Académique Documents
Professionnel Documents
Culture Documents
November 2017
CTO Cabinets
Fast delivery: Standard cabinets are available with short lead Base enclosure models are available:
times when ordered for direct shipment to site.
For different cabinet sizes / entry (Front Access or Front and
Reduced system footprint: Equipment room footprint is Rear access).
reduced by eliminating the traditional marshalling cabinets with
For different power distribution needs: DC powered or
cross wiring to traditional I/O cards.
AC powered.
Significantly reduce cabinet design engineering: The CHARM
For different world area design standards and regulations:
I/O cabinets use DeltaV Electronic Marshalling, which allows
EUR (Europe) and NA (US/Canada).
any channel to be assigned to any one of four controllers. This
eliminates the task of rationalizing I/O to specific controllers and Configurable options examples: type of CHARMs (I.S. or non
preserves I/O flexibility to handle late changes to the system. I.S.), type of controllers, type of I/O cards, side panels, cabinet
light, nameplate engraving and injected power.
Fully documented package: Each cabinet is supplied with full
documentation showing internal lay-out, bill of materials and All cabinets come with following equipment installed:
internal wiring. Drawings can be incorporated into the project Primary and secondary 24VDC power distribution for CHARM
drawing package. I/O Cards and field instrumentation
www.emerson.com/deltav 2
CTO Cabinets November 2017
Incoming Permitted
#
Power Location
Base Model Number Description CHARM
Requirements / World
IO
(Prim and Sec) Area
AC Powered Electronic Marshalling Cabinet for
252 CHARM I/O; 800mm W x 600mm D; Safe Area
EU-CAB-800F-252-AC-CIOC 252 230V AC
Front Access; Europe Design Standards EUR
and Regulations.
AC Powered Electronic Marshalling Cabinet for
504 CHARM I/O; 800mm W x 800mm D; Safe Area
EU-CAB-800FR-504-AC-CIOC 504 230V AC
Front and Rear Access; Europe Design Standards EUR
and Regulations.
AC Powered Electronic Marshalling Cabinet for
168 CHARM I/O; 800mm W x 600mm D; Safe Area
EU-CAB-800F-168-AC-CIOC 168 230V AC
Front Access; Europe Design Standards EUR
and Regulations.
AC Powered Electronic Marshalling Cabinet for
336 CHARM I/O; 800mm W x 800mm D; Safe Area
EU-CAB-800FR-336-AC-CIOC 336 230V AC
Front and Rear Access; Europe Design Standards EUR
and Regulations.
DC Powered Electronic Marshalling Cabinet for
288 CHARM I/O; 800mm W x 600mm D; Safe Area
EU-CAB-800F-288-DC-CIOC 288 24V DC
Front Access; Europe Design Standards EUR
and Regulations.
DC Powered Electronic Marshalling Cabinet
for 576 CHARM I/O; 800mm W x 800mm D; Safe Area
EU-CAB-800FR-576-DC-CIOC 576 24V DC
Front and Rear Access; Europe Design Standards EUR
and Regulations.
AC Powered Controller and Electronic
Marshalling Cabinet for 288 CHARM I/O; Safe Area
288 230V AC
EU-CAB-800FR-AC-CNTR-288 800mm W x 800mm D; Front and Rear Access; EUR
Europe Design Standards and Regulations.
AC Powered Controller Cabinet; 800mm W x
Safe Area
EU-CAB-800F-AC-CNTR 600mm D; Front Access; N/A 230V AC
EUR
Europe Design Standards and Regulations.
AC Powered Controller Cabinet;
Safe Area
EU-CAB-800FR-AC-CNTR 800mm W x 800mm D; Front and Rear Access; N/A 230V AC
EUR
Europe Design Standards and Regulations.
The CTO base model reference for cabinets uses the following naming convention:
“EU-CAB-XXXYY-ZZZ-IP-DDDD”, where
• EU: Europe Design Standards and Regulations . • ZZZ = maximum I/O’s count in this CTO.
• XXX = cabinet width (mm), e.g. “800”, “1200”. • IP =AC / DC Incoming Power, DC = 24V DC or AC =
120/230V AC.
• YY = “F” for Front only access (600 mm deep), “FR” for
Front and Rear access (800 mm deep). • DDDD = short description of content and purpose.
www.emerson.com/deltav 3
CTO Cabinets November 2017
Incoming Permitted
#
Power Location
Base Model Number Description CHARM
Requirements / World
IO
(Prim and Sec) Area
AC Powered Electronic Marshalling Cabinet for
Safe
252 CHARM I/O; 800mm W x 600mm D;
NA-CAB-800F-252-AC-CIOC 252 120V AC Area US/
Front Access; US/Canada Design Standards
CANADA
and Regulations.
AC Powered Electronic Marshalling Cabinet for
Safe
504 CHARM I/O; 800mm W x 800mm D; Front
NA-CAB-800FR-504-AC-CIOC 504 120V AC Area US/
and Rear Access; US/Canada Design Standards
CANADA
and Regulations.
DC Powered Electronic Marshalling Cabinet for
Safe
288 CHARM I/O; 800mm W x 600mm D;
NA-CAB-800F-288-DC-CIOC 288 24V DC Area US/
Front Access; US/Canada Design Standards
CANADA
and Regulations.
DC Powered Electronic Marshalling Cabinet for
Safe
576 CHARM I/O; 800mm W x 800mm D;
NA-CAB-800FR-576-DC-CIOC 576 24V DC Area US/
Front and Rear Access; US/Canada Design
CANADA
Standards and Regulations.
AC Powered Controller and Electronic
Safe
Marshalling Cabinet for 288 CHARM I/O;
NA-CAB-800FR-AC-CNTR-288 288 120V AC Area US/
800mm W x 800mm D; Front and Rear Access;
CANADA
US/Canada Design Standards and Regulations.
AC Powered Controller Cabinet; Safe
NA-CAB-800F-AC-CNTR 800mm W x 600mm D; Front Access; N/A 120V AC Area US/
US/Canada Design Standards and Regulations. CANADA
AC Powered Controller Cabinet; Safe
NA-CAB-800FR-AC-CNTR 800mm W x 800mm D; Front and Rear Access; N/A 120V AC Area US/
US/Canada Design Standards and Regulations. CANADA
The CTO base model reference for cabinets uses the following naming convention:
“NA-CAB-XXXYY-ZZZ-IP-DDDD”, where
• YY = “F” for Front only access (600 mm deep), “FR” for Front and Rear access (800 mm deep).
www.emerson.com/deltav 4
CTO Cabinets November 2017
E U -CAB-80 0FR-AC-CNTR-2 88
E U -CAB-80 0FR-50 4-AC-CIO C
E U -CAB-80 0FR-AC-CNTR
E U -CAB-80 0F-AC-CNTR
Ba se Mode l
W o rld Are a EUR EUR EUR EUR EUR EUR EUR EUR EUR
P o we r In p u t (D C: 2 4VD C, AC:1 20 /2 3 0VAC) AC AC AC AC DC DC AC AC AC
En clo su re Acce ss (F: Fro n t , FR: Fro n t-Re ar) F F/R F F/R F FR FR F F/R
# CH ARM I/O 252 504 168 336 288 576 288
En clo su re O p t io ns
0 No ○ ○ ○ ○ ○ ○ ○ ○ ○
N am e p lat e En g ravin g G
1 Ye s ● ● ● ● ● ● ● ● ●
0 No ○ ○ ○ ○ ○ ○ ○ ○ ○
S id e P an e ls S ● ● ● ● ● ● ● ● ●
1 Ye s
0 No ● ● ● ● ● ● ● ● ●
B ayin g Kit B
1 Ye s ○ ○ ○ ○ ○ ○ ○ ○ ○
0 No ● ● ● ● ● ● ● ● ●
Cab le Clam p s Rail R
1 Ye s ○ ○ ○ ○ ○ ○ ○ ○ ○
0 O n Le ft ● ● ● ● ● ● ● ● ●
D o o r H in g e s D ○ ○ ○
1 O n Rig h t ○ ○ ○ ○ ○ ○
0 100mm ● ● ● ● ● ● ● ● ●
P lin t h I 1 200mm ○ ○ ○ ○ ○ ○ ○ ○ ○
0 Cab le D u ct ● ● ● ● ● ● ● ● ●
Fie ld Cab le Ro u t in g F ○ ○ ○
1 W ire B aske t ○ ○ ○ ○ ○ ○
0 Co p p e r ● ● ● ● ● ●
Et h e rn e t E 1 Fib e r (M M ) ○ ○ ○ ○ ○ ○ NA
1 Co n t in u o u s Ru n ○ ○ ○ ○ ○ ○ ○
D o o r Fan s F
2 T h e rm o st at Co n t ro lled ● ● ● ● NA ● ● ●
1 No ○ ○ ○ ○ ○ ○ ○ ○ ○
Cab in e t Lig h t LED light with motion sensor ● ● ● ● ● ● ● ● ●
L 2
0 No ● ● ● ● ● ● ● ● ●
U t ilit y S ocke t S elect io n U ○ ○ ○ ○ ○ ○ ○ ○ ○
1 Ye s
0 CE ● ● ● ● ● ● ● ● ●
Ce rt ificat io n Z
1 No ○ ○ ○ ○ ○ ○ ○ ○ ○
1 Fro n t : Re d u n d an t 2 0 A ● ● ● ● ● ● ●
2 Fro n t : Re d u n d an t 4 0 A ○ ○ ○ ○ ○ ○ ○
P o we r S u p p ly Rat in g P
3 Re ar: Re d u n d an t 2 0 A ● ● ● ●
NA NA ○ ○ NA ○
4 Re ar: Re d u n d an t 4 0 A NA
T yp e o f CH ARM S 1 N o n I.S . ● ● ● ● ● ● ●
(to be specified for each row of CHARMS)
C
2 I.S . ○ ○ ○ ○ ○ ○ ○ NA
0 CIO C In je ct e d Po wer Fro n t : N O ● ● ● ● ● ●
NA
1 CIO C In je ct e d Po wer Fro n t : YES ○ ○ ○ ○ ○ ○
2 CIO C In je ct e d Po wer Re ar : N O ● ● ● ● NA
Fie ld P o we r A 3 CIO C In je ct e d Po wer Re ar : YES
NA
○
NA
○ NA ○ ○ NA
4 S -Co n ve n t io nal 2 4 VDC Fie ld P o we r REAR: N O ○
5 S -Co n ve n t io nal 2 4 VDC Fie ld P o we r REAR: YES
NA ●
www.emerson.com/deltav 5
CTO Cabinets November 2017
• : D e fau lt o p t io nse tt in g
o : Co n fig u re T o O rd e r o p t io n se tt in g , d iffere n t fro m d e fault
b lan k : o p t io n se t ting n o t p o ssib le fo r t he b ase e nclo su re
1
o : O p t io n s availab le fo r b o t h fro n t an d re ar side o f t he cab in e t if re ar sid e is co nfig ure d as a N O N De lt aV S IS sid e
: In t e n t io n ally le ft b lan k t o fill in yo u r co n fig u rat io n ch o ice s
Following more detailed options can be specified upon order (if applicable):
Disconnect switches for DC power feeds can be configured separately for CIOC power and for injected power inputs.
Power supply configuration: Power for CIOC and/or injected power (with diode), Front and Rear position in cabinet.
Wiring color scheme different from default: US (L- Black, N- White) / EUR (L- Brown, N- Blue).
www.emerson.com/deltav 6
CTO Cabinets November 2017
Cabinet Specifications
EU-CAB-800F-252-AC-CIOC
Dimensions 800mm (W) x 600mm (D) x 2000mm (H) + 100mm/200mm Plinth configurable
Access Front Access – single door, right/left hand hinged configurable, latch type lock and
2 sets of keys (key N°3524E)
Protection Category IP54 – NEMA 12
Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting
eye bolts on top, bottom cable entry, removable gland plate
Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.
Certifications Installation in Safe Area locations; Default Certification: CE (Europe); Optional: None
Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power
through switches and fused terminals (mounted in right side).
Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.
Daisy chained primary and secondary control network between all 3 CIOC carriers is
included (can be changed if required).
3 CHARM IO rails, for total of 252 I/O, each rail containing:
Front View
www.emerson.com/deltav 7
CTO Cabinets November 2017
EU-CAB-800F-252-AC-CIOC
Top View
Front View
www.emersonprocess.com/deltav 8
CTO Cabinets November 2017
NA-CAB-800F-252-AC-CIOC
Access Front Access – single door, right hand hinged, latch type lock and 2 sets of keys
(key N°3524E)
Protection Category IP54 – NEMA 12
Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye
bolts on top, bottom cable entry, removable gland plate
Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.
Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through
switches and fused terminals (mounted in right side).
Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.
Daisy chained primary and secondary control network between all 3 CIOC carriers is
included (can be changed if required).
Example BOM:
Front View
www.emerson.com/deltav 9
CTO Cabinets November 2017
NA-CAB-800F-252-AC-CIOC
Top View
Front View
www.emerson.com/deltav 10
CTO Cabinets November 2017
EU-CAB-800FR-504-AC-CIOC
Dimensions 800mm (W) x 800mm (D) x 2000mm (H) + 100mm/200mm Plinth configurable
Access Front and Rear Access, single doors, Right/Left hand hinged configurable, latch type lock
and 2 sets of keys (key N°3524E)
Protection Category IP54 – NEMA 12
Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye
bolts on top, bottom cable entry, removable gland plate
Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.
Certifications Installation in Safe Area locations; Default Certification: CE (Europe); Optional: None
Power Supply Rating Individually configurable as 2 X 40A for Front and Rear
Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through
switches and fused terminals (mounted in right side).
Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.
Daisy chained primary and secondary control network between all 3 CIOC carriers is
included (can be changed if required).
Example BOM:
www.emerson.com/deltav 11
CTO Cabinets November 2017
EU-CAB-800FR-504-AC-CIOC
Top View
Top View
External Layout Drawing for EU-CAB-800FR-504-AC-CIOC: Front, Rear, and Top View.
www.emersonprocess.com/deltav 12
CTO Cabinets November 2017
NA-CAB-800FR-504-AC-CIOC
Dimensions 800mm (W) x 800mm (D) x 2000mm (H) + 100mm Plinth
Access Front and Rear Access, single doors, right hand hinged, latch type lock and 2 sets of keys
(key N°3524E)
Protection Category IP54 – NEMA 12
Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye
bolts on top, bottom cable entry, removable gland plate
Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.
Power Supply Rating Individually configurable as 2 X 20A or 2 X 40A for Front and Rear
Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through
switches and fused terminals (mounted in right side).
Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.
Daisy chained primary and secondary control network between all 3 CIOC carriers is
included (can be changed if required).
Example BOM:
www.emerson.com/deltav 13
CTO Cabinets November 2017
NA-CAB-800FR-504-AC-CIOC
Top View
Size of Wire Baskets: 150mm H x 54mm D
Top View
External Layout Drawing for NA-CAB-800FR-504-AC-CIOC: Front, Rear, and Top View.
www.emerson.com/deltav 14
CTO Cabinets November 2017
EU-CAB-800F-168-AC-CIOC
Access Front Access, single door, right hand hinged, latch type lock and 2 sets of keys (key
N°3524E)
Protection Category IP54 – NEMA 12
Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye
bolts on top, bottom cable entry, removable gland plate
Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.
Certifications Installation in Safe Area locations; Default Certification: None; Optional: CSA (US/Canada)
Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through
switches and fused terminals (mounted in right side).
Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.
Daisy chained primary and secondary control network between both 2 CIOC carriers is
included (can be changed if required).
Example BOM:
Front View
www.emerson.com/deltav 15
CTO Cabinets November 2017
EU-CAB-800F-168-AC-IOC
Top View
Front View
Top View
www.emerson.com/deltav 16
CTO Cabinets November 2017
EU-CAB-800FR-336-AC-CIOC
Dimensions 800mm (W) x 800mm (D) x 2000mm (H) + 100mm/200mm Plinth configurable
Access Front and Rear Access, single doors, Right/Left hand hinged configurable, latch type lock
and 2 sets of keys (key N°3524E)
Protection Category IP54 – NEMA 12
Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye
bolts on top, bottom cable entry, removable gland plate
Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.
Certifications Installation in Safe Area locations; Default Certification: CE (Europe); Optional: None
Power Supply Rating Individually configurable as 2 X 40A for Front and Rear
Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through
switches and fused terminals (mounted in right side).
Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.
Daisy chained primary and secondary control network between all 4 CIOC carriers
is included (can be changed if required).
Example BOM:
www.emerson.com/deltav 17
CTO Cabinets November 2017
EU-CAB-800FR-336-AC-CIOC
Top View
Top View
External Layout Drawing for EU-CAB-800FR-336-AC-CIOC: Front, Rear, and Top View.
www.emerson.com/deltav 18
CTO Cabinets November 2017
EU-CAB-800F-288-DC-CIOC
Dimensions 800mm (W) x 600mm (D) x 2000mm (H) + 100mm/200mm Plinth configurable
Access Front Access – single door, right/left hand hinged configurable, latch type lock and
2 sets of keys (key N°3524E)
Protection Category IP54 – NEMA 12
Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye
bolts on top, bottom cable entry, removable gland plate
Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.
Certifications Installation in Safe Area locations; Default Certification: CE (Europe); Optional: None
Power Requirements – Primary and secondary 24VDC power to be supplied from outside the cabinet
Internal Power Distribution (e.g. from adjacent cabinet or dedicated Power Supply Cabinet).
Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through
switches and fused terminals (mounted in left side).
Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.
Daisy chained primary and secondary control network between all 3 CIOC carriers is
included (can be changed if required).
Example BOM:
Front View
www.emerson.com/deltav 19
CTO Cabinets November 2017
EUR-CAB-800F-288-DC-CIOC
Top View
Front View
www.emerson.com/deltav 20
CTO Cabinets November 2017
NA-CAB-800F-288-DC-CIOC
Dimensions 800mm (W) x 600mm (D) x 2000mm (H) + 100mm Plinth
Access Front Access – single door, right hand hinged, latch type lock and 2 sets of keys
(key N°3524E)
Protection Category IP54 – NEMA 12
Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye
bolts on top, bottom cable entry, removable gland plate
Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.
Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through
switches and fused terminals (mounted in left side)
Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.
Daisy chained primary and secondary control network between all 3 CIOC carriers is
included (can be changed if required).
Example BOM:
Front View
www.emerson.com/deltav 21
CTO Cabinets November 2017
NA-CAB-800F-288IO-DC-CIOC
Top View
Front View
External Layout Drawing for for NA-CAB-800F-288-DC-CIOC: Front and Top View.
www.emerson.com/deltav 22
CTO Cabinets November 2017
EU-CAB-800FR-576-DC-CIOC
Dimensions 800mm (W) x 800mm (D) x 2000mm (H) + 100mm/200mm Plinth configurable
Access Front and Rear Access, single doors, right/left hand hinged configurable, latch type lock
and 2 sets of keys (key N°3524E)
Protection Category IP54 – NEMA 12
Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye
bolts on top, bottom cable entry, removable gland plate
Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.
Certifications Installation in Safe Area locations; Default Certification: CE (Europe); Optional: None
Power Requirements – Primary and secondary 24VDC power to be supplied from outside the cabinet
Internal Power Distribution (e.g. from adjacent cabinet or dedicated Power Supply Cabinet).
Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through
switches and fused terminals (mounted in sides).
Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.
Daisy chained Primary and secondary control network between all 6 CIOC carriers is
included (can be changed if required).
Example BOM:
Front View
www.emerson.com/deltav 23
CTO Cabinets November 2017
EUR-CAB-800FR-576-DC-CIOC
Top View
External Layout Drawing for EU-CAB-800FR-576-DC-CIOC: Front, Rear, and Top View.
www.emerson.com/deltav 24
CTO Cabinets November 2017
NA-CAB-800FR-576-DC-CIOC
Access Front and Rear Access, single doors, right hand hinged, latch type lock and 2 sets of keys
(key N°3524E)
Protection Category IP54 – NEMA 12
Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye
bolts on top, bottom cable entry, removable gland plate
Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.
Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through
switches and fused terminals (mounted in sides).
Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.
Daisy chained Primary and secondary control network between all 6 CIOC carriers is
included (can be changed if required).
Example BOM:
Front View
www.emerson.com/deltav 25
CTO Cabinets November 2017
NA-CAB-800FR-576IO-DC-CIOC
Top View
External Layout Drawing for NA-CAB-800FR-576-DC-CIOC: Front, Rear, and Top View.
www.emerson.com/deltav 26
CTO Cabinets November 2017
EU-CAB-800FR-AC-CNTR-288
Dimensions 800mm (W) x 800mm (D) x 2000mm (H) + 100mm/200mm Plinth configurable
Access Front and Rear Access, single doors, right/left hand hinged configurable, latch type lock
and 2 sets of keys (key N°3524E)
Protection Category IP54 – NEMA 12
Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye
bolts on top, bottom cable entry, removable gland plate
Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.
Certifications Installation in Safe Area locations; Default Certification: CE (Europe); Optional: None
Power Supply Rating Individually configurable as 2 X 20A or 2 X 40A for Front and Rear
Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through
switches and fused terminals (mounted in right side).
Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.
Daisy chained primary and secondary control network between all 3 CIOC carriers is
included (can be changed if required).
Example BOM front:
Front View
www.emerson.com/deltav 27
CTO Cabinets November 2017
EU-CAB-800FR-AC-CNTR-288
Rear View
Top View
External Layout Drawing for EU-CAB-800FR-AC-CNTR-288: Front, Rear, and Top View.
www.emerson.com/deltav 28
CTO Cabinets November 2017
NA-CAB-800FR-AC-CNTR-288
Access Front and Rear Access, single doors, right hand hinged, latch type lock and 2 sets of keys
(key N°3524E)
Protection Category IP54 – NEMA 12
Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye
bolts on top, bottom cable entry, removable gland plate
Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.
Certifications Installation in Safe Area locations ; Default Certification: None; Optional: CSA (US/Canada)
Power Supply Rating Individually configurable as 2 X 40A for Front and Rear
Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through
switches and fused terminals (mounted in right side).
Control Network Redundant 100BASE-FX, RJ45 connectors, to be connected to first CIOC carrier.
Daisy chained primary and secondary control network between all 3 CIOC carriers is
included (can be changed if required).
Example BOM front:
Front View
www.emerson.com/deltav 29
CTO Cabinets November 2017
NA-CAB-800FR-AC-CNTR-288
Rear View
Top View
External Layout Drawing for NA-CAB-800FR-AC-CNTR-288: Front, Rear, and Top View.
www.emerson.com/deltav 30
CTO Cabinets November 2017
EU-CAB-800F-AC-CNTR
Dimensions 800mm (W) x 600mm (D) x 2000mm (H) + 100mm/200mm Plinth configurable
Access Front Access, single door, right/left hand hinged configurable, latch type lock and 2 sets of
keys (key N°3524E)
Protection Category IP54 – NEMA 12
Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye
bolts on top, bottom cable entry, removable gland plate
Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.
Certifications Installation in Safe Area locations; Default Certification: CE (Europe); Optional: None
Power Supply Rating Individually configurable as 2 X 20A or 2 X 40A for Front and Rear
Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through
switches and fused terminals (mounted in right side).
Control Network Redundant 100BASE-FX, RJ45 connectors
Front View
www.emerson.com/deltav 31
CTO Cabinets November 2017
EU-CAB-800F-AC-CNTR
Top View
Front View
www.emerson.com/deltav 32
CTO Cabinets November 2017
NA-CAB-800F-AC-CNTR
Dimensions 800mm (W) x 600mm (D) x 2000mm (H) + 100mm Plinth
Access Front Access, single door, right hand hinged, latch type lock and 2 sets of keys
(key N°3524E)
Protection Category IP54 – NEMA 12
Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye
bolts on top, bottom cable entry, removable gland plate
Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.
Certifications Installation in Safe Area locations; Default Certification: None; Optional: CSA (US/Canada)
Power Supply Rating Individually configurable as 2 X 20A or 2 X 40A for Front and Rear
Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through
switches and fused terminals (mounted in right side).
Control Network Redundant 100BASE-FX, RJ45 connectors
Front View
www.emerson.com/deltav 33
CTO Cabinets November 2017
NA-CAB-800F-AC-CNTR
Top View
Front View
www.emerson.com/deltav 34
CTO Cabinets November 2017
EU-CAB-800FR-AC-CNTR
Dimensions 800mm (W) x 800mm (D) x 2000mm (H) + 100mm/200mm Plinth configurable
Access Front and Rear Access, single doors, right/left hand hinged configurable, latch type lock
and 2 sets of keys (key N°3524E)
Protection Category IP54 – NEMA 12
Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye
bolts on top, bottom cable entry, removable gland plate
Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.
Certifications Installation in Safe Area locations; Default Certification: CE (Europe); Optional: None
Power Supply Rating Individually configurable as 2 X 20A or 2 X 40A for Front and Rear
Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through
switches and fused terminals (mounted in right side).
Control Network Redundant 100BASE-FX, RJ45 connectors
Front View
www.emerson.com/deltav 35
CTO Cabinets November 2017
EU-CAB-800FR-AC-CNTR
Rear View
Top View
External Layout Drawing for for EU-CAB-800FR-AC-CNTR: Front, Rear, and Top View.
www.emerson.com/deltav 36
CTO Cabinets November 2017
NA-CAB-800FR-AC-CNTR
Dimensions 800mm (W) x 800mm (D) x 2000mm (H) + 100mm Plinth
Access Front and Rear Access, single doors, right hand hinged, latch type lock and 2 sets of keys
(key N°3524E)
Protection Category IP54 – NEMA 12
Other Louvered doors with filter, mounting plate, grounding bars, wiring plan pocket, lifting eye
bolts on top, bottom cable entry, removable gland plate
Environmental Specifications Equipment/rack room installation (HVAC controlled), 30°C Max.
Certifications Installation in Safe Area locations; Default Certification: None; Optional: CSA (US/Canada)
Power Supply Rating Individually configurable as 2 X 20A or 2 X 40A for Front and Rear
Fully redundant 24VDC distribution for CHARM I/O cards and bussed field power through
switches and fused terminals (mounted in right side).
Control Network Redundant 100BASE-FX, RJ45 connectors
Front View
www.emerson.com/deltav 37
CTO Cabinets November 2017
NA-CAB-800FR-AC-CNTR
Rear View
Top View
External Layout Drawing for NA-CAB-800FR-AC-CNTR: Front, Rear, and Top View.
www.emerson.com/deltav 38
CTO Cabinets November 2017
For US/Canada St. Louis iCenter: CSA Mark for US and Canada
iCenterSTL.Quotes@Emerson.com
For Europe Design Standards and Regulations, the cabinet
For Europe Cluj iCenter: default comes with CE Certification. Optionally, no certification
Cabinets.Quotes@Emerson.com can be specified.
For Asia Pacific Singapore iCenter: For US/Canada Design Standards and Regulations, the cabinet
iCenterSGPQuotes@Emerson.com default does not come with certification. The CSA Certification
is optional.
www.emerson.com/deltav 39
CTO Cabinets November 2017
Related Products
CHARM I/O Cards must be ordered separately
Emerson
North America, Latin America: ©2017, Emerson. All rights reserved.
+1 800 833 8314 or
The Emerson logo is a trademark and service mark of Emerson Electric Co. The DeltaV logo is
+1 512 832 3774
a mark of one of the Emerson family of companies. All other marks are the property of their
respective owners.
Asia Pacific:
+65 6777 8211 The contents of this publication are presented for informational purposes only, and while every
effort has been made to ensure their accuracy, they are not to be construed as warranties or
Europe, Middle East: guarantees, express or implied, regarding the products or services described herein or their
+41 41 768 6111 use or applicability. All sales are governed by our terms and conditions, which are available on
request. We reserve the right to modify or improve the designs or specifications of our products
www.emerson.com/deltav at any time without notice.