ECP NUEVO TRANSFORMADOR DE LA SUBESTACION

MOTUPE 60/22.9/10 KV

ANEXO N°8

PLANILLAS DE AJUSTES DE LOS


RELES DE PROTECCION

Revisión: 01 Página 167 de 184 Fecha: 30-10-2008


ECP NUEVO TRANSFORMADOR DE LA SUBESTACION
MOTUPE 60/22.9/10 KV

S.E. MOTUPE: TRANSFORMADOR DE POTENCIA 7-9/7-9/2-3 MVA,


60/22.9/10 KV – RELE DIFERENCIAL GENERAL
ELECTRIC T60

\MOTUPE\
DEVICE DEFINITION
ORDER CODE: T60-H03-HCH-F8F-H6A-M8H
VERSION: 5.4X
DESCRIPTION: (NONE)
TEXT COLOR

SYSTEM SETUP
AC INPUTS
CURRENT

CT F1: Phase CT Primary 100 A


CT F1: Phase CT Secondary 1A
CT F1: Ground CT Primary 100 A
CT F1: Ground CT Secondary 1A
CT M1: Phase CT Primary 250 A
CT M1: Phase CT Secondary 1A
CT M1: Ground CT Primary 250 A
CT M1: Ground CT Secondary 1A
CT M5: Phase CT Primary 200 A
CT M5: Phase CT Secondary 1A
CT M5: Ground CT Primary 200 A
CT M5: Ground CT Secondary 1A

VOLTAGE

VT F5: Phase VT Connection Wye


VT F5: Phase VT Secondary 57.7 V
VT F5: Phase VT Ratio 600.00 :1
VT F5: Auxiliary VT Connection Vag
VT F5: Auxiliary VT Secondary 115.0 V
VT F5: Auxiliary VT Ratio 115.00 :1

POWER SYSTEM

Nominal Frequency 60 Hz
Phase Rotation ABC
Frequency And Phase Reference SRC 1
Frequency Tracking Function Disabled

SIGNAL SOURCES

SOURCE 1: Name SRC 1


SOURCE 1: Phase CT F1
SOURCE 1: Ground CT F1
SOURCE 1: Phase VT F5
SOURCE 1: Auxiliary VT None
SOURCE 2: Name SRC 2
SOURCE 2: Phase CT M1

Revisión: 01 Página 168 de 184 Fecha: 30-10-2008


ECP NUEVO TRANSFORMADOR DE LA SUBESTACION
MOTUPE 60/22.9/10 KV

SOURCE 2: Ground CT M1
SOURCE 2: Phase VT None
SOURCE 2: Auxiliary VT None
SOURCE 3: Name SRC 3
SOURCE 3: Phase CT M5
SOURCE 3: Ground CT M5
SOURCE 3: Phase VT None
SOURCE 3: Auxiliary VT None

TRANSFORMER
GENERAL

Number Of Windings 3
Reference Winding Selection 0
Phase Compensation Internal (software)
Load Loss At Rated Load 100 kW
Rated Winding Temperature Rise 65°C (oil)
No Load Loss 10 kW
Type Of Cooling OA
Top-oil Rise Over Ambient 35 °C
Thermal Capacity 100.00 kWh/°C
Winding Thermal Time Constant 2.00 min

WINDINGS

WINDING 1: Source SRC 1


WINDING 1: Rated MVA 7.000 MVA
WINDING 1: Nominal Phs-phs Voltage 60.000 kV
WINDING 1: Connection Wye
WINDING 1: Grounding Within zone
WINDING 1: Angle Wrt Winding 1 0.0 deg
WINDING 1: Resistance 10.0000 ohms
WINDING 2: Source SRC 2
WINDING 2: Rated MVA 7.000 MVA
WINDING 2: Nominal Phs-phs Voltage 22.900 kV
WINDING 2: Connection Wye
WINDING 2: Grounding Within zone
WINDING 2: Angle Wrt Winding 1 0.0 deg
WINDING 2: Resistance 10.0000 ohms
WINDING 3: Source SRC 3
WINDING 3: Rated MVA 2.000 MVA
WINDING 3: Nominal Phs-phs Voltage 10.000 kV
WINDING 3: Connection Delta
WINDING 3: Grounding Not within zone
WINDING 3: Angle Wrt Winding 1 -150.0 deg
WINDING 3: Resistance 10.0000 ohms

GROUPED ELEMENTS
GROUP 1
TRANSFORMER
PERCENT DIFFERENTIAL [GROUP 1]

Revisión: 01 Página 169 de 184 Fecha: 30-10-2008


ECP NUEVO TRANSFORMADOR DE LA SUBESTACION
MOTUPE 60/22.9/10 KV

Function Enabled
Pickup 0.250 pu
Slope 1 30 %
Break 1 2.000 pu
Break 2 8.000 pu
Slope 2 60 %
Inrush Inhibit Function Adapt. 2nd
Inrush Inhibit Mode Per phase
Inrush Inhibit Level 15.0 % fo
Overexcitation Inhibit Function 5th
Overexcitation Inhibit Level 35.0 % fo
Block OFF
Target Latched
Events Enabled

INSTANTANEOUS DIFFERENTIAL [GROUP 1]

Function Enabled
Pickup 8.000 pu
Block OFF
Target Latched
Events Enabled

PHASE CURRENT
PHASE TOC [GROUP 1]

PHASE TOC1: Function Enabled


PHASE TOC1: Signal Source SRC 1
PHASE TOC1: Input Phasor
PHASE TOC1: Pickup 1.100 pu
PHASE TOC1: Curve IEC Curve A
PHASE TOC1: TD Multiplier 0.13
PHASE TOC1: Reset Instantaneous
PHASE TOC1: Voltage Restraint Disabled
PHASE TOC1: Block A OFF
PHASE TOC1: Block B OFF
PHASE TOC1: Block C OFF
PHASE TOC1: Target Latched
PHASE TOC1: Events Enabled
PHASE TOC2: Function Enabled
PHASE TOC2: Signal Source SRC 2
PHASE TOC2: Input Phasor
PHASE TOC2: Pickup 1.200 pu
PHASE TOC2: Curve IEC Curve A
PHASE TOC2: TD Multiplier 0.07
PHASE TOC2: Reset Instantaneous
PHASE TOC2: Voltage Restraint Disabled
PHASE TOC2: Block A OFF
PHASE TOC2: Block B OFF
PHASE TOC2: Block C OFF
PHASE TOC2: Target Latched
PHASE TOC2: Events Enabled
PHASE TOC3: Function Enabled
PHASE TOC3: Signal Source SRC 3
PHASE TOC3: Input Phasor

Revisión: 01 Página 170 de 184 Fecha: 30-10-2008


ECP NUEVO TRANSFORMADOR DE LA SUBESTACION
MOTUPE 60/22.9/10 KV

PHASE TOC3: Pickup 1.100 pu


PHASE TOC3: Curve IEC Curve A
PHASE TOC3: TD Multiplier 0.13
PHASE TOC3: Reset Instantaneous
PHASE TOC3: Voltage Restraint Disabled
PHASE TOC3: Block A OFF
PHASE TOC3: Block B OFF
PHASE TOC3: Block C OFF
PHASE TOC3: Target Latched
PHASE TOC3: Events Enabled

PHASE IOC [GROUP 1]

PHASE IOC1: Function Enabled


PHASE IOC1: Source SRC 1
PHASE IOC1: Pickup 5.000 pu
PHASE IOC1: Delay 0.25 s
PHASE IOC1: Reset Delay 0.00 s
PHASE IOC1: Block A OFF
PHASE IOC1: Block B OFF
PHASE IOC1: Block C OFF
PHASE IOC1: Target Latched
PHASE IOC1: Events Enabled
PHASE IOC2: Function Enabled
PHASE IOC2: Source SRC 2
PHASE IOC2: Pickup 2.800 pu
PHASE IOC2: Delay 0.20 s
PHASE IOC2: Reset Delay 0.00 s
PHASE IOC2: Block A OFF
PHASE IOC2: Block B OFF
PHASE IOC2: Block C OFF
PHASE IOC2: Target Latched
PHASE IOC2: Events Enabled
PHASE IOC3: Function Enabled
PHASE IOC3: Source SRC 3
PHASE IOC3: Pickup 7.500 pu
PHASE IOC3: Delay 0.20 s
PHASE IOC3: Reset Delay 0.00 s
PHASE IOC3: Block A OFF
PHASE IOC3: Block B OFF
PHASE IOC3: Block C OFF
PHASE IOC3: Target Latched
PHASE IOC3: Events Enabled

NEUTRAL CURRENT
NEUTRAL TOC [GROUP 1]

NEUTRAL TOC1: Function Enabled


NEUTRAL TOC1: Source SRC 1
NEUTRAL TOC1: Input Phasor
NEUTRAL TOC1: Pickup 0.250 pu
NEUTRAL TOC1: Curve IEC Curve A
NEUTRAL TOC1: TD Multiplier 0.11
NEUTRAL TOC1: Reset Instantaneous
NEUTRAL TOC1: Block OFF

Revisión: 01 Página 171 de 184 Fecha: 30-10-2008


ECP NUEVO TRANSFORMADOR DE LA SUBESTACION
MOTUPE 60/22.9/10 KV

NEUTRAL TOC1: Target Latched


NEUTRAL TOC1: Events Enabled
NEUTRAL TOC2: Function Enabled
NEUTRAL TOC2: Source SRC 2
NEUTRAL TOC2: Input Phasor
NEUTRAL TOC2: Pickup 0.300 pu
NEUTRAL TOC2: Curve IEC Curve A
NEUTRAL TOC2: TD Multiplier 0.12
NEUTRAL TOC2: Reset Instantaneous
NEUTRAL TOC2: Block OFF
NEUTRAL TOC2: Target Latched
NEUTRAL TOC2: Events Enabled

NEUTRAL IOC [GROUP 1]

NEUTRAL IOC1: Function Enabled


NEUTRAL IOC1: Source SRC 1
NEUTRAL IOC1: Pickup 2.200 pu
NEUTRAL IOC1: Delay 0.25 s
NEUTRAL IOC1: Reset Delay 0.00 s
NEUTRAL IOC1: Block OFF
NEUTRAL IOC1: Target Latched
NEUTRAL IOC1: Events Enabled
NEUTRAL IOC2: Function Enabled
NEUTRAL IOC2: Source SRC 2
NEUTRAL IOC2: Pickup 4.000 pu
NEUTRAL IOC2: Delay 0.25 s
NEUTRAL IOC2: Reset Delay 0.00 s
NEUTRAL IOC2: Block OFF
NEUTRAL IOC2: Target Latched
NEUTRAL IOC2: Events Enabled

Revisión: 01 Página 172 de 184 Fecha: 30-10-2008


ECP NUEVO TRANSFORMADOR DE LA SUBESTACION
MOTUPE 60/22.9/10 KV

S.E. MOTUPE: TRANSFORMADOR DE POTENCIA 7-9/7-9/2-3 MVA,


60/22.9/10 KV – RELE DE SOBRECORRIENTE
GENERAL ELECTRIC F650 – LADO 60 KV
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup
File Name: MOTUPE 60KV.650
Comment: MOTUPE 60KV
Model: F650***F2G0***
Version: 1.70
Part: 5.8.4.0

SETPOINTS
SERIAL PORTS
NAME VALUE UNIT
COM1 Baud Rate 19200
COM2 Baud Rate 19200
Parity NONE

OSCILLOGRAPHY
NAME VALUE UNIT
Function ENABLED
Trigger Position 30 [5 : 95] %
Samples/Cycle 64
Max. Number Osc. 4 [1 : 20]
Automatic Overwrite DISABLED
Snapshot Events ENABLED

GENERAL SETTINGS
NAME VALUE UNIT
Phase CT Ratio 100. [1 : 6000]
Ground CT Ratio 100. [1 : 6000]
Stv Ground CT Ratio 1. [1 : 6000]
Phase VT Ratio 1. [1 : 6000]
Phase VT Connection WYE
Nominal Voltage 100.0 [1.0 : 250.0] V
Nominal Frequency 60 Hz
Phase Rotation ABC
Frequency Reference VI
Auxiliary Voltage VX
Snapshot Events DISABLED

PHASE TOC HIGH 1


NAME VALUE UNIT
Function ENABLED
Input PHASOR(DFT)
Pickup Level 1.10 [0.05 : 160.00] A
Curve IEC Curve A
TD Multiplier 0.13 [0.00 : 900.00] s
Reset INSTANTANEOUS
Voltage Restraint DISABLED
Snapshot Events ENABLED

PHASE IOC HIGH 1


NAME VALUE UNIT
Function ENABLED
Input PHASOR(DFT)
Pickup Level 5.00 [0.05 : 160.00] A
Trip Delay 0.25 [0.00 : 900.00] s
Reset Delay 0.00 [0.00 : 900.00] s
Snapshot Events ENABLED

Revisión: 01 Página 173 de 184 Fecha: 30-10-2008


ECP NUEVO TRANSFORMADOR DE LA SUBESTACION
MOTUPE 60/22.9/10 KV

NEUTRAL TOC 1
NAME VALUE UNIT
Function ENABLED
Pickup Level 0.25 [0.05 : 160.00] A
Curve IEC Curve A
TD Multiplier 0.11 [0.00 : 900.00] s
Reset INSTANTANEOUS
Snapshot Events ENABLED

NEUTRAL IOC 1
NAME VALUE UNIT
Function ENABLED
Pickup Level 2.20 [0.05 : 160.00] A
Trip Delay 0.25 [0.00 : 900.00] s
Reset Delay 0.00 [0.00 : 900.00] s
Snapshot Events ENABLED

SETTING GROUP
NAME VALUE UNIT
Function ENABLED
Active Group GROUP 1
Snapshot Events ENABLED

Revisión: 01 Página 174 de 184 Fecha: 30-10-2008


ECP NUEVO TRANSFORMADOR DE LA SUBESTACION
MOTUPE 60/22.9/10 KV

S.E. MOTUPE: TRANSFORMADOR DE POTENCIA 7-9/7-9/2-3 MVA,


60/22.9/10 KV – RELE DE SOBRECORRIENTE
GENERAL ELECTRIC F650 – LADO 22.9 KV

GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup


File Name: MOTUPE 22.9.650
Comment: MOTUPE 60KV
Model: F650***F2G0***
Version: 1.70
Part: 5.8.4.0

SETPOINTS
SERIAL PORTS
NAME VALUE UNIT
COM1 Baud Rate 19200
COM2 Baud Rate 19200
Parity NONE

OSCILLOGRAPHY
NAME VALUE UNIT
Function ENABLED
Trigger Position 30 [5 : 95] %
Samples/Cycle 64
Max. Number Osc. 4 [1 : 20]
Automatic Overwrite DISABLED
Snapshot Events ENABLED

GENERAL SETTINGS
NAME VALUE UNIT
Phase CT Ratio 250. [1 : 6000]
Ground CT Ratio 250. [1 : 6000]
Stv Ground CT Ratio 1. [1 : 6000]
Phase VT Ratio 1. [1 : 6000]
Phase VT Connection WYE
Nominal Voltage 100.0 [1.0 : 250.0] V
Nominal Frequency 60 Hz
Phase Rotation ABC
Frequency Reference VI
Auxiliary Voltage VX
Snapshot Events DISABLED

PHASE TOC HIGH 1


NAME VALUE UNIT
Function ENABLED
Input PHASOR(DFT)
Pickup Level 1.20 [0.05 : 160.00] A
Curve IEC Curve A
TD Multiplier 0.07 [0.00 : 900.00] s
Reset INSTANTANEOUS
Voltage Restraint DISABLED
Snapshot Events ENABLED

PHASE IOC HIGH 1


NAME VALUE UNIT
Function ENABLED
Input PHASOR(DFT)
Pickup Level 2.80 [0.05 : 160.00] A
Trip Delay 0.20 [0.00 : 900.00] s
Reset Delay 0.00 [0.00 : 900.00] s
Snapshot Events ENABLED

Revisión: 01 Página 175 de 184 Fecha: 30-10-2008


ECP NUEVO TRANSFORMADOR DE LA SUBESTACION
MOTUPE 60/22.9/10 KV

NEUTRAL TOC 1
NAME VALUE UNIT
Function ENABLED
Pickup Level 0.30 [0.05 : 160.00] A
Curve IEC Curve A
TD Multiplier 0.12 [0.00 : 900.00] s
Reset INSTANTANEOUS
Snapshot Events ENABLED

NEUTRAL IOC 1
NAME VALUE UNIT
Function ENABLED
Pickup Level 4.00 [0.05 : 160.00] A
Trip Delay 0.25 [0.00 : 900.00] s
Reset Delay 0.00 [0.00 : 900.00] s
Snapshot Events ENABLED

SETTING GROUP
NAME VALUE UNIT
Function ENABLED
Active Group GROUP 1
Snapshot Events ENABLED

Revisión: 01 Página 176 de 184 Fecha: 30-10-2008


ECP NUEVO TRANSFORMADOR DE LA SUBESTACION
MOTUPE 60/22.9/10 KV

S.E. MOTUPE: TRANSFORMADOR DE POTENCIA 7-9/7-9/2-3 MVA,


60/22.9/10 KV – RELE DE SOBRECORRIENTE
GENERAL ELECTRIC F650 – LADO 10 KV

GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup


File Name: MOTUPE 10KV.650
Comment: MOTUPE 60KV
Model: F650***F2G0***
Version: 1.70
Part: 5.8.4.0

SETPOINTS
SERIAL PORTS
NAME VALUE UNIT
COM1 Baud Rate 19200
COM2 Baud Rate 19200
Parity NONE

OSCILLOGRAPHY
NAME VALUE UNIT
Function ENABLED
Trigger Position 30 [5 : 95] %
Samples/Cycle 64
Max. Number Osc. 4 [1 : 20]
Automatic Overwrite DISABLED
Snapshot Events ENABLED

GENERAL SETTINGS
NAME VALUE UNIT
Phase CT Ratio 200. [1 : 6000]
Ground CT Ratio 200. [1 : 6000]
Stv Ground CT Ratio 1. [1 : 6000]
Phase VT Ratio 1. [1 : 6000]
Phase VT Connection WYE
Nominal Voltage 100.0 [1.0 : 250.0] V
Nominal Frequency 60 Hz
Phase Rotation ABC
Frequency Reference VI
Auxiliary Voltage VX
Snapshot Events DISABLED

PHASE TOC HIGH 1


NAME VALUE UNIT
Function ENABLED
Input PHASOR(DFT)
Pickup Level 1.10 [0.05 : 160.00] A
Curve IEC Curve A
TD Multiplier 0.13 [0.00 : 900.00] s
Reset INSTANTANEOUS
Voltage Restraint DISABLED
Snapshot Events ENABLED

PHASE IOC HIGH 1


NAME VALUE UNIT
Function ENABLED
Input PHASOR(DFT)
Pickup Level 7.50 [0.05 : 160.00] A
Trip Delay 0.20 [0.00 : 900.00] s
Reset Delay 0.00 [0.00 : 900.00] s
Snapshot Events ENABLED
SETTING GROUP
NAME VALUE UNIT
Function ENABLED
Active Group GROUP 1
Snapshot Events ENABLED

Revisión: 01 Página 177 de 184 Fecha: 30-10-2008


ECP NUEVO TRANSFORMADOR DE LA SUBESTACION
MOTUPE 60/22.9/10 KV

S.E. OLMOS: TRANSFORMADOR DE POTENCIA 1.6 MVA, 60/10 KV –


RELE DIFERENCIAL GENERAL ELECTRIC T60

\OLMOS\
DEVICE DEFINITION
ORDER CODE: T60-H03-HCH-F8F-H6A-M8H
VERSION: 5.4X
DESCRIPTION: (NONE)
TEXT COLOR

SYSTEM SETUP
AC INPUTS
CURRENT

CT F1: Phase CT Primary 50 A


CT F1: Phase CT Secondary 1A
CT F1: Ground CT Primary 50 A
CT F1: Ground CT Secondary 1A
CT M1: Phase CT Primary 100 A
CT M1: Phase CT Secondary 1A
CT M1: Ground CT Primary 100 A
CT M1: Ground CT Secondary 1A
CT M5: Phase CT Primary 1A
CT M5: Phase CT Secondary 1A
CT M5: Ground CT Primary 1A
CT M5: Ground CT Secondary 1A

VOLTAGE

VT F5: Phase VT Connection Wye


VT F5: Phase VT Secondary 57.7 V
VT F5: Phase VT Ratio 600.00 :1
VT F5: Auxiliary VT Connection Vag
VT F5: Auxiliary VT Secondary 115.0 V
VT F5: Auxiliary VT Ratio 115.00 :1

POWER SYSTEM

Nominal Frequency 60 Hz
Phase Rotation ABC
Frequency And Phase Reference SRC 1
Frequency Tracking Function Disabled

SIGNAL SOURCES

SOURCE 1: Name SRC 1


SOURCE 1: Phase CT F1
SOURCE 1: Ground CT F1
SOURCE 1: Phase VT F5
SOURCE 1: Auxiliary VT None
SOURCE 2: Name SRC 2
SOURCE 2: Phase CT M1
SOURCE 2: Ground CT M1

Revisión: 01 Página 178 de 184 Fecha: 30-10-2008


ECP NUEVO TRANSFORMADOR DE LA SUBESTACION
MOTUPE 60/22.9/10 KV

SOURCE 2: Phase VT None


SOURCE 2: Auxiliary VT None

TRANSFORMER
GENERAL

Number Of Windings 2
Reference Winding Selection 0
Phase Compensation Internal (software)
Load Loss At Rated Load 100 kW
Rated Winding Temperature Rise 65°C (oil)
No Load Loss 10 kW
Type Of Cooling OA
Top-oil Rise Over Ambient 35 °C
Thermal Capacity 100.00 kWh/°C
Winding Thermal Time Constant 2.00 min

WINDINGS

WINDING 1: Source SRC 1


WINDING 1: Rated MVA 1.600 MVA
WINDING 1: Nominal Phs-phs Voltage 60.000 kV
WINDING 1: Connection Wye
WINDING 1: Grounding Within zone
WINDING 1: Angle Wrt Winding 1 0.0 deg
WINDING 1: Resistance 10.0000 ohms
WINDING 2: Source SRC 2
WINDING 2: Rated MVA 1.600 MVA
WINDING 2: Nominal Phs-phs Voltage 10.000 kV
WINDING 2: Connection Delta
WINDING 2: Grounding Not within zone
WINDING 2: Angle Wrt Winding 1 -330.0 deg
WINDING 2: Resistance 10.0000 ohms

GROUPED ELEMENTS
GROUP 1
TRANSFORMER
PERCENT DIFFERENTIAL [GROUP 1]

Function Enabled
Pickup 0.200 pu
Slope 1 25 %
Break 1 2.000 pu
Break 2 8.000 pu
Slope 2 60 %
Inrush Inhibit Function Adapt. 2nd
Inrush Inhibit Mode Per phase
Inrush Inhibit Level 15.0 % fo
Overexcitation Inhibit Function 5th
Overexcitation Inhibit Level 35.0 % fo
Block OFF
Target Latched
Events Enabled

Revisión: 01 Página 179 de 184 Fecha: 30-10-2008


ECP NUEVO TRANSFORMADOR DE LA SUBESTACION
MOTUPE 60/22.9/10 KV

INSTANTANEOUS DIFFERENTIAL [GROUP 1]

Function Enabled
Pickup 8.000 pu
Block OFF
Target Latched
Events Enabled

PHASE CURRENT
PHASE TOC [GROUP 1]

PHASE TOC1: Function Enabled


PHASE TOC1: Signal Source SRC 1
PHASE TOC1: Input Phasor
PHASE TOC1: Pickup 0.500 pu
PHASE TOC1: Curve IEC Curve A
PHASE TOC1: TD Multiplier 0.17
PHASE TOC1: Reset Instantaneous
PHASE TOC1: Voltage Restraint Disabled
PHASE TOC1: Block A OFF
PHASE TOC1: Block B OFF
PHASE TOC1: Block C OFF
PHASE TOC1: Target Latched
PHASE TOC1: Events Enabled
PHASE TOC2: Function Enabled
PHASE TOC2: Signal Source SRC 2
PHASE TOC2: Input Phasor
PHASE TOC2: Pickup 1.200 pu
PHASE TOC2: Curve IEC Curve A
PHASE TOC2: TD Multiplier 0.11
PHASE TOC2: Reset Instantaneous
PHASE TOC2: Voltage Restraint Disabled
PHASE TOC2: Block A OFF
PHASE TOC2: Block B OFF
PHASE TOC2: Block C OFF
PHASE TOC2: Target Latched
PHASE TOC2: Events Enabled

PHASE IOC [GROUP 1]

PHASE IOC1: Function Enabled


PHASE IOC1: Source SRC 1
PHASE IOC1: Pickup 4.500 pu
PHASE IOC1: Delay 0.25 s
PHASE IOC1: Reset Delay 0.00 s
PHASE IOC1: Block A OFF
PHASE IOC1: Block B OFF
PHASE IOC1: Block C OFF
PHASE IOC1: Target Latched
PHASE IOC1: Events Enabled
PHASE IOC2: Function Enabled
PHASE IOC2: Source SRC 2
PHASE IOC2: Pickup 7.500 pu
PHASE IOC2: Delay 0.20 s
PHASE IOC2: Reset Delay 0.00 s

Revisión: 01 Página 180 de 184 Fecha: 30-10-2008


ECP NUEVO TRANSFORMADOR DE LA SUBESTACION
MOTUPE 60/22.9/10 KV

PHASE IOC2: Block A OFF


PHASE IOC2: Block B OFF
PHASE IOC2: Block C OFF
PHASE IOC2: Target Latched
PHASE IOC2: Events Enabled

NEUTRAL CURRENT
NEUTRAL TOC [GROUP 1]

NEUTRAL TOC1: Function Enabled


NEUTRAL TOC1: Source SRC 1
NEUTRAL TOC1: Input Phasor
NEUTRAL TOC1: Pickup 0.400 pu
NEUTRAL TOC1: Curve IEC Curve A
NEUTRAL TOC1: TD Multiplier 0.16
NEUTRAL TOC1: Reset Instantaneous
NEUTRAL TOC1: Block OFF
NEUTRAL TOC1: Target Latched
NEUTRAL TOC1: Events Enabled

NEUTRAL IOC [GROUP 1]

NEUTRAL IOC1: Function Enabled


NEUTRAL IOC1: Source SRC 1
NEUTRAL IOC1: Pickup 4.000 pu
NEUTRAL IOC1: Delay 0.25 s
NEUTRAL IOC1: Reset Delay 0.00 s
NEUTRAL IOC1: Block OFF
NEUTRAL IOC1: Target Latched
NEUTRAL IOC1: Events Enabled

Revisión: 01 Página 181 de 184 Fecha: 30-10-2008


ECP NUEVO TRANSFORMADOR DE LA SUBESTACION
MOTUPE 60/22.9/10 KV

S.E. OLMOS: TRANSFORMADOR DE POTENCIA 1.6 MVA, 60/10 KV –


RELE DE SOBRECORRIENTE GENERAL ELECTRIC F650 –
LADO 60 KV

GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup


File Name: OLMOS 60KV.650
Comment: MOTUPE 60KV
Model: F650***F2G0***
Version: 1.70
Part: 5.8.4.0

SETPOINTS
SERIAL PORTS
NAME VALUE UNIT
COM1 Baud Rate 19200
COM2 Baud Rate 19200
Parity NONE

OSCILLOGRAPHY
NAME VALUE UNIT
Function ENABLED
Trigger Position 30 [5 : 95] %
Samples/Cycle 64
Max. Number Osc. 4 [1 : 20]
Automatic Overwrite DISABLED
Snapshot Events ENABLED

GENERAL SETTINGS
NAME VALUE UNIT
Phase CT Ratio 50. [1 : 6000]
Ground CT Ratio 50. [1 : 6000]
Stv Ground CT Ratio 1. [1 : 6000]
Phase VT Ratio 1. [1 : 6000]
Phase VT Connection WYE
Nominal Voltage 100.0 [1.0 : 250.0] V
Nominal Frequency 60 Hz
Phase Rotation ABC
Frequency Reference VI
Auxiliary Voltage VX
Snapshot Events DISABLED

PHASE TOC HIGH 1


NAME VALUE UNIT
Function ENABLED
Input PHASOR(DFT)
Pickup Level 0.50 [0.05 : 160.00] A
Curve IEC Curve A
TD Multiplier 0.17 [0.00 : 900.00] s
Reset INSTANTANEOUS
Voltage Restraint DISABLED
Snapshot Events ENABLED

PHASE IOC HIGH 1


NAME VALUE UNIT
Function ENABLED
Input PHASOR(DFT)
Pickup Level 4.50 [0.05 : 160.00] A
Trip Delay 0.25 [0.00 : 900.00] s
Reset Delay 0.00 [0.00 : 900.00] s
Snapshot Events ENABLED

Revisión: 01 Página 182 de 184 Fecha: 30-10-2008


ECP NUEVO TRANSFORMADOR DE LA SUBESTACION
MOTUPE 60/22.9/10 KV

NEUTRAL TOC 1
NAME VALUE UNIT
Function ENABLED
Pickup Level 0.40 [0.05 : 160.00] A
Curve IEC Curve A
TD Multiplier 0.16 [0.00 : 900.00] s
Reset INSTANTANEOUS
Snapshot Events ENABLED

NEUTRAL IOC 1
NAME VALUE UNIT
Function ENABLED
Pickup Level 4.00 [0.05 : 160.00] A
Trip Delay 0.25 [0.00 : 900.00] s
Reset Delay 0.00 [0.00 : 900.00] s
Snapshot Events ENABLED

SETTING GROUP
NAME VALUE UNIT
Function ENABLED
Active Group GROUP 1
Snapshot Events ENABLED

Revisión: 01 Página 183 de 184 Fecha: 30-10-2008


ECP NUEVO TRANSFORMADOR DE LA SUBESTACION
MOTUPE 60/22.9/10 KV

S.E. OLMOS: TRANSFORMADOR DE POTENCIA 1.6 MVA, 60/10 KV –


RELE DE SOBRECORRIENTE GENERAL ELECTRIC F650 –
LADO 10 KV
GE Power Management 650 SETPOINT FILE INFORMATION EnerVista 650 Setup
File Name: OLMOS 10KV.650
Comment: MOTUPE 60KV
Model: F650***F2G0***
Version: 1.70
Part: 5.8.4.0

SETPOINTS
SERIAL PORTS
NAME VALUE UNIT
COM1 Baud Rate 19200
COM2 Baud Rate 19200
Parity NONE

OSCILLOGRAPHY
NAME VALUE UNIT
Function ENABLED
Trigger Position 30 [5 : 95] %
Samples/Cycle 64
Max. Number Osc. 4 [1 : 20]
Automatic Overwrite DISABLED
Snapshot Events ENABLED

GENERAL SETTINGS
NAME VALUE UNIT
Phase CT Ratio 100. [1 : 6000]
Ground CT Ratio 100. [1 : 6000]
Stv Ground CT Ratio 1. [1 : 6000]
Phase VT Ratio 1. [1 : 6000]
Phase VT Connection WYE
Nominal Voltage 100.0 [1.0 : 250.0] V
Nominal Frequency 60 Hz
Phase Rotation ABC
Frequency Reference VI
Auxiliary Voltage VX
Snapshot Events DISABLED

PHASE TOC HIGH 1


NAME VALUE UNIT
Function ENABLED
Input PHASOR(DFT)
Pickup Level 1.20 [0.05 : 160.00] A
Curve IEC Curve A
TD Multiplier 0.11 [0.00 : 900.00] s
Reset INSTANTANEOUS
Voltage Restraint DISABLED
Snapshot Events ENABLED

PHASE IOC HIGH 1


NAME VALUE UNIT
Function ENABLED
Input PHASOR(DFT)
Pickup Level 7.50 [0.05 : 160.00] A
Trip Delay 0.20 [0.00 : 900.00] s
Reset Delay 0.00 [0.00 : 900.00] s
Snapshot Events ENABLED

SETTING GROUP
NAME VALUE UNIT
Function ENABLED
Active Group GROUP 1
Snapshot Events ENABLED

Revisión: 01 Página 184 de 184 Fecha: 30-10-2008