6 5 4 3 2 1

Dewberry Architects Inc.

HVAC SYMBOL LEGEND HVAC ABBREVIATIONS HVAC GENERAL NOTES 401 SW Water St.
Suite 701
Peoria, IL 61602
SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION 309.282.8000 Phone
1. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH MANUFACTURER'S CERTIFIED
DRAWINGS. TRANSITIONS TO ALL EQUIPMENT SHALL BE VERIFIED AND PROVIDED 309.282.8001 Fax
-CEILING DIFFUSER, ROUND NECK -FIRE DAMPER -TERMINAL UNIT, VARIABLE/CONSTANT AIR FOR EQUIPMENT FURNISHED.
F (CEILING DIFFUSERS ARE 4-WAY THROW UNO) (WITH ACCESS PANEL) VOLUME WITH ELECTRIC HEAT AFD -ADJUSTABLE FREQUENCY DRIVE LD -LINEAR DIFFUSER
-TERMINAL UNIT, VARIABLE/CONSTANT AIR AFF -ABOVE FINISHED FLOOR MBH 2. DIMENSIONS SHALL BE FIELD-VERIFIED AND COORDINATED PRIOR TO PROCUREMENT OR
-THOUSAND BTUs PER HOUR
VOLUME WITH ELECTRIC HEAT FABRICATION. COORDINATE THE WORK WITH OTHER TRADES INVOLVED. FIELD MODIFICATIONS
-ROUND DIFFUSER -FIRE & SMOKE DAMPER AFR -ABOVE FINISHED ROOF MCA
(WITH ACCESS PANEL) -MINIMUM CIRCUIT AMPS SUCH AS OFFSETS IN PIPING OR DUCTWORK (INCLUDING DIVIDED DUCTWORK) NEEDED DUE TO
AHU -AIR HANDLING UNIT OBSTRUCTIONS OR INTERFERENCES SHALL BE PROVIDED AT NO ADDITIONAL COST. FOR PROJECTS
MOCP -MAXIMUM OVER CURRENT PROTECTION INVOLVING RENOVATION, COORDINATE NEW WORK WITH EXISTING ELEMENTS SUCH AS THE
-CEILING RETURN AP -ACCESS PANEL BUILDING STRUCTURE AND ARCHITECTURAL FEATURES, SPRINKLER PIPING, LIGHTS, PLUMBING, AND
-EXISTING FIRE DAMPER TO REMAIN MOD -MOTOR OPERATED CONTROL DAMPER (MOD)
ELECTRICAL CONDUIT.
BOP -BOTTOM OF PIPE NC
-CEILING EXHAUST -NORMALLY CLOSED
-TERMINAL UNIT, VARIABLE/CONSTANT AIR BHP 3. DUCT CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE
-EXISTING FIRE & SMOKE DAMPER TO REMAIN VOLUME, FAN POWERED -BRAKE HORSEPOWER NO -NORMALLY OPEN SMACNA HVAC DUCT CONSTRUCTION STANDARD.
-CEILING DIFFUSER, RECTANGULAR OR BTU -BRITISH THERMAL UNIT NTS -NOT TO SCALE
SQUARE NECK (CEILING DIFFUSERS 4. SEE SPECIFICATIONS FOR GAUGES, THICKNESS, BRACING, REQUIREMENTS, ETC., OF DUCTWORK.
h -CENTER LINE OA
ARE 4-WAY THROW UNO) SA-1 -SOUND ATTENUATOR -OUTSIDE AIR
c -CFM (CUBIC FEET PER MINUTE) 5. PROVIDE AIR TURNING VANES IN ALL 90 DEGREE RECTANGULAR DUCT ELBOWS.
-TERMINAL UNIT, VARIABLE/CONSTANT AIR OAL -OUTSIDE AIR LOUVER
-SUPPLY REGISTER OR GRILLE VOLUME, FAN POWERED, WITH ELECTRIC CD -CEILING DIFFUSER PRV -PRESSURE REDUCING VALVE 6. DUCT SIZES AND ALL OPENINGS THROUGH BUILDING CONSTRUCTION SHALL SUIT EQUIPMENT
(VERTICAL MOUNT, SIDEWALL) -MOTOR OPERATED CONTROL DAMPER (MOD) HEAT
CT FURNISHED.
-COOLING TOWER PRS
M -ELECTRIC DUCT HEATER -PRESSURE REDUCING STATION
-RETURN/EXHAUST REGISTER OR GRILLE CV -CONSTANT AIR VOLUME 7. COORDINATE DIFFUSER, GRILLE AND REGISTER LOCATIONS WITH ARCHITECTURAL
(W/ PANEL CLEARANCE) PSI -POUNDS PER SQUARE INCH
(VERTICAL MOUNT, SIDEWALL) -AIR FLOW MEASURING STATION REFLECTED CEILING PLANS AND EQUIPMENT OF ALL TRADES.
FM P -CHANGE IN PRESSURE PSIG -PSI GAUGE
1 -REVISION REFERENCE 8. LOCATE THERMOSTATS, TEMPERATURE SENSORS, HUMIDISTATS, AND HUMIDITY SENSORS AT 48"
T -CHANGE IN TEMPERATURE PTAC -PACKAGED TERMINAL AIR CONDITIONER ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. COORDINATE LOCATIONS WITH OTHER
-DETAIL REFERENCE: TOP-DETAIL#, -MANUAL BALANCING DAMPER
1 CFM -CUBIC FEET PER MINUTE EQUIPMENT, FURNITURE, AND DOOR SWINGS.
BOTTOM-DRAWING# SHOWN ON PVC -POLYVINYL CHLORIDE PIPE
M-1
-HYDRONIC REHEAT COIL CU -CONDENSING UNIT RA 9. ALL EQUIPMENT, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED AND/OR SPECIFIED. PROVIDE
-DOOR GRILLE -RETURN AIR
T -THERMOSTAT/TEMPERATURE SENSOR ADDITIONAL SUPPORTS AS REQUIRED TO PROVIDE A VIBRATION-FREE, RIGID INSTALLATION.
DDC -DIRECT DIGITAL CONTROLS RHC -REHEAT COIL
H -HUMIDISTAT/HUMIDITY SENSOR DN -DOWN 10. ALL DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.
RHP -ROOFTOP HEAT PUMP
-INLINE CENTRIFUGAL FAN

UC
-DUCT SMOKE DETECTOR -UNDERCUT DOOR EAT -ENTERING AIR TEMPERATURE RPM 11. DAMPERS AND INSIDES OF DUCTS VISIBLE THROUGH GRILLES, REGISTERS AND DIFFUSERS SHALL BE
-REVOLUTIONS PER MINUTE
ESP -EXTERNAL STATIC PRESSURE PAINTED FLAT BLACK.

Infrastructure Criteria Package - Drawings


RS/L -REFRIGERANT SUCTION & LIQUID LINES
E -CONNECT TO EXISTING
-ACCESS DOORS, VERTICAL OR HORIZONTAL -PACKAGED TERMINAL AIR CONDITIONER EWT -ENTERING WATER TEMPERATURE RTU -ROOFTOP AIR HANDLING UNIT
12. REFER TO TYPICAL DETAILS FOR PIPING AND INSTALLATION OF EQUIPMENT.
-DEMOLISH TO POINT INDICATED (PTAC)
FCU -FAN COIL UNIT SA 13. TRAPPED CONDENSATE DRAINS FROM ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED FOR
-SUPPLY AIR
-MOTORIZED CONTROL DAMPER FD -FIRE DAMPER PROPER DRAINAGE TO SUIT EQUIPMENT FURNISHED.
M -STAINLESS STEEL DUCTWORK SP -STATIC PRESSURE
UP DN
-CHANGE OF ELEVATION FF -FINAL FILTERS TSP 14. ACCESS PANELS IN DUCTWORK AND CEILINGS SHALL BE PROVIDED WHERE REQUIRED FOR
TS -TEMPERATURE SENSOR -TOTAL STATIC PRESSURE

Pinellas County Jail Phase I


OPERATION, BALANCING OR MAINTENANCE OF ALL MECHANICAL EQUIPMENT.
-FLEXIBLE CONNECTION FLA -FULL LOAD AMPS UNO -UNLESS NOTED OTHERWISE

114400 North 49th Street


P -PRESSURE SENSOR
-FLEXIBLE DUCT FPM 15. ALL DUCTWORK AND PIPING IS SHOWN SCHEMATICALLY. PROVIDE ALL TRANSITIONS, TURNING
-FEET PER MINUTE V/PH -VOLTS/PHASE VANES, ELBOWS, FITTINGS, ETC., TO ALLOW SMOOTH FLOWS. ALL SPLIT DUCT FITTINGS SHALL
BD -BACKDRAFT DAMPER 12x8 -FLAT OVAL DUCT
GPM -GALLONS PER MINUTE TRANSITION TO FULL SIZE OF THE SUM OF BOTH BRANCHES, UPSTREAM OF SPLIT.
VAV -VARIABLE AIR VOLUME

Pinellas County

Clearwater, FL.
0 -NEUTRAL RELATIVE PRESSURE -TRANSITION, CONCENTRIC KW -KILOWATT
VFD 16. PROVIDE CONCRETE HOUSEKEEPING PAD UNDER ALL FLOOR-MOUNTED EQUIPMENT. REFER TO
24x12 -VARIABLE FREQUENCY DRIVE
-NEW DUCTWORK, FIRST DIMENSION IS SIDE SHOWN LAT SPECIFICATIONS FOR DETAILED REQUIREMENTS.
+ -POSITIVE RELATIVE PRESSURE -LEAVING AIR TEMPERATURE
-TRANSITION, ECCENTRIC LWT -LEAVING WATER TEMPERATURE 17. VERIFY FINISH WITH ARCHITECT PRIOR TO PURCHASING GRILLES, REGISTERS, DIFFUSERS, LOUVERS
_ -NEGATIVE RELATIVE PRESSURE 24x12 -EXISTING DUCTWORK TO REMAIN AND OTHER AIR DISTRIBUTION DEVICES.

1 -SHEET NOTE CALLOUT 24x12 -EXISTING DUCTWORK TO BE REMOVED 10x8 -TRANSITION, SQUARE TO ROUND 18. PROVIDE FLEXIBLE DUCT CONNECTIONS ON ALL DUCTWORK CONNECTING TO EACH FAN, AIR
HANDLING UNITS, AND FAN COIL UNITS.
1 -SHEET NOTE CALLOUT 24x12
-DUCT ELBOW, POSITIVE PRESSURE (SUPPLY), FIRST 19. PROVIDE TRANSITIONS AT DIFFUSER NECKS AS REQUIRED TO MATCH SIZES OF FLEX DUCTS TO BE
-SQUARE THROAT TEE CONNECTED.
1 -SHEET NOTE CALLOUT
DOWN UP W/IN FLOOR DIMENSION INDICATES SIDE TO WHICH ARROW IS POINTING
20. INTERRUPTIONS TO EXISTING SERVICES SHALL BE SCHEDULED FOR TIMES OTHER THAN NORMAL
-CEILING MOUNTED ACCESS DOOR OPERATING HOURS (SUCH AS NIGHTS AND WEEKENDS). SUCH INTERRUPTIONS TO SERVICES SHALL
-DUCT ELBOW, EXHAUST NOT BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF THE OWNER'S REPRESENTATIVE AND
PROPER COORDINATION WITH OTHER TRADES. PRE-WORK SHALL BE PERFORMED TO MAKE THE
SHUTDOWN PERIOD AS BRIEF AS POSSIBLE.
-DUCT ELBOW, NEGATIVE PRESSURE, RETURN
12x8 -RADIUS TEE
21. ALL EQUIPMENT, DUCTWORK, ETC., TO BE REMOVED SHALL REMAIN PROPERTY OF THE OWNER OR
-DUCT ELBOW UP THROUGH ROOF OR SLAB ABOVE DISPOSED OF LEGALLY, AS DIRECTED BY OWNER.

D -RECTANGULAR DUCT SECTION UP, POSITIVE PRESSURE,


22. MAINTAIN CLEARANCE OF A MINIMUM OF 6" BETWEEN DUCTWORK, PIPING, EQUIPMENT, ETC., AND ALL
-RECTANGLE-TO-ROUND TAKE-OFF FIRE RATED AND FIRE/SMOKE RATED PARTITIONS, TO ALLOW FOR INSPECTIONS OF RATED WALLS.
SUPPLY OR OUTSIDE AIR
23. LOCATE ALL OUTSIDE AIR INTAKES A MINIMUM OF 10' CLEAR FROM ALL PLUMBING VENTS AND
-RECTANGULAR DUCT SECTION UP, EXHAUST AIR DISCHARGE LOCATIONS.
NEGATIVE PRESSURE, RETURN
-STANDARD BRANCH TAKE-OFF
-RECTANGULAR DUCT SECTION UP, EXHAUST 24. DUCT RUNOUTS TO DIFFUSERS SHALL MATCH THE SIZE OF THE DIFFUSER NECK.

25. WATER PRESSURE DROPS THROUGH COIL CONTROL VALVES SHALL NOT EXCEED 5 PSI.
-ROUND DUCT SECTION UP -SPIN-IN TAKE-OFF
26. UNLESS OTHERWISE NOTED, ALL EQUIPMENT AND VALVE DRAINS SHALL BE INDEPENDENTLY PIPED
-FLAT OVAL DUCT SECTION UP FULL SIZE TO THE NEAREST PLUMBING DRAIN.
-SQUARE THROAT ELBOW
W/TURNING VANES 27. SLEEVE AND SEAL ALL PIPING PENETRATIONS THROUGH BUILDING PARTITIONS. PROVIDE MANUAL AIR
VENTS AT ALL HIGH POINTS IN CHILLED WATER AND HOT WATER PIPING.

28. PIPING, DUCTWORK, LEAK PROTECTION APPARATUS, OR OTHER EQUIPMENT FOREIGN TO ELECTRICAL
SWITCHBOARDS, PANELBOARDS, DISTRIBUTION BOARDS, OR MOTOR CONTROL CENTERS SHALL NOT
-RADIUS ELBOW
BE INSTALLED WITHIN THE REQUIRED SPACE FOR WORKING CLEARANCES OR DEDICATED SPACES OF
THE ELECTRICAL EQUIPMENT, EXTENDING IN FRONT OF AND FROM FLOOR TO STRUCTURAL CEILING SEAL
WITH A WIDTH AND DEPTH OF THE ELECTRICAL EQUIPMENT IN ACCORDANCE WITH NEC-110.26.

-RECTANGULAR/ROUND BRANCH TAKE-OFF


OR ROUND/ROUND BRANCH TAKE-OFF

PRELIMINARY DOCUMENTS
-EXHAUST DUCT UP THROUGH SLAB W/ NOT FOR CONSTRUCTION
FAN ON ROOF ABOVE

-EXHAUST FAN ON ROOF W/ DUCT DOWN


THROUGH ROOF

KEY PLAN
C

HVAC PIPING SYMBOL LEGEND HVAC EQUIPMENT TAGS


SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION
TAG

EQUIP. A 200 -AIR DISTRIBUTION DEVICE


CWS -FLOW DIRECTION - P-TRAP
-CONDENSER WATER SUPPLY
CFM
CWR -CONDENSER WATER RETURN -GATE VALVE
-TWO-WAY CHECK VALVE SCALE
CHWS -CHILLED WATER SUPPLY -BALL VALVE
MV AHU NUMBER
CHWR -CHILLED WATER RETURN -MANUAL VENT
-CALIBRATING BALANCING VALVE
AHU-1 -AIR HANDLING UNIT
CD -CONDENSATE -BUTTERFLY VALVE
12" = 1'-0"
CR -CONDENSATE RETURN -PRESSURE GAUGE
-GAS COCK
PC -PUMPED CONDENSATE -RELIEF VALVE
-UNION AHU NUMBER COIL NUMBER
HWR -HOT WATER RETURN
-STRAINER FM -FLOW METER -REHEAT COIL
RHC-1-1
HWS -HOT WATER SUPPLY
-CONTROL VALVE M -WATER METER
HPS -HIGH PRESSURE STEAM SUPPLY
S VARIABLE/CONSTANT AIR VOLUME TERMINAL UNITS
-SOLENOID VALVE -INLINE PUMP
MPS -MEDIUM PRESSURE STEAM SUPPLY
TERMINAL UNIT TYPE
-PSI REG. AHU NUMBER
LPS -LOW PRESSURE STEAM SUPPLY -INLINE PUMP VTU - VARIABLE TERMINAL UNIT
B -CHECK VALVE CTU - CONSTANT TERMINAL UNIT TERMINAL NUMBER
HPR -HIGH PRESSURE STEAM RETURN -VALVE ON RISER PTU - PARALLEL TERMINAL UNIT
VTU-1-1
STU - SERIES TERMINAL UNIT
MPR -MEDIUM PRESSURE STEAM RETURN -FLOW SWITCH -CAP

LPR -LOW PRESSURE STEAM RETURN -SLOPE DIRECTION (DOWN) -CONNECTION, BOTTOM

RL -CONNECTION, TOP
-REFRIGERANT LIQUID -FLEX CONNECTION No. Description Date
-COUPLING
RS -REFRIGERANT SUCTION
-O.S.&Y. GATE VALVE -ELBOW, 90° REVISIONS
-TEE, OUTLET DOWN
-STEAM TRAP -ELBOW, 45°
-TEE, OUTLET UP DRAWN BY HAT
D D -THREE-WAY CONTROL VALVE -ELBOW, TURNED DOWN
APPROVED BY LTE
-45° PIPE RISE (R) / DROP (D)
-ELBOW, TURNED UP
CHECKED BY LTE
-PIPE ANCHORS -THERMOMETER
DATE 03/19/2014
-CONCENTRIC REDUCER

-ECCENTRIC REDUCER TITLE

MECHANICAL
LEGEND
A
NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT
PROJECT NO. 50057109

M-000
SHEET NO.
6 5 4 3 2 1

Dewberry Architects Inc.

401 SW Water St.


Suite 701
Peoria, IL 61602
309.282.8000 Phone
309.282.8001 Fax

SAFE HARBOR

GENERAL NOTES:

1. ALL EXISTING, PLASTIC CHILLED WATER PIPING SHALL BE


DEMOLISHED/ABANDONED. ANY METALLIC BRANCH PIPING
THAT IS CONNECTED TO PLASTIC MAIN PIPE SHALL BE
DISCONNECTED FROM THE PLASTIC PIPE. METAL ENDS SHALL
BE CAPPED AND LEFT IN SUITABLE CONDITION FOR
CONNECTION TO NEW, METALLIC UNDERGROUND CHILLED
WATER LINES. CONTRACTOR TO VERIFY WHERE PLASTIC PIPE
ENDS AND METAL PIPE BEGINS.

2. FINAL PIPE SIZE TO BE DETERMINED BY FINAL DESIGN BUILD


(N)CHWS/R BRANCH TO CONTRACTOR.
NEW BUILDING

(N)CHWS/R BRANCH TO
NEW BUILDING

Infrastructure Criteria Package - Drawings


(N)CHWS/R DISTRIBUTION
E

AYO
(N)CHWS/R DISTRIBUTION

SB
(E)4" CHWS/R

Pinellas County Jail Phase I


(E)4" CHWS/R

114400 North 49th Street


OS
"M1"
(E)6" CHWS/R (E)6" CHWS/R

CR

Pinellas County

Clearwater, FL.
(E)1" BALL VALVES
(N) CHWS/R DISTRIBUTION
HEALTH CARE FACILITY 145TH AVE N
"B"
(E)4" CHWS/R (E) CHWS/R
(E)8" CHWS/R VALVE BOX

"A"
SHERIFF ADMIN.
(E)4" CHWS/R

2' V ALLEY GU TTER


(E)4" CHWS/R

"C"
"M2"
D (E)3" CHWS/R

49TH ST N
(E)3" CHWS/R

(E)8" CHWS/R

142ND AVE N
(N) 20" CHWS/R DISTRIBUTION RUN PARALLEL TO EXISTING
PIPING SERVING CENTRAL/INTAKE AND HOUSING A-G SEAL

(E) CHWS/R CENTRAL DIVISION POND


POND

PRELIMINARY DOCUMENTS
NOT FOR CONSTRUCTION

PINELLAS COUNTY KEY PLAN


C
SOUTH DIVISION CRIMINAL COURT
(E) CHWS/R (N)CHWS/R PIPING BRIDGED OVER TO
COMPLEX
"G"
STATE ATTORNEY/ CJC CENTER

POND POND

"F" "E" "D" "C" SCALE


MAINTENANCE

1" = 100'-0"

SIR LB021
(FI R 1/2" LB1344 0.30' S., 0.50' W.)

OHE OHE OHE

LAND LINE
JURISDICT IONAL WET

No. Description Date

REVISIONS

DRAWN BY HAT

APPROVED BY LTE

CHECKED BY LTE

DATE 03/19/2014
JUVENILE DETENTION CENTER TITLE

MECHANICAL SITE
EDGE OF W ATER
PLAN
A
ASPHALT WALK

EDGE OF W ATER
PROJECT NO. 50057109
FIR 1/2" LB1344

140TH AVE N
1
MECHANICAL SITE PLAN M-001
Scale: 1" = 100'-0"
SHEET NO.
6 5 4 3 2 1

Keynotes
1 AREA TO BE PROVIDED WITH DEDICATED CHILLED
WATER FAN COIL UNIT. Dewberry Architects Inc.
2 AREA TO BE EXHAUSTED. FAN TO BE CHEMICAL
RATED. 401 SW Water St.
Suite 701
3 AREA TO BE EXHAUSTED.
Peoria, IL 61602
4 VAV BOX WITH ELECTRIC HEAT. PROVIDE ACCESS 309.282.8000 Phone
PANEL AS REQUIRED. 309.282.8001 Fax
5 PROVIDE LINT TRAP.
6 DRYER EXHAUST FAN. ROUTE TO EXTERIOR WALL.
F 7 COMBUSTION AIR MAKE UP FAN. ROUTE TO
EXTERIOR WALL.

1 1.1 3 5 6.9 7

USED OIL TANK NEW OIL TANK

A A
S
A.1 A.1

BULK DRY PROGRAM PROGRAM


STORAGE MEETING ROOM MEETING ROOM WORKER
STAGING

Infrastructure Criteria Package - Drawings


108 110 116
E 122

Pinellas County Jail Phase I


LOADING
DOCK 3

114400 North 49th Street


105 INMATE
TOILET
121
PROGRAM

Pinellas County

Clearwater, FL.
MEETING ROOM SEARCH
111 123
DOCK 4
STAGING
STORAGE
107

T
T T

B JANITOR B
114 3
3
T
STORAGE 4 INMATE
TOILET
4
BULK REFIG 112
SECURITY 1 SALLYPORT INMATE STAFF 119
ELECTRONICS SERVICE DRIVE STORAGE TOILET 4 4
JANITOR 109
101 DOCK 103 142 113 118
STORAGE 3 3
102 T 3 T
D S S

STAIR
A
SA1
MEDIUM PRESSURE SUPPLY DUCT ESTIMATED 80x30

FEC FEC
C

WATER
HEATER
124
CO AND NO2 SENSORS LINKED TO ALARM
1 STAIR
ELEVATOR CART ELEVATOR ELEVATOR B
A OFFICE/ WASH ELECTRICAL B C SB1
EA 139 140 EB EC
137

SEAL
C C
3

STAFF
TOILET PRELIMINARY DOCUMENTS
125
NOT FOR CONSTRUCTION

AIR
1
COMPRESSOR
GARBAGE/ 126
RECYCLE DOCK KEY PLAN
C 106 3

UTILITY
TRASH COMPACTOR
WASH
136

CLEAN LAUNDRY
STORAGE
135
T CENTRAL SCALE
LAUNDRY
138

D D
1/8" = 1'-0"
4
T
S
STORAGE DRYERS
134 127
PARKING AREA

WATER TANK
STORAGE MAINTENANCE
SUPPLY
104 T
133
B S
7
4

T T
RISER INMATE
ROOM UNIFORM TOILET CHEMICAL
132 BREAK 129 STORAGE
STORAGE ROOM
6 5 No. Description Date
131 128
130 3 2
E.9 REVISIONS
E.9

H
2448 2448

C
DRAWN BY HAT
F F
APPROVED BY LTE

CHECKED BY LTE

DATE 03/19/2014

TITLE

FIRST FLOOR
1 1.1 3 5 6.9 7
MECHANICAL
PLAN
A FIRST FLOOR MECHANICAL PLAN
1 Scale: 1/8" = 1'-0"
PROJECT NO. 50057109

M-110
SHEET NO.
6 5 4 3 2 1

Keynotes
1 ROUTE EXHAUST DUCTWORK, APPROXIMATELY 60x20, TO
KITCHEN HOODS. COORDINATE WITH KITCHEN
DESIGNER. Dewberry Architects Inc.
2 ROUTE MAKE UP DUCTWORK, APPROXIMATELY 50x20, TO
KITCHEN EQUIPMENT. COORDINATE WITH KITCHEN 401 SW Water St.
DESIGNER. Suite 701
3 ROUTE SUPPLY AND DUCTING TO MECHANICAL CHASE. Peoria, IL 61602
4 AREA TO BE EXHAUSTED. 309.282.8000 Phone
5 AREA TO BE EXHAUSTED. FAN TO BE CHEMICAL RATED. 309.282.8001 Fax
6 AREA TO BE PROVIDED WITH DEDICATED CHILLED
F WATER FAN COIL UNIT.
7 REFRIGERATER/ FREEZER AREA. SEE KITCHEN
EQUIPMENT PLANS.

1 1.1 3 5 6.9 7

A H
C H
A
C

A.1 CHEMICAL STORAGE A.1


(SECURE)
5 216
DRY FOOD
STORAGE
204 SECURED
STORAGE BREAK
209 ROOM

Infrastructure Criteria Package - Drawings


211 WARE WASH
E AREA
215
4

Pinellas County Jail Phase I


STORAGE/
CORRIDOR
FUTURE LINK
212

114400 North 49th Street


217

CORRIDOR

Pinellas County

Clearwater, FL.
4 210
INMATE

H
TOILET 6

C
H
208

C
KITCHEN/LAUNDRY JAN/EQUIP EQUIPMENT
STORAGE SUPPLIES STORAGE OFFICE TRAY
201 202 203 213 MAKE-UP
INMATE 220
TOILET
B 207 B
FOOD SERVICE
UNIFORM 4 MGMT OFFICE
205 214
STORAGE
CART STORAGE

C
STAFF 218
TOILET AND WASHING
206 219
4
4

D STAIR
A CORRIDOR
SA2 CORRIDOR 221
250

FEC 6 FEC

4
4
DAIRY STAIR
JAN COLDROOM TRASH ELEVATOR ICE/BEV. ELEVATOR ELEVATOR B
249 247 HOLDING A 234 ELEC B C SB2

D
246 EA 233 EB EC

D
C D2

C1
D2

C1
C
SEAL
BULK PRODUCE
COLDROOM E1 E1
3
E2 E2

248
G G
D1 D1

STAFF DINING
MULTI-PURPOSE
HOT FOOD
232 CORRIDOR
PRELIMINARY DOCUMENTS
PRODUCTION
235 222 NOT FOR CONSTRUCTION
FINISH PRODUCE

#321.6R
CORRIDOR
COLDROOM

G
251
245

G
G G

1075 CFM
.27" S.P.
12"X12"
1648 CFM
.47" S.P.
12"X11"
2 3
FOOD PREP

G
G
SERVICE AREA SERVING
KEY PLAN
C

#321.6L
230 231

CO N TRO L
BULK MEAT

STEAM

VALVE
FIRE CABINET

R
D
COLDROOM

#321.2R

.27" S.P.

R
937 CFM

G G
12"X12"
242

SAFET Y VA LVE

.07" S.P.
538 CFM
9"X8"
1456 CFM
.39" S.P.
12"X10"
CO N TRO L
STEAM

VALVE
SATE
1/ 2" N PT

RETU RN

TRAP AN D ST RAI N ER
STEAM CO N DEN SATE
12"X9"CO N DEN
1217 CFM
.37" S.P.

R
D
SAFET Y VA LVE

R
1379 CFM
.42" S.P.
12"X10"
.27" S.P.
937 CFM
12"X12"

FINISHED BULK

CO N TRO L
STEAM

VALVE
1216 CFM
CO N DEN SATE
1/ 2" N PT

RETU RN

.37" S.P.

TRAP AN D ST RAI N ER
STEAM CO N DEN SATE
X9"
COLDROOM

12"
243
SAFET Y VA LVE

.27" S.P.
937 CFM
12"X12"
#321.1L

1
CO N TRO L
RETU RN STEAM
VALVE
CO N DEN SATE
1/ 2" N PT

TRAP AN D ST RAI N ER
STEAM CO N DEN SATE

C
JAN

#321.2L
.20" S.P.
809 CFM
12"X10"

SAFET Y VA LVE

C
.27" S.P.
937 CFM
G

12"X12"
228
C D

SCALE
CO N TRO L

D
D D
STEAM

VALVE
1012 CFM
.29" S.P.

C
11"X8"

CO N DEN SATE
1/ 2" N PT

TRAP AN D ST RAI N ER
STEAM CO N DEN SATE
RETU RN

1353 CFM
.43" S.P.
12"X10"

H
APPROXIMATE RETURN DUCT SIZE 70x24
G

SAFET Y VA LVE

C
BULK
1011 CFM
.29" S.P.
11"X8"

THAW/PULL 1/8" = 1'-0"


DEN SATE
1/ 2" N PT

STEAM CO N DEN SATE


RN

TRAP AN D ST RAI N ER
12"X10"CO N RETU

H C
G G

COLDROOM 4
1352 CFM
.43" S.P.

241
FAUCET, TANGENT DRAW-OFF

242
ARE OPTIONAL
#321.1R
.20" S.P.
809 CFM
12"X10"

.27" S.P.
937 CFM
12"X12"

4
G

MULTI-PURPOSE
FIRE CABINET

STAFF

C
D

D
TOILET 223
227

CORRIDOR
STAFF 4 229
APPROXIMATE SUPPLY DUCT SIZE 96x24 TOILET
226
H

B
C
H

FINISH MEAT FINISH VEG DAILY DRY

MIC MIC
-20 FREEZER -10 FREEZER
C

REF
240 239 PREP PREP STORAGE
238 237 236
A/V

REF
CLOSET
224 6

No. Description Date


E.9 E.9
C C
H H
REVISIONS
F F
7 DRAWN BY HAT
CONNECTOR TO APPROVED BY LTE
CENTRAL TOWER
CN
CHECKED BY LTE

DATE 03/19/2014

TITLE

1 1.1 3 5 6.9 7 SECOND FLOOR


MECHANICAL
SECOND FLOOR MECHANICAL PLAN PLAN
1 Scale: 1/8" = 1'-0"
A

PROJECT NO. 50057109

M-120
SHEET NO.
6 5 4 3 2 1

Keynotes
1 GENERATOR RADIATOR. PIPE TO AND FROM
GENERATOR.
2 THREE- WAY CATALYST INSTALLED ON EXHAUST GAS
PIPE.
Dewberry Architects Inc.
3 ROUTE EXHAUST GAS PIPE SHORTEST DISTANCE TO
ABSORPTION CHILLER.
401 SW Water St.
4 NEW CHILLED WATER FAN COIL UNIT. ROUTE OUTSIDE
AIR THROUGH ROOF. COORDINATE ROOF PENETRATIONS
Suite 701
WITH STRUCTURAL. Peoria, IL 61602
309.282.8000 Phone
5 AREA TO BE PROVIDED WITH DEDICATED CHILLED
309.282.8001 Fax
WATER FAN COIL UNIT.
6 AREA TO BE EXHAUSTED.
F 7 ROOFTOP CHILLED WATER AIR HANDLER. PROVIDE
MANUFACTURER'S CLEARANCES. SUPPLY AND RETURN
DUCTING PENETRATIONS TO BE COORDINATED WITH
STRUCTURE.
8 ROOFTOP MAKE UP FAN FOR KITCHEN EQUIPMENT.
COORDINATE WITH KITCHEN DESIGNER. COORDINATE
ROOF PENETRATIONS WITH STRUCTURAL.
9 ROOFTOP EXHAUST FAN FOR KITCHEN EQUIPMENT.
COORDINATE WITH KITCHEN DESIGNER. COORDINATE
ROOF PENETRATIONS WITH STRUCTURAL.
10 ROUTE ABSORPTION CHILLER EXHAUST THROUGH ROOF
TO MUFFLER. COORDINATE ROOF PENETRATIONS WITH
STRUCTURAL.
11 PROVIDE DEDICATED DX/ CHILLED WATER UNIT FOR
ELEVATOR MACHINE ROOM.
1 1.1 3 5 6.9 7 12 ACOUSTICAL TREATED WALL. PROVIDE ACOUSTICAL
WRAP FOR PIPING PENETRATIONS.
13 REFRIGERANT PURGE SYSTEM FAN.
14 PROVIDE OUTSIDE AIR DROP FOR PURGE SYSTEM.

13
14
A A

A.1 CWP- CHWP- CWP-2 CHWP-2 CWP-1 CHWP-1 A.1

Infrastructure Criteria Package - Drawings


FUTURE FUTURE ABS ABS ABS ABS
E ABS ABS
CONTROL
CONFERENCE RM
313
FUTURE ELECTRIC CHILLER ELECTRIC CHILLER ELECTRIC CHILLER
CONTROL

Pinellas County Jail Phase I


SYS PUMP FUTURE SYS PUMP ROOM
302

114400 North 49th Street


FUTURE ABSORPTION CHILLER
ABSORPTION CHILLER
CHW FAN COIL
REF

Pinellas County

Clearwater, FL.
OFFICE
4301
10 10

4 REF
B B
CHW FAN COIL
5
STAIR
A STAFF
TOILET VESTIBULE
SA3 CWP- FUTURE
305 303
D 6

CHWP-FUTURE
CHW FAN COIL
ELEVATOR
LOBBY
STAIR
B
CWP-3 CHWP-3 CWP- 2 CHWP-2 CWP-1 CHWP-1
WATER CHW FAN COIL SB3
4
TREATMENT AND
CHW/ DX FAN COIL CHW FAN COIL HYDRONIC
CHW FAN COIL
SPECIALTIES AREA I.T.
GENERATOR ROOM
ELEVATOR CONTROL
COUPON RACK AND ELEVATOR 3065
5
A 310 309 CHEMICALS C
EA CHEMICAL EC
STORAGE SEAL
11 4 SHOT FEEDER &
PUMPS
ELECTRICAL
C C
312
PRELIMINARY DOCUMENTS
LAUNDRY CHW AHU NOT FOR CONSTRUCTION

KEY PLAN
C
8
7
1
2

GAS ENGINE
SCALE
9
3

1/8" = 1'-0"
D GENERATOR D
ROOM KITCHEN CHW AHU
EXTERIOR EXTERIOR
ROOF 311 ROOF
ER1 ER2

1 2

7
B

FUTURE GAS ENGINE

KITCHEN EQUIPMENT
3 No. Description Date
CONDENSING UNIT
REVISIONS

DRAWN BY HAT
E.9 12 E.9
APPROVED BY LTE

F F CHECKED BY LTE

DATE 03/19/2014
20" CHWS/R PIPING TO SOUTH CAMPUS.
SEE STRUCTURAL AND ARCHITECTURAL FOR ROUTING.
TITLE

THIRD FLOOR
MECHANICAL
1 1.1 3 5 6.9 7 PLAN
A
THIRD FLOOR PIPING PLAN PROJECT NO. 50057109
1 Scale: 1/8" = 1'-0"

M-130
SHEET NO.
6 5 4 3 2 1

Dewberry Architects Inc.


Keynotes
1 ROUTE CONDENSER PIPING FROM TOWER 401 SW Water St.
THROUGH ROOF SLAB TO PUMP LOCATED IN Suite 701
MECHANICAL ROOM. COORDINATE ROOF Peoria, IL 61602
PENETRATION WITH STRUCTURAL. 309.282.8000 Phone
2 GENERATOR ROOM INTAKE FAN. COORDINATE 309.282.8001 Fax
FAN WITH STRUCTURE. PROVIDE PENTHOUSE.
PROVIDE SILENCERS AS REQUIRED.
F 3 GENERATOR ROOM EXHAUST FAN.
COORDINATE FAN WITH STRUCTURE. PROVIDE
PENTHOUSE. PROVIDE SILENCERS AS
REQUIRED.
4 ABSORPTION CHILLER MUFFLER AND
SILENCER. PROVIDE HEAT RECOVERY SYSTEM.

1 1.1 3 5 6.9 7

A A

A.1 MUFFLER FUTURE MUFFLER A.1

Infrastructure Criteria Package - Drawings


E

Pinellas County Jail Phase I

114400 North 49th Street


4
4

Pinellas County

Clearwater, FL.
1
FUTURE 2-CELL 1 1 (2) SINGLE-CELL COOLING TOWERS
COOLING TOWER (ABSORPTION CHILLERS)
2-CELL COOLING TOWER 2-CELL COOLING TOWER 1
(ELECTRIC CHILLER) (1) FUTURE
(ELECTRIC CHILLER) (ELECTRIC CHILLER)
B B

STAIR
A
SA4

SEAL

C C

1 PRELIMINARY DOCUMENTS
STAIR
B NOT FOR CONSTRUCTION
SB4

KEY PLAN
C
2 3

SCALE

D D 1/8" = 1'-0"

2
3
B

No. Description Date


FUTURE SUPPLY FAN FUTURE EXHAUST FAN
REVISIONS

E.9 E.9
DRAWN BY HAT

F F APPROVED BY LTE

CHECKED BY LTE

DATE 03/19/2014

TITLE

ROOF
1 1.1 3 5 6.9 7 MECHANICAL
PLAN
A ROOF PIPING PLAN
1 Scale: 1/8" = 1'-0"
PROJECT NO. 50057109

M-140
SHEET NO.
6 5 4 3 2 1

Dewberry Architects Inc.

401 SW Water St.


Suite 701
Peoria, IL 61602
309.282.8000 Phone
309.282.8001 Fax

PIPING SYMBOL LEGEND


-FLOW DIRECTION

-GATE VALVE

-BALL VALVE

-CALIBRATING BALANCING VALVE

-BUTTERFLY VALVE

-GAS COCK

-UNION

-STRAINER

Infrastructure Criteria Package - Drawings


E -CONTROL VALVE

-CHECK VALVE

-FLOW SWITCH

Pinellas County Jail Phase I


-FLEX CONNECTION

114400 North 49th Street


-O.S.&Y. GATE VALVE

-THREE-WAY CONTROL VALVE

Pinellas County

Clearwater, FL.
-THERMOMETER

-TWO-WAY CHECK VALVE

-RELIEF VALVE

FUTURE ABSORPTION CHWP


MV
-MANUAL VENT

ABSORPTION CHWP
BYPASS

FUTURE CHWP
EXPANSION TANK -PRESSURE GAUGE

FM -FLOW METER

CHWP-2

CHWP-1
M -WATER METER

-INLINE PUMP

-INLINE PUMP
D FUTURE CHILLER

FROM BLDG

AIR SEPARATOR

TO BLDG.

FUTURE SYSTEM PUMP

SEAL
CH-2

PRELIMINARY DOCUMENTS
NOT FOR CONSTRUCTION
SYSTEM PUMP

KEY PLAN
C

CH-1

SCALE

NOT TO SCALE

ABSORPTION CHILLER

FUTURE ABSORPTION CHILLER


No. Description Date

REVISIONS

DRAWN BY HAT
CHILLED WATER PIPING DIAGRAM 1 APPROVED BY LTE
No Scale
CHECKED BY LTE

DATE 03/19/2014

TITLE

MECHANICAL
DIAGRAMS
A

PROJECT NO. 50057109

M-200
SHEET NO.
6 5 4 3 2 1

Dewberry Architects Inc.

401 SW Water St.


Suite 701
Peoria, IL 61602
309.282.8000 Phone
309.282.8001 Fax

PIPING SYMBOL LEGEND


-FLOW DIRECTION

-GATE VALVE

-BALL VALVE

-CALIBRATING BALANCING VALVE

-BUTTERFLY VALVE

-GAS COCK

-UNION

Infrastructure Criteria Package - Drawings


E -STRAINER

-CONTROL VALVE

-CHECK VALVE

-FLOW SWITCH

Pinellas County Jail Phase I


-FLEX CONNECTION

114400 North 49th Street


-O.S.&Y. GATE VALVE

Pinellas County

Clearwater, FL.
-THREE-WAY CONTROL VALVE

-THERMOMETER
CT-ABSORPTION FUTURE CT-ABSORPTION CT-1 CT-2 CT-FUTURE
-TWO-WAY CHECK VALVE

-RELIEF VALVE

MV
-MANUAL VENT

-PRESSURE GAUGE

FM -FLOW METER

M -WATER METER

-INLINE PUMP

D -INLINE PUMP

FUTURE
CWP-ABSORPTION CWP-ABSORPTION

CWP-1 CWP-2 CWP- FUTURE

FUTURE CHILLER CH-2 CH-1 SEAL

PRELIMINARY DOCUMENTS
NOT FOR CONSTRUCTION

KEY PLAN
C

ABSORPTION CHILLER

SCALE

FUTURE ABSORPTION CHILLER

NOT TO SCALE

No. Description Date

REVISIONS

DRAWN BY HAT

CONDENSER WATER PIPING DIAGRAM 1 APPROVED BY LTE

No Scale CHECKED BY LTE

DATE 03/19/2014

TITLE

MECHANICAL
DIAGRAMS
A

PROJECT NO. 50057109

M-201
SHEET NO.
6 5 4 3 2 1

Dewberry Architects Inc.

401 SW Water St.


Suite 701
Peoria, IL 61602
309.282.8000 Phone
309.282.8001 Fax

REFER TO P201, DETAIL 9 FOR FURTHER DETAIL

PLUMBING SYSTEM
TO FROM

SILENCER

Infrastructure Criteria Package - Drawings


HEAT RECOVERY RECIRC PUMP
E
HOT EXHAUST GAS

Pinellas County Jail Phase I


HEAT RECOVERY HEAT EXCHANGER, SHELL IN TUBE

114400 North 49th Street


EXHAUST BYPASS VALVE
NO NO
FLEX CONNECTION (TYP)
NC ENGINE HIGH TEMP RADIATOR

Pinellas County

Clearwater, FL.
NATURAL GAS
ABSORPTION CHILLER GENSET

3-WAY CATALYTIC HIGH TEMP PUMP RETURN TEMPERAURE


REGULATING 3-WAY VALVE

EXPANSION TANK

COGENERATOR DIAGRAM 1
No Scale

SEAL

PRELIMINARY DOCUMENTS
NOT FOR CONSTRUCTION

KEY PLAN
C

FUTURE EXPANSION TANK ON TOP OF RADIATOR EXPANSION TANK ON TOP OF RADIATOR


SCALE
MOUNT HEAT EXCHANGER AS CLOSE
FLOW LIMITING AS POSSIBLE TO RADIATOR.
12" MAX. VALVES
NOT TO SCALE
TYPICAL FLEXIBLE CONNECTIONS
HOT WATER PIPING PIPING TO PLUMBING SYSTEM
(200 F.) OFF THE DUAL ENGINES SEE PLUMBING FOR CONTINUATION REFER TO P201, DETAIL 9 FOR FURTHER DETAIL

TYPICAL SHUT-OFF VALVE


RADIATOR HEAT EXCHANGER
12" MAX.

No. Description Date

REVISIONS

DRAWN BY HAT

COGENERATOR DIAGRAM 2 APPROVED BY LTE

No Scale CHECKED BY LTE

DATE 03/19/2014

TITLE

MECHANICAL
DIAGRAMS
A

PROJECT NO. 50057109

M-202
SHEET NO.
6 5 4 3 2 1

Dewberry Architects Inc.

401 SW Water St.


Suite 701
Peoria, IL 61602
309.282.8000 Phone
309.282.8001 Fax

F AUTOMATIC FLOW
CONTROL
DEVICE PRESET BY MANUF.
W/ P & T TEST PORTS, EXTENDED OPERATOR
STRAINER, AND DRAIN. THREE WAY SPIN-IN FITTING W/VOLUME ON BALANCE DAMPER
(PRE-MANUF. SINGLE CONTROL CONTROL DAMPER (INSUL.
ASSEMBLY ACCEPTABLE) VALVE PER SPEC.)
MANUAL AIR VENT
W/AUTO
DRAW BAND
SHUT-OFF COCK STEEL RODS W/THREADED
COIL THREADED CAP, HAND TIGHTENED
ENDS (TYP. 4 PLACES)
(PRE-MANUF. SINGLE SUPPORT FROM STRUCTURE
ASSEMBLY ACCEPTABLE) ABOVE AS REQUIRED PROVIDE WITH FILTER
OVER OPENING
THREADED CAP WITH 1/4" DIA. SPRING VIB. ISOLATORS
RETURN HOLE DRILLED IN TOP, HAND
UNION TIGHTENED. FLEXIBLE DUCT MAX.
8'-0" IN LENGTH FLEX CONN. (TYP.)
COOLING COIL
FULLY EXTENDED.

SA RA
FAN
SUPPLY PLUG
COCK

B
SHUT-OFF VALVE (TYP.) A DRAW BAND
DRAIN PAN
SLOPE TO DRAIN BLANK-OFF PLATES
P/T TEST PORTS

C
CASING SLEEVE WHERE REQUIRED FLOAT SWITCH
AIR FLOW DIFFUSER NECK (INSUL. PER SPEC.)
STRAINER W / BLOWDOWN

Infrastructure Criteria Package - Drawings


PRESSURE GAUGE &
E COCK (TYP.) DIFFUSER CONE (INSUL. PER SPEC.)
UNION (TYP.)
SNUBBER CONDENSATE DRAIN PIPING DIMENSIONS:
THERMOMETER W/SEPARABLE WELL (TYP.) CEILING TEE ROUTE MAIN CONDENSATE CEILING
A = FULL SIZE OF UNIT DRAIN CONNECTION LINE TO FLOOR DRAIN
B > 1-1/2" TIMES FAN SUCTION STATIC PRESSURE

Pinellas County Jail Phase I


BALL VALVE C > FAN DISCHARGE STATIC PRESSURE PLUS 1/2" INCH GALVANIZED SHEET METAL SECONDARY

114400 North 49th Street


DRAIN PAN TO EXTEND 3" BEYOND UNIT
FLEX. CONNECTION (TYP.) COORDINATE MOUNTING/CURB HEIGHT AS REQUIRED TO PROVIDE PROPER CONDENSATE DRAINAGE. ON ALL SIDES BY 1-1/2" DEEP
NOTES: 1. PROVIDE (4 x DIA.) OF STRAIGHT PIPE ON BOTH SIDES OF LIGHT

Pinellas County

Clearwater, FL.
BALANCING VALVE
2. ALL COMPONENTS FULL LINE SIZE UNLESS NOTED OTHERWISE
3. LOCATE UNIONS TO ALLOW FOR COIL PULL

3-WAY COIL PIPING DIAGRAM (FCU-4)


NOT TO SCALE
1 AHU CONDENSATE DRAIN TRAP
NOT TO SCALE
2 DIFFUSER MOUNTING
NOT TO SCALE
3 FAN COIL UNIT
NOT TO SCALE
4

D GEAR W/HAND WHEEL


5" AND LARGER
LEVER LATH HANDLE TAP, TYPICAL 45
W/MEMORY STOP DEGREE BOOT
4" AND SMALLER
DAMPER, TYPICAL
PRESSURE GAUGE MANUAL BALANCING
BUTTERFLY
TOP OF DUCT TO BE VALVE (TYP.)
THREE LAYERS OF 5/8" GYPBOARD, REFER
AS HIGH AS POSSIBLE SNUBBER
TO SPECIFICATION SECTION 15910

BALL VALVE DIFFERENTIAL


EXTEND TREATMENT
ACROSS OPEN CEILING PRESSURE
DRAW BAND
SEE PLAN DRWGS. P/T PORT W/BLOWDOWN TRANSMITTER
VALVE (TYP.) NON-SLAM CHECK
VALVE
SEAL
FLEXIBLE CONNECTER
SUPPLY
SILENCER DUCT
DIAMETER TO MATCH FLEXIBLE
SYSTEM PIPING CONNECTOR
DIAMETER PRELIMINARY DOCUMENTS
NOT FOR CONSTRUCTION
SUCTION DIFFUSER W/INTEGRAL s" PUMP DRAIN, FLEXIBLE DUCT
STRAINER & 3/4" BLOW DOWN EXTEND TO FLOOR
VALVE. EXTEND TO NEAREST NEAREST DRAIN
FLOOR DRAIN SPIN-IN FITTING W/VOLUME RADIUS ELBOWS MAY
CONTROL DAMPER (INSUL. PER BE USED IN LIEU OF KEY PLAN
C PIPE SUPPORT SPEC. REQ'D.) SQUARE ELBOWS

WALL

DIAMETER TO MATCH PUMP PIPE SUPPORT CONCRETE


INLET DIAMETER HOUSEKEEPING
PAD

NOISE CONTROL TREATMENT AT DUCT SILENCER


NOT TO SCALE
5 SPLIT-CASE DOUBLE SUCTION PUMP
NOT TO SCALE
6 TYPICAL FLEX DUCT CONNECTION
NOT TO SCALE
7 TYPICAL PRESSURE DUCTWORK
NOT TO SCALE
8
SCALE

NOT TO SCALE
VALVES ABOVE TUBE
PULL (TYP.)
ACTUATOR & VALVE
BY CONTROLS
LUG TYPE BUTTERFLY
CONTRACTOR (TYP.)
VALVE W/GEAR
OPERATOR (TYP.) TEMP. SENSOR
PROVIDE NEW REMOTE A (TYP.)
ANALOG OUTPUT 120 VAC ALARM WIRING PER ALARM BEACON
DIFFERENTIAL PRESSURE A
WIRING ASHRAE 15 TO EMS OUTSIDE ALL
BEACON CHILLER ROOM SENSOR/TRANSMITTER
ENTRY DOORS (TYP.)

CWS
B
R OOF

CHWR
THERMOMETER (TYP.)

CWR
CHILLER DIFFERENTIAL PRESSURE

CHWS
SWITCH TO CHILLER CONTROL PANEL
PRESSURE GAUGE W/
REFRIGERANT SNUBBER & BALL
ROCK FREE BACKFILL MONITOR VALVES (TYP.)
PANEL SAMPLE LINES
CONNECT NEW FLEXIBLE
RELIEF PIPING TO CONNECTOR
EXISTING RELIEF No. Description Date
RELIEF VENT
PIPING HEADER.
1'-0" MIN.

FLEX CONNECTION RELIEF PIPING SHALL BE SIZED


SUPPORT TO AND INSTALLED IN ACCORDANCE REVISIONS
COLUMN OR
PITTWRAP JACKETING WITH ASHRAE STANDARD 15.
WALL CONTROL
MINIMUM RELIEF PIPING SIZE DRAWN BY HAT
PANEL
TO CHILLER INDICATED ON FLOOR PLAN.
FLANGED JOINT
FOAMGLASS INSULATION RESETTING RELIEF ASSEMBLY DEVIATION FROM SIZE INDICATED CONDENSER APPROVED BY LTE
BY EQUIPMENT MANUFACTURER IS ACCEPTABLE ONLY AFTER
SAMPLE TUBE
SAND BACKFILL RECOMMENDATION FROM CHECKED BY LTE
TO CONTROL
6".

CHILLER MANUFACTURER AND


6" MIN. PANEL
COMPRESSION APPROVAL OF THE ENGINEER. DATE 03/19/2014
COUPLING
COORDINATE RELIEF PIPING VIBRATION ISOLATION
NOTES:
6" MIN.

SPRINGS (TYP.) EVAPORATOR TITLE


1. PROVIDE REFRIGERANT MONITOR CAPABLE OF FULL SIZE OF VENT REQUIREMENTS WITH CHILLER
SENSING R-123 REFRIGERANT. FILTER CHILLER OPENING (MIN.) OR AS MANUFACTURER.
PIPE HOUSEKEEPING
2.
3.
NEW EXHAUST FAN.
PROVIDE TWO REFRIGERANT SAMPLE LINES I
COMPRESSOR
SUCTION
CODE REQUIRES
PAD
FLANGED ELBOW W/
MECHANICAL
LOCATIONS AS SHOWN ON PLANS.
DETAILS
6".

CONNECTION LIFT PLATE (TYP.)


12" TO 18" FLOOR SLAB
GRAVEL
FLOOR
MECHANICAL JOINT (SIMILIAR PETE'S PLUG (TYP.)
r" FL x r" NPT DRAIN
TO A VICTAULIC COUPLING)
A 6" MINIMUM VALVE (5'-0" ABOVE FLR.)

PROJECT NO. 50057109

UNDERGROUND PIPING INSTALLATION


NOT TO SCALE
9 REFRIGERANT MONITORING
NOT TO SCALE
10 RELIEF PIPING
NOT TO SCALE
11 WATER COOLED CHILLER
NOT TO SCALE
12 M-300
SHEET NO.