Areamaster™ Generation 2 LED Luminaire

Floodlight for Hazardous Locations

NEC/CEC: NEC/CEC: ATEX/IECEx:


Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2 and 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T5

Applications
• Enclosed and gasketed fixtures suitable for use in:
— A wide range of industrial, chemical processing and other
areas where flammable gases and vapors are present, for
example
— Oil and Gas Refineries
— Petrochemical Plants
— Foundries
— Drilling Rigs
— Pulp and Paper Mills
— Food and Beverage Processing Facilities
— Loading Docks
— Power Plants
— Water and Wastewater Treatment Facilities
— Other areas where corrosive, wet, dirty and tough
environments are a problem
• IP66/IP67, Type 4X, marine and wet locations
• Locations requiring dependable, consistent lighting in extreme
hot/cold temperature environments. -40°C to +65°C
(-40°F to +149°F) ambient temperature range
Features
• Three lumen outputs provide up to 19,500 lumens.

Nominal Wattage Efficacy HID Model
Lumens  (W) (lpw) Equivalent Number
9,500 70 136 175W-250W AMLGL6

LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed



15,000 110 136 250W-400W AMLGL7
19,500 150 130 400W-750W AMLGL8

 Nominal lumen value for 5000K, detailed lumen information
provided in tables. Standard Materials
• Choice of optics for optimal light distribution in a variety of • Housing and lens door: copperfree (4/10 of 1% max.) aluminum
applications. • Gaskets: silicone rubber
• Separate field wiring compartment with screw terminal block for • Yoke: zinc plated HR steel
easy and secure connection (can accept UL/CSA 26-10AWG). • Bolts: stainless steel
• Two 3/4” NPT entries provided. • Close up plugs: (1) aluminum provided
• Yoke bracket is designed to accommodate traditional • Guard and safety cable: stainless steel
Areamaster brackets and slipfitters for easy retrofit. • Visor: Aluminum
• Choice of color temperature (CCT); 5000K cool white or 3000K
warm white.
Standard Finishes
• Rugged and compact housing with superior thermal design • Housing, lens cover, visor and yoke mount: architectural bronze
translates to long luminaire life. polyester
• Heavy duty, high temperature silicone rubber gaskets. Related Products
• Thermal shock and impact resistant clear or frosted glass lens.
• Round Tapered Steel Poles
• Standard 6KV surge protection.
• Hinged Steel Poled
• Captive fasteners secure one piece lens.
• Square Tapered Steel Poles
• Field replaceable LED driver and lens cover.
• Square Steel Poles
Options • Floodlight Mounting Brackets
• Improved safety cable design with multiple retention points, NEC/CEC Certifications and Compliances
purchase separately
• UL Standards:
• Guard and visor available, purchase separately
— UL844, Luminaires for Use in Hazardous Locations
• Slip-fitters and mounting brackets available for easy pole or
— UL1598, Luminaires
wall mounting
— UL1598A, Luminaires for Installation on Marine Vessels
• 10KV Surge Protection
— UL 8750, LED Equipment for Use in Lighting Products
• CSA Standards:
— CSA C22.2 No. 250.0, Luminaires
— CSA C22.2 No. 137, Luminaires for Use in Hazardous
Locations
• cCSAus: 164460, Certificate Number: 70073611

Visit our website at www.emerson.com or contact us at (800) 621-1506. 261


© April 2018
Areamaster™ Generation 2 LED Luminaire
Floodlight for Hazardous Locations
NEC/CEC: NEC/CEC: ATEX/IECEx:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2 and 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T5

ATEX/IECEx Certifications and Compliances DesignLights™ Consortium (for the following models)
• Certification Type: Areamaster Gen 2 • All models pending.
— Gas: Zone 2
– Conforming to ATEX 2014/34/EU: II 3 G
– Type of Protection: Ex ec IIC Gc
– Temperature Class: T5 to T3
— Dust: Zone 22
– Conforming to ATEX 2014/34/EU: II 3 D
– Type of Protection: Ex tc IIIC Dc
– Surface Temperature: +85°C to +100°C (+185°F to +212°F)
• Ambient Temperature: -40°C up to +65°C (-40°F up to +268°F)
• EU Declaration of Conformity: 50317
• ATEX Certificate: SIRA 17ATEX3241
• IECEx Certificate: IECEx SIR 17.0079
• Index of Protection according EN/IEC 60529: IP66
• Impact Resistance (shock): IK10
• Photobiological Safety, IEC 62778 and IEC 62471: RG0

Order using catalog numbering guides below or select catalog number from tables on following pages.
AMLG L7 C G 7 BU S

Series: Color Temp CCT: Beam Spread: Options:


LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed

AMLG: C - 5000K 6 - 7x7 (non-optic) F - Fusing 


Areamaster 2 LED W - 3000K  7 - 7x6 S - 10 KV Surge
Lumen Level : Diffusion: Voltage: Protection 
L6 - 9K G - Clear Glass BU - 120-277 Vac M - M20 Metric
L7 - 15K F - Frosted Glass  50/60 Hz,
L8 - 19K D - Diffused 170-300Vdc
Polycarbonate  BH - 347-480Vac
50/60 Hz 

Lumen Output Tables :


Lumen Output for Clear Glass Lens
AMLGL6 AMLGL7 AMLGL8
NEMA 7x7 (Non Optic),
9,900 15,300 19,900
5000K CCT, CRI 70
NEMA 7x6, 3000K CCT, CRI 80 8,100 11,900 15,500
NEMA 7x6, 5000K CCT, CRI 70 9,000 14,200 18,400

Lumen Output for Frosted Glass Lens


AMLGL6 AMLGL7 AMLGL8
NEMA 7x7 (Non Optic),
8,000 12,600 16,300
5000K CCT

 3000K CCT (warm) is not available with NEMA 7x7 light pattern
 Frosted Glass is only available with NEMA 7x7 light pattern
 Use of fuse voids Marine rating. Fusing not available for NEC/CEC.
 All lumen values are typical (tolerance +/-10%).
 BH voltage available for NEC/CEC only.
 10 KV Surge Protection available for NEC/CEC only.
 Diffused polycarbonate available for NEC/CEC only.

262 Visit our website at www.emerson.com or contact us at (800) 621-1506.


© April 2018
Areamaster™ Generation 2 LED Luminaire
Floodlight for Hazardous Locations
NEC/CEC: NEC/CEC: ATEX/IECEx:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2 and 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T5

Electrical Ratings 
Input Current Total Harmonic
Voltage Suffix Voltage (V) Input Power (Watts) (Amps) Power Factor (PF) Distortion (THD) Model Number
120 Vac 73 0.62
>.9 <20%
277 Vac 71 0.27
BU
170 Vdc 69 0.41
N/A N/A AMLGL6
300 Vdc 68 0.23
347 Vac 71 0.21
BH >.9 <20%
480 Vac 71 0.16
120 Vac 111 0.94
>.9 <20%
277 Vac 106 0.43
BU
170 Vdc 113 0.67
N/A N/A AMLGL7
300 Vdc 111 0.37
347 Vac 115 0.33
BH >.9 <20%
480 Vac 115 0.25
120 Vac 154 1.30
>.9 <20%
277 Vac 146 0.56
BU
170 Vdc 156 0.92

LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed


N/A N/A AMLGL8
300 Vdc 152 0.51
347 Vac 150 0.43
BH >.9 <20%
480 Vac 149 0.32

Frontal Projected Area Drag Coefficient Effective Projected Area


Luminaire Category Image (FPA) ft2 (DC) (EPA) = FPA*DC ft2

90° to Ground-Worst
1.52 1.20 1.82
Case Mounting
Wind Direction

45° to Ground-Standard
1.07 1.2 1.28
Mounting

Wind Direction

Surge Protection: Integral 6KV surge protection. Option for up to 10KV surge protection. (cCSAus only).
 All ratings are typical.

Visit our website at www.emerson.com or contact us at (800) 621-1506. 263


© April 2018
Areamaster™ Generation 2 LED Luminaire
Floodlight for Hazardous Locations

NEC/CEC: NEC/CEC: ATEX/IECEx:


Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2 and 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T5

NEC/CEC Temperature Codes


Lamp Gas Dust
Class I Division
Ambient Supply Wire Class I, Class II, 2 and
Temperature Temperature Division 2  Class I, Zone 2 Division 1 Zone 20, Class 2 Model
Line Voltage °C (°F) °C (°F) Groups A, B, C, D Group IIC Groups E,F,G Group IIIC Division I Number
40 (104) 90 (194) T5 T5 T6 T6 T4A
120-277 Vac/
170-300 Vdc; 55 (131) 90 (194) T4A T4 T6 T6 T4A AMLGL6
347-480 Vac
65 (149) 90 (194) T4A T4 T6 T6 T4
40 (104) 90 (194) T4A T4 T6 T6 T4
120-277 Vac/
170-300 Vdc; 55 (131) 90 (194) T3C T3 T6 T6 T3C AMLGL7
347-480 Vac
65 (149) 90 (194) T3C T3 T5 T5 T3C
40 (104) 90 (194) T3C T3 T6 T6 T3C
120-277 Vac/
170-300 Vdc; 55 (131) 90 (194) T3B T3 T5 T5 T3A AMLGL8
347-480 Vac
65 (149) 90 (194) T3A T3 T5 T5 T3A

ATEX/IECEx Temperature Codes


Gas Dust
T Rating Surface Temperature
LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed

Ta= +40 °C Ta= +55 °C Ta= +65 °C Ta= +40 °C Ta= +55 °C Ta= +65 °C Model
(+104 °F) (+131 °F) (+149 °F) (+104 °F) (+131 °F) (+149 °F) Number
T5 T4 T4 T85°C T85°C T85°C AMLGL6
T4 T3 T3 T85°C T85°C T100°C AMLGL7
T3 T3 T3 T85°C T100°C T100°C AMLGL8

“T” Numbers Represent the Maximum Internal Temperature  or Maximum Surface Temperature 
NEC/CEC
“T” # T1 350 325 T2 T2A T2B T2C T2D T3 T3A T3B T3C T4 T4A T5 T6
Temp. 351- 326- 301- 281- 261- 231- 216- 201- 181- 166- 161- 136- 121- 101- 86-
85
450 350 325 300 280 260 230 215 200 180 165 160 135 120 100
Range
(664- (619- (574- (538- (502- (448- (421- (394- (358- (331- (322- (277- (250- (214- (187-
ºC (˚ºF) (185)
842) 662) 617) 572) 536) 500) 446) 419) 392) 356) 329) 320) 275) 248) 212)
ATEX/IECEx
“T” # T1 T2 T3 T4 T5 T6
Temp. 86-
301-450 201-300 136-200 101-135 85
100
Range
(187-
ºC (˚ºF) (547-842) (394-572) (277-392) (214-275) (185)
212)

 T numbers represent the maximum internal temperature for Class I, Division 2 and Class I, Zone 2 locations designated by the NEC.
 T numbers represent the maximum surface temperature under a dust blanket for Class II, Division 1 and 2 as designated by the NEC.

264 Visit our website at www.emerson.com or contact us at (800) 621-1506.


© April 2018
Areamaster™ Generation 2 LED Luminaire
Floodlight for Hazardous Locations

NEC/CEC: NEC/CEC: ATEX/IECEx:


Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2 and 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T5

Lumen Efficacy Optical Catalog


CCT Output Wattage (lm/W) Pattern Number 
Clear Glass
120-277 Vac/170-300 Vdc
5000K (cool white) 9900 70 141 NEMA 7x7 (150°x150°) AMLGL6CG6BU
5000K (cool white) 9000 70 129 NEMA 7x6 (136°x113°) AMLGL6CG7BU
3000K (warm white) 8100 70 116 NEMA 7x6 (136°x113°) AMLGL6WG7BU
5000K (cool white) 15300 111 138 NEMA 7x7 (150°x150°) AMLGL7CG6BU
5000K (cool white) 14200 111 128 NEMA 7x6 (136°x113°) AMLGL7CG7BU
3000K (warm white) 11900 111 107 NEMA 7x6 (136°x113°) AMLGL7WG7BU
5000K (cool white) 19900 158 126 NEMA 7x7 (150°x150°) AMLGL8CG6BU
5000K (cool white) 18400 158 116 NEMA 7x6 (136°x113°) AMLGL8CG7BU
3000K (warm white) 15500 158 98 NEMA 7x6 (136°x113°) AMLGL8WG7BU
347-480 Vac
5000K (cool white) 9900 71 139 NEMA 7x7 (150°x150°) AMLGL6CG6BH
5000K (cool white) 9000 71 127 NEMA 7x6 (136°x113°) AMLGL6CG7BH
3000K (warm white) 8100 71 114 NEMA 7x6 (136°x113°) AMLGL6WG7BH

LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed


5000K (cool white) 15300 115 133 NEMA 7x7 (150°x150°) AMLGL7CG6BH
5000K (cool white) 14200 115 123 NEMA 7x6 (136°x113°) AMLGL7CG7BH
3000K (warm white) 11900 109 109 NEMA 7x6 (136°x113°) AMLGL7WG7BH
5000K (cool white) 19900 157 127 NEMA 7x7 (150°x150°) AMLGL8CG6BH
5000K (cool white) 18400 157 117 NEMA 7x6 (136°x113°) AMLGL8CG7BH
3000K (warm white) 15500 150 103 NEMA 7x6 (136°x113°) AMLGL8WG7BH
Frosted Glass
120-277 Vac/170-300 Vdc
5000K (cool white) 8100 70 116 NEMA 7x7 (150°x150°) AMLGL6CF6BU
5000K (cool white) 12700 111 114 NEMA 7x7 (150°x150°) AMLGL7CF6BU
5000K (cool white) 16500 158 104 NEMA 7x7 (150°x150°) AMLGL8CF6BU
347-480 Vac
5000K (cool white) 8100 71 114 NEMA 7x7 (150°x150°) AMLGL6CF6BH
5000K (cool white) 12700 115 110 NEMA 7x7 (150°x150°) AMLGL7CF6BH
5000K (cool white) 16500 157 105 NEMA 7x7 (150x150) AMLGL8CF6BH

 For Fusing option, add suffix F to end of part number, example AMLGL8CG6BUF.
For 10KV surge protection, add suffix S to end of part number, example AMLGL7CG7BUS.
For both Fusing and 10KV surge, add suffix FS to end of part number, example AMLGL8CG7BUFS.

Visit our website at www.emerson.com or contact us at (800) 621-1506. 265


© April 2018
Areamaster™ Generation 2 LED Luminaire
Floodlight for Hazardous Locations

NEC/CEC: NEC/CEC: ATEX/IECEx:


Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2 and 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T5

Accessories and Replacement Parts

Description Catalog Number


Crossarm Mounting Bracket

Has 180° horizontal adjustment — degree marked. Facilitates


mounting floodlight to crossarm or other flat surface, or to G-AM-
G-AM-8-CA
8-WB. Includes floodlight yoke bolts. Malleable iron, zinc plated,
chromate sealed, architectural bronze polyester finish.

Pipe or Wall Mount Bracket

Used with G-AM-8-CA. Clamps to 1” to 2-1/2” pipe, vertical


or horizontal, or mounts on flat surfaces. Includes U-bolt and
G-AM-8-WB
crossarm bracket bolts. Malleable iron, zinc plated, chromate
sealed, with architectural bronze polyester finish.
LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed

Crossarm Mounting Bracket (G-AM-8-CA) used with Pipe or Wall Mount Bracket (G-AM-8-WB).
Poletop Slip-Fitter

Slip-fits 1-1/2” or 2” pipe size poletop tenons. Includes floodlight


yoke bolts, 3 locking bolts, and cord grip. Body is malleable iron-
G-SF20
zinc plated, chromate sealed, with cast aluminum cap. Assembly
has architectural bronze polyester finish.

Slip-fits 1" or 1-1/2” pipe size poletop tenons. Includes floodlight


yoke bolts, 3 locking bolts, and cord grip. Body is malleable iron-
AMLEDSF1
zinc plated, chromate sealed, with cast aluminum cap. Assembly
has architectural bronze polyester finish.

Poletop Slip-Fitter

Slip-fits 2” or 2-1/2” poletop tenons. Includes floodlight yoke


bolts, 3 locking bolts, and cord grip. Malleable iron, zinc plated, G-AM-8-SF
chromate sealed, with architectural bronze polyester finish.

266 Visit our website at www.emerson.com or contact us at (800) 621-1506.


© April 2018
Areamaster™ Generation 2 LED Luminaire
Floodlight for Hazardous Locations

NEC/CEC: NEC/CEC: ATEX/IECEx:


Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2 and 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T5

Accessories and Replacement Parts


Description Catalog Number
Wall Mount Bracket

Used with G-AM-8-SF and GSF-20 to provide a wall mounting


GPSWB6GAL
option. Galvanized Steel.

Wire Guard

Stainless steel. LGGUARD

Safety Cable

Stainless steel. LEDSC

LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed


Visor

Steel with architectural bronze polyester finish. For Dark Sky


AMLGV
Friendly design.

Portable Floodlight Base

Portable floodlight base for temporary lighting applications. To be


used with wire guard. G-AM-PFB
Malleable iron with architectural bronze polyester finish.

Replacement Covers

AMLGCLEAR

AMLGFROST

Visit our website at www.emerson.com or contact us at (800) 621-1506. 267


© April 2018
Areamaster™ Generation 2 LED Luminaire
Floodlight for Hazardous Locations

NEC/CEC: NEC/CEC: ATEX/IECEx:


Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2 and 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T5

Replacement Drivers
Driver Constant
Voltage Wattage Current Setting Luminaire Model CCT Catalog Number

BU AMLGL6C, APMS100C105UD41
100 watt 410mA 5K and 3K
BH AMLGL6W APMS100C105HD41

BU APMS150C105UD65
150 watt 650mA AMLGL7W 3K
BH APMS150C105HD65
BU APMS150C105UD68
150 watt 680mA AMLGL7C 5k
BH APMS150C105HD68
BU APMS150C105UD89
150 watt 890mA AMLGL8W 3K
BH APMS150C105HD89
BU APMS150C105UD93
150 watt 930mA AMLGL8C 5k
BH APMS150C105HD93

Areamaster Generation 2 Accessory Weights


LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed

Description Weight in kg (lbs)


AMLGL6, AMLGL7, AMLGL8 Luminaires 9.8 (21.6)
Yoke Bracket 1.41 (3.1)
Visor 0.2 (0.4)
Guard 0.2 (0.4)
Safety Cable 0.2 (0.4)
Crossarm Mounting Bracket G-AM-8-CA 1.4 (3.1)
Pipe or Wall Mount Bracket G-AM-8-WB 2.9 (6.4)
Poletop Slip-Fitter GSF20 1.4 (3.1)
Poletop Slip-Fitter AMLEDSF1 2.4 (5.3)
Poletop Slip-Fitter GAM8SF —
— —

268 Visit our website at www.emerson.com or contact us at (800) 621-1506.


© April 2018
Areamaster™ Generation 2 LED Luminaire
Floodlight for Hazardous Locations
NEC/CEC: NEC/CEC: ATEX/IECEx:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2 and 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T5

Dimensions in Millimeters (Inches)


Floodlight
128.3 mm
328.7 mm (5.05 in)
(12.94 in)

156.5 mm
(6.16 in) 351.5 mm
413.5 mm Square (13.84 in)
(16.28 in)

(4) Yoke
Bolts

152.4 mm
Conduit Entry Yoke (6.00 in)
57.2 mm

LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed


(2.25 in)

44.5 mm
(1.75 in) (3) Mounting Holes 152.4 mm (6.00 in) Turning Radius
Ø 14 mm (0.56 in) 180° Rotation
88.9 mm
(3.5 in)

(4) 1/4-20 UNC-2B Thread

(2) Hubs for 3/4” NPT Conduit

Visit our website at www.emerson.com or contact us at (800) 621-1506. 269


© April 2018
Areamaster™ Generation 2 LED Luminaire
Floodlight for Hazardous Locations
NEC/CEC: NEC/CEC: ATEX/IECEx:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2 and 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T5

Photometric Data — DATA SHOWN IS ABSOLUTE


NEMA 7x7, Clear Glass
REPORT NUMBER: AMLGL6CG6BU
Luminaire Lumens 9,964

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary

Efficiency Lumens Horizontal Spread Vertical Spread


3 2 1 0 1 2 3 4 Field (10%) 98.5% 9,817.4 150 148
180° 170° 160° 150° 140° Beam (50%) 82.2% 8,196.6 117.3 116.2
3,400
3
2,833
Total 100% 9,964.0
130°
2
2,267
Tilt Angle- 45 Degree LLF-0.9
120°
1
1,700

110°
1,133 0 Forward Throw Distance
567 100°
1
Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
90°
Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
0
2 6 (20) 1.51 14 (45) 11 (35) 7 (24) 3 (11)
567 80° 9 (30) 0.68 14 (47) 11 (36) 6 (21) —
3
1,133
70° 12 (40) 0.38 15 (50) 11 (35) — —
1,700 4
60°
2,267
20 fc 1fc
2,833 50° 10 fc 0.5 fc Side-to-Side Distance
5 fc 0.2 fc Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
3,400 2.5 fc 0.1 fc
LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed

0° 10° 20° 30° 40° Height m (ft) m (ft) m (ft) m (ft) m (ft)
Point of Max FC: 10.02
6 (20) 20 (66) 15 (50) 12 (38) 5 (16)
-0° H -22.5° H
-90° H -45° H 9 (30) 24 (78) 15 (50) 9 (28) —
-67.5° H 12 (40) 21 (70) 12 (40) — —

NEMA 7x7, Frosted Glass


REPORT NUMBER: AMLGL6CF6BU
Luminaire Lumens 8,115

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary

Efficiency Lumens Horizontal Spread Vertical Spread


180° 170° 160° 150° 140° 3 2 1 0 1 2 3 4 Field (10%) 98.1% 7,961.7 155.3 151.5
3,100
Beam (50%) 71.5% 5,804.1 105.8 105.5
2,583 130° 3
Total 100% 8,112.2
2,067 2
120° Tilt Angle- 45 Degree LLF-0.9
1,550
1

1,033 110°
0
Forward Throw Distance
100°
517 Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
0 90°
1
Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
6 (20) 2.49 13 (42) 10 (33) 7 (24) 2 (8)
517 80° 2
9 (30) 1.1 14 (45) 10 (32) 5 (15) —
1,033
70° 3 12 (40) 0.62 15 (48) 8 (25) — —
1,550
60° 4
2,067

2,583 20 fc 1fc Side-to-Side Distance


50°
10 fc 0.5 fc Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
3,100 5 fc 0.2 fc
0° 10° 20° 30° 40° 2 fc 0.1 fc Height m (ft) m (ft) m (ft) m (ft) m (ft)
6 (20) 18 (60) 13 (44) 9 (30) 1 (4)
-0° H -22.5° H 9 (30) 20 (64) 10 (34) 6 (20) —
-90° H -45° H 12 (40) 17 (56) 9 (30) — —
-67.5° H

270 Visit our website at www.emerson.com or contact us at (800) 621-1506.


© April 2018
Areamaster™ Generation 2 LED Luminaire
Floodlight for Hazardous Locations

NEC/CEC: NEC/CEC: ATEX/IECEx:


Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2 and 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T5

Photometric Data — DATA SHOWN IS ABSOLUTE


NEMA 7x7, Clear Glass
REPORT NUMBER: AMLGL7CG6BU

Luminaire Lumens 15,320

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary

3 2 1 0 1 2 3 4
Efficiency Lumens Horizontal Spread Vertical Spread
180° 170° 160° 150° 140° Field (10%) 98.5% 15,102.6 151.2 147
5,300
3 Beam (50%) 81.9% 12,555.7 117 115.4
4,417 130° Total 100% 15,320.4
2
3,533
120° 1 Tilt Angle- 45 Degree LLF-0.9
2,650

1,767 110° 0
Forward Throw Distance
100°
883
1 Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
0 90° Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
2
6 (20) 4.42 15 (50) 12 (39) 9 (29) 5 (16)
883 80°
3
9 (30) 1.97 17 (55) 13 (43) 8 (25) —
1,767
70° 12 (40) 1.11 17 (57) 12 (40) 6 (19) —
2,650 4
60°
3,533
20 fc 1fc
4,417 50° 10 fc 0.5 fc Side-to-Side Distance
5 fc 0.2 fc Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx

LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed


5,300 2.5 fc 0.1 fc
0° 10° 20° 30° 40° Height m (ft) m (ft) m (ft) m (ft) m (ft)
Point of Max FC: 10.02
6 (20) 21 (70) 56 (17) 12 (40) 6 (20)
-0° H -22.5° H 9 (30) 24 (80) 58 (18) 12 (38) —
-90° H -45° H 12 (40) 24 (80) 50 (15) 5 (16) —
-67.5° H

NEMA 7x7, Frosted Glass


REPORT NUMBER: AMLGL7CF6BU
Luminaire Lumens 12,782

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary

Efficiency Lumens Horizontal Spread Vertical Spread


180° 170° 160° 150° 140°
4,900 3 2 1 0 1 2 3 4 Field (10%) 98.1% 12,536.1 155.4 150.7
4,083 130°
Beam (50%) 71.3% 9,112.8 105.4 105.6
3
Total 100% 12,777.9
3,267
120° 2
2,450 Tilt Angle- 45 Degree LLF-0.9
1
1,633 110°

0
Forward Throw Distance
817 100°
Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
0 90° 1
Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
817 80°
6 (20) 2.91 18 (59) 14 (45) 11 (35) 7 (22)
2
9 (30) 1.29 19 (63) 16 (51) 10 (33) 4 (12)
1,633
70° 3 12 (40) 0.73 21 (70) 15 (50) 9 (30) —
2,450
60° 4
3,267

4,083 20 fc 1fc Side-to-Side Distance


50°
10 fc 0.5 fc Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
5 fc 0.2 fc
4,900
0° 10° 20° 30° 40° 2 fc 0.1 fc Height m (ft) m (ft) m (ft) m (ft) m (ft)
6 (20) 26 (84) 21 (70) 16 (52) 10 (32)
-0° H -22.5° H 9 (30) 29 (96) 22 (72) 16 (54) 5 (15)
-90° H -45° H 12 (40) 32 (104) 22 (72) 15 (48) —
-67.5° H

Visit our website at www.emerson.com or contact us at (800) 621-1506. 271


© April 2018
Areamaster™ Generation 2 LED Luminaire
Floodlight for Hazardous Locations

NEC/CEC: NEC/CEC: ATEX/IECEx:


Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2 and 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T5

Photometric Data — DATA SHOWN IS ABSOLUTE


NEMA 7x7, Clear Glass
REPORT NUMBER: AMLGL8CG6BU

Luminaire Lumens 19,895

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary

Efficiency Lumens Horizontal Spread Vertical Spread


180° 170° 160° 150° 140°
6,900
4 3 2 1 0 1 2 3 4 5
Field (10%) 98.6% 19,614.8 151 146.8
5
5,750 130° Beam (50%) 81.7% 16,267.6 116.7 115.2
4 Total 100% 19,895.4
4,600
3
120°
3,450
2
Tilt Angle- 45 Degree LLF-0.9
2,300 110°
1
1,150 100° Forward Throw Distance
0
90°
Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
0
1 Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
1,150 80°
2
6 (20) 3.18 13 (44) 11 (36) 9 (30) 5 (16)
2,300
70°
9 (30) 1.41 16 (53) 13 (42) 8 (27) —
3
3,450
12 (40) 0.81 17 (56) 12 (40) — —
60° 4
4,600
5
5,750 50° Side-to-Side Distance
6,900
20 fc 1fc Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed

0° 10° 20° 30° 40° 10 fc 0.5 fc


5 fc 0.2 fc Height m (ft) m (ft) m (ft) m (ft) m (ft)
2.5 fc 0.1 fc 6 (20) 26 (84) 20 (64) 13 (44) 5 (16)
-0° H -22.5° H
-90° H -45° H Point of Max FC: 10.02 9 (30) 27 (90) 20 (66) 11 (36) —
-67.5° H 12 (40) 29 (96) 17 (56) — —

NEMA 7x7, Frosted Glass


REPORT NUMBER: AMLGL8CF6BU
Luminaire Lumens 16,503

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary

Efficiency Lumens Horizontal Spread Vertical Spread


180° 170° 160° 150° 140° Field (10%) 98.1% 16,189.8 155.3 150.7
6,400 3 2 1 0 1 2 3 4
Beam (50%) 71.3% 11,766.7 105.2 105.5
5,333 130° 3 Total 100% 16,498.6
4,267
120° 2
3,200 Tilt Angle- 45 Degree LLF-0.9
1
2,133 110°
Forward Throw Distance
1,067 100° 0
Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
0 90° 1 Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
1,067 80° 6 (20) 5.76 17 (55) 11 (36) 10 (32) 6 (20)
2
9 (30) 2.56 16 (53) 9 (31) 9 (31) —
2,133
70°
3 12 (40) 1.43 17 (56) 19 (62) 9 (29) —
3,200
60°
4,267 4

5,333 50° 20 fc 1fc Side-to-Side Distance


6,400
10 fc 0.5 fc Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
5 fc 0.2 fc
0° 10° 20° 30° 40°
2 fc 0.1 fc Height m (ft) m (ft) m (ft) m (ft) m (ft)
6 (20) 24 (78) 18 (60) 13 (44) 7 (22)
-0° H -22.5° H 9 (30) 27 (88) 19 (62) 10 (34) —
-90° H -45° H
12 (40) 30 (98) 18 (58) 12 (38) —
-67.5° H

272 Visit our website at www.emerson.com or contact us at (800) 621-1506.


© April 2018
Areamaster™ Generation 2 LED Luminaire
Floodlight for Hazardous Locations

NEC/CEC: NEC/CEC: ATEX/IECEx:


Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2 and 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T5

Photometric Data — DATA SHOWN IS ABSOLUTE


NEMA 7x6, Clear Glass
REPORT NUMBER: AMLGL6CG7BU

Luminaire Lumens 9,086

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary

180° 170° 160° 150° 140° 0


Efficiency Lumens Horizontal Spread Vertical Spread
2 1 1 2 3
5,500 3
Field (10%) 96.2% 8,738.1 134.9 112.1
4,583 130° Beam (50%) 62% 5,631.5 120.5 45.2
3,667
2
Total 100% 9,086.2
120°
2,750
1 Tilt Angle- 45 Degree LLF-0.9
1,833 110°

917 100° 0
Forward Throw Distance
0 90° Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
1 Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
917 80°
6 (20) 2.92 13 (42) 11 (36) 9 (28) 5 (15)
1,833
70° 2 9 (30) 1.3 16 (53) 13 (42) 7 (24) —
2,750 12 (40) 0.73 17 (56) 11 (36) — —
60°
3
3,667

4,583 50° 20 fc 1fc


10 fc 0.5 fc
Side-to-Side Distance
5,500
5 fc 0.2 fc Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx

LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed


0° 10° 20° 30° 40°
2 fc 0.1 fc Height m (ft) m (ft) m (ft) m (ft) m (ft)
6 (20) 24 (80) Point
20 of Max FC: 10.02
(64) 13 (44) 5 (16)
-0° H -22.5° H
-90° H -45° H 9 (30) 26 (84) 18 (60) 11 (36) —
-67.5° H 12 (40) 27 (88) 15 (48) — —

NEMA 7x6, Clear Glass


REPORT NUMBER: AMLGL6WG7BU

Luminaire Lumens 8,111

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary

Efficiency Lumens Horizontal Spread Vertical Spread


2 1 0 1 2 3
180° 170° 160° 150° 140° 3
Field (10%) 96.1% 7,798.3 135.3 112
5,000
Beam (50%) 61.5% 4,987.0 119.9 45
4,167 130° 2
Total 100% 8,111.0
3,333
120° 1
2,500 Tilt Angle- 45 Degree LLF-0.9
1,667 110° 0
Forward Throw Distance
833 100°
1 Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
0 90° Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
833 80° 2 6 (20) 2.92 13 (42) 11 (36) 9 (28) 5 (15)
9 (30) 1.30 16 (53) 13 (42) 7 (24) —
1,667
70° 3 12 (40) 0.73 17 (56) 11 (36) — —
2,500
60° 20 fc 1fc
3,333 10 fc 0.5 fc
5 fc 0.2 fc Side-to-Side Distance
4,167 50° 2 fc 0.1 fc
Mounting 0.5fc/5lx 1fc/11lx
Point 2fc/22lx
of Max FC: 10.02 5fc/54lx
5,000
0° 10° 20° 30° 40° Height m (ft) m (ft) m (ft) m (ft) m (ft)
6 (20) 24 (80) 20 (64) 13 (44) 5 (16)
-0° H -22.5° H 9 (30) 26 (84) 18 (60) 11 (36) —
-90° H -45° H
12 (40) 27 (88) 15 (48) — —
-67.5° H

Visit our website at www.emerson.com or contact us at (800) 621-1506. 273


© April 2018
Areamaster™ Generation 2 LED Luminaire
Floodlight for Hazardous Locations

NEC/CEC: NEC/CEC: ATEX/IECEx:


Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2 and 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T5

Photometric Data — DATA SHOWN IS ABSOLUTE


NEMA 7x6, Clear Glass
REPORT NUMBER: AMLGL7CG7BU

Luminaire Lumens 14,205

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary

Efficiency Lumens Horizontal Spread Vertical Spread


180° 170° 160° 150° 140° Field (10%) 96.3% 13,678.5 135.3 112.5
8,400

7,000
3 2 1 0 1 2 3 4 Beam (50%) 62.6% 8,887.6 120.7 45.7
130°
Total 100% 14,205.3
3
5,600
120°
4,200 2 Tilt Angle- 45 Degree LLF-0.9
2,800 110°
1
Forward Throw Distance
1,400 100°
0 Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
0 90° Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
1,400 80°
1 6 (20) 4.91 15 (48) 12 (40) 11 (35) 7 (25)
2,800
9 (30) 2.22 18 (60) 14 (45) 12 (38) —
70° 2
12 (40) 1.25 20 (64) 16 (52) — —
4,200
60° 3
5,600
4
7,000 50° Side-to-Side Distance
Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed

8,400 20 fc 1fc
0° 10° 20° 30° 40° 10 fc 0.5 fc Height m (ft) m (ft) m (ft) m (ft) m (ft)
5 fc 0.2 fc 6 (20) 29 (96) 24 (80) 18 (60) 11 (36)
-0° H -22.5° H 2 fc 0.1 fc
-90° H -45° H 9 (30) 33 (108) 27 (90) 16 (54) —
-67.5° H 12 (40) 37 (120) 24 (80) — —

NEMA 7x6, Clear Glass


REPORT NUMBER: AMLGL7WG7BU

Luminaire Lumens 11,971

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary

Efficiency Lumens Horizontal Spread Vertical Spread


180° 170° 160° 150° 140° Field (10%) 96.1% 11,503.9 135.2 112
7,300
3
2 1 0 1 2 3 Beam (50%) 62% 7,424.4 119.8 45.2
6,083 130° Total 100% 11,971.9
2
4,867
120° Tilt Angle- 45 Degree LLF-0.9
3,650
1

2,433 110°
Forward Throw Distance
0
1,217 100° Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
0 90° Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
1
6 (20) 4.30 14 (46) 12 (40) 10 (32) 6 (20)
1,217 80°
9 (30) 1.91 17 (54) 14 (45) 33 (10) —
2
2,433
70° 12 (40) 1.07 20 (64) 15 (50) — —
3,650
3
60°
4,867
20 fc 1fc Side-to-Side Distance
6,083 50° 10 fc 0.5 fc
5 fc 0.2 fc Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
7,300 2 fc 0.1 fc Height m (ft) m (ft) m (ft) m (ft) m (ft)
0° 10° 20° 30° 40° Point of Max FC: 10.02
6 (20) 27 (90) 22 (72) 16 (52) 9 (30)
-0° H -22.5° H 9 (30) 33 (108) 24 (78) 15 (48) —
-90° H -45° H 12 (40) 34 (112) 22 (72) — —
-67.5° H

274 Visit our website at www.emerson.com or contact us at (800) 621-1506.


© April 2018
Areamaster™ Generation 2 LED Luminaire
Floodlight for Hazardous Locations

NEC/CEC: NEC/CEC: ATEX/IECEx:


Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2 and 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T5

Photometric Data — DATA SHOWN IS ABSOLUTE


NEMA 7x6, Clear Glass
REPORT NUMBER: AMLGL8CG7BU

Luminaire Lumens 18,467

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary

3 2 1 0 1 2 3 4 Efficiency Lumens Horizontal Spread Vertical Spread


180° 170° 160° 150° 140° Field (10%) 96.2% 17,761.1 135.1 112.2
12,000 3
Beam (50%) 62.5% 11,537.1 120.5 45.3
10,000 130°
2
Total 100% 18,467.4
8,000 Tilt Angle- 45 Degree LLF-0.9
120° 1
6,000

110° 0
Forward Throw Distance
4,000
Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
2,000 100° 1 Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
0 90° 6 (20) 6.44 16 (52) 13 (44) 11 (36) 8 (26)
2
2,000 80° 9 (30) 2.86 19 (63) 16 (54) 12 (39) 6 (21)
3 12 (40) 1.63 22 (72) 18 (60) 12 (40) —
4,000
70°
6,000 4
60°
8,000
20 fc 1fc Side-to-Side Distance
10,000 50° 10 fc 0.5 fc Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
5 fc 0.2 fc
12,000 Height m (ft) m (ft) m (ft) m (ft) m (ft)

LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed


0° 10° 20° 30° 40°
2 fc 0.1 fc
Point of Max FC: 10.02 6 (20) 32 (104) 26 (84) 21 (68) 12 (40)
-0° H -22.5° H 9 (30) 37 (120) 31 (102) 20 (66) 4 (12)
-90° H -45° H 12 (40) 39 (128) 29 (96) 15 (48) —
-67.5° H

NEMA 7x6, Clear Glass


REPORT NUMBER: AMLGL8WG7BU

Luminaire Lumens 15,556

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary

Efficiency Lumens Horizontal Spread Vertical Spread


3 2 1 0 1 2 3 4
180° 170° 160° 150° 140° Field (10%) 96.1% 14,945.7 135 111.8
9,500
3 Beam (50%) 62% 9,641.5 119.5 45
7,917 130° Total 100% 15,555.8
2
6,333

4,750
120°
1
Tilt Angle- 45 Degree LLF-0.9

3,167 110°
0 Forward Throw Distance
1,583 100° Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
1

0 90° Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)


2 6 (20) 5.61 15 (50) 13 (42) 11 (36) 8 (26)
1,583 80°
9 (30) 2.50 18 (60) 16 (53) 12 (38) —
3
3,167
70° 12 (40) 1.40 21 (70) 17 (56) 11 (36) —
4,750 4
60°
6,333
20 fc 1fc Side-to-Side Distance
7,917 50° 10 fc 0.5 fc
5 fc 0.2 fc Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
9,500 2 fc 0.1 fc Height m (ft) m (ft) m (ft) m (ft) m (ft)
0° 10° 20° 30° 40°
6 (20) 30 (100) 24 (80) 20 (64) 11 (36)
-0° H -22.5° H 9 (30) 36 (117) 27 (90) 18 (60) —
-90° H -45° H 12 (40) 37 (120) 24 (80) 12 (40) —
-67.5° H

Visit our website at www.emerson.com or contact us at (800) 621-1506. 275


© April 2018
Areamaster™ Generation 2 HL LED Luminaire
Floodlight for Hazardous Locations
NEC/CEC: NEC/CEC: ATEX/IECEx:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2, 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T4

Applications
• Enclosed and gasketed fixtures suitable for use in:
— A wide range of industrial, chemical processing and other
areas where flammable gases and vapors are present, for
example
— Oil and Gas Refineries
— Petrochemical Plants
— Foundries
— Drilling Rigs
— Pulp and Paper Mills
— Food and Beverage Processing Facilities
— Loading Docks
— Power Plants
— Water and Wastewater Treatment Facilities
— Other areas where corrosive, wet, dirty and tough
environments are a problem
• IP66/IP67, Type 4X, marine and wet locations
• Locations requiring dependable, consistent lighting in extreme
hot/cold temperature environments. -40°C to +65°C
(-40°F to +149°F) ambient temperature range Floodlight
Features
• Three lumen outputs provide up to 38,000 lumens.

Nominal Wattage Efficacy HID Model Standard Materials
Lumens  (W) (lpw) Equivalent Number
• Housing and lens door: copperfree (4/10 of 1% max.) aluminum
LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed

24,000 180 133 1000W AMLHL1 • Gaskets: silicone rubber


30,000 225 133 1000-1500W AMLHL2 • Yoke: zinc plated HR steel
38,000 310 123 1500W AMLHL3
• Bolts: stainless steel
 Nominal lumen value for 5000K, detailed lumen information • Close up plugs: (1) aluminum provided
provided in tables. • Guard and safety cable: stainless steel
• Choice of optics for optimal light distribution in a variety of • Visor: Aluminum
applications. Standard Finishes
• Separate field wiring compartment with screw terminal block for
• Housing, lens cover, visor and yoke mount: architectural bronze
easy and secure connection (can accept UL/CSA 26-10AWG).
polyester
• Two ¾” NPT entries provided.
• Yoke bracket is designed to accommodate traditional Related Products
Areamaster brackets and slipfitters for easy retrofit. • Round Tapered Steel Poles
• Choice of color temperature (CCT); 5000K cool white or 3000K • Hinged Steel Poled
warm white. • Square Tapered Steel Poles
• Rugged and compact housing with superior thermal design • Square Steel Poles
translates to long luminaire life. • Floodlight Mounting Brackets
• Heavy duty, high temperature silicone rubber gaskets.
• Thermal shock and impact resistant clear or frosted glass lens. NEC/CEC Certifications and Compliances
• Standard 6KV surge protection. • UL Standards:
• Captive fasteners secure one piece lens. — UL844, Luminaires for Use in Hazardous Locations
• Field replaceable LED driver and lens cover. — UL1598, Luminaires
Options — UL1598A, Luminaires for Installation on Marine Vessels
— UL 8750, LED Equipment for Use in Lighting Products
• Improved safety cable design with multiple retention points, • CSA Standards:
purchase separately — CSA C22.2 No. 250.0, Luminaires
• Guard and visor available, purchase separately — CSA C22.2 No. 137, Luminaires for Use in Hazardous
• Slip-fitters and mounting brackets available for easy pole or Locations
wall mounting • cCSAus: 164460 Certificate Number: 70073613
• 10 KV Surge Protection
• Metric M20 thread adapter

276 Visit our website at www.emerson.com or contact us at (800) 621-1506.


© April 2018
Areamaster™ Generation 2 HL LED Luminaire
Floodlight for Hazardous Locations
NEC/CEC: NEC/CEC: ATEX/IECEx:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2, 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T4

ATEX/IECEx Certifications and Compliances DesignLights™ Consortium (for the following models)
• Certification Type: Areamaster High Lumen • All models pending.
— Gas: Zone 2
– Type of Protection: Ex ec IIC Gc
– Temperature Class: T4 to T3
— Dust: Zone 22
– Type of Protection: Ex tc IIIC Dc
– Surface Temperature: +85°C to +100°C (+185°F to +212°F)
• Ambient Temperature: -40°C up to +65°C (-40°F up to +268 °F)
• ATEX Certificate: SIRA 17ATEX3241
• IECEx Certificate: IECEx SIR 17.0079
• Index of Protection according EN/IEC 60529: IP66
• Impact Resistance (shock): IK10
• Photobiological Safety, IEC 62778 and IEC 62471: RG0

Order using catalog numbering guides below or select catalog number from tables on following pages.
AMLH L1 C G 7 BU S

Series: Color Temp CCT: Beam Spread Options:


AMLH: Areamaster 2 HL LED C - 5000K 3 - 3x3 F - Fusing 
Series W - 3000K  5 = 5x5 S - 10 KV Surge Protection 
6 = 7x7 (non-optic) M - M20 Metric
7 = 7X6

LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed


Lumen Level : Diffusion: Voltage:
L1 - 24K G - Clear Glass BU = 120V-277 Vac 50/60 Hz, 170-300Vdc
L2 - 30K F - Frosted Glass  BH = 347-480 Vac 50/60 Hz 
L3 - 38K

Lumen Output Tables :


Lumen Output for Clear Glass Lens
AMLHL1 AMLHL2 AMLHL3
NEMA 7x7 (Non Optic), 5000K CCT, CRI 70 23,500 30,100 37,000
NEMA 7x6, 3000K CCT, CRI 80 19,800 23,500 30,300
NEMA 7x6, 5000K CCT, CRI 70 22,700 28,100 35,400
NEMA 5x5, 3000K CCT, CRI 80 21,400 25,500 32,800
NEMA 5x5, 5000K CCT, CRI 70 24,100 30,000 38,300

Lumen Output for Frosted Glass Lens


AMLHL1 AMLHL2 AMLHL3
NEMA 7x7 (Non Optic), 5000K CCT 20,600 25,600 31,600

 3000K CCT (warm) is not available with NEMA 7x7 light pattern.
 Frosted Glass is only available with NEMA 7x7 light pattern.
 Use of fuse voids Marine rating. Fusing not available for NEC/CEC.
 All lumen values are typical (tolerance +/-10%).
 BH Voltage available for NEC/CEC only.
 10Kv Surge Protection available for NEC/CEC only.

Visit our website at www.emerson.com or contact us at (800) 621-1506. 277


© April 2018
Areamaster™ Generation 2 HL LED Luminaire
Floodlight for Hazardous Locations
NEC/CEC: NEC/CEC: ATEX/IECEx:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2, 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T4

Electrical Ratings 
Input Current Total Harmonic
Voltage Suffix Voltage (V) Input Power (Watts) (Amps) Power Factor (PF) Distortion (THD) Model Number
120 Vac 180 1.52
>.9 <20%
277 Vac 176 0.67
BU
170 Vdc 172 1.02
N/A N/A AMLHL1
300 Vdc 170 0.57
347 Vac 179 0.52
BH >.9 <20%
480 Vac 179 0.39
120 Vac 231 1.94
>.9 <20%
277 Vac 231 0.88
BU
170 Vdc 220 1.30
N/A N/A AMLHL2
300 Vdc 217 0.72
347 Vac 219 0.64
BH >.9 <20%
480 Vac 219 0.47
120 Vac 317 2.67
>.9 <20%
277 Vac 303 1.15
BU
170 Vdc 305 1.80
LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed

N/A N/A AMLHL3


300 Vdc 298 0.99
347 Vac 299 0.87
BH >.9 <20%
480 Vac 298 0.63

Frontal Projected Area Drag Coefficient Effective Projected Area


Luminaire Category Image (FPA) ft2 (DC) (EPA) = FPA*DC ft2

90° to Ground-Worst
2.04 1.20 2.45
Case Mounting
Wind Direction

45° to Ground-Standard
1.44 1.20 1.73
Mounting Wind Direction

Surge Protection: Integral 6KV surge protection. Option for up to 10KV surge protection. (cCSAus only).
 All ratings are typical.

278 Visit our website at www.emerson.com or contact us at (800) 621-1506.


© April 2018
Areamaster™ Generation 2 HL LED Luminaire
Floodlight for Hazardous Locations
NEC/CEC: NEC/CEC: ATEX/IECEx:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2, 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T4

NEC/CEC Temperature Codes


Lamp Gas Dust

Ambient Supply Wire Class I, Class II, Class I Division 2


Temperature Temperature Division 2  Class I, Zone 2 Division 1 Zone 20, and Model
Line Voltage °C (°F) °C (°F) Groups A, B, C, D Group IIC Groups E,F,G Group IIIC Class 2 Division I Number
40 (104) 90 (194) T4A T4 T6 T6 T4A
120-277 Vac/
170-300 Vdc; 55 (131) 90 (194) T4A T4 T6 T6 T4A AMLHL1
347-480 Vac
65 (149) 90 (194) T4 T4 T5 T5 T4

40 (104) 90 (194) T4 T4 T6 T6 T4
120-277 Vac/
170-300 Vdc; 55 (131) 90 (194) T4 T4 T5 T5 T4 AMLHL2
347-480 Vac
65 (149) 90 (194) T3C T3 T5 T5 T3C
120-277 Vac/ 40 (104) 90 (194) T3C T3 T6 T6 T3C
170-300 Vdc; AMLHL3
347-480 Vac 55 (131) 90 (194) T3C T3 T5 T5 T3C

Ambient Temperature Range: -40 °C to +65 °C (-40 °F to +149 °F)

ATEX/IECEx Temperature Codes

LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed


Gas Dust
T Rating Surface Temperature
Ta= +40 °C Ta= +55 °C Ta= +65 °C Ta= +40 °C Ta= +55 °C Ta= +65 °C Model
(+104 °F) (+131 °F) (+149 °F) (+104 °F) (+131 °F) (+149 °F) Number
T4 T4 T4 T85°C T85°C T100°C AMLGL6

T4 T4 T3 T85°C T100°C T100°C AMLGL7

T3 T3 — T85°C T100°C — AMLGL8

“T” Numbers Represent the Maximum Internal Temperature  or Maximum Surface Temperature 
NEC/CEC
“T” # T1 350 325 T2 T2A T2B T2C T2D T3 T3A T3B T3C T4 T4A T5 T6
Temp. 351- 326- 301- 281- 261- 231- 216- 201- 181- 166- 161- 136- 121- 101- 86-
85
450 350 325 300 280 260 230 215 200 180 165 160 135 120 100
Range
(664- (619- (574- (538- (502- (448- (421- (394- (358- (331- (322- (277- (250- (214- (187-
ºC (˚ºF) (185)
842) 662) 617) 572) 536) 500) 446) 419) 392) 356) 329) 320) 275) 248) 212)

ATEX/IECEx
“T” # T1 T2 T3 T4 T5 T6
Temp. 301-450 201-300 136-200 101-135 86-100 85
Range
ºC (˚ºF) (547-842) (394-572) (277-392) (214-275) (187-212) (185)

 T numbers represent the maximum internal temperature for Class I, Division 2 and Class I, Zone 2 locations designated by the NEC.
 T numbers represent the maximum surface temperature under a dust blanket for Class II, Division 1 and 2 as designated by the NEC.

Visit our website at www.emerson.com or contact us at (800) 621-1506. 279


© April 2018
Areamaster™ Generation 2 HL LED Luminaire
Floodlight for Hazardous Locations
NEC/CEC: NEC/CEC: ATEX/IECEx:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2, 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T4

Lumen Efficacy Optical Catalog


CCT Output Wattage (lm/W) Pattern Number 
Clear Glass
120-277 Vac/170-300 Vdc
5000K (cool white) 23500 174 135 NEMA 7x7 (150°x150°) AMLHL1CG6BU
5000K (cool white) 24100 177 136 NEMA 5x5 (75°x75°) AMLHL1CG5BU
5000K (cool white) 22700 177 128 NEMA 7x6 (136°x113°) AMLHL1CG7BU
3000K (warm white) 21400 176 122 NEMA 5x5 (75°x75°) AMLHL1WG5BU
3000K (warm white) 19800 177 112 NEMA 7x6 (136°x113°) AMLHL1WG7BU
5000K (cool white) 30100 226 133 NEMA 7x7 (150°x150°) AMLHL2CG6BU
5000K (cool white) 30000 228 132 NEMA 5x5 (75°x75°) AMLHL2CG5BU
5000K (cool white) 28100 226 124 NEMA 7x6 (136°x113°) AMLHL2CG7BU
3000K (warm white) 25500 215 119 NEMA 5x5 (75°x75°) AMLHL2WG5BU
3000K (warm white) 23500 214 110 NEMA 7x6 (136°x113°) AMLHL2WG7BU
5000K (cool white) 37000 303 122 NEMA 7x7 (150°x150°) AMLHL3CG6BU
5000K (cool white) 38300 313 122 NEMA 5x5 (75°x75°) AMLHL3CG5BU
5000K (cool white) 35400 306 116 NEMA 7x6 (136°x113°) AMLHL3CG7BU
3000K (warm white) 32800 295 111 NEMA 5x5 (75°x75°) AMLHL3WG5BU
3000K (warm white) 30300 295 103 NEMA 7x6 (136°x113°) AMLHL3WG7BU
347-480 Vac
5000K (cool white) 23500 174 135 NEMA 7x7 (150°x150°) AMLHL1CG6BH
LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed

5000K (cool white) 24100 177 136 NEMA 5x5 (75°x75°) AMLHL1CG5BH
5000K (cool white) 22700 177 128 NEMA 7x6 (136°x113°) AMLHL1CG7BH
3000K (warm white) 21400 176 122 NEMA 5x5 (75°x75°) AMLHL1WG5BH
3000K (warm white) 19800 177 112 NEMA 7x6 (136°x113°) AMLHL1WG7BH
5000K (cool white) 30100 226 133 NEMA 7x7 (150°x150°) AMLHL2CG6BH
5000K (cool white) 30000 228 132 NEMA 5x5 (75°x75°) AMLHL2CG5BH
5000K (cool white) 28100 226 124 NEMA 7x6 (136°x113°) AMLHL2CG7BH
3000K (warm white) 25500 215 119 NEMA 5x5 (75°x75°) AMLHL2WG5BH
3000K (warm white) 23500 214 110 NEMA 7x6 (136°x113°) AMLHL2WG7BH
5000K (cool white) 37000 303 122 NEMA 7x7 (150°x150°) AMLHL3CG6BH
5000K (cool white) 38300 313 122 NEMA 5x5 (75°x75°) AMLHL3CG5BH
5000K (cool white) 35400 306 116 NEMA 7x6 (136°x113°) AMLHL3CG7BH
3000K (warm white) 32800 295 111 NEMA 5x5 (75°x75°) AMLHL3WG5BH
3000K (warm white) 30300 295 103 NEMA 7x6 (136°x113°) AMLHL3WG7BH
Frosted Glass
120-277 Vac/170-300 Vdc
5000K (cool white) 20600 176 116 NEMA 7x7 (150x150) AMLHL1CF6BU
5000K (cool white) 25600 226 113 NEMA 7x7 (150x150) AMLHL2CF6BU
5000K (cool white) 31600 303 104 NEMA 7x7 (150x150) AMLHL3CF6BU
347-480 Vac
5000K (cool white) 20600 176 116 NEMA 7x7 (150x150) AMLHL1CF6BH
5000K (cool white) 25600 226 113 NEMA 7x7 (150x150) AMLHL2CF6BH
5000K (cool white) 31600 303 104 NEMA 7x7 (150x150) AMLHL3CF6BH

 For Fusing option, add suffix F to end of part number, example AMLHL1CG6BUF.
For 10KV surge protection, add suffix S to end of part number, example AMLHL1CG7BUS.
For both Fusing and 10KV surge, add suffix FS to end of part number, example AMLHL1CG7BUFS.

280 Visit our website at www.emerson.com or contact us at (800) 621-1506.


© April 2018
Areamaster™ Generation 2 HL LED Luminaire
Floodlight for Hazardous Locations
NEC/CEC: NEC/CEC: ATEX/IECEx:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2, 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T4

Accessories and Replacement Parts


Description Catalog Number
Crossarm Mounting Bracket

Has 180° horizontal adjustment — degree marked. Facilitates


mounting floodlight to crossarm or other flat surface, or to G-AM-
G-AM-8-CA
8-WB. Includes floodlight yoke bolts. Malleable iron, zinc plated,
chromate sealed, architectural bronze polyester finish.

Pipe or Wall Mount Bracket

Used with G-AM-8-CA. Clamps to 1” to 2-1/2” pipe, vertical


or horizontal, or mounts on flat surfaces. Includes U-bolt and
G-AM-8-WB
crossarm bracket bolts. Malleable iron, zinc plated, chromate
sealed, with architectural bronze polyester finish.

LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed


Crossarm Mounting Bracket (G-AM-8-CA) used with Pipe or Wall Mount Bracket (G-AM-8-WB).
Poletop Slip-Fitter

Slip-fits 1-1/2” or 2” pipe size poletop tenons. Includes floodlight


yoke bolts, 3 locking bolts, and cord grip. Body is malleable iron-
G-SF20
zinc plated, chromate sealed, with cast aluminum cap. Assembly
has architectural bronze polyester finish.

Slip-fits 1" or 1-1/2” pipe size poletop tenons. Includes floodlight


yoke bolts, 3 locking bolts, and cord grip. Body is malleable iron-
AMLEDSF1
zinc plated, chromate sealed, with cast aluminum cap. Assembly
has architectural bronze polyester finish.

Poletop Slip-Fitter

Slip-fits 2” or 2-1/2” poletop tenons. Includes floodlight yoke


bolts, 3 locking bolts, and cord grip. Malleable iron, zinc plated, G-AM-8-SF
chromate sealed, with architectural bronze polyester finish.

Visit our website at www.emerson.com or contact us at (800) 621-1506. 281


© April 2018
Areamaster™ Generation 2 HL LED Luminaire
Floodlight for Hazardous Locations
NEC/CEC: NEC/CEC: ATEX/IECEx:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2, 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T4

Accessories and Replacement Parts


Description Catalog Number
Wall Mount Bracket

Used with G-AM-8-SF and GSF-20 to provide a wall mounting


GPSWB6
option. Galvanized Steel.

Wire Guard

Stainless steel. LHGUARD


LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed

Safety Cable

Stainless steel. LEDSC

Visor

Steel with architectural bronze polyester finish. For Dark Sky


AMLHV
Friendly design.

Portable Floodlight Base

Portable floodlight base for temporary lighting applications. To be


used with wire guard. G-AM-PFB
Malleable iron with architectural bronze polyester finish.

282 Visit our website at www.emerson.com or contact us at (800) 621-1506.


© April 2018
Areamaster™ Generation 2 HL LED Luminaire
Floodlight for Hazardous Locations
NEC/CEC: NEC/CEC: ATEX/IECEx:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2, 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T4

Accessories and Replacement Parts


Replacement Covers

AMLHCLEAR

AMLHFROST

Replacement Drivers
Driver Constant
Voltage Wattage Current Setting Luminaire Model CCT Catalog Number

BU APMS150C105UD91
150 watt 915mA AMLHL3C 5K
BH APMS150C105HD91

BU APMS150C105U68
150 watt 680mA AMLHL2C 5k
BH APMS150C105HD68
BU APMS150C105UD89
150 watt 890mA AMLHL3W 3K

LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed


BH APMS150C105HD89
BU APMS150C105UD65
150 watt 650mA AMLHL2C 3K
BH APMS150C105HD65
BU AMLHL1C, APMS100C105UD53
100 watt 530mA 5K and 3K
BH AMLHL1W APMS100C105HD53

Areamaster Generation 2 Accessory Weights


Description Weight in kg (lbs)
AMLHL1, AMLHL2, AMLHL3 Luminaires 16.1 (35.4)
Yoke Bracket 1.4 (3.1)
Visor 0.3 (0.6)
Guard 0.2 (0.4)
Safety Cable 0.2 (0.4)
Crossarm Mounting Bracket G-AM-8-CA 1.4 (3.1)
Pipe or Wall Mount Bracket G-AM-8-WB 2.9 (6.4)
Poletop Slip-Fitter GSF20 1.4 (3.1)
Poletop Slip-Fitter AMLEDSF1 2.4 (5.3)
Poletop Slip-Fitter GAM8SF —
— —

Visit our website at www.emerson.com or contact us at (800) 621-1506. 283


© April 2018
Areamaster™ Generation 2 HL LED Luminaire
Floodlight for Hazardous Locations
NEC/CEC: NEC/CEC: ATEX/IECEx:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2, 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T4

Dimensions in Millimeters (Inches)


Floodlight
404.9 mm
(15.94 in)
213.4 mm 130.3 mm
(8.40 in) (5.13in)

203.2 mm
(8.00 in) 411.7 mm
474.2 mm (16.21 in)
(18.67 in)

(4) Yoke
Bolts
Yoke
LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed

152.4 mm
Conduit Entry 57.2 mm (6.00 in)
(2.25 in)

44.5 mm
(1.75 in) (3) Mounting Holes 152.4 mm (6.00 in) Turning Radius
88.9 mm Ø 14 mm (0.56 in) 180° Rotation
(3.50 in)

(4) 1/4-20 UNC-2B Thread

(2) Hubs for 3/4” NPT Conduit

284 Visit our website at www.emerson.com or contact us at (800) 621-1506.


© April 2018
Areamaster™ Generation 2 HL LED Luminaire
Floodlight for Hazardous Locations
NEC/CEC: NEC/CEC: ATEX/IECEx:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2, 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T4

Photometric Data — DATA SHOWN IS ABSOLUTE


NEMA 5x5, Clear Glass
REPORT NUMBER: AMLHL1CG5BU

Luminaire Lumens 24,140

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary

Efficiency Lumens Horizontal Spread Vertical Spread


Field (10%) 94.8% 22,874.5 91.7 91.3
180° 170° 160° 150° 140°
Beam (50%) 84% 20,284.1 75.4 75.9
17,000
3 2 1 0 1 2 3 4
Total 100% 24,137.4
14,167 130°

11,333 3
Tilt Angle- 45 Degree LLF-0.9
120°
8,500
2

5,667 110° Forward Throw Distance


2,833 100°
1
Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
0 90° 0
9 (30) 8.96 27 (90) 21 (68) 16 (54) 10 (33)
2,833 80° 1 12 (40) 5.04 29 (96) 22 (72) 16 (52) 9 (28)
5,667
70° 15 (50) 3.19 30 (100) 23 (75) 15 (50) —
2
8,500 18 (60) 2.22 32 (105) 24 (78) 14 (45) —
60°
11,333 3

14,167 50°
4
Side-to-Side Distance

LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed


17,000
0° 10° 20° 30° 40°
20 fc 1fc Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
10 fc 0.5 fc Height m (ft) m (ft) m (ft) m (ft) m (ft)
Max Cd: 135°C -22.5° H 5 fc 0.2 fc
-0° H -45° H 2 fc 0.1 fc 9 (30) 29 (96) 24 (78) 19 (63) 14 (45)
-90° H -67.5° H
Point of Max FC: 9.90 12 (40) 32 (104) 27 (88) 20 (64) 10 (32)
15 (50) 37 (120) 29 (95) 18 (60) —
18 (60) 40 (132) 29 (96) 15 (48) —
NEMA 5x5, Clear Glass
REPORT NUMBER: AMLHL1WG5BU

Luminaire Lumens 21,416

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary

Efficiency Lumens Horizontal Spread Vertical Spread


180° 170° 160° 150° 140° Field (10%) 95% 20,343.5 95.6 94.3
15,000
Beam (50%) 84% 17,982.6 79.7 80.3
12,500 130° Total 100% 21,416.2
3 2 1 0 1 2 3 4
10,000
120° Tilt Angle- 45 Degree LLF-0.9
3
7,500

5,000 110° 2 Forward Throw Distance


2,500 100° Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
1
Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
0 90°
0 9 (30) 8.96 29 (96) 23 (75) 17 (57) 36 (11)
2,500 80° 12 (40) 5.04 32 (104) 24 (80) 18 (60) 10 (32)
1
5,000 15 (50) 3.19 34 (110) 26 (85) 18 (60) 8 (25)
70°
2 18 (60) 2.22 36 (117) 27 (90) 16 (54) —
7,500
60°
10,000 3

12,500 50° 4 Side-to-Side Distance


15,000 Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
0° 10° 20° 30° 40° 20 fc 1fc Height m (ft) m (ft) m (ft) m (ft) m (ft)
10 fc 0.5 fc
-0° H -22.5° H 5 fc 0.2 fc 9 (30) 27 (90) 22 (72) 18 (60) 13 (42)
2 fc 0.1 fc 12 (40) 30 (100) 24 (80) 20 (64) 7 (24)
-90° H -45° H
Point of Max FC: 10.02
-67.5° H 15 (50) 37 (120) 27 (90) 18 (60) —
18 (60) 37 (120) 27 (90) 15 (48) —

Visit our website at www.emerson.com or contact us at (800) 621-1506. 285


© April 2018
Areamaster™ Generation 2 HL LED Luminaire
Floodlight for Hazardous Locations
NEC/CEC: NEC/CEC: ATEX/IECEx:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2, 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T4

Photometric Data — DATA SHOWN IS ABSOLUTE


NEMA 5x5, Clear Glass
REPORT NUMBER: AMLHL2CG5BU

Luminaire Lumens 30,068

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary

Efficiency Lumens Horizontal Spread Vertical Spread


Field (10%) 94.6% 28,436.7 95.8 93.5
180° 170° 160° 150° 140°
21,000 Beam (50%) 83.6% 25,124.4 78.8 79.8
17,500 130° Total 100% 30,069.5
4 3 2 1 0 1 2 3 4 5
5
14,000
120° 4
10,500 Tilt Angle- 45 Degree LLF-0.9
3
7,000 110°
2 Forward Throw Distance
3,500 100°
1 Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
0 90° Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
0
3,500 80° 9 (30) 3.84 29 (96) 23 (75) 17 (57) 36 (11)
1
12 (40) 2.15 32 (104) 24 (80) 18 (60) 10 (32)
7,000
70° 2 15 (50) 1.38 34 (110) 26 (85) 18 (60) 8 (25)
10,500
60°
3 18 (60) 0.97 36 (117) 27 (90) 16 (54) —
14,000
4

17,500 50°
LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed

21,000
Side-to-Side Distance
0° 10° 20° 30° 40° 20 fc 1fc Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
10 fc 0.5 fc
5 fc 0.2 fc Height m (ft) m (ft) m (ft) m (ft) m (ft)
-0° H -22.5° H
-90° H -45° H 2 fc 0.1 fc 9 (30) 31 (102) 26 (84) 19 (61) 15 (48)
Point of Max FC: 6.49 12 (40) 34 (112) 29 (96) 22 (72) 12 (40)
-67.5° H
15 (50) 40 (130) 30 (100) 24 (80) 9 (30)
18 (60) 44 (144) 33 (108) 22 (72) —
NEMA 5x5, Clear Glass
REPORT NUMBER: AMLHL2WG5BU

Luminaire Lumens 25.490

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary

Efficiency Lumens Horizontal Spread Vertical Spread


180° 170° 160° 150° 140° Field (10%) 94.9% 24,197.1 95.5 93.5
18,000
Beam (50%) 84.5% 21,539.9 80 79.7
15,000 130°
5
4 3 2 1 0 1 2 3 4 5 Total 100% 25,489.8
12,000
120° 4 Tilt Angle- 45 Degree LLF-0.9
9,000
3
110°
6,000
2
Forward Throw Distance m (ft)
3,000 100° Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
1
Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
0 90°
0
9 (30) 6.94 28 (93) 21 (69) 16 (54) 10 (33)
3,000 80° 1 12 (40) 3.85 30 (100) 23 (76) 17 (56) 9 (28)
6,000
70° 2 15 (50) 2.46 31 (103) 23 (75) 15 (50) —
9,000 3
18 (60) 1.71 33 (108) 24 (78) 15 (48) —
60°
12,000 4

15,000 50° 5
Side-to-Side Distance
18,000
20 fc 1fc Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
0° 10° 20° 30° 40°
10 fc 0.5 fc Height m (ft) m (ft) m (ft) m (ft) m (ft)
5 fc 0.2 fc
-0° H -22.5° H 2 fc 0.1 fc 9 (30) 27 (90) 22 (72) 18 (60) 13 (42)
-90° H -45° H Point of Max FC: 6.97 12 (40) 30 (100) 24 (80) 20 (64) 7 (24)
-67.5° H 15 (50) 37 (120) 27 (90) 18 (60) —
18 (60) 37 (120) 27 (90) 15 (48) —

286 Visit our website at www.emerson.com or contact us at (800) 621-1506.


© April 2018
Areamaster™ Generation 2 HL LED Luminaire
Floodlight for Hazardous Locations
NEC/CEC: NEC/CEC: ATEX/IECEx:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2, 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T4

Photometric Data — DATA SHOWN IS ABSOLUTE


NEMA 5x5, Clear Glass
REPORT NUMBER: AMLHL3CG5BU

Luminaire Lumens 38,350

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary


Efficiency Lumens Horizontal Spread Vertical Spread
Field (10%) 95.3% 36,528.8 89.8 92.9
180° 170° 160° 150° 140°
27,000 Beam (50%) 84.4% 32,367.7 73.5 79.7
22,500 130°
Total 100% 38,348.7
4 3 2 1 0 1 2 3 4 5
5
18,000
120° 4 Tilt Angle- 45 Degree LLF-0.9
13,500
3

9,000 110° Forward Throw Distance


2

4,500 100° Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx


1
Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
0 90°
0 9 (30) 4.96 32 (105) 26 (84) 19 (63) 13 (42)
4,500 80° 1 12 (40) 2.78 35 (116) 27 (88) 21 (68) 12 (40)
9,000 15 (50) 1.78 34 (110) 26 (85) 18 (60) 8 (25)
70° 2
18 (60) 1.23 38 (126) 29 (96) 20 (66) 5 (18)
13,500 3
60°
18,000 4

22,500 50° 5
Side-to-Side Distance m (ft)

LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed


27,000
20 fc 1fc
Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
0° 10° 20° 30° 40°
10 fc 0.5 fc Height m (ft) m (ft) m (ft) m (ft) m (ft)
5 fc 0.2 fc 9 (30) 33 (108) 27 (90) 22 (72) 16 (54)
-0° H -22.5° H 2 fc 0.1 fc
-90° H -45° H Point of Max FC: 5.03
12 (40) 37 (120) 30 (100) 24 (80) 15 (48)
-67.5° H 15 (50) 40 (130) 30 (100) 24 (80) 9 (30)
18 (60) 44 (144) 37 (120) 26 (84) 4 (12)
NEMA 5x5, Clear Glass
REPORT NUMBER: AMLHL3WG5BU

Luminaire Lumens 32,835

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary


Efficiency Lumens Horizontal Spread Vertical Spread
180° 170° 160° 150° 140° Field (10%) 95% 31,186.0 96.1 93.5
23,000 Beam (50%) 84% 27,593.2 80.4 79.8
19,167 130° Total 100% 32,832.0
4 3 2 1 0 1 2 3 4 5
5
15,333
Tilt Angle- 45 Degree LLF-0.9
120° 4
11,500
3
7,667 110° Forward Throw Distance m (ft)
100°
2 Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
3,833
1 Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
0 90° 9 (30) 7.95 30 (99) 25 (81) 18 (60) 12 (39)
0
3,833 80° 12 (40) 4.40 34 (112) 26 (84) 18 (60) 11 (36)
1
15 (50) 2.82 34 (110) 27 (90) 18 (60) 8 (25)
7,667
70° 2 18 (60) 1.96 37 (120) 27 (90) 18 (60) —
11,500
3
60°
15,333
4

19,167 50° 5
Side-to-Side Distance m (ft)
23,000 Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
0° 10° 20° 30° 40° 20 fc 1fc Height m (ft) m (ft) m (ft) m (ft) m (ft)
10 fc 0.5 fc
5 fc 0.2 fc 9 (30) 33 (108) 26 (84) 20 (66) 16 (54)
-0° H -22.5° H 2 fc 0.1 fc
-90° H -45° H 12 (40) 37 (120) 29 (96) 24 (80) 12 (48)
Point of Max FC: 7.75
-67.5° H 15 (50) 40 (130) 30 (100) 24 (80) 9 (30)
18 (60) 40 (132) 35 (114) 22 (72) —

Visit our website at www.emerson.com or contact us at (800) 621-1506. 287


© April 2018
Areamaster™ Generation 2 HL LED Luminaire
Floodlight for Hazardous Locations
NEC/CEC: NEC/CEC: ATEX/IECEx:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2, 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T4

Photometric Data — DATA SHOWN IS ABSOLUTE


NEMA 7x6 Clear Glass
REPORT NUMBER: AMLHL1CG7BU

Luminaire Lumens 22,661

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary

3 2 1 0 1 2 3 4
Efficiency Lumens Horizontal Spread Vertical Spread
Field (10%) 95.8% 21,708.2 134.1 111.1
180° 170° 160° 150° 140°
15,000 3 Beam (50%) 61.4% 13,911.6 118.5 44.9
12,500 130° Total 100% 22,657.0
2
10,000
120° 1 Tilt Angle- 45 Degree LLF-0.9
7,500

5,000 110° 0
Forward Throw Distance m (ft)
2,500 100° 1 Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
0 90° Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
2 9 (30) 3.64 19 (63) 17 (57) 14 (54) 9 (29)
2,500 80°
12 (40) 2.08 23 (76) 20 (64) 15 (48) —
3
5,000
70° 15 (50) 1.33 26 (85) 20 (65) 12 (40) —
7,500 4 18 (60) 0.93 27 (90) 20 (66) — —
60°
10,000
20 fc 1fc
12,500 50° 10 fc 0.5 fc
5 fc 0.2 fc Side-to-Side Distance
LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed

15,000 2 fc 0.1 fc
0° 10° 20° 30° 40° Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
Height m (ft) m (ft) m (ft) m (ft) m (ft)
-0° H -22.5° H 9 (30) 38 (126) 33 (108) 23 (75) 13 (42)
-90° H -45° H 12 (40) 44 (144) 32 (104) 22 (72) —
-67.5° H 15 (50) 46 (150) 30 (100) 15 (50) —
18 (60) 46 (150) 29 (96) — —
NEMA 7x6 Clear Glass
REPORT NUMBER: AMLHL1WG7BU

Luminaire Lumens 19,753

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary


3 2 1 0 1 2 3 4 Efficiency Lumens Horizontal Spread Vertical Spread
180° 170° 160° 150° 140° Field (10%) 95.8% 18,919.3 134.7 111.5
13,000 3 Beam (50%) 61.1% 12,060.3 117.9 45.1
10,833 130° Total 100% 19,750.3
2
8,667
120° 1 Tilt Angle- 45 Degree LLF-0.9
6,500

4,333 110° 0
Forward Throw Distance
2,167 100° 1 Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
0 90° Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
2
9 (30) 3.26 19 (63) 16 (54) 14 (45) 8 (27)
2,167 80°
3
12 (40) 1.78 22 (72) 19 (62) 13 (42) —
4,333
70° 15 (50) 1.16 24 (80) 19 (62) 11 (35) —
6,500 4 18 (60) 0.81 27 (90) 18 (60) — —
60°
8,667
20 fc 1fc
10,833 50°
10 fc 0.5 fc
5 fc 0.2 fc Side-to-Side Distance
13,000 2 fc 0.1 fc
0° 10° 20° 30° 40° Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
Height m (ft) m (ft) m (ft) m (ft) m (ft)
-0° H -22.5° H 9 (30) 37 (120) 27 (90) 21 (70) 8 (25)
-90° H -45° H 12 (40) 40 (130) 30 (100) 18 (60) —
-67.5° H 15 (50) 43 (140) 27 (90) 6 (20) —
18 (60) 43 (140) 24 (80) — —

288 Visit our website at www.emerson.com or contact us at (800) 621-1506.


© April 2018
Areamaster™ Generation 2 HL LED Luminaire
Floodlight for Hazardous Locations
NEC/CEC: NEC/CEC: ATEX/IECEx:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2, 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T4

Photometric Data — DATA SHOWN IS ABSOLUTE


NEMA 7x6 Clear Glass
REPORT NUMBER: AMLHL2CG7BU

Luminaire Lumens 28,063

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary


Efficiency Lumens Horizontal Spread Vertical Spread
3 2 1 0 1 2 3 4 Field (10%) 95.8% 26,888.8 134.1 111.1
180° 170° 160° 150° 140° Beam (50%) 61.5% 17,260.6 118.6 45
18,000 3
Total 100% 28,058.5
15,000 130°
2
12,000
Tilt Angle- 45 Degree LLF-0.9
120° 1
9,000

6,000 110° 0 Forward Throw Distance


Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
3,000 100° 1
Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
0 90°
2
9 (30) 4.49 21 (68) 18 (60) 15 (48) 10 (32)
3,000 80° 12 (40) 2.57 24 (80) 22 (72) 16 (52) —
3 15 (50) 1.64 27 (90) 23 (75) 15 (50) —
6,000
70° 18 (60) 1.14 29 (96) 23 (75) 13 (42) —
9,000 4
60°
12,000
20 fc 1fc
15,000 50° 10 fc 0.5 fc Side-to-Side Distance
5 fc 0.2 fc

LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed


18,000 2 fc 0.1 fc Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
0° 10° 20° 30° 40° Height m (ft) m (ft) m (ft) m (ft) m (ft)
9 (30) 41 (135) 35 (114) 24 (78) 15 (48)
-0° H -22.5° H
-45° H 12 (40) 46 (152) 37 (120) 24 (80) —
-90° H
-67.5° H 15 (50) 49 (160) 37 (120) 23 (75) —
18 (60) 48 (156) 33 (108) 9 (30) —
NEMA 7x6 Clear Glass
REPORT NUMBER: AMLHL2WG7BU

Luminaire Lumens 23,532

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary


Efficiency Lumens Horizontal Spread Vertical Spread
3 2 1 0 1 2 3 4
Field (10%) 95.7% 22,530.7 134.6 111
180° 170° 160° 150° 140°
15,000 3
Beam (50%) 60.9% 14,337.3 117.9 44.7
12,500 130°
Total 100% 23,528.4
2
10,000
120° 1
Tilt Angle- 45 Degree LLF-0.9
7,500

5,000 110° 0 Forward Throw Distance


2,500 100° Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
1
Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
0 90°
2 9 (30) 3.80 20 (66) 17 (57) 14 (45) 10 (32)
2,500 80° 12 (40) 2.17 23 (76) 18 (60) 15 (48) —
3
5,000 15 (50) 1.39 26 (85) 21 (70) 14 (45) —
70°
4
18 (60) 0.97 27 (90) 20 (66) — —
7,500
60°
10,000
20 fc 1fc
12,500 10 fc 0.5 fc
50°
5 fc 0.2 fc Side-to-Side Distance
15,000 2 fc 0.1 fc Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
0° 10° 20° 30° 40°
Height m (ft) m (ft) m (ft) m (ft) m (ft)
-0° H -22.5° H 9 (30) 38 (126) 33 (108) 22 (72) 13 (42)
-90° H -45° H 12 (40) 44 (144) 34 (112) 22 (72) —
-67.5° H 15 (50) 46 (150) 30 (100) 18 (60) —
18 (60) 48 (156) 29 (96) — —

Visit our website at www.emerson.com or contact us at (800) 621-1506. 289


© April 2018
Areamaster™ Generation 2 HL LED Luminaire
Floodlight for Hazardous Locations
NEC/CEC: NEC/CEC: ATEX/IECEx:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2, 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T4

Photometric Data — DATA SHOWN IS ABSOLUTE


NEMA 7x6 Clear Glass
REPORT NUMBER: AMLHL3CG7BU

Luminaire Lumens 35,430

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary


Efficiency Lumens Horizontal Spread Vertical Spread
Field (10%) 95.7% 33,908.8 139 111.1
180° 170° 160° 150° 140°
22,000 Beam (50%) 60.9% 21,578.5 115.4 45.6
4 3 2 1 0 1 2 3 4 5
18,333
5 Total 100% 35,424.1
130°
4
14,667
120° 3
Tilt Angle- 45 Degree LLF-0.9
11,000
2
7,333 110° Forward Throw Distance
3,667 100°
1 Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
0 Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
90°
0
9 (30) 5.69 22 (72) 19 (62) 16 (54) 11 (36)
1
3,667 80° 12 (40) 3.20 26 (84) 22 (72) 17 (56) 10 (32)
7,333
2
15 (50) 2.05 29 (95) 24 (80) 18 (60) —
70°
3 18 (60) 1.42 32 (105) 24 (78) 16 (54) —
11,000
60° 4
14,667
5
18,333 50° Side-to-Side Distance
LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed

22,000 20 fc 1fc Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx


0° 10° 20° 30° 40° 10 fc 0.5 fc Height m (ft) m (ft) m (ft) m (ft) m (ft)
5 fc 0.2 fc
2 fc 0.1 fc 9 (30) 42 (138) 37 (120) 27 (90) 18 (60)
-0° H -22.5° H
-90° H -45° H 12 (40) 49 (160)
Point 37 (120)
of Max FC: 5.03 27 (88) 12 (40)
-67.5° H 15 (50) 55 (180) 40 (130) 27 (90) —
18 (60) 55 (180) 40 (132) 22 (72) —
NEMA 7x6 Clear Glass
REPORT NUMBER: AMLHL3WG7BU

Luminaire Lumens 30,346

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary


Efficiency Lumens Horizontal Spread Vertical Spread
3 2 1 0 1 2 3 4 Field (10%) 95% 31,186.0 96.1 93.5
180° 170° 160° 150° 140° Beam (50%) 84% 27,593.2 80.4 79.8
19,000 3
Total 100% 32,832.0
15,833 130°
2
12,667
Tilt Angle- 45 Degree LLF-0.9
120° 1
9,500

6,333 110° 0 Forward Throw Distance


Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
3,167 100° 1
Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
0 90°
2
9 (30) 4.99 21 (69) 18 (60) 16 (54) 10 (33)
3,167 80° 12 (40) 2.81 25 (82) 22 (72) 16 (52) 9 (28)
3 15 (50) 1.79 27 (90) 23 (75) 17 (55) —
6,333
70°
18 (60) 1.25 29 (96) 23 (75) 15 (48) —
9,500 4
60°
12,667
20 fc 1fc
15,833 50° 10 fc 0.5 fc Side-to-Side Distance
5 fc 0.2 fc
19,000 2 fc 0.1 fc Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
0° 10° 20° 30° 40° Height m (ft) m (ft) m (ft) m (ft) m (ft)
9 (30) 41 (135) 35 (114) 26 (84) 16 (54)
-0° H -22.5° H
-90° H -45° H 12 (40) 49 (160) 37 (120) 24 (80) 2 (8)
-67.5° H 15 (50) 49 (160) 37 (120) 23 (75) —
18 (60) 51 (168) 37 (120) 18 (60) —

290 Visit our website at www.emerson.com or contact us at (800) 621-1506.


© April 2018
Areamaster™ Generation 2 HL LED Luminaire
Floodlight for Hazardous Locations
NEC/CEC: NEC/CEC: ATEX/IECEx:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2, 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T4

Photometric Data — DATA SHOWN IS ABSOLUTE


NEMA 7x7 Diffused Glass
REPORT NUMBER: AMLHL1CF6BU

Luminaire Lumens 20,578

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary


Efficiency Lumens Horizontal Spread Vertical Spread
Field (10%) 98% 20,176.5 155.7 154.5
180° 170° 160° 150° 140°
8,000 Beam (50%) 70.2% 14,453.8 104.6 103.6
6,667 Total 100% 20,571.8
130° 3 2 1 0 1 2 3 4

5,333
120° 3 Tilt Angle- 45 Degree LLF-0.9
4,000
2
2,667 110° Forward Throw Distance
1,333 100° 1 Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
0 90° 0 9 (30) 2.47 20 (66) 16 (54) 11 (36) 4 (12)
1,333 80° 1
12 (40) 1.40 22 (72) 16 (52) 10 (32) —
2,667
15 (50) 0.89 21 (70) 15 (50) 6 (20) —
70°
2 18 (60) 0.62 22 (72) 13 (42) — —
4,000
60° 3
5,333

6,667 50° 4
Side-to-Side Distance

LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed


8,000 Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
0° 10° 20° 30° 40° 20 fc 1fc
10 fc 0.5 fc Height m (ft) m (ft) m (ft) m (ft) m (ft)
5 fc 0.2 fc 9 (30) 31 (102) 22 (72) 16 (54) 4 (12)
-0° H -22.5° H 2 fc 0.1 fc
-90° H 12 (40) 32 (104) 22 (72) 12 (40) —
-45° H Point of Max FC: 2.51
-67.5° H 15 (50) 30 (100) 21 (70) 5 (15) —
18 (60) 33 (108) 15 (48) — —
NEMA 7x7 Clear Glass
REPORT NUMBER: AMLHL1CG6BU rotated

Luminaire Lumens 23,457

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary


Efficiency Lumens Horizontal Spread Vertical Spread
Field (10%) 98.4% 23,090.9 151.1 151.2
180° 170° 160° 150° 140°
8,200 Beam (50%) 80.3% 18,837.0 115.2 116.4
6,833 130°
3 2 1 0 1 2 3 4 Total 100% 23,448.8

5,467 3
120° Tilt Angle- 45 Degree LLF-0.9
4,100
2

2,733 110° Forward Throw Distance m (ft)


1
1,367 100° Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
0
Height m (ft) Point (fc) m (ft) m (ft) m (ft)
0 90°
9 (30) 2.84 20 (66) 16 (54) 11 (36) 5 (15)
1,367 80° 1 12 (40) 1.60 22 (72) 17 (56) 10 (32) —
2,733
15 (50) 1.03 23 (75) 15 (50) 6 (20) —
70° 2
18 (60) 0.71 23 (75) 14 (45) — —
4,100
60° 3
5,467
4
6,833 50° Side-to-Side Distance m (ft)
8,200 20 fc 1fc Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
0° 10° 20° 30° 40° 10 fc 0.5 fc Height m (ft) m (ft) m (ft) m (ft) m (ft)
5 fc 0.2 fc
9 (30) 33 (108) 24 (78) 18 (60) 7 (24)
-0° H -22.5° H 2 fc 0.1 fc
-90° H -45° H 12 (40) 34 (112) 24 (80) 15 (48) —
Point of Max FC: 2.88
-67.5° H 15 (50) 37 (120) 24 (80) 12 (40) —
18 (60) 35 (114) 18 (60) — —

Visit our website at www.emerson.com or contact us at (800) 621-1506. 291


© April 2018
Areamaster™ Generation 2 HL LED Luminaire
Floodlight for Hazardous Locations
NEC/CEC: NEC/CEC: ATEX/IECEx:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2, 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T4

Photometric Data — DATA SHOWN IS ABSOLUTE


NEMA 7x7 Diffused Glass
REPORT NUMBER: AMLHL2CF6BU

Luminaire Lumens 25,616

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary


Efficiency Lumens Horizontal Spread Vertical Spread
Field (10%) 98.1% 25,135.5 155.9 154.5
180° 170° 160° 150° 140°
9,900 Beam (50%) 69.9% 17,911.8 104.6 103.7
8,250 130° 4 3 2 1 0 1 2 3 4 5
Total 100% 25,609.0
5

6,600
120°
4
Tilt Angle- 45 Degree LLF-0.9
4,950 3

3,300 110° 2 Forward Throw Distance


1,650 100° 1
Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
0 90° 0
9 (30) 3.07 22 (72) 17 (57) 12 (39) 6 (21)
1,650 80° 1
12 (40) 1.70 24 (80) 17 (56) 12 (40) —
3,300
2 15 (50) 1.09 24 (80) 18 (60) 9 (30) —
70°
3 18 (60) 0.76 24 (78) 16 (54) — —
4,950
60° 4
6,600
5
8,250 50° Side-to-Side Distance
LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed

9,900 20 fc 1fc Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx


0° 10° 20° 30° 40° 10 fc 0.5 fc Height m (ft) m (ft) m (ft) m (ft) m (ft)
5 fc 0.2 fc
-0° H -22.5° H 2 fc 0.1 fc 9 (30) 33 (108) 24 (78) 18 (60) 7 (24)
-90° H -45° H Point of Max FC: 3.10 12 (40) 34 (112) 24 (80) 17 (56) —
-67.5° H 15 (50) 37 (120) 24 (80) 15 (50) —
18 (60) 37 (120) 18 (60) — —
NEMA 7x7 Clear Glass
REPORT NUMBER: AMLHL2CG6BU

Luminaire Lumens 30,157

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary


Efficiency Lumens Horizontal Spread Vertical Spread
180° 170° 160° 150° 140° Field (10%) 98.2% 29,616.7 151.4 145.9
11,000 Beam (50%) 81.2% 24,501.2 116.8 117.7
9,167 130° 3 2 1 0 1 2 3 4 Total 100% 30,147.4
7,333
3
120° Tilt Angle- 45 Degree LLF-0.9
5,500
2
3,667 110° Forward Throw Distance
1
1,833 100° Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
0
0 90° 9 (30) 4.17 23 (75) 17 (57) 13 (42) 7 (24)
1,833 80° 1 12 (40) 2.35 24 (80) 18 (60) 12 (40) —
15 (50) 1.49 24 (80) 18 (60) 9 (30) —
3,667
70° 2
18 (60) 1.04 26 (84) 16 (54) 7 (24) —
5,500
3
60°
7,333
4
9,167 50° Side-to-Side Distance
20 fc 1fc Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
11,000
0° 10° 20° 30° 40° 10 fc 0.5 fc Height m (ft) m (ft) m (ft) m (ft) m (ft)
5 fc 0.2 fc 9 (30) 35 (114) 26 (84) 19 (63) 9 (30)
2 fc 0.1 fc
-0° H -22.5° H 12 (40) 37 (120) 27 (88) 20 (64) —
-90° H -45° H Point of Max FC: 4.11
15 (50) 37 (120) 24 (80) 15 (50) —
-67.5° H 18 (60) 37 (120) 22 (72) 9 (30) —

292 Visit our website at www.emerson.com or contact us at (800) 621-1506.


© April 2018
Areamaster™ Generation 2 HL LED Luminaire
Floodlight for Hazardous Locations
NEC/CEC: NEC/CEC: ATEX/IECEx:
Class I, Division 2, Groups A, B, C, D Zone 22, Group IIIB Zone 2, 22
Class I, Zone 2 Group IIC Simultaneous Exposure IP66
Class II, Division 1 and 2, Groups E, F, G Marine Outside Type (Salt Water) for USA ONLY II 3GD
Class III Wet Locations IK10
Zone 20 and 21 Group IIIC Type 3R, 4, 4X, IP66/67 Ex ec llC T4

Photometric Data — DATA SHOWN IS ABSOLUTE


NEMA 7x7 Diffused Glass
REPORT NUMBER: AMLHL3CF6BU rotated

Luminaire Lumens 31,600

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary


Efficiency Lumens Horizontal Spread Vertical Spread
180° 170° 160° 150° 140° Field (10%) 97.9% 30,947.7 156 154.1
13,000
5
4 3 2 1 0 1 2 3 4 5 Beam (50%) 69.5% 21,961.6 104 102.9
10,833 130° 4
Total 100% 31,591.2
8,667 3

120° Tilt Angle- 45 Degree LLF-0.9


6,500 2

4,333 110° 1
Forward Throw Distance
2,167 100°
0
Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
1 Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
0 90° 9 (30) 3.82 24 (78) 18 (60) 13 (42) 8 (27)
2

2,167 80° 3
12 (40) 2.15 26 (84) 18 (60) 13 (44) —
15 (50) 1.38 27 (88) 20 (65) 12 (40) —
4,333
70° 4
18 (60) 0.96 27 (90) 20 (66) 7 (24) —
6,500 5
60°
8,667
20 fc 1fc
10 fc 0.5 fc Side-to-Side Distance
10,833 50° 5 fc 0.2 fc

LED/Floodlights: NEC/CEC, Atex/Iecex Enclosed and Gasketed


2 fc 0.1 fc Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
13,000 Point of Max FC: 3.85
0° 10° 20° 30° 40° Height m (ft) m (ft) m (ft) m (ft) m (ft)
9 (30) 35 (114) 26 (84) 18 (60) 9 (30)
-0° H -22.5° H 12 (40) 37 (120) 27 (88) 20 (56) —
-90° H -45° H 15 (50) 38 (125) 27 (90) 15 (50) —
-67.5° H 18 (60) 40 (132) 22 (72) — —
NEMA 7x7 Clear Glass
REPORT NUMBER: AMLHL3CG6BU rotated

Luminaire Lumens 37,039

Polar Candela Distribution Isofoot Candle Plot at 45° Flood Summary


Efficiency Lumens Horizontal Spread Vertical Spread
180° 170° 160° 150° 140° Field (10%) 98.3% 36,391.3 152.3 150.9
13,000
Beam (50%) 79.5% 29,452.1 114.2 115.8
10,833 130°
5
4 3 2 1 0 1 2 3 4 5 Total 100% 37,028.2
8,667
4
120°
6,500 3
Tilt Angle- 45 Degree LLF-0.9
4,333 110° 2
Forward Throw Distance
2,167 100° 1
Mounting Maximum 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
0 90° 0 Height m (ft) Point (fc) m (ft) m (ft) m (ft) m (ft)
1 9 (30) 2.44 26 (84) 19 (63) 14 (45) 8 (27)
2,167 80°
2
12 (40) 1.37 27 (88) 21 (68) 15 (48) 5 (16)
4,333
70° 15 (50) 0.88 27 (90) 20 (65) 12 (40) —
3

6,500 18 (60) 0.60 27 (90) 20 (66) 9 (30) —


4
60°
8,667
5

10,833 50°
20 fc 1fc Side-to-Side Distance
13,000 10 fc 0.5 fc Mounting 0.5fc/5lx 1fc/11lx 2fc/22lx 5fc/54lx
0° 10° 20° 30° 40° 5 fc 0.2 fc
2 fc 0.1 fc Height m (ft) m (ft) m (ft) m (ft) m (ft)
Point of Max FC: 2.49 9 (30) 37 (120) 27 (90) 22 (72) 13 (42)
-0° H -22.5° H
-90° H -45° H 12 (40) 41 (136) 30 (100) 22 (72) 6 (20)
-67.5° H 15 (50) 40 (130) 30 (100) 18 (60) —
18 (60) 44 (144) 29 (96) 15 (48) —

Visit our website at www.emerson.com or contact us at (800) 621-1506. 293