Académique Documents
Professionnel Documents
Culture Documents
Report On
Practical Training
Taken At
I would like to express my deep gratitude to Er. Neeraj Bakshi (Junior Engineer)
and Er. Nishant Tayagi of PGCIL Samba substation for their active support and
continuous guidance without it would have been for me to complete this project.
They were generous enough to take time out of their regular work to lend a
helping hand whenever I needed one and enabling me to complete this project.
Single line diagram (SLD) is a line diagram of a concerned electrical system which
includes all the electrical equipments connection sequence wise from the point of
entrance of power up to the end of the scope of the mentioned work. As the
feeders enter the station they are to pass through various instruments. The
instrument has their usual functioning.
S.No. Description Of Parameters 400kV
System
1. System Operating Voltage 400kV
2. Maximum Operating Voltage Of The System (rms) 420kV
3. Rated Frequency 50Hz
4. Number Of Phases 3
5. Corona Extinction Voltage 320kV
6. Rated 3-Phase Symmetrical Short Circuit Current Withstand 40kA/1sec
Capacity
7. System Neutral Earthing Effect
Earthed
5. CLASSIFICATION OF SUBSTATION
According to service requirement:
SUBSTATION COMPONENTS:
1. Lightening Arrestors
2. Capacitive Voltage Transformer (CVT)
3. Wave Trap
4. Isolators
5. Current Transformer (CT)
6. Circuit Breakers (CB)
7. Bus Bars
8. Interconnected Transformers (ICT’s)
9. Post Insulators
10. Bus Reactor
Graphical symbols for various apparatus and circuit
elements in substation:
Inter-connected Transformer (ICT):
Inter-connected transformer is usually an autotransformer which connects two grids at
different voltages. All over India all the ICT’s at different substations are interconnected
Lightening Arrester:
Lightning Arrester is a device which provides a low
resistive path to atmospheric lightening. This device acts
as a non-linear resistance. Atmospheric lightening has a
high voltage, high current and high frequency. When the
lightning strikes the transmission lines the lightning
arrester being a non-linear resistance, when the voltage
is high its resistance reduces and the lightning will be
earthed through this connection. These lightening
arresters are connected in parallel with line.
Lightening Arrester
Uses:
For protection of equipment connected ahead of the transmission line from high
voltages.
Protection from Ground surge voltage produced during off load, when switching.
Wave Trap:
Wave trap is used to create high impedance to the
carrier wave having high frequency, for communication
to enter in the substation. Carrier wave communication
uses up to 150kHz to 800kHz frequency for all the
communication. These high frequency damages
Wave Trap
Isolators:
Isolator is a type of mechanical switch, which is used for opening an electrical circuit in
the no-load condition. These are generally employed on both ends of circuit breaker so
that circuit breaker repair can be done without any risk of high electric currents.
Classification of Isolators based on requirement of system:
Double Break Type Isolator
Single Break Type Isolator
Earth Switch:
Earth switch is used to ground the residual charge remaining in the circuit when the circuit is
broken or opened by circuit breaker and isolator. Earth switch earthing arms are usually
aligned horizontally at off condition. These earthing arms rotate and move to vertical
position and make contact with earth female contacts fitted at the top of post insulator.
The earthing arms are so interlocked with the main isolator such that the earthing
switch is closed only when isolator is open and similarly isolator contacts can be closed
only when the earth switch is open.
This scheme is used in 200 KV yard and this yard has 12 lines connected. On BUS-I, 6
lines are connected, and on BUS-II, remaining 6 lines are connected. When there is high
load on any main bus, then some load is shifted to other main using bus coupler.
The two buses are connected to each other by using a tie circuit breaker. This breaker is
used when we have to work on any of the main circuit breakers. The power is shifted
through this breaker in order to prevent shutdown of the supply.
Circuit Breaker:
An electrical circuit breaker is a switching device which can be operated manually and
automatically for controlling and protecting an electrical power system. Circuit breaker
is an on-load switch.
Reactor:
Reactor is a device which is connected to the line. The main purpose of the reactor is to
decrease the reactive power generated by the capacitance, by consuming the reactive
power in the line.
Types of reactor:
Line Reactor:
In long transmission lines, line
capacitance is generated
between HV power lines and
ground. Due to this capacitance,
voltage at the receiving end gets
increased in comparison to
sending end voltage. This
phenomenon happens when
there is open circuit or lightly
loaded at receiving end. This
effect is known as Ferranti effect.
The line reactor is used to
consume this increase in the
voltage. The line reactor is a
device which contains coils and acts as an inductor. This inductor cancels the effect of
the capacitance.
The leading power factor is generated by the capacitance. The inductor creates a lagging
power factor. This balances out the net effect on the power factor.
Bus Reactor:
A bus reactor is a type of air core inductor, or in some cases, oil filled, connected
between two buses or two sections of the same bus in order to limit the voltage
transients on either bus.
It is installed in a bus to maintain system voltage when the load of the bus changes. It
adds inductance to the system to offset the capacitance of the line which varies due to
load, humidity, weather, generator excitation and temperature. It is also used to
maintain the power factor.
Insulators:
An electrical insulator is a material whose internal electric charges do not flow freely
and which therefore does not conduct an electric current under the influence of electric
field.
Types of insulators: -
Pin type insulator
Suspension insulator
Strain insulator
Shackle insulator
Post insulator
Suspension insulator:
For high voltages (>33 KV),
suspension type insulators are
used which consist of no. of
porcelain discs flexibly
connected in series by metal
links in the form of a string.
Strain insulator:
When there is a dead end of the line, or there is a corner or a sharp curve,
or the line crosses the river etc., the line is subjected to greater tension.
Then we use shackle insulator for high voltages and for low voltages we
use shackle insulator.
It consists of assembly of suspension type insulators. The discs of strain
insulators are employed in vertical plane.
Post Insulator:
These are generally subjected to bending, torsion and compression forces. These
are used as supports for conductors connecting bus-bars. It consists of porcelain
body, cast iron cap and flanged cast iron base.
Protective Relays:
It is a device that detects the faults and initiates the operation of circuit breakers to
isolate the defective elements from the rest of the system. The relay ensures the safety
of circuit equipment from any damage which might be caused by the fault.
Distance relay:
It a protective relay whose action depends upon the distance of the feeding point
to the fault. The time of operation of such relays is a function of the ratio of
voltage and current i.e. impedance.
The impedance between relay and fault depends upon the distance between
them.
The relay will only operate when the impedance of the line becomes less than
predetermined impedance. As the impedance of the transmission line is directly
proportional to its length. So, a distance relay can only operate if fault occurs
within a predefined distance or length of wire.
Substation Earthing: -
Substation earthing system has buried horizontal mesh of steel rods and vertical
electrodes welded to the mesh. The vertical risers and galvanized steel grounding strips
are connected between the grounding mesh and the point to be grounded. The earth
points are held near earth potential by low resistance conductor connections with earth
mat which is also known as earth grid.
The new criteria of substation earthing are that they should have low earth resistance,
low touch potential and low step potential.
Power Transformers installed in the substations will have oil as cooling and
insulating medium. Oil leakage takes place during operation or when changing
the oil in the transformer. These oil spillages which can catch fire is dangerous to
the switchyard operation and even catch fire. So, Stones/Gravel is provided to
protection.
Stones eliminate the growth of small weeds and plants inside the switch yard
Corona Ring:
These rings are anti-corona rings, are a torroid made from a conductive material. The
role of corona ring is to distribute the electric field gradient and lower its maximum
value below corona threshold, preventing corona.
Corona occurs when the electric field at the surface of conductors exceeds a critical
value of dielectric strength of air. It is around 30kV/cm, but decreases with increase in
pressure. So, corona is more at high altitudes.
The electric field at a conductor is greatest where the curvature is sharpest. So, corona
discharge occurs first at these sharp points, corners and edges. So, corona rings are used
at these locations to distribute the electric field concentrated here and thus avoid
corona.
The generator is turned on when there is a failure in the supply of power, from the
transformer which is used for powering all the equipment. Generator is powered by
petrol and converts mechanical energy to electrical energy.
Faults:
Electrical fault is a deviation of voltages and currents from its nominal values. When
fault occurs, it causes excessively high currents to flow which causes damage to
equipment and devices.
Symmetric Faults:
These are very severe faults and occur infrequently in the power system. These
are also known as balanced faults.
1. LLLG fault:
2. LLL fault:
Unsymmetrical faults:
They are very common and less severe than symmetrical faults. This fault
occurrence cause’s unbalance in the system. It means that the impedance values
are different in each phase causing unbalance current to flow in the phases.
The main causes of this fault are weather conditions, equipment failure, human
errors smoke or fires.
1. LG fault
2. LL fault
3. LLG fault
Line to ground (LG) fault is most common fault and 65% - 70% faults are of this type. It
causes the conductor to make contact with the earth or ground.
Line to line fault occurs when two conductors make contact with each other mainly
while swinging of wires due to winds. 5% -10% of faults are of this type.
15% -20% of faults are double line to ground, and causes two conductors to make
contact with ground.
Transformer
Working principle of Transformer
Types of Transformer
Components of Transformer
Core
Windings
Insulating materials and Transformer oil
Tap changer
Oil conservation tank
Breather
Buchholz Relay
Cooling tubes and radiator
Current transformer
Capacitive voltage transformer
Transformer:
A transformer is an electric device which transfers electric device which transfers
electric energy from one circuit to another through process of electromagnetic
induction.
Vp - Primary Voltage
Vs - Secondary Voltage
Np – No of Primary Windings
Ns – No of Secondary Windings
Φ – Flux Linkage
The core of transformer provides a low reluctance path to the flux created by primary
winding. The core acts a medium for linking of flux to secondary winding.
The sheets are laminated in order to reduce the eddy current losses.
In case of an ideal transformer the power available at output is equal to the power at
the input. This means there is no power loss in the core and the windings, and we get an
efficiency of 100%.
But in case of practical transformer the efficiency is around 94 % to 96%. Because there
are losses in the core and windings. If a transformer operating with a constant voltage
and frequency with a very high capacity, the efficiency can be made as high as 98 %.
Types of transformers: -
The transformers can be classified into various types based on their use, constructions,
supply and purpose. A few types are
Single-Phase Transformer:
The single-phase transformer has only one set of windings.
i.e. one primary and one secondary winding.
These are usually found in small electronic equipment like power supply,
inverters etc.
Three-phase transformer:
In this type of transformer there are three high voltage and three low voltage
windings wound on a single core. These types of transformers are used primarily
in Generation, Transmission and Distribution of power.
Power Transformer:
These transformers usually have high ratings and are used primarily to transfer
power. They are used in generating stations to step-up the voltage and are also
used in sub-stations to further transfer power to distribution stations.
Distribution Transformer:
These transformers are having low rating and are used in distribution of
electricity to the consumers. They step down the voltage to 220V or 400V. These
transformers can be found in in local distribution centers.
These transformers usually have a delta connection on primary side and a star or
Y connection on the secondary or output side.
Instrument Transformer:
These types of transformers are used for measurement and protection. These
transformers are connected to relay panels which continuously monitor the
values of current and voltage and in case of a fault the value of current and
voltages changes and crosses a certain limit the relay panel then trips the line in a
sub-station.
Core:
The core of a transformer is made up of laminated soft iron core. It provides a
support for the windings and also acts as a low reluctance medium for the flux to
pass through the transformer.
The core is made of thin laminated sheets of silicon steel in order to reduce the eddy
currents in the core when magnetic field is created in the core. The eddy current
causes heating and energy losses in transformer thereby decreasing efficiency.
The composition of a transformer core depends on factors like voltage, current and
frequency.
The diameter of the transformer core is directly proportional to iron losses and is
inversely proportional to copper losses. If diameter of core is decreased, the weight
of iron in the core is reduced, which leads to less core losses of the transformer but
the no of windings is increased and will have higher copper losses.
So, the diameter of core of transformer should be optimized considering both losses
into consideration.
The main factors that are taken into consideration while designing a transformer
core are
Higher reliability.
Reduction in iron losses in transformer and magnetizing current.
Lowering material cost and labor cost.
Decreasing of noise levels.
Windings:
Windings are copper conductor wound on the transformer core. The windings can be
two or more than two.
It has high conductivity. This minimizes copper losses in windings and also
reduces copper needed for winding.
It has high ductility. So, it can be easily wound into tight windings around
transformer core.
The transformer oil is usually hydrocarbon mineral oil. Oil contamination is a serious
problem as contamination affects the dielectric properties and renders it useless as an
insulating medium.
The transformer has another insulation method which is called bushing. Bushing is done
to prevent flashover from the high voltage terminal to the earthed tank. Bushing is used
at the high voltage terminal and also at the intermediate and low voltage terminal.
Bushing is made up of porcelain which has good insulation properties.
Tap changer:
Tap changer is used to change the tapings of a transformer. Tapings are terminals at
fixed no of turns of the windings where terminals can be connected. During loaded
conditions the voltage at the receiving end gets reduced and during lightly loaded
conditions the voltage at the receiving end gets increased. Due to this there is a change
in values of voltage at receiving end so in order to keep a constant voltage at receiving
end the tapings of the transformer are changed accordingly.
The conservator tank is vented to the atmosphere at the top to release the moisture
generated in the oil. The venting is done through breather.
The oil is kept at the middle of the conservator tank because as the temperature rises
and cools down the oil expands and contracts. So, in order to give it room for
contraction and expansion the tank is only half filled.
The conservator tank is connected to the main tank of transformer through a pipe, the
mai
n
tank
of
tran
sfor
mer
is
com
plet
ely
filled with oil.
The conservator tank comes with a gauge which indicates the current level of the
transformer oil in the conservator.
Breather:
Breather controls the moisture level in the
transformer. Moisture can arise due to variation
of the oil temperature, which then causes the
pressure variations in the conservator tank. This
pressure is balanced out by allowing the
atmospheric air to go inside the tank and out of
the tank. This way moisture gets inside the oil
conservator.
The breather acts as an air filter for the transformer and controls the moisture level
inside the transformer. Breather is connected to the end of the breather pipe.
Buchholz Relay:
It is a type of oil and gas actuated protection relay which is used on transformers. The
relay is placed between transformer tank and the conservator tank.
It is used for the protection of transformer from the faults occurring inside the
transformer. The internal faults include, Short circuit faults, core faults, winding faults
etc. The transformer oil in such cases will breakdown and gas bubbles will be created
inside of the transformer oil. The relay will sense such faults and close the alarm circuit.
The relay consists of two mercury switch upper switch is connected to the alarm circuit
and the lower mercury switch is connected to external trip circuit which will trip the
transformer.
Whenever there is a fault in the transformer, the oil in the transformer gets overheated
and as a result gases generated. The generation of the gases depends mainly on the
intensity of the fault produced. The gases produced can be used to detect the winding
faults.
The gases will displace the oil in the relay it tilts the switch at the top of the chamber
and thereby closing the mercury switch and alarm circuit will be closed indicating the
fault in the transformer.
The collected can be viewed through the window provided on the walls of the chamber.
The samples of gas can be taken and analyzed for determining faults.
During severe faults such as phase to earth faults and faults in tap changing gear, the
amount of gas produced will be more and it will float at the bottom chamber of the
relay and closing the mercury switch at the bottom of the chamber and trip the circuit
and isolate the transformer.
The level of explosion vent is normally maintained above the level of the conservator
tank.
In transformers of high ratings there is pressure release valve which is used instead of
explosion vent to provide a path for the boiling oil to flow from in case of a severe fault.
In this method the oil from the radiator to transformer is forced by pumping oil
with a pump. The radiator is cooled by using fans. When there is a light load the
system will become like an ONAN by switching off the pump and fans.
During peak loading conditions the pump and fans are switched on and it becomes
OFAF. This method is used in transformers having ratings more than 30MVA.
Current Transformer:
This is a measurement transformer which is used to measure current in a transmission
line and for the protection. The transformer steps up the voltage which leads to lower
current in the secondary windings of the transformer. This transformer is connected in
series with the line.
The primary winding is usually a single line and secondary is wound around the core and
have different tapings. The ammeter is connected to the secondary windings.
When there is a rise in current in the primary winding, the current in the secondary
winding will also increase. It will be connected to the relay panel which will trip the line
if current rises beyond a fixed maximum value.
Live Tank
In this Current transformer the
core is the transformer tank is at
top with the core and secondary
windings in it.
The primary terminal is
connected at the tank. The
secondary output terminal is at
the bottom in base of the
transformer.
These transformers are compact
and reliable.
The heat produced in this
transformer is less as the
primary winding is of shortest
possible length. The insulation is
robust and reliable.
Dead Tank
In this type of current transformer, the
core and the secondary winding are
housed in the tank at the bottom of the
transformer.
In this the primary is brought from top to
the bottom of the tank and is highly
insulated as it carries high current.
In this the transformer is bulky and costly.
The insulation is not robust.
CVT (Capacitive
voltage transformer):
The CVT is a type of instrument transformer
which is used to measure the voltage of the line.
CVT is preferred over the potential transformer
because CVT is cheap to use for voltage above
100kV.
CVT is placed parallel to the line and the voltage of the line is measured.
Uses:
For measurement of the line voltage.
For protection of the equipment from overvoltage.
For Power Line Communication Carrier (PLCC).