Vous êtes sur la page 1sur 9

INSTALLATION GUIDE

Single Duct VAV Package


DNT-VAV-DG1 (Rev 1.0)
Document Edition 1.1

Product Description

The DNT-VAV-DG1 package consists of an


intelligent LCD thermostat (DNT-T103) and a
remote termination Module (DTM-VAV-DG1) for
single duct VAV applications.

The thermostat has an LCD display, four pushbuttons


for setpoint and occupancy override, and contains a
configurable VAV algorithm suitable for controlling
the termination Module.

The remote termination Module, which is designed to


mount on the side of the VAV box, comes complete
with a damper actuator, flow sensor, and housing. It
also has termination points for optional control of a
fan or a single stage of auxiliary reheat.

Related Documents

It is highly recommended that the following documents are available for Reference while installing this product:

• Delta Controls Wiring Guidelines (for detailed Power, I/O & Network wiring instructions)
• DSC/DAC Release Notes (for information on the firmware loaded in this device)
• Delta V3 System Description (Delta Products System Architecture description)

Important Information

1. When using the DNT-T103 with the DG1 termination board package the outputs should always be set
to internal power. Attempting to use the external power option with the DG1 termination board could
result in equipment damage.
2. The Termination Board mounted to the VAV/VVT box is not a programmable controller. All control
and network functions are performed by the BACstat
3. BACstats are not flash loadable in the field – an upgrade requires swapping out physical product.

Document Edition 1.1 Page 1 of 9


Single Duct VAV Package DNT-VAV-DG1 (Rev 1.0) Installation Guide

Mounting the VAV

WARNING:
Do not open the actuator or the controller.
Place the actuator on the damper shaft so that the front side, (label) of the actuator is accessible.

Steps to mounting the VAV:


1. According to the Damper Shaft sizes as indicated above, ensure that the shaft insert is correct for the size of the damper
shaft.
The Actuator can be used with 3/8, 1/2, and 5/8 inch damper shaft sizes:

• A 1/2 inch shaft size guide is factory installed. If the damper shaft size is not 1/2 inch, then remove the shaft guide
from actuator through the damper shaft hole on bottom of product.
• 3/8 inch shaft adjustment: Remove the 1/2 inch shaft size guide, then install the 3/8 inch shaft insert so that the
raised tabs are inserted last, through the damper shaft hole on bottom of product.
• 5/8 inch shaft adjustment: remove any shaft guides or adapters from the actuator through the damper shaft hole on
bottom of product.
2. The actuator on one end of the Integrated Housing fits over the damper shaft on the VAV box. Slide the controller over
the damper shaft.
3. Secure the plastic housing to the VAV box with a sheet metal screw (through the mounting slots and brass bushing
provided). It is recommended that the screw be positioned near the center of the slot (triangle mark in the plastic).
4. Determine whether the damper will rotate clockwise or counterclockwise to open, then secure the actuator to the
damper shaft as follows:

Clockwise to Open Counter Clockwise to Open

• Remove power, if connected.


• Slide the manual override switch to manual, and move the adjustment lever to the position as indicated by the
drawing. Return the switch to automatic.
• Tighten 3mm allen-screw on to damper shaft, torque 55-60 lb-in (6.5-7 Nm).

5. Ensure that the damper is fully closed. The indicator on the end of the damper shaft should be vertical (up-down).
6. To ensure proper functionality of the damper, depress the clutch, and stroke the damper fully in both directions.

Mounting the Thermostat


The thermostat backplate is designed for mounting directly on standard North American, European or
Australian electrical boxes.

Page 2 of 9 Document Edition 1.1


Delta Controls

Cautions and Warnings

CAUTION:
Installations requiring CE conformance
All wiring for CE rated products must use an extra low voltage (SELV) or protective extra low voltage
(PELV) transformer. Use safety isolating transformers, (Class III transformer) per EN61558.
The transformer must be rated for 100% duty cycle.

WARNING:
WARNING
The controller is an Electro-statically sensitive device. Proper ESD protection (ground strap)
should be used when installing this product so that damage to the product does not occur.

Wiring General

All wiring must conform to NEC and local codes and regulations.
Use earth ground isolating step-down Class 2 transformers. Do not use auto-transformers.
Determine supply transformer rating by summing total VA of product and output loads.
• CAUTION – Risk of Electric Shock – More than one disconnect switch may be required to de-energize the
equipment before servicing.
• CAUTION – Input Class 2 Power Supplies are interconnected. To Reduce the Risk of Fire or Electric Shock,
Use only Class 2 sources Suitable for Interconnection.
• All terminals are Acceptable for Class 2 Circuit Connections Only.
• Select an external power supply that is certified for safety for the correct destination country and that has an
output rating, which is considered an NEC Class 2 or Limited Power Source with the rating not to exceed 30 V
rms, 42.4 V peak, 100 VA.
• Use copper conductors only.
• Apply minimum 6.0 lb-in torque for tightening field wires into the terminal blocks.

Document Edition 1.1 Page 3 of 9


Single Duct VAV Package DNT-VAV-DG1 (Rev 1.0) Installation Guide

Power

This product is designed to be powered from a 24V AC Class 2 power supply. Typically power is applied to the
Termination Module and is fed down to the DNT-T103 through the “Controller” terminal block.
A single transformer may be used to power multiple controllers and/or auxiliary field devices (actuators etc),
provided the following conditions are met:
All devices MUST be ½ wave rectified. Mixing power between ½ wave and full wave rectified
devices will damage both the transformer and connected equipment.
The transformer is properly sized, including line losses for the total VA requirements
Polarity is observed between controllers (with respect to 24~ and Gnd).
Each device is grounded as shown in the diagram below. (This is important to protect equipment and
ensure a common ground reference for RS-485 communications.)
The transformer secondary is fused for it’s maximum rated load. (4A max for Class 2 circuits.)

Page 4 of 9 Document Edition 1.1


Delta Controls

Network Communications Setup


The DNT-T103 communicates on a BACnet MS/TP network at a default speed of 76800 bps. Refer to the
ORCAview Technical Reference Manual for further detail on configuring the BACnet MS/TP network or
changing baud rates, etc.

RS485 Wiring

Notes:
1. The proper spec’d cabling must be used to ensure reliable communications. (22-24 AWG twisted pair, 100-120
ohms impedance, 17 pF/ft or lower capacitance, with a braided or aluminum foil shield.)
2. Controllers should always be wired together in a daisy-chain fashion attempting to connect them using a starred
or bus configuration will cause problems on the network.
3. Networks with a total length greater than 4000 ft or with more than 50 devices require a repeater (RPT-768)
4. LINKnet networks with only 1-2 devices and less then 100 ft of cable length do not require network terminators.

For much more detailed information on MS/TP and LINKnet wiring/installation refer to the Delta Controls Wiring
Guidelines document.

CAUTION:
The network shield and any other bare wires should be bent back and taped to ensure that they do not come
into contact with the board electronics and cause a short. Otherwise you run the risk of damaging the
BACstat.

CAUTION:
Do not use the same cabling for network and controller connections, as it will not meet the balanced cable
requirements for the MS/TP networks. Use a separate cable for the network connections.

Document Edition 1.1 Page 5 of 9


Single Duct VAV Package DNT-VAV-DG1 (Rev 1.0) Installation Guide

Input & Output Wiring

Inputs and outputs on the DNT-T103 follow the same general wiring connection diagrams as other Delta
products. Refer to Delta Controls Wiring Guidelines for more details.

Input Wiring

Input Configuration Jumpers


The input must be configured to accept the signal used by the input device. Place
the jumper for each input in the correct location on the Input Type Selector Block.
10K
The diagram to the right shows the factory default selection of 10 KΩ.

5V
10K For 10 KΩ Thermistor temperature sensors,
as well as Dry Contact binary inputs.
10V
5V For sensors that use a 0 to 5 VDC signal.
10V For sensors that use a 0 to 10 VDC signal.

Output Wiring

BINARY OUTPUT POWER SOURCE


INTERNAL
The binary triac outputs can be selected to use either an internal or
external power source by placing the two jumpers in the correct locations.
The diagram to the right shows the factory default selection of External
Power Source.
EXTERNAL
Internal 24 VAC Power is provided internally from within the board
right to the output terminals. No external transformer is
required. The associated triac outputs are “hot” contacts. Note
that the power supply should be sized appropriately to handle
the additional loading.

External Power needs to be provided externally to the board from a


nearby transformer appropriately connected to the output
wiring. The associated triac outputs are not “hot” contacts,
except by means of the external transformer.

NOTE: Triacs are solid-state components that are only appropriate for
switching 24 VAC. They cannot be used to switch DC voltage. They
also have a small leakage current and may not be appropriate for certain
“dry contact” applications.

CAUTION:
When using the DNT-T103 with the DG1 termination board package this jumper should always be set to
internal power. Attempting to use the external power option with the DG1 termination board could result in
equipment damage.

Page 6 of 9 Document Edition 1.1


Delta Controls

Wiring Diagram – BACstat / Termination Module Connections

Factory wired to
Damper Actuator
AUX CONTROLLER DAMPER

FLO AUX DPR POWER


GND OP3 24~ GND IP2 OP1 COM OP2 COM OP3 OP2 OP1 F/B 24~ GND
VLT RED ORN P1 P2 P3

PWR PWR
24~ GND 24~ GND

LO HI(+)
1 2 1 2 1 2 3 4 5 6 1 2

Air Flow
GND L H
Fan or Reheat
If a multi-conductor cable is Flow Sensor
used then DC components
must be shielded from AC
components (FAN and
24~). If shielding is not
24VAC
used then a multi-conductor
may not be used.

Shielded MS/TP Network 24VAC field


cable. See Network Cabling installed power
Requirements for specs. source

Optional
PWR NET
COM
Disconnect
+ - COM
24~ GND IP2 OP1 1&2 OP2 3 OP3
Switch

L1 N
1 2 3 4 5 1 2 3 4 5

Shield wire 120 or 277V


connected in
electrical box
DNT-T103 Field Installed
Power Source
using wire nut

CAUTION:
If a multi-conductor cable is used then DC components must be shielded from AC components (FAN and
24~). If shielding is not used then a multi-conductor may not be used.
AC signals will interfere will DC signal levels if in extremely close proximity without the use of shielding.

CAUTION:
The network shield and any other bare wires should be bent back and taped to ensure that they do not come
into contact with the board electronics and cause a short. Otherwise you run the risk of damaging the
BACstat.

Document Edition 1.1 Page 7 of 9


Single Duct VAV Package DNT-VAV-DG1 (Rev 1.0) Installation Guide

Product Specifications

Power Requirements 24 VAC Class 2

Power Consumption 48 VA max combined DNT and DTM (with fully loaded Universal Outputs).
38 VA max for DNT (with fully loaded Universal Outputs).
10 VA max for DTM
Note: Typically the thermostat is powered through the power out connection on the termination
module.

Ambient Rating 32° to 131°F (0° to 55°C), 10 to 90% RH (non condensing)

Actuator The DNT-VAV-DG1 can be ordered with either a Siemens or a Belimo


actuator
Siemens Specs
• 44 in-lbs (nominal torque)
• 90 to 108 seconds running time
• 90º maximum angle of rotation
• External slide knob for manual override
• Less than 35 db (A) noise level
• 2 VA
Belimo Specs
• 35 in-lbs (nominal torque)
• 95 seconds running time (Load Independent)
• 95º maximum angle of rotation
• External slide knob for manual override
• Less than 35 db (A) noise level
• 3 VA

Differential Pressure Sensor 0 to 1” H2O (0 to 248.8 Pa)


0.5 – 4.5 VDC Output

Tubing Flow Sensor tubing must be 5/32 inch inside diameter

Technology 8-bit Processor c/w internal A/D, Flash, and RAM


3-value LCD c/w icons (96 total segments)

Communication Ports NET1 – BACnet MS/TP LAN for connecting to a network of DAC/DNT devices.
Service Port
• RJ-11 jack for PC/laptop connection (requires a Delta CON-768 RS232
to RS485 converter).

Internal Temperature Input Thermistor Input – 10,000 ohm @ 77 ºF (25 ºC)


Accuracy of +/- 0.36 ºF from 32 - 158 ºF (+/- 0.2 ºC from 0 - 70 ºC)
Display Resolution of 0.1 ºF or ºC
Stability of 0.24 ºF over 5 years (0.13 ºC)

Additional Inputs 1 Universal Inputs (10 bit), jumper configurable for the following input types:
• 0-5 VDC

Page 8 of 9 Document Edition 1.1


Delta Controls

• 0-10 VDC
• 10 KΩ Thermistor
• Dry Contact (using 10 KΩ Thermistor jumper setting)

Outputs 3 Binary Triac Outputs


• Switching 24 VAC @ 0.5 Amp maximum per output
• Leakage Current per Triac is 160 µA

Listings BACnet Testing Labs – BTL Listed (with at least V322 firmware).
Refer to http://www.bacnetassociation.org/bacnet_testing.htm
UL916

Compliance CE – EMC Directive 89/336/EEC


FCC – Class A
ICES-003 – Class A

Model Numbers
Order the controller according to the following product number:

Model Name Description


DNT-VAV-DG1-A DNT-T103, and DG1 Termination Module w/ Siemens Actuator
DNT-VAV-DG1-A-B DNT-T103, and DG1 Termination Module w/ Belimo Actuator

Document Edition 1.1 Page 9 of 9

Vous aimerez peut-être aussi