Académique Documents
Professionnel Documents
Culture Documents
Abstract
Efficient joints in copper bus bar conductors can be made very simply by bolting and clamping. This paper
proposes the method to maximize the jointing efficiency in order to eliminate hot spots in switchgears by optimizing
the effect of spreading resistance and interface resistance
Key Words
Copper Bus bar Joint efficiency, Streamline effect, Interface resistance, Hot spots, Silver Plating, Belleville Washer.
1. Introduction
The resistance of a joint is affected mainly by two factors:
a) Streamline effect or spreading resistance Rs, the diversion of the current flow through a joint.
b) The contact resistance or interface resistance of the joint Ri.
The hardness of the contact material also affects the resistance to current flow across the joint. A microscopic view
(Fig-1) of the contact surfaces shows that they are rough and irregular. Current flows across constricted areas where
these rough surfaces make contact.
Our aim in this paper is to optimize the above mentioned factors in order to achieve excellent joint efficiency and
zero hot spots in switchgears.
2. Problem formulation
The bus bar considered in this paper for maximizing jointing efficiency is copper bus bar.
Different factors that will determine the efficiency of the joint with possible remedies are as follows:
a. Streamline effect:
The distortion of the lines of current flow at an overlapping joint between two conductors affects the resistance of
the joint. In case of an overlapping joint between two flat copper bars the streamline effect is dependent only on the
ratio of the length of the overlap to the thickness of the bars and not on the width. Hence the efficiency of an
overlapping joint does not increase as the length of the overlap increases and from the electrical point of view no
advantage is to be gained by employing an unduly long overlap.
The resistance ratio e in fig -2 is the ratio of the resistance of a joint due to streamline effect Rs, to the resistance of
an equal length of single conductor Rb:
From the graph it can be seen that the effect falls very rapidly for ratios to two and then very much slowly for
values up to seven. This means that in most cases the streamline effect has very little effect as the overlap is of
necessity much greater than seven.
Where
Ri = resistance of the contact.
P= total contact pressure.
n=exponent between 0.4 and 1.
C= a constant.
The greater the applied total pressure the lower will be the joint resistance and therefore for high efficiency joints
high pressure is usually necessary. The Fig-5 shows the effect of pressure on joint resistance.
Fig-5: Effect of pressure on contact resistance of a joint between two copper conductors
The joint resistance falls rapidly with increasing pressure, but above a pressure of about 15N/mm2 there is little
further improvement. These busbar joint may heat up under load as the contact pressure applied with steel bolts
tends to increase because of the difference in expansion coefficient between two dissimilar metals, copper and steel.
The temperature of the joint increases due to wattage loss and then decreases when the source is disconnected. Such
repeated thermal expansions and contractions of dissimilar metals will vary the contact force and eventually will
cause loose joints. To compensate for these changes, spring pressure should be added to this joint. Belleville
washers are frequently used to compensate for thermal expansion and contraction in clamped joints. It is important
that these washers are not over stressed.
Fig-6 shows a bolted joint with Belleville washer
The following method can be used to calculate the size and material properties of Belleville washers (Refer Fig-07
& Fig-08)). Load and stress are calculated according to the following equations:
Ef f 3
F(load) (h 2 )(h - f)(t t )
(1 - )M(D 2 / D1 ) 2
2
MS(D 2 /D1 ) 2 (1 σ 2 ) f C 2
h t
EfC1 2 C1
Where
F = load, lb
S = stress, psi at the inside diameter.
f = deflection, in.
t = thickness, in.
E = modulus of elasticity of material, 30x 106 psi
σ = Poissons ratio for material ( 0.3 value for steel)
h = height, in.
D1 = inner diameter, in.
D2 = outer diameter, in.
Washer dimensions are shown schematically in fig-8. The constants C1,C2 and M can be taken from fig-7.
110
AL-AL 474 Watt/ FDR
100 105 mV/ Joint
CU-CU
90
SL-SL
80
294 Watt/ FDR
70 79 Mv/ Joint
MV drop
Fig-9 mV drop and power loss at different load at joints in case of Aluminum bus bars , Copper bus bars and silver plated copper bus bars
In the graph above we are trying to compare results obtained while jointing Aluminum bus bars , Copper bus bars
and silver plated copper bus bars at different loads ( from 106 amperes to 302 amperes) . In all these three cases we
have kept same overlap between the bus bars, applied optimum pressure and used Belleville washers.
X axis of the curve is showing current flowing through the bus bar joints .
Y axis is showing milli-volt drop taking place in the joints. Watt loss measured is also mentioned along with the
milli-volt drop readings.
Green line indicates result of joints between two busbars, ie (AL-AL)
Pink line indicates result of Copper to Copper bus bars ie (CU-CU)
Blue line indicates result of Silver plated Copper to Silver Copper bus bars ie (SL-SL)
In case of AL-AL joints at test current of 106 ampere the mV drop is around 28 where as corresponding watt
loss is 45. This mV drop and watt loss increases with the increase of test current. At maximum test current of
302 ampere the watt loss is 105 watt.
In case of CU-CU joints at test current of 106 ampere the mV drop is very low and corresponding watt loss is
also very low . This mV drop and watt loss remains very low and does not increases with the increase of test
current.
In case of Silver plated Copper busbar joints at test current of 106 ampere the mV drop is very low, almost same
as that of Cu-Cu joints and corresponding watt loss is also very low . This mV drop and watt loss is even lower
then that of Cu-Cu joints in case of higher test current.
These results clearly shows the supremacy of silver plated copper bus bars over jointing normal aluminum bus bars
and bare copper bus bars.
5. Conclusion:
It is evident from the experimental results that while jointing two copper bus bars maximum jointing efficiency
can be achieved by using silver plated copper busbars as compared to normal aluminum bus bars and bare copper
bus bars while keeping other constraints like overlap between the bus bars, applied optimum pressure, size and type
of washer, application of thin film of petroleum coating on contact surfaces unchanged.
6. Acknowledgment:
I would like to express my deep sense of gratitude to Mr. J.S. Trada who helped me to carry out the experiment.
References
[1] Frank W. Kussy & Jack L Warren, “Design Fundamentals For Low-Voltage Distribution and Control” Marcel Dekker Inc, 1987.
[2] R Holm, Electrical Contacts, Springer-Verlag, New York (English version) 1967.
[3] Stephan Schoft, Josef Kindersberger, Helmut Löbl “Joint Resistance of Busbar-Joints with Randomly Rough Surfaces” , Proceedings of the
21th Conference on Electrical Contacts 2002, Zurich.
[4] Almen and Laszlo, “Belleville Washers, Trans. ASME, Vol. 58, 1936”.
[5] A.K. Sawhney, A Course In Electrical Machine Design ,2006.
[6] Bella H. Chudnovsky, “Degradation of Power Contacts in Industrial Atmosphere: Silver Corrosion and Whiskers “, Proceedings of the 48th
IEEE Holm Conference on Electrical Contacts,2002.