) 2283.333
d = mean bore of the pipe (in MM) 200 To Find Reff Sprinkler
C = a constant for the type and condition of pipe 120
L = equivalent length of pipe and fittings (in M) 600 AS per the Drawing

The following values shall be used for ‘C’ in sprinkler installations for
calculation purpose:
cast iron = 100
mild steel = 120
galvanized steel = 120

605000
7022.3958231677
160700074789.647
1128499533985554
5.36110101759018E-10
3.21666061055411E-07
1634380.74083836
0.5257248152 Bar Pressure

To find a Pump Head MWC

head shall be 3.5 bar + pressure loss through the pipes / fittings / valves etc.
Pressure required at
remotest point 3.5 Kg/CM2 For Ordinary Hazard
Static head 5 Kg/CM3 Height of the Building
Total Head 9.0257248152 Bar 10 m = 1 Kg/CM2
90.2572481517 MWC

Vous aimerez peut-être aussi