DESIGN ANALYSIS

PANEL BOARD 1

Circuit 1 branch circuit conductor lighting load

I= (24x 20VA)/230V= 480VA/230V= 2.09A (continuous load)

I= 2.09A x 1.25= 2.61A

2
Use 2-3.5 mm THW Cu conductor, 15AT 100AF 2P 10kAIC CB

Circuit 2 branch circuit conductor lighting load

I= (14x 20VA)/230V= 280VA/230V= 1.22A (continuous load)

I= 1.22A x 1.25= 1.52A

2
Use 2-3.5 mm THW Cu conductor, 15AT 100AF 2P 10kAIC CB

Circuit 3 branch circuit conductor lighting load

I= (21x 20VA)/230V= 420VA/230V= 1.83A (continuous load)

I= 1.83A x 1.25= 2.28A

2
Use 2-3.5 mm THW Cu conductor, 15AT 100AF 2P 10kAIC CB

Circuit 4 convenience outlet electrical load

I= (11x 180VA)/230V= 1890VA/230V= 8.61A

2
Use 2-3.5 mm THW Cu conductor, 20AT 100AF 2P 10kAIC CB

Circuit 5 convenience outlet electrical load

I= (12x 180VA)/230V= 2160VA/230V= 9.39A

2
Use 2-3.5 mm THW Cu conductor, 20AT 100AF 2P 10kAIC CB

Circuit 6 convenience outlet electrical load

I= (8x 180VA)/230V= 1440VA/230V= 6.26A

2
Use 2-3.5 mm THW Cu conductor, 20AT 100AF 2P 10kAIC CB

Circuit 7 convenience outlet electrical load

I= (20x 180VA)/230V= 3600VA/230V= 15.65A


2
Use 2-3.5 mm THW Cu conductor, 20AT 100AF 2P 10kAIC CB

Circuit 8 chiller/freezer electrical load

I= 200VA/230V= 0.87A (continuous load)

I= 0.87A x 1.25= 1.09A

2
Use 2-3.5 mm THW Cu conductor, 20AT 100AF 2P 10kAIC CB

Circuit 9 chiller/freezer electrical load

I= 200VA/230V= 0.87A (continuous load)

I= 0.87A x 1.25= 1.09A

2
Use 2-3.5 mm THW Cu conductor, 20AT 100AF 2P 10kAIC CB

Circuit 10 chiller/freezer electrical load

I= 200VA/230V= 0.87A (continuous load)

I= 0.87A x 1.25= 1.09A

2
Use 2-3.5 mm THW Cu conductor, 20AT 100AF 2P 10kAIC CB

Circuit 11 chiller/freezer electrical load

I= 200VA/230V= 0.87A (continuous load)

I= 0.87A x 1.25= 1.09A

2
Use 2-3.5 mm THW Cu conductor, 20AT 100AF 2P 10kAIC CB

Circuit 12 A.C.U electrical load (0.5HP)

I= 1127VA/230V= 4.9A (continuous load)

I= 4.9A x 1.25= 6.125A

2
Use 2-3.5 mm THW Cu conductor, 20AT 100AF 2P 10kAIC CB

Circuit 13 A.C.U electrical load (0.5HP)

I= 1127VA/230V= 4.9A (continuous load)

I= 4.9A x 1.25= 6.125A

2
Use 2-3.5 mm THW Cu conductor, 20AT 100AF 2P 10kAIC CB
Circuit 14 A.C.U electrical load (0.5HP)

I= 1127VA/230V= 4.9A (continuous load)

I= 4.9A x 1.25= 6.125A

2
Use 2-3.5 mm THW Cu conductor, 20AT 100AF 2P 10kAIC CB

Circuit 15 A.C.U electrical load (1HP)

I= 1840VA/230V= 8A (continuous load)

I= 8A x 1.25= 10A

2
Use 2-3.5 mm THW Cu conductor, 20AT 100AF 2P 10kAIC CB

Circuit 16 A.C.U electrical load (0.5HP)

I= 1127VA/230V= 4.9A (continuous load)

I= 4.9A x 1.25= 6.125A

2
Use 2-3.5 mm THW Cu conductor, 20AT 100AF 2P 10kAIC CB

Circuit 17 A.C.U electrical load (1.5HP)

I= 2300VA/230V= 10A (continuous load)

I= 10A x 1.25= 12.5A

2
Use 2-3.5 mm THW Cu conductor, 20AT 100AF 2P 10kAIC CB

Circuit 18 A.C.U electrical load (0.75HP)

I= 1587VA/230V= 6.9A (continuous load)

I= 6.9A x 1.25= 8.625A

2
Use 2-3.5 mm THW Cu conductor, 20AT 100AF 2P 10kAIC CB

Circuit 19 A.C.U electrical load (0.75HP)

I= 1587VA/230V= 6.9A (continuous load)

I= 6.9A x 1.25= 8.625A

2
Use 2-3.5 mm THW Cu conductor, 20AT 100AF 2P 10kAIC CB

Circuit 20 A.C.U electrical load (1HP)


I= 1840VA/230V= 8A (continuous load)

I= 8A x 1.25= 10A

2
Use 2-3.5 mm THW Cu conductor, 20AT 100AF 2P 10kAIC CB

Circuit 21 A.C.U electrical load (1HP)

I= 2300VA/230V= 10A (continuous load)

I= 10A x 1.25= 12.5A

2
Use 2-3.5 mm THW Cu conductor, 20AT 100AF 2P 10kAIC CB

Circuit 22 meat/fish slicer and grinder electrical load

I= 450VA/230V= 1.96A

2
Use 2-3.5 mm THW Cu conductor, 20AT 100AF 2P 10kAIC CB

Circuit 23 refrigerator electrical load

I= 200VA/230V= 0.87A (continuous load)

I= 0.87A x 1.25= 1.09A

2
Use 2-3.5 mm THW Cu conductor, 20AT 100AF 2P 10kAIC CB

Circuit 24 Service Entrance for P2

Circuit 25 SPARE

Circuit 26 SPARE

Circuit 27 SPARE

Circuit 28 SPARE

Service Entrance for Panel Board 1

Total Current= (47.235A x 1.7321) + 59.94A + (19A x 0.25)= 146.51A

2
Use 3-38 mm THW Cu conductor, 160AT 100AF 3P 10kAIC CB