MV electrical network management Description

The HU250 module of the Easergy T300 range is the communication gateway dedicated to remote control
applications for T300 units.

NOTICE

DE53832.eps
Easergy T300 range

HU250
HAZARD OF INCORRECT CURRENT MEASUREMENTS
GPS
bb Do not expose the device to conditions exceeding the
2G/3G electrical values specified in this document.
or 3G/4G bb The device should be installed vertically in an electrical
cabinet, in accordance with the local regulations in force.
7 bb The product must be connected to the ground (DIN rail)
1 to help ensure compliance with electromagnetic
Control and communication unit compatibility (EMC) limits.
2 8 bb Standby protection should be provided in accordance
with national and international cabling regulations.
bb An appropriate electrical disconnecting device must be
installed in the building in question.

Installation 3
5 bb Use only the type of connector supplied as an accessory
for the HU250 module (product reference: EMS59010).

Guide 4 6 bb Check that the connections correspond to the


recommended cables before powering up the equipment.
NHA7792507 bb Use appropriate tools to perform cabling on the
9 connectors (suitable screwdriver, crimped end-pieces, etc.).
bb Strip the wires appropriately (not excessively) before
NOTE connecting them to the connectors (see the
Electrical equipment should be installed, recommandations in this document).
operated, serviced, and maintained only by Failure to follow these instructions can result in
qualified personnel. No responsibility is equipment damage.
14 13 11 10 12
assumed by Schneider Electric for any
consequences arising out of the use of this
material.
The HU250 includes the following components:
A qualified person is one who has skills and
knowledge related to the construction, Port Characteristics Description
installation, and operation of electrical
equipment and has received safety training to 1 2 Communication RS232/RS485: For the remote link to the control center, customizable
recognize and avoid the hazards involved. ports RJ45 connector including modem boxes including the following modems:
the following connections: bb RS232/485 (EMS59151):
RS232 Speed: up to 115200 baud
RS232 1 TXD Isolation: 2 kVAC
RS485 2 RXD
3 CTS bb 2G/3G (Option, ref. EMS59152):
4 DTR
1 8
5 DSR Parameter Value Unit
7
TX

6
6 RTS
RX

7 DCD Operating frequency range 900 - 1800 MHz


5
4 8 GND 2G
RS485 (2-wire) Maximum transmitted power 33 dBm
3
2 1 Operating frequency range 900 - 2100 MHz
1 2 3G
3 Maximum transmitted power 24 dBm
4 D1 (B)
5 D0 (A)
6 bb 3G/4G + GPS (Option, ref. EMS59153 &
2G/3G or 7 EMS59154) with GPS time synchronization.
3G/4G 8 GND
RS422 (4-wire) Parameter Value Unit
2 1 RXD0 (A’)
2 RXD1 (B’) Operating frequency range 900 - 1800 MHz
3 2G
4 TXD1 (B) Maximum transmitted power 33 dBm
5 TXD0 (A) Operating frequency range 900 - 2100 MHz
6
7 3G
Maximum transmitted power 24 dBm
8 GND (C/C’)
Operating frequency range 800, 900, 1800, 2100, 2600 MHz
4G
Maximum transmitted power 23 dBm
Note: The ports 1 and 2 can include only one 2G/3G
or 3G/4G modem.

Port Characteristics Description Port Port Port


3 Local 10/100 Base-T RJ45 connector Ethernet port used for the link to an
10 Digital inputs Plug-in screw connectors: 8 digital inputs:
communication EXT
ETH1 external device in the MV substation
Digital inputs 1 bb 4 unallocated digital inputs (for free use)
Ethernet port or for connection to a PC. 1 1 Common (0 V) bb 4 dedicated digital inputs for:
Isolation: 2 kVAC DI1 2 2 Digital input 1
DI2 3 3 Digital input 2 vv voltage presence (e.g. via the PS50 module)
4 Digital input 3
DI3 4
5 Digital input 4
vv connection of a door open switch
DI4 5 vv connection of an external Local/Remote switch
10/100 Base-T RJ45 connectorw Ethernet port used for the remote Digital inputs 2
4 Remote V present
1
1 Common (0 V)
communication EXT
ETH2 link to the control center, via a Door open
2
3
2 Voltage presence
modem or router. 3 Door open
Ethernet port 4
4 Common (0 V) 1 2 3 4 5 1 2 3 4 5 6
Isolation: 4 kVAC Local 5 5 Local Note: The «Door open» and «Local/Remote» dedicated digital
Remote 6 6 Remote inputs correspond to a default T300 application. They can be
used differently for another application by configuration.

11 Digital outputs Plug-in screw connector: 2 dry-contact digital outputs for free use.
10/100 Base-T RJ45 connectors Double ports dedicated to internal
5 Double Digital outputs Breaking capacity: 2000 VA
communication between T300 1
Ethernet ports modules or for connection to a PC.
D01
2
1 DO1 Max. voltage: 60 VDC
2 DO1
LAN 1 and 2 Isolation: 2 kVAC D02
3 3 DO2 Max. current: 2 A 1 2 3 4
4 4 DO2
DM
10 Ethernet jumpers (Ref: Isolation: 2 kVAC
3
Flair 2 EMS59528) provide as accessories
allow the internal Ethernet 12 Analog inputs Plug-in leaf-spring connector: 2 analog inputs for connection of one 3 wire
connection between the modules PT100 PT100 temperature sensor.
1 1 In1 Measurement: -55°C to 250°C
HU250, SC150 and LV150. 2 2 In2
PT100
3 3 Réf (-67°F to 482°F)
RJ45 connector capable of Port dedicated to internal Modbus 1 23
6 RS485 port Resolution: 1°C (1°F)
including the following connections: communication with the Easergy
PS50 power supply module or any Plug-in screw connector: 2 polarized indicator outputs for external indication
RS485 (2-wire) 13 Indicator outputs
1 1 other device communicating in Indicator lamps outside the MV substation. These indicators can be
2
D1 3 Modbus protocol 1 Indicator 1 assigned by configuration to fault current detection
D0
4 D1 (B) 2 Common 5 V
5 D0 (A)
Speed: up to 38400 baud 3 Indicator 2 indication (directional indication).
Common
6 Isolation: 2 kVAC 1 2 3 Refer to the T300 Quick start.
7
8 Voltage delivered: 5 V
Indicator 1
1 Max. current: 100 mA
7 WI-FI port Dual-band concurrent WI-FI WI-FI hotspot with security for local Indicator 2
2
Note: These outputs are polarized. Comply
3
(2.4GHz/5GHz) connection with a PC, tablet or with the direction of connection.
Parameter Value Unit smartphone to:
bb The T300’s embedded Web 14 Power supply Plug-in screw connectors: 2 power supply connectors connected
Operating
server Power supply internally, facilitating serial connections and
frequency 2400 - 2483.5 MHz
range bb The Easergy Builder advanced
+ +VDC (+12 V to +48 V) allowing looping of power supplies between the
- 0V
Maximum configuration tool T300 modules. (See Power Supply section).
transmitted 18.2 dBm 12-48V
power

8 Expert USB port Mini USB connector Mini USB port dedicated to
equipment maintenance (reserved Cabling
Recommendations for length of cable less than 2 meters.
for qualified personnel). X
mm2
Requires the installation of a specific N.m

driver.
10
9 Host USB port A type USB connector Multi-purpose USB peripheral
11 7 mm 0.5 mm² 0.22-0.25 N.m
NOTICE 0.276 in 20 AWG 1.9-2.2 lb-in

HAZARD OF TERMINAL DAMAGE OR INCORRECT POWER SUPPLY 13


bb Use appropriate tightening torques for tightening connector screws (tightening torque values provided in this document).
bb The digitial inputs accept only dry contacts. Consequently, these inputs must not receive voltage. 8 mm 0.14-0.5 mm²
12 -
bb The HU250 module must be powered by a power supply of the SELV/PELV type (e.g. the PS50 module). 0.315 in 26-20 AWG
bb The supply voltage of the HU250 module must not exceed 57.6 VDC. 7 mm 1-2.5 mm² 0.5-0.6 N.m
Failure to follow these instructions can result in equipment damage. 14 12-48 V
0.276 in 17 AWG 4.4-5.3 lb-in
Installation 2G/3G or 3G/4G modem

DE53845.eps
This modem allows a SIM card
Installing the enclosure to be inserted in one of the two available SIM card slots,
The HU250 module is fastened to a DIN rail. No tool is needed for mounting. without there being any difference at the operating level.
Simply clip it in order to fasten it as shown below.
The GPS and GSM antenna connectors and the SIM cards are accessible on the front of the modem.
140 mm / 5.51 in
DE53831.eps

DE53833.eps
129 mm / 5.08 in
Mounting the GPS antenna:
90 mm 104.5 mm bb Attach the GPS antenna to the wall of the substation (preferably outside).
3.54 in 5.53 in bb Connect the antenna cable to the modem connector marked «GPS».
15 mm 7 mm
0.59 in 0.28 in bb Insert the SIM card(s) (preferably with HU250 switched off).
Note: The GSM antenna requires no outside mounting. It is a short antenna connected to the modem itself. This
93.4 mm
3.78 in
108.5 mm
4.27 in

antenna is installed in factory.


140 mm
5.51 in

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
bb Wear your personal protective equipment (PPE) and comply with the safe electrical work practices. See NFPA 70E in
the USA or applicable local standards.
bb Only qualified person should install this equipment. Such work should be performed only after reading this entire set of
External dimensions of the HU250 enclosure
instructions.
bb Switch off the electric power supply of the HU250 and of all the devices to which the HU250 is connected before any
handling or replacement operation.
DE53837.eps

DE53860.eps bb Always use a properly rated voltage sensing device to confirm that all power is off.
Failure to follow these instructions will result in death or serious injury.

Power supply
The HU250 includes two connectors to connect the power supply. These two connectors are connected
together internally in the HU250. Having two power supply connections can facilitate connection between the
2 modules. No strapping is necessary.
Click! Connect the HU250 as shown in the following diagram.
1 3

DM105361.eps
PS50 HU250 SC150 LV150
Installing the HU250 module on DIN rail Installing the HU250 module on a PS50 enclosure

12V/48V 12V/48V 12V/48V 12V/48V


Installation of a modem box + - - + + - - + + - - + + - - +
Each modem box can be installed or interchanged easily and quickly in the HU250. The modem box is installed
in factory, but if necessary it is possible to dismount it and replace it with another type of modem. To install a Parameters setup
modem box:
Installation of the HU250 module requires no parameters setup. This is performed during the commissioning/
configuration stages.
bb Install the modem box in the required slot on the HU250 (port 1 or Refer to the User manual and the T300 Quick start for any further information.
DE53835.eps

port 2 slot).
bb Press the front panel to insert the rear panel connector in the HU250 Identification
(be careful not to over-force during insertion). The serial number of the HU250 is formed as follows: Year - Week - Work order
bb Tighten the screw on the front panel using a flat or Phillips-head e.g. 15340265 (265th product manufactured, week 34 of the year 2015)
screwdriver to fasten the modem box to the HU250.
Grounding
To withdraw a modem box from its slot, perform the operation in reverse. The HU250 module must be connected to the ground via the mounting DIN rail. The DIN rail helps ensure
Note: When changing a modem box it is also necessary to have the electrical continuity (preferably use a DIN rail in 304L stainless steel to withstand the climatic conditions).
configuration changed by an expert using the Easergy Builder
advanced configuration tool. To do so, refer to the Easergy Builder NOTICE
user guide.
HAZARD OF INCORRECT CURRENT MEASUREMENTS
Modem box
mounting bb The DIN rail on which the HU250 is installed must be grounded and of metallic type and must comply with electrical
screw continuity in all climatic conditions.
bb If the HU250 is installed on a PS50 power supply module, the grounding of the module is done via the PS50's DIN rail,
which must be grounded via a dedicated terminal near the PS50 power input connector. Refer to the Installation Guide of
the PS50 power supply.
Failure to follow these instructions can result in equipment damage.

Operation
Meaning of indications for each color or
DE53834.eps

Once the HU250 has been powered up, some indicator lamps on the front panel may be lit to indicate 1 2 3
certain operating states. indicator lamp state.
The buttons allow the user to perform actions. These indications and actions are summarized in the table below:
Flashing Steady
Part Description of indications and actions Easergy Indicator state Unlit
Red Green Red Green Orange
1 1.1
HU250 states
1.1 HU250 operating 1 1.1 Boot - Fault OK Com fault -
1.2 1.2
1.2 Equipment status - - Major Fault - Minor fault OK
1.3 1.3
1.3 WI-FI access operating (activated by Local mode) - - Fault ON In progress OFF
1.4 1.4 OK
1.4 Communication status with modules (SC150, LV150, PS50,...). AC
Supply
- - Fault - -

2
48/24V
2 2.1 Local/Remote 12V 2.1 - - - Remote - Local
2.1 Remote position: All local controls on switches via the SC150 module are locked (via the front 7 TX EXT

2.2 RX 2.2 - - Local - - Remote


panel and WI-FI) 6
2.3 2.2 Local position: All remote controls are locked 3 2.3
RS232-RS485

2.3 Push button that can be used to change Local/Remote state 3.1 - - - ON - OFF
3.2 - - OFF - - ON
Note: Switching to local mode activates WI-FI access. 3.3 - - - - Locked Non-locked
3G-GPS

3 and 8 Automatic control states and checks HU250 4 3.4


3.1 Automatic control enabled 012345
Supply
3.1 3.2 Automatic control disabled
YYMMXXXX
4.1 AC - - AC OFF AC ON - -
3.2 4.2 48/24V
- - Fault OK - -
3.3 3.3 Automatic control locked 4.3 8.1 12V - - Fault OK - -
4.4
3.4 Automatic control change-of-state button (ON/OFF).
EXT
- - Fault OK - -
4.5
- - Fault OK - -
3.4 8.1 Change-of-state enabling button. The two buttons, change of state and enabling, must be
pressed simultaneously for the change of state to take place. This change is performed (1)
5
simultaneously on all the T300 modules using automatic control functions.
8.1 5.1 - - - - ON OFF
Note: Change of state of the automatic control system by means of the buttons is possible only in
5.2 - - - - ON OFF
Local mode.
5.3 - - - - ON OFF
4 Power supply 10 5 4 9 8
Supply 4.1 Mains power supply operating For HU250: Hereby, Schneider Electric declares that 6
4.1 AC 6.1 - Active - - - Inactive
4.2 48/24V
4.2 48 V/24 V motor pack power supply operating the radio equipment of type communication gateway is in
4.3 4.3 Transmission equipment power supply operating 6.2 - - Fault - - OK
compliance with directive 2014/53/EU. The full text of the
12V
4.4 EXT
4.4 Over consumption on Transmission equipment power supply 6.3 - Active and - No sync - Deactivated
4.5 EU declaration of conformity is available at the following
4.5 Battery status sync
Note: These states correspond to information retransmitted by the PS50 module via Modbus internet address: https://www.schneider-electric.com/en/
communication between modules. When another type of power supply module is used, these indicators download/document/HU250_RED_DoC/.
7 - Transmitting - - - Inactive
7.1 TX

can be customized by configuration via the Easergy Builder advanced configuration tool. For modem boxes: Hereby, Schneider Electric declares 7.2 RX - Receiving - - - Inactive
Customizable indicator lamps that the radio equipement of type cellular modem is in
5 (1) Indicators customizable by configuration. Only default values shown.
5.1 5.1;5.2;5.3 3 unassigned indicator lamps configurable for indication of customized states. compliance with directive 2014/53/EU. The full text of
5.2 Note: Customization of these indicators is performed via the Easergy Builder advanced the EU declaration of conformity is available at the Note: The indications in bold letters correspond to normal operation
5.3 configuration tool. Refer to the Quick start manual. following internet address: https:/www.schneider- (first power up without existence of a potential issue indication).
electric.com/en/download/document/K7_RED_DoC/.
6 2G/3G or 3G/4G modem box indicator lamps
6.1 6.1 Indicator of activity on the mobile network. This indicator flashes in particular during a research of NOTE
6.2 network or a data transfer. Easergy HU250, FCC ID : 2AHHK-EASERGYHU250
6.2 Modem status indicator lamp: lights for a SIM card status or to indicate a problem of connection to the Easergy GSM/3G modem box contains FCC ID : QIPPHS8-P
6.3 This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable
mobile network (low level of reception,...). protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with
6.3 GPS signal reception status indicator. the instruction, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception which can be determined by turning the equipment off and on, the user is encouraged to try to correct interference by one or more
7 RS232-RS485 modem box indicator of the following measures:
7.1 TX
- Reorient or relocate the receiving antenna.
7.1 TX: RS232/RS485 data transmission indicator lamp. - Increase the separation between the equipment and receiver.
7.2 RX
7.2 RX: RS232/RS485 data reception indicator lamp. - Connect the equipment into an outlet on circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
9 Reset This device complies with FCC RF radiation exposure limits set forth for general population. This device must be installed to provide a separation distance of at least 20cm from all persons
and must not be co-located or operating in conjunction with any other antenna or transmitter.
9.1 9.1 Reset button reinitializing all fault current indications on all the SC150 modules and
automatic control locking. Schneider Electric
35 rue Joseph Monier As standards, specifications and designs change from time to time,
10 Indicator test 92500 Rueil Malmaison - France always ask for confirmation of the information given in this publication.
10.1 10.1 Indicator test button for forced setting of lighting of all indicator lamps on the front panel of Phone: +33 (0)1 41 29 70 00
the T300 modules and the external indicator lamp. Makes it possible to detect any anomaly www.schneider-electric.com
concerning the indicator lamps. Publication: Schneider Electric Made in France