A p pe nd i x - E nv i r o nm e nt al ( H VA C ) r eq u i r em e nts

HVAC inspection certification and site checkout proforma

Table C-2 HVAC certification

Dear Customer,

In order to provide optimal system performance of the Xerox iGen3 press, it is critical that the
exhaust duct pressure, temperature, and humidity at your Xerox iGen3 installation site be
maintained within the ranges defined in the Xerox iGen3 Installation Planning Guide. To ensure
that your environment can be maintained within these ranges, Xerox requires that a qualified
HVAC Engineer certify your installation site. Appendix C of the Installation Planning Guide and
the below Site Checkout Proforma will provide your HVAC expert with such temperature, humidity
ranges, and exhaust duct pressures. iGen3 is a highly sophisticated electronic printing press that
requires the room to be environmentally controlled as specified in the Installation Planning Guide
in order to maintain optimum Image Quality Performance. Failure to adequately control the room
will result in more frequent service calls, Dry Ink problems, and Image Quality degradation.
Proper performance of the Xerox iGen3 system can only be achieved by ensuring that the proper
duct exhausts pressure, temperature, and humidity consistently remains within the identified
ranges and specifications.

The performance of the Xerox iGen3 in any environment outside of these ranges cannot be
guaranteed. If compliance to these environmental specs falls outside the appropriate ranges and
causes performance problems, unless such non-compliance was due to circumstances outside
the customer's control, (e.g. power outage), Xerox reserves the right to suspend service for your
iGen3 until the appropriate environmental range is restored and, when such ranges are restored,
Xerox will attempt to fix the problem but may charge you time and materials rates to do so.

If the iGen3 press will include a Xerox or third party inline finisher, it is critical to also consider the
unique environmental specifications of the finishing equipment. Make sure to refer to that
finisher’s Solutions Planning Guide, supplied by your local Xerox Sales Analyst, for the
appropriate temperature and humidity levels required to properly operate the finisher. The iGen3
temperature and humidity levels specified in this document must be maintained when operating
with Xerox or third party inline finishing equipment.

Site Checkout Proforma questions to be answered by the HVAC engineer include:


1. Are there other heat producing devices in the room that consume the __ Yes
cooling and heating capacity of the HVAC system? __ No
2. Will the other heat producing devices be operating in the room while the __ Yes
iGen3 is operating? __ No
3. Is there an energy saving night setback or weekend shutdown routine __ Yes
programming for the room A/C rooftops? __ No
4. Will any other exhaust vents be operated, contributing to the room make-up __ Yes
air requirement? __ No
5. Will there be a heat exhaust plenum attached to the Print Engine (PE)? __ Yes
__ No
6. Is the cooling and heating capacity in the room sufficient to accommodate __ Yes
the additional heat load from the PE? (Refer to IPG for PE heat loads.) __ No

X er o x i G e n 3 In s ta l l at i on P l a nn i ng G ui d e C-13
A pp e nd i x - E nv i r o nm e ntal ( HVA C) r e qu i r em e nts

Table C-2 HVAC certification

7. Is the room air-conditioned? __ Yes


__ No
8. Can the room A/C controls be programmed for lower than the 75° F (24° C) __ Yes
set point? __ No
9. Is there adequate supply air to the room? __ Yes
__ No
10. Is the air-intake and air exhaust balanced to the room? __ Yes
__ No
11. Are supply-air plenum vents and exhaust air plenum vents kept apart? __ Yes
__ No
12. Are Room HVAC Air Filters cleaned and replaced per required intervals? __ Yes
__ No
13. Will the temperature of the room with the PE never be allowed to exceed __ Yes
85° F (29°C)? __ No
14. Will the temperature of the room with the PE never be allowed to drop below __ Yes
55° F (13°C)? __ No
15. Will the moisture content of the ambient air never be allowed to exceed 120 __ Yes
GOW (grains of water)? __ No
16. Will the moisture content of the ambient air never be allowed to drop below __ Yes
30 GOW? __ No
17. Is the drain line run horizontally to free drain (gravity) once it is out of the __ Yes
room? __ No
The desired output of this Site Checkout Performa:
Question 1 through 4 is NO.
Question 5 is either YES or NO, based on the site venting method.
Question 6 through 17 is YES.

Your signature below indicates your acceptance to the above as well as your willingness to make
the necessary investments to have the Xerox iGen3 installation site comply with the proper
exhaust duct pressure, temperature, and humidity ranges and specification specified by Xerox
and to maintain such compliance.

Customer Company

Customer Phone

Customer Contact

Customer Signature

C-1 4 X e r o x i G e n3 I ns tal l a ti o n Pl a n ni n g G ui d e