Académique Documents
Professionnel Documents
Culture Documents
Tap-changer know-how
Enhancing the switching capacity of change-over selectors with mini-
mized gas production
1. General often feature a change-over selector to is connected to the end of the main
reverse the polarity of the regulating winding. The regulating winding and
Regulated power transformers are winding or to add or bypass a coarse the change-over selector are in no-load
equipped with a regulating winding with tap winding. The change-over selector condition then.
multiple taps which are connected to a can only be operated in the mechanical
tap-changer to adjust the transformer mid-position of the tap selector. At When the change-over selector is operated,
ratio. On-load tap-changers (OLTCs) this position, the load current flows the regulating winding (and so the +/-
are used if the ratio shall be changed through the tap selector terminal which contacts of the change-over selector) take
while the transformer is under load.
These tap-changers consist of a tap
selector which connects two adjacent
taps of the regulating winding and a
Increasing transformer ratings require ever
diverter switch which performs the increasing optimization of transformer
load switching operation between the
two selected taps without interrupting
windings design, putting tap-changers under
the load current. The tap selectors more and more severe operating conditions
18 TRANSFORMERS MAGAZINE | Volume 3, Issue 4
Rainer FROTSCHER
Tank
Core
K
regulating winding, the geometric winding
arrangement and the ratio between C1 and
C2. They can reach values which cause UF
0
+
- C2
Winding 1
U1
R1
Winding 2 +
R2 UC1 UC2
C1 C2
UF
L UW+ -
UW-
r
j
0
Figure 2. Cylindrical capacitor model for calculation of capacitances Figure 3. Vector diagram
Figure 2: cylindrical capacitor model for calculation of capacitances between windings
between windings
Figure 3: vector diagram
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 19
COLUMN
U1 U 1 U3 U3 Uf Uf U 2 U 2 U1 U1
Coarse
Coarse
C1 C1 Uc U c C2 C2
Uf U f C1 C1 C 2 C2
Fine
Fine
Main HV
Main HV
- -
Core
Core
Core
Core
Parallel
Parallel
Tertiary
Tertiary
Tank
Tank
Tank
Tank
Series
Series
Fine
Fine
+ +
+ +
Fine
Fine
Uf U f
- -
Coarse
Coarse
K K
Uc U c
K K
r1 r1 r1 r1
r2 r2 r2 r2
r3 r3 r3 r3
r4 r4 r4 r4
Figure
Figure 4:4.
a)4:a)
Figure a)Stacked
stacked
stacked coarse/fine
coarse/fine
coarse/fine taparrangement
tap winding winding
tap winding arrangement
arrangement b)b)b)Autotransformer,
Autotransformer,
Autotransformer, regulating
regulating
regulating
winding winding
winding
coupled
coupled coupled
to tertiary
to tertiary to
windingtertiary winding
winding
can be quite complicated. Fig. 4a shows maximum switching capacity by evaluating or arcs cause free gases of a few milliliters
an example with stacked and parallel the discharge (arcing) time in relation to which fully dissolve in the oil. The typi-
windings (coarse/fine), Fig. 4b shows an the total switching time of the change-over cal composition of gases is shown in Fig.
autotransformer where the regulating selector; see Fig. 5. The admissible limit 6. The dominating gas is H2, followed by
winding couples to a delta-connected for the discharge time has been set in the some C2H2 and CH4. The H2/CH4 ratio in
tertiary winding. Many different winding range of half of the total switching time of this example is calculated to 4.74, which
geometries are used, some of them re the change-over selector (the time between is in the range for low energy discharges,
quire consideration of a third or fourth electrical opening and closing of contacts). acc. to IEC60599. Similar values were re-
capacitance. Such arrangements are wisely Several calculation examples for different corded by DGA from tap selectors in field
calculated by using software for electrical winding arrangements with all formulae service. Overall, the H2/CH4 ratio can
network calculations. can be found in [1], pages 145ff. appear in the range of 4-30 – which iden-
tifies the discharges as discharges of low
The calculation result can show values for 3. Effects of arcing by change- energy, sparks or partial discharges.
Is+/- of several hundred milliamperes and up
to 100 kV for Uw+/-. It must now be evaluated
over selector operation The amount of gases depends not only on
if the calculated values meet the switching Breaking capacitive currents of hundreds of the absolute values for Is and Uw but also on
capacity of the chosen tap selector model. milliamperes followed by recovery voltages the phase angle between Uw and Is, and on
All tap selector models have been tested of several ten kilovolts causes switching the contact opening speed. In case of high
with different loads (Is, Uw) to determine the sparks or low-energy arcs. These sparks Is and Uw values, the arcing/sparking sound
can be audible outside the transformer.
Usually it is a short, sharp, “spiky” sound;
for stronger switching arcs it changes to a
bright sound, similar when hitting a ham-
50
mer on a (dampened) steel plate. The sound
kV
can be scary – but it is definitely harmless.
UW
The question is now, if and how these gases
-50
can influence transformer DGA. Users
0,5 are very sensitive on acetylene (C2H2) in
A the transformer oil, as it is usually an in-
IS dication for serious (and unwanted) ar-
a
cing. So it is necessary to give an estimate.
-0,5 c During the lifetime of a transformer (with
b
7
tap-changer), the number of change-over
operations is usually low. One can say that
Movement
U1
C1
+
UF C2
0 -
RP
Figure 7. a) Additional tie-in resistor and potential switch b) Stack of tie-in resistors in new RD tap selector model
Figure 7a: Additional tie-in resistor and potential switch
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 21
COLUMN
w w w . t ra n sfo r m e r s - m a g a z i n e . co m 23
COLUMN