As per submitted drawings, Proposed box culverts are balancing in nature. Please Clarify.
Reply:-
As per IRC-SP-13 , Longitudinal slope of 0.1 % should be provided to bottom slab of culvert
Reply:-
Same invert levels at upstream & Downstream side are shown in drawing. However, Invert
levels at upstream & Downstream side should be decided by considering longitudinal slope
of bottom slab
Reply:-
W-beam crash barrier is shown in drawing. However, Thrie beam crash barrier should be
provided as per SCHEDULE-C, Clause no.2.2.7.
Reply:-
Floor aprons shown in drawing is not complying with MORTH specifications & IRC-SP-
13. Please amend the same.
Reply:-
Please submit the design calculations for distribution reinforcement in bottom slab & Top
slab.
Reply:-
2. "DETAIL - 4" shown in drawing seems to be incorrect. Please check & amend the drawing
accordingly.
Reply:-