Académique Documents
Professionnel Documents
Culture Documents
GUIDELINES
FIRE, LIFE & SAFETY
REVISION 2019
TABLE OF CONTENTS
1. GENERAL 2
1.1 DESIGNER’S RESPONSIBILITIES 2
1.2 CODES AND STANDARDS COMPLIANCE 2
1.3 DESIGN AND TECHNICAL SUBMISSIONS 3
1.4 GENERAL PRINCIPLES OF DESIGN AND INSTALLATION 3
2. FIRE ALARM SYSTEM 4
2.1 DESIGN CRITERIA 4
2.2 SYSTEM REQUIREMENTS AND SPECIFICATION 4
2.2.1 FIRE CONTROL PANEL 4
2.2.2 FIRE ALARM DETECTORS 4
2.2.3 ALARM AND COMMUNICATION DEVICES 5
2.2.4 CABLING & WIRING 5
3. EMERGENCY LIGHTING 6
4. EXIT SIGNS 7
5. FIRE SUPPRESSION 8
6. FIRE HYDRANTS 9
7. FIRE EXTINGUISHERS 10
8. SMOKE CONTROL 11
9. GAS DETECTION 12
Page | 1
1 GENERAL
Page | 2
All references in the National Fire Codes, to "authority having jurisdiction" must be
interpreted as referring to the competent local authority, as appropriate
Best Western must approve the substitution of any standards from NFPA
Page | 3
2 FIRE ALARM SYSTEM
2.1 DESIGN CRITERIA
Equipment and device comprise of Underwriters Laboratory approved.
The installation, location and spacing of equipment and devices must be in accordance with
the latest edition of NFPA 72 or codes specified by the governmental authority having
jurisdiction
Page | 4
Where atriums are present, optical beam detectors must be provided for detection of
smoke in the atrium and operation of the atrium smoke control system
Duct Smoke detectors shall be provided in the supply duct for shut down of associated AHU
and annunciation at the Fire Panel
Page | 5
3 EMERGENCY LIGHTING
Page | 6
4 EXIT SIGNS
Page | 7
5 FIRE SUPPRESSION
Fire suppression systems shall be strictly in accordance with this brief and the local fire
officer’s particular specific requirements
All hotels must have a sprinkler system installed throughout
Sprinklers to be provided to refuse and laundry chutes and laundry rooms where included
Standpipes must be provided in all new build high rise hotels 25 m
Hose valves and/or reels must be provided in accordance with local codes requirements
Fire pump(s) and fire water storage shall be installed
Automatic suppression system shall be provided to main engineering plant room
Automatic suppression system shall be provided to all I.T. and main telephone rooms.
Automatic wet chemical fire suppression shall be provided for cooking ranges in the
kitchens.
Activation of automatic suppression system shall:
o Interface with the main building fire alarm system for annunciation
o Isolate the gas and power supplies to all kitchen equipment automatically on
activation of the suppression system
o Switch off the supply and exhaust ventilation system serving the kitchen unless the
fire suppression system within a grease hood has gone off
o Typically the supply fan is de-energized and the exhaust fan remains operational
Page | 8
6 FIRE HYDRANTS
A fire hydrant or other water supply approved by the fire brigade must be provided for the
Fire Fighting water supplies to the building.
Hydrants must be installed in accordance with local fire officer/authority requirements
Page | 9
7 FIRE EXTINGUISHERS
Handheld extinguishers must be of a type of appropriate to their environment that is CO2
near electrical switch panels, fire blankets in kitchens etc.
The maximum travel distance to a fire extinguisher will not exceed 25 m
Fire extinguishers must be contained in appropriate recessed cabinets in public spaces
according to relevant codes
Fire extinguishers must be mounted in public areas, laundry, plant rooms, corridors and
near storage rooms include otherwise where required by the local codes
Fire extinguishers must be in clear view and reach with no obstruction
Portable Fire extinguishers must be provided and installed for restaurant kitchens in
accordance with NFPA 10 and NFPA 96
Page | 10
8 SMOKE CONTROL
Buildings in excess of 23m (75ft) to the top most occupiable floor or where required by local
codes shall be provided with:
o Stair pressurization in guest floor fire exit staircases
o Lobby relief in guest corridors (for smoke exhaust and to enable the pressurization
system to operate)
o Zone smoke control to all public areas
o Activation of the smoke control system shall be via the area smoke detectors or
sprinkler flow switches, and shall activate the HVAC equipment per the specified
smoke control sequence of operation
o Manual override of these systems shall be provided in a Fireman’s Fire Control
Panel, located adjacent to the Fire Alarm Control Panel.
o The systems shall be controlled direct from the fire detection and alarm system in
hard wire fire rated cabling
o The systems shall be tested to clear “cold smoke” so that exit signs are visible within
10 minutes of activation
o The system’s compliance with NFPA or local codes, the more stringent code shall be
applied
Page | 11
9 GAS DETECTION
Natural gas (methane, LPG, etc.), LP, CO, CO2 gas detection shall be installed where
required by local codes or where a gas intake/fume exhaust point is such that any escape
could cause a buildup of gas that be hazardous to either personnel or the facility
Interface with the fire alarm system and fire suppression system shall be provided to shut
down the gas supply on an alarm
Page | 12