Manufacturer assumes no responsibility for a hazard or 1.

Features
damage caused by incorrect or non-application of any of the
instructions attached herein. Under no circumstance shall · Accuracy class 1 as per IEC 62053-21, · 2 Analog input and output can be independently
Larsen & Toubro be liable for any consequential or resulting class 0.5, 0.5S, 0.2, 0.2S as per IEC 62053-22 programmed for 0-20 / 4-20 mA configurable for
injury or for loss, damage or expense directly or indirectly from VLL, A, F, W, PF, VA (optional)
the use of this product. Sufficient care is taken to provide all · True RMS measurement
information regarding the product but Larsen & Toubro does · Password protection provision · Direct access key for basic parameters, Power and
not claim any responsibility for the damage caused by using the · OLD registers to store the previously Energy parameters
product directly or indirectly. Use according to the operating
instructions, professional practices, wiring rules, codes, safety cleared energy value and Load hours · Autoscrolling & freeze mode provision is available
regulations applicable to the given installation. · High/Low V, A, Hz, W, VA, VAr, PF value storage · Terminals with sealing provision (optional)
Digital Panel Meter · Auto-scaling of Kilo, Mega & Giga value · Favourite screen option for user selectable
During normal operation of this instrument ,hazardous voltages · THD for Voltage and Current parameters
Multifunction Meter are present at the rear terminals, which can cause injury or death.
Installation ,disconnection or removal of the meter should be
· Site selectable for 3 Ph 4 W, 3 Ph 3 W, 1 Ph · Phase wise Voltage and Current waveforms
44XX Series LCD Type carried out only by qualified, trained personnel, after de- · Site programmable CT/PT ratio · Power saving mode
energizing connected circuits. Improper installation , including · Maximum demand measurement with
improper grounding will void warranty. Product warranty void if
seal is broken. real time clock in 4440 series

2. Technical Specification
3 P 4 W, 3 P 3 W, 1 P Impulse voltage test ±6 kV as per IEC 62052-11
Insulation
Type of Type AC voltage test 4 kV double insulation as per IEC 62053-21
measurement True RMS, 128 samples per cycle, properties
1 sec update time Insulation resistance 500 V DC as per IS 13779
O O
Operating temperature -10 C to +55 C
Class 1 as per IEC 62053-21 O O
Measurement Operating Storage temperature -25 C to +70 C
Accuracy Class 0.5, 0.5s as per IEC 62053-22
conditions Humidity 5% to 95% relative humidity non-condensing
Class 0.2, 0.2s as per IEC 62053-22
Recommended wire 2.5 sq mm
Display type LCD 4 digit for instantaneous and 6 digits
and resolution for cumulative Shock As per standard IEC 60068-2
Mechanical
50 - 550 VLL Vibration 10 to 55 Hz, 0.15 mm amplitude
conditions
PT Primary and Secondary user programmable Casing Plastic mould protected to IP51 from front side
Input voltage for LT and HT applications Measurement category CAT III
Burden: 0.2VA max per phase Safety Pollution degree 2
-/5A and -/1A site selectable Protection IP20 at terminals, IP51 on front
Measuring circuit 300 gms
Current range from 10% to 120% of In (50mA-6A), Product weight
Input current Starting current : 0.4% of full scale Weight & Bezel dimension (W x H x D) 96 x 96 x 58 mm
dimensions
CT Primary and Secondary user Panel cutout 92 x 92 mm +0.8
-0.0
programmable for LT and HT applications Outputs Meter constant: 10000/(external CT ratio x PT ratio)
Frequency 40 - 70 Hz Type RS485 port Modbus RTU
Aux voltage 80 - 300VAC/DC Baud rate 2400, 4800, 9600, 19200 bps (site selectable)
Auxiliary circuit Aux burden <5VA Parity Odd, Even, None
Communication
Freq range 40 - 70 Hz Slave id 1 to 247 (programmable)
Test of power consumption as per IEC 62053-21 2 kVAC isolation for 1 minute between
Electrical Isolation
Voltage dips and interrupts as per IEC 62053-21 communication and other circuits
requirements
Short time over current protection 10A max continuous, 20 times of In for 3 sec Certifications CE, RoHS
Fast transients burst test ±4 kV as per IEC 61000-4-4

Immunity to electrostatic discharge ±8 kV air discharge, ±6 kV contact


discharge as per IEC 61000-4-2
Radiated, radio-frequency, 10 V/m as per 61000-4-3
Electro- electromagnetic field immunity test
magnetic Immunity to electromagnetic HF
compatibility 10 V/m as per IEC 61000-4-6
fields through conducted lines
(EMC)
Surge immunity test ±6 kV as per IEC 61000-4-5

Rated power frequency magnetic fields 1 A/m as per IEC 61000-4-8

Emission Class B as per CISPR 22

3. LED Indication WC 4410 WC 4410 WC 4410

Four parameter Three user selectable parameters available in


0.000 LL 0.000 A view display
415.0 LL 1.000 A single screen Wh is fixed and any two
0.000 Ay
0.000 Ln 0.000 F 230.0 Ln 50.00 F parameters selectable from 0.000 LL FAV
Wh Wh W,F,A,VLL,Ab,Ay,Ar,VA,PF Wh
Digital Outputs Fixed for quick
0.00000 (if available in meter) view of energy 1234.56 Disable Auto scroll mode and switch to Fav 0.00000
parameter always screen using Options button
I/0 I/0 I/0
Communication ON 1 2 3 4
Pulse ON 1 2 3 4 1 2 3 4

B P E B P E B P E
To view parameters CLR PRG
CLR PRG
To select and to accept the CLR PRG

MULTIFUNCTION METER value/Parameter in setup MULTIFUNCTION METER MULTIFUNCTION METER


To edit the value/ mode and scroll through
system type downward To edit the value/system the Energy parameters
in edit mode & scroll type upward in edit mode
through the basic & scroll through the
parameters Power parameters

4. Display Of Parameters
4.1 Display of Parameters for multifunction meter

Display Meaning Display Meaning Display Meaning


W Watts A Current Average HI High Level of Parameter
VA Total VA F Frequency Lo Low Level of Parameter
Vr Total VAR An Neutral Current V.thd Voltage THD
PF Power Factor RPM Revolution Per Minute (RPM) Ah Amps hour
Wh Active Energy Received V.Ph.ANG Voltage Phase Angle A.thd Amps THD
VAh Apparent Energy A.Ph.ANG Current Phase Angle K.FACt.U. K-Factor V
VArh.L Reactive Inductive Energy Un.BAL.V Unbalance Voltage K.FACt.A. K-Factor A
VArh.C Reactive Capacitive Energy Un.BAL.A Unbalance Current lntr Number of Interrupts
AVG Average On.hr On Hour b Baud Rate
Ld.Hr. Load Hour O Old d Delivered
L Lagging Power Factor CLr Clear C Leading Power Factor
LL Voltage line to line rd Rising Demand
Ln Voltage line to Neutral Fd Forecast Demand
rY Voltage RY Phase Md Maximum Demand
Yb Voltage YB Phase AL Additional Load
br Voltage BR Phase Et Elapse Time

Precautionary Measures to be taken while Wiring the Circuit :


· Turn OFF the power to the circuit, when wiring the circuit. Connecting or removing measurement cables while the power is turned ON is dangerous
· Take special caution not to wire a current measurement circuit to the voltage input terminal or vice-versa
· Strip the insulation cover of the measurement cable so that when it is wired to the input terminal, the conductive parts (bare wires) do not protrude from the terminal.
It is recommended to use appropriate pre lug after crimping the wire. Also, make sure to fasten the input terminal screws securely so that the cable does not come loose
· Use cables with safety terminals that cover the conductive parts for connecting to the voltage input terminals. Using a terminal with bare conductive parts is dangerous if the terminal comes loose
· After connecting the measurement cable, attach the current input protection cover for your safety. Make sure that the conductive parts are not exposed from the protection cover
· Use the suitable star screw driver and apply optimum torque to prevent damage to the meter terminals

Preventive Measures :
· Fuse : To avoid the possibility of short circuit, use a slow blow fuse that has a voltage rating
VAC : 250V, Fuse current : 200 mA, Breaking capacity : 10kA@ 125 VAC When replacing a fuse,
turn OFF the power and unplug the power cord. Never short the fuse holder
5.1 Programming Mode 5.2 General Programming Guide 5.3 Setting or Configuration of Parameter
Programming keys ·Press UP + E to enter Programming Mode · Press E to enter Edit Mode
·Press Down to enter Password (Default Value 0000) · Blinking of parameter/value indicates Edit Mode is ON
·Digit blinking indicates Edit Mode is ON · Press UP or DOWN to increment/decrement values
ENTER - to enter Edit Mode and save parameter
·Press UP or DOWN to increment and decrement or to select from available options
DOWN - to decrement value or parameter · Press E to accept the value of the parameter
value 0/1/2/3/4/5/6/7/8/9
UP - to increment value or parameter · Press DOWN to move to next parameters till end
·Press E to edit the next digit till 4th digit
 after configuration of last parameter display screen
·If Password is correct, meter displays next
will prompt “SAVE”, Display reads “Y” (YES)
parameter in editable mode
· Press Down if changes are not to be saved, display
·If Password is incorrect, meter will display next reads “ ” (no)
parameter but cannot be edited · Press E to save the option

CONFIG ROW 1: Parameter Pulse POP.ON.T


5.4 Display : 3P.4W
ROW 2: Options /Set options Demand Type* Sliding Sliding/Block** 250.0 50 to 500 msec
output on time
Programming Parameter Option/Range Demand Parameter* Watts Watts/VAR/A Avg/VA Analog Output 1
Default VLL/A/Freq/Watts/PF/VA
parameter AO.1.PAR diSAbL
CONFIG 3P 4W Demand Period* 15 5 - 30 mins
(Defines the power 3P 4W 3P 3W Analog Output 1
High Limit 1* 1800 1% to 100% of Full scale 0 to 20mA 0 to 20mA/4 to 20mA
system configuration.) 1 Phase Offset AO.1.OFS
100V-999kV High Limit 2* 1700 50% to 99% of High Limit 1 Analog Output 2
To set 33kV Set first four digits parameter AO.2.PAR diSAbL VLL/A/Freq/Watts/PF/VA
(3300) as explained above press
PT Primary 415 UP/DOWN key to place decimal point Low Limit* 1300 50% to 99% of High limit 2
Analog Output 2
at appropriate location.
Offset AO.2.OFS 0 to 20mA 0 to 20mA/4 to 20mA
Letter K/M will indicate the Kilo/Mega. 2400, 4800, 9600, 19.2k
M & K both LED will glow for Giga Baud rate BAUD 9600
Power PWR.SAV Disable Disable/Enable
PT Secondary 415.0 50V to 550V Parity PARITY Even Even/Odd/none saver mode
CT Primary 5.000 0.5A - 99kA Slave Id SL.Id 1.000 1 to 247 *Applicable for 4420 and 4430 Model
**Applicable for 4440 model
*** not applicable for model 4430
CT Secondary 5.000 0.5A - 6A
No of Poles (For rpm) 4.000 1 to 28 5.5. Enabling & Disabling Auto Scrolling
Method of VA Selection: Press DOWN for 6 secs
VA selection VEC.Har Arithmetic /Vector harmonics Yes/No Display Shows: EnAbLE Auto.sc
/Vector Reverse lock*** REV.LOC No If YES it blocks energy
accumulation in case the CT Again press DOWN for 6 sec
Options: Watts/FREQ/A/ polarity reverse. Display Shows: diSAbL Auto.sc
Programmable
Watts VLL/Ab/Ay/Ar/VA/PF 5.6.Clearing Parameter
Parameter 1 PARAM 1 PASSWORD PASWd 0000 0000 to 9999
· Press UP+ DOWN to enter Clear Mode
Programmable Options: Watts/FREQ/A/
PF Energy ENERGY Resolution Resolution/Counter · Press DOWN to enter Password (0000 Default)
Parameter 2 PARAM 2 VLL/Ab/Ay/Ar/VA/PF · Press E to clear
YEAr** x Range: 2012 to 2052 Starting Current 0.400 · Select :
START.A 0.4 to 20% of Full Scale
-CLR. int to clear integrator (all energy parameter)
dAtE** x Jan 01 to December 31 Display update time 1.000 -CLR. Hi. L clear max or min value
DISP.U.R 1 to 5 seconds
-CLR. Md clear max demand
Time** x 00:00 to 23.59 Display autoscroll Time Auto.T 5.000 1 to 10 seconds · Once parameter to be cleared is selected it prompt
to “Y” (YES) or “ ” (no) for conformation

6. Wiring Diagram
Received (Import) Delivered (Export) Received (Import) Delivered (Export) Received (Import) Delivered (Export)

Load Line Load Line Load Line

AMF IP AMF IP AMF IP


240V AC 240V AC 240V AC

3 Phase 4 Wire System 3 Phase 3 Wire System Single Phase System

7. Memory Map
Address Parameter Data type Address Parameter Data type Address Parameter Data type Address Parameter Data type
40101 Watts Total float 40157 Frequency float 40223 MD Occurrence time Unsigned long 40315 PF Min. (absolute min.) float
40103 Watts R Ph float 40159 Wh Received float 40233 V R Ph angle float 40479 V R Har. float
40105 Watts Y Ph float 40161 VAh Received float 40235 V Y Ph angle float 40481 V Y Har. float
40107 Watts B Ph float 40163 VARh Ind. Received float 40237 V B Ph angle float 40483 V B Har. float
40109 VAR Total float 40165 VARh Cap. Received float 40239 I R Ph angle float 40485 I R Har. float
40111 VAR R Ph float 40167** Wh Delivered float 40241 I Y Ph angle float 40487 I Y Har. float
40113 VAR Y Ph float 40169** Vah Delivered float 40243 I B Ph angle float 40489 I B Har. float
40115 VAR B Ph float 40171** VARh Ind. Delivered float 40259 V Unbal R Ph float 40491 K factor V R Ph float
40117 PF Avg (inst) float 40173** VARh Cap. Delivered float 40261 V Unbal Y Ph float 40493 K factor V Y Ph float
40119 PF R Ph float 40175 PF Avg. Received float 40263 V Unbal B Ph float 40495 K factor V B Ph float
40121 PF Y Ph float 40177 Ampere Hour float 40265 I Unbal R Ph float 40497 K factor I R Ph float
40123 PF B Ph float 40179** PF Avg. Delivered float 40267 I Unbal Y Ph float 40499 K factor I Y Ph float
40125 VA Total float 40181** Ampere Hour Delivered float 40269 I Unbal B Ph float 40501 K factor I B Ph float
40127 VA R Ph float 40183 Neutral Current float 40285 VLL Max. float ** Applicable for 4430 Model

40129 VA Y Ph float 40185 V R Har. float 40287 VLL Min. float


40131 VA B Ph float 40187 V Y Har. float 40289 VLN Max. float
40133 VLL Avg float 40189 V B Har. float 40291 VLN Min. float
40135 VRY Ph float 40191 I R Har. float 40293 Amps Max. float
40137 VYB Ph float 40193 I Y Har. float 40295 Amps Min. float
40139 VBR Ph float 40195 I B Har. float 40297 Frequency Max. float
40141 VLN Avg float 40197 Rising Demand float 40299 Frequency Min. float
40143 V R Ph float 40201 Max. Demand float 40301 Watts Max. float
40145 V Y Ph float 40203** Rising Demand Delivered float 40303 Watts Min. float
40147 V B Ph float 40207** Max. Demand Delivered float 40305 VAR Max. (absolute max.) float
40149 I Total float 40215 RPM float 40307 VAR Min. (absolute min) float
40151 I R Ph float 40217 Load Hours Received Unsigned long 40309 VA Max. float
40153 I Y Ph float 40219** Load Hours Delivered Unsigned long 40311 VA Min. float
40155 I B Ph float 40221 No of interruptions Unsigned long 40313 PF Max. (absolute max.) float

8. Mounting Dimensions : 9. Troubleshooting


1) Meter display does not turn ON. In case of complaint please contact
WC44XX0501A

90 +2.0 Steps for Mounting


- 0.0
Insert meter to panel a) Check that there is power supply applied on Aux supply terminals. CUSTOMER INTERACTION CENTRE (CIC)
1
without clamps b) Check fuse connection (Use fuse connection of specified ratings). TOLL-Free: 1800 233 5858, 1800 200 5858

2
2) Data displayed / reading incorrect. Telephone : 022 6774 5858
1 Insert both clamps a) Check that CT /PT ratios are properly set. email: cic@LNTEBG.com
2 3
b) Check if proper configuration mode 3P4W, 3P3W, 1Phase is correctly set.
90 +2.0
- 0.0
3) Pt reading are incorrect / Active Power reading is negative.
a) CT connections may be reversed, check and correct CT connection.
b) Check voltage and current phases are connected in proper sequence. L&T Electrical & Automation
4) RS485 communication does not work.
a) Check baud rate & parity maintained in the connected computers is same as Meter. Electrical Standard Products
b) Memory mapping in software is correct. L&T Business Park, Tower 'B' / 3rd Floor
3 54mm
c) Check Slave ID of meter is Unique & properly maintained. Saki Vihar Road, Powai Mumbai 400 072
4mm
d) Check converter is working properly. Website: www.Lntebg.com