Technical Data Submittal Document


Model GPY
Full Service Reduced Voltage
Wye-delta Open
Electric Fire Pump Controller

Contents:
• Data Sheets
• Dimensional Data
• Wiring Schematics
• Field Connections

Note: The drawings included in this package are for controllers covered under our standard offering.
Actual AS BUILT drawings may differ from what is shown in this package.

July 2016
Technical Data
Model GPY Electric Fire Pump Controller

3L3 1M T3
From normal
3L2 T2
incoming power through
Disconnecting Means 3L1 T1

(IS/CB)*
M
CR4
1M 2M T5
CR5 1S T4
2M
T6
CR5 2M
3L1
1S
1S

GPY 3L2

Across-the line
600 starting
Open transition
Locked rotor current
% of full load
Line current

Transition current
Starting Method: Reduced Voltage
Wye-delta open 210
Typical Voltage Applied at Start: 100% Wye delta starting

Inrush Current: 33% of normal load current Full load current

Starting Torque: 33%


20 40 60 80 100
Motor Type: Wye-delta Percent of motor speed (%)
No. of Contactors: 2 at 58%, 1 at 33% of motor FLC
Min. ampacity of motor conductors: 6 at 125% x 58% of FLC

Built to NFPA 20 (latest edition)


• UL218 - Fire Pump Controllers
Underwriters Laboratory (UL)
• CSA C22.2 No. 14 Industrial Control Equipment
Standard,
Listings, FM Global Class 1321/1323
Approvals and New York City Accepted for use in the City of New York by the Department of Buildings
Certifications Seismic Certification See page 5 for details
Optional
□ CE Mark Various EN, IEC & CEE directives and standards
Protection Rating
□ Standard: NEMA 2 (IP31)
Optional
□ NEMA 12 □ NEMA 4X-304 sst painted □ IP54
□ NEMA 3 □ NEMA 4X-304 sst brushed finish □ IP55
Enclosure □ NEMA 3R □ NEMA 4X-316 sst painted □ IP65
□ NEMA 4 □ NEMA 4X-316 sst brushed finish □ IP66
Accessories Paint Specifications
• Bottom entry gland plate • Red RAL3002
• Lifting Lugs • Powder coating
• Keylock handle • Glossy textured finish
*Please see Disconnecting Means details on page 3.

July 2016 2
Technical Data
Model GPY Electric Fire Pump Controller

Shortcircuit 200V to 208V 220V to 240V 380V to 416V 440V to 480V 575V to 600V
Withstand 60Hz 60Hz 50 Hz / 60Hz 60Hz 60Hz
Rating HP (kw)

� Standard 100kA
5-150 (3.7 - 110) 5-200 (3.7 - 147) 5-300 (3.7 - 220) 5-450 (3.7 - 335) n/a
� Optional 150kA
� Standard 50kA 200 (147) 250 (184) 350 - 450 (257 - 335) 500 (373) 5-500
� Optional 100kA n/a n/a n/a n/a (3.7- 373)

Ambient Standard: Optional:


Temperature □ 5°C to 40°C / 41°F to 104°F □ 5°C to 55°C / 41°F to 131°F
Rating

Surge
Surge arrestor rated to suppress surges above line voltage
Suppression
• Isolating switch and circuit breaker assembly:
- Door interlocked in the ON position
- Isolating switch rated not less than 115% of motor full load current
Disconnecting
- Circuit breaker continuous rating not less than 115% of motor full load current
Means
- Overcurrent sensing non-thermal type, magnetic only
- Instantaneous trip setting of not more than 20 times the motor full load current
• Common flange mounted operating handle
Service Entrance
Suitable as service entrance equipment
Rating

Emergency Start • Flange mounted • Integrated limit switch


Handle • Pull and latch activation • Across the line start (direct on line)

Locked Rotor • Operate shunt trip to open circuit breaker • Trip between 8 and 20 seconds
Protector • Factory set at 600% of motor full load current

Electrical • Voltage phase to phase (normal power)


Readings • Amperage of each phase when motor is running
Pressure • Continuous system pressure display
Readings • Cut-in and Cut-out pressure settings
• Pressure readings with date stamp
• Event recording with date stamp
Pressure and
• Under regular maintained operation, events can be stored in memory for up to 5 years.
Event recorder
• Data viewable on operator interface display screen
• Downloadable by USB port to external memory device
• Pressure transducer and run test solenoid valve assembly for fresh water application
• Pressure sensing line connection 1/2” Female NPT
Pressure Sensing • Drain connection 3/8”
• Rated for 0-500PSI working pressure (standard display at 0-300psi)
• Externally mounted with protective cover

July 2016 3
Technical Data
Model GPY Electric Fire Pump Controller

Audible Alarm 4” alarm bell - 85 dB at 10ft. (3m)


• Power available • Locked rotor • Manual start
• Phase reversal • Periodic test • Deluge valve start
• Motor run • Fail to start • Remote automatic start
Visual Indications • Pump room alarm • Low discharge pressure • Remote manual start
& Alarms • Motor trouble • Low pump room temperature • Overcurrent
• Phase loss • Pump room temperature (ºF or ºC) • Undercurrent
• Phase unbalance • Pump on demand/Automatic start • Undervoltage
• Low water level • Emergency start • Overvoltage
SPDT-8A-250V.AC
• Power available
• Phase reversal
• Motor run
• Common pump room alarm (field re-assignable)**
Remote Alarm
• Overvoltage • Undervoltage • Phase unbalance
Contacts
• Low pump room temperature • High Pump room temperature
• Common motor trouble (field re-assignable)**
• Overcurrent • Fail to start
• Undercurrent • Ground fault
• Free (field programmable)**
• Embedded microcomputer with software PLC logic
• 4.2” color touch screen (HMI technology)
ViZiTouch
• Upgradable software
Operator Interface
• Expandable storage
• Multi-language
• Protocol: Modbus
Communication
• Connection type: Shielded female connector RJ45
Protocol
• Frame Format: TCP/IP
Capability
• Addresses: See bulletin MOD-GPx
• Start on pressure drop
Automatic Start
• Remote start signal from automatic device
• Start pushbutton
• Run test pushbutton
Manual Start
• Deluge valve start
• Remote start from manual device
• Manual with Stop pushbutton
Stopping
Operation • Automatic after expiration of minimum run timer ***
• Minimum run timer ***(off delay)
Field Adjustable &
Timers • Sequential start timer (on delay)
Visual Countdown
• Periodic test timer
• Pressure
Actuation
• Non-pressure
Visual Indication
• Automatic
Mode
• Non-automatic

**Tornatech reserves the right to use any of these three alarm points for special specific application requirements.
***Can only be used if approved by the AHJ

July 2016 4
Technical Data
Model GPY Electric Fire Pump Controller

Seismic
TRU Compliance, LLC
Certification TWEI Project No.: 15014
A Tobalski Watkins Affiliate
Company
Mounting
Rigid base and wall mounting
details
Seismic
Building Test Seismic AFLX-H ARIG-H AFLX-V ARIG-V
Certification
Code Criteria Parameters
SDS z/h IP
Seismic IBC
Information ICC- 2.0 1.0 1.5 3.20 2.40 1.33 0.53
2015, ASCE 7-10
ES
CBC Chapter 13
AC156 3.2 0.0 1.5 3.20 1.28 2.13 0.85
2016

RRS for Nonstructural Components Testing


10.0
Spectral Response Acceleration (g)

1.0

0.1
0.1 1.0 10.0
Frequency, f (Hz)

Horiz. Level 1 Vert. Level 1

Notes:
• Components are tested in accordance with ICC-ES AC156, IBC 2015 & CBC 2016.
• OSHPD Special Seismic Certification Preapproval (OSP)

July 2016 5
Technical Data
Model GPY Electric Fire Pump Controller

A4 Flow switch provision C20 Manual start alarm contact (Form C-SPDT)

Foam pump application w/o pressure transducer and run C21 Deluge valve start alarm contact (Form C-SPDT)
A8
test solenoid valve C22 Remote automatic start alarm contact (Form C-SPDT)
A9 Low zone pump control function C23 Remote manual start alarm contact (Form C-SPDT)
A10 Middle zone pump control function C24 High pump room temperature alarm contact (Form C-SPDT)
A11 High zone pump control function Second set of standard alarm contacts (Form C-SPDT)
C25
Non-pressure actuated controller w/o pressure transducer (Typical for city of Los Angeles and Denver)
A13
and run test solenoid valve Additional visual and alarm contact
Cx
Lockout/interlock circuit from equipment installed inside the (specify function) (Form C-SPDT)
A16
pump room Low suction pressure transducer for fresh water rated at
D1
Built in alarm panel (120V.AC supervisory power) providing 0-300PSI with visual indication and alarm contact
indication for: Low suction pressure transducer for sea water rated at
B11 • Audible alarm & silence pushbutton for motor run, phase D1A
0-300PSI with visual indication and alarm contact
reversal, loss of phase.
Pressure transducer and run test solenoid valve for fresh
• Pilot lights for loss of phase & supervisory power available D5
water rated for 0-500PSI (for factory calibration purposes only)
Built in alarm panel same as B11 but 220-240VAC
B11B Pressure transducer and run test solenoid valve
supervisory power D5D
for sea water rated for 0-500PSI
High motor temperature c/w thermoster relay and alarm
B19A D10 Omit mounting feet (when applicable)
contacts (Form C-SPDT)
High withstand rating for (normal power section)
High motor temperature c/w PT100 relay and alarm D13
B19B • 208V to 480V = 150kA • 600V = 100kA
contacts (Form C-SPDT)
D14 Anti-condensation heater & thermostat
Ground fault alarm detection c/w visual indication and alarm
B21
contact (Form C-SPDT) D14A Anti-condensation heater & humidistat
C1 Extra motor run alarm contact (Form C-SPDT) D14B Anti-condensation heater & thermostat & humidistat
C4 Periodic test alarm contact (Form C-SPDT) D15 Tropicalization
C6 Low discharge pressure alarm contact (Form C-SPDT) D18 CE Mark with factory certificate
C7 Low pump room temperature alarm contact (Form C-SPDT) D26 Modbus with RTU frame format and RS485 connection
C10 Low water reservoir level alarm contact (Form C-SPDT) Motor heater connection (external single phase power
D27
source and heater on/off contact)
High electric motor temperature alarm contact
C11
(Form C-SPDT) Motor heater connection (internal single phase power
D27A
source and heater on/off contact)
High electric motor vibration c/w visual indication and alarm
C12
contact (Form C-SPDT) D28 Customized drawing set
Pump on demand / automatic start alarm contact D34 Field programmable I/O board - 8 Input / 5 output
C14
(Form C-SPDT)
D35 Field programmable I/O board - 8 Input / 10 output
C15 Pump fail to start alarm contact (Form C-SPDT)
Redundant pressure transducer for fresh water rated for
D36
C16 Control voltage healthy alarm contact (Form C-SPDT) 0-500PSI
Flow meter valve loop open c/w visual indication and alarm Redundant pressure transducer for sea water rated for
C17 D36A
contact (Form C-SPDT) 0-500PSI
High water reservoir level c/w visual indication and alarm D37 Window kit for operator interface
C18
contact (Form C-SPDT)
C19 Emergency start alarm contact (Form C-SPDT)

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

July 2016 6
Technical Data
Model GPY Electric Fire Pump Controller

L01 Other language and English (bilingual) L14 Russian


L02 French L15 Turkish
L03 Spanish L16 Swedish
L04 German L17 Bulgarian
L05 Italian L18 Thai
L06 Polish L19 Indonesian
L07 Romanian L20 Slovenian
L08 Hungarian L21 Danish
L09 Slovak L22 Greek
L10 Croatian L23 Arabic
L11 Czech L24 Hebrew
L12 Portuguese L25 Chinese
L13 Dutch

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

July 2016 7
Technical Data
Model GPY Electric Fire Pump Controller

ViZiTouch Operator Interface

3
1

PMS 295 PMS 361 Noir

4 5 6 7 8
8

9
10

11 12

13
?

1 - Power on LED 8 - USB port


2 - Color touch screen 9 - START button
3 - Alarm LED 10 - Contextual navigation pad
4 - HOME page button 11 - STOP button
5 - ALARM page button 12 - RUN TEST button
6 - CONFIGURATION page button 13 - HELP button
7 - HISTORY page button

July 2016 8
Electric Fire Pump Controller Model:GPA/GPP/GPY
Dimensions Built to the latest edition of the NFPA 20 standard

23 3/8" [592]
22 3/8" [569]
15 7/8" [403] 20" [508]

12" [305] 18 3/4" [476]


Ø7/8" [Ø23] X2 Ø3/8" [Ø10] X4

See Notes

42" [1068] 37 3/8" [949]


36" [914]
38 1/4" [972] 30" [763]

17 5/8" [448]

3 1/4" [83]

7" [178] 5" [127]


5" [127]

Sensing Line Connection - 1/2 " F.NPT 7" [178]


Drain - 3/8 " M.TUBE Ø1/2" [Ø13] X3

7" [179] 6" [152]


Normal
8 5/8" [218] 7" [178] Power and
Motor Leads
Entrance

Voltage / Power Table 1" [25]


2 1/2" [64] 3" [76] 3" [76]
1 1/4" [31]

Voltage Min HP Max HP

208 5 30 Notes:
220 - 240 5 30
- Standard NEMA: NEMA 2
- Standard Paint : Textured Red RAL 3002.
380 - 400 - 415 5 60 - All Dimensions are in Inches [Millimeters].
- Center of ViZiTouch Screen: 30-5/8" [7778] from Bottom (No Feet).
440 - 480 5 60 - Bottom Conduit Entrance Through Removable Gland Plate Recommended.
- Use Watertight Conduit and Connector Only.
600 5 75 - Protect Equipment Against Drilling Chips.
- Door Swing Equal to Door Width.
- Seismic mounting to be rigid wall and base only.
Drawing for information only. Projection
Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
12 MODIFIED TORNATECH & SEISMIC LOGO 22/12/15
Approved
11 ADDED SEISMIC LOGO 19/08/15 GPX-DI111 /E
10 GENERAL REVISION 16/06/14 CDL
2016 All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Electric Fire Pump Controller
Reduced Voltage / Wye-Delta (Open Transition)
Model: GPY
Wiring schematic Built to the latest edition of the NFPA 20 standard
IS CB
1L3 3L3 CT3 1M*
1L2 3L2 CT2
1L1 3L1 CT1
CR4

White

White

White
White

Black

Black

Black
Black
17
2M*

Red
ST 1M 64 66 68
SA CR5 1S
65 67 69
18 20
3 2
2M
To J45 3L1 CR5 2M
19 21
1S To J57 To J76 1S
1M-1 1M
1M-2
14 14
Motor J19 J18 1M-3 3L2
11 11
Running 1M
12 12

Power 14
J40 J36
12 CR4-1
CR4-2
CR4
Available 11
TB1 11
12 14

Phase 14
J42 J38
12
CR5-1
CR5-2
CR5
Reversal 11
TB2 11
12 14

14 (+)
Common J37 J14
Pump Room 11
TB3 AI4-IN
Alarm 12 (-)

Common 14 (+)
Motor J39 J15
11 AI3-IN
Trouble TB4
12 (-)

Pressure
14
J41 J16
(+) Red
White
PT1 transducer
11 PT1-IN
TB5 type 0-5V
12 (-) Black

(+)
J17 PT2-IN
(-)
Green / Yellow SV1
G SV1-1 Brown
J43 SV1 SV1-2 Blue

3
J45 GND
2 To shunt trip
ST2

GND
J44 +
1 XTR1
REC 3L2
X1 H2
1 24VAC
J47 N
3 3 X2 H1
L 3L1

J8

LS1* LS1-1
J1
21 P1 J11
LS1-2
22
Temperature
REMOTE 23 P1 Probe 1
MANUAL START J6
24
TM1
25
LOCKOUT 8
26
7 VIZITOUCH
27 69
REMOTE J1*
AUTOMATIC START 28
6
68
MAIN BOARD
J25 5 J3
DELUGE J2* 29 J76 4
67 P2
VALVE 30 66 To CT1-2-3
3
Red Red + -
WATER RESERVOIR 31
2
65 J16 (+) AB1
Black
LOW 32 64 (-)
1 Black
33
34
J53 2
J14 J13
35
1
COM

COM

COM

COM

COM

COM

COM

COM

GND
24V
DI7

DI6

DI5

DI4

DI3

DI2

DI1

DI0

36
37 3L3
7
38
6
5
J57 4
3L2
To 3L1-2-3
3
2
3L1
1
I/O RELAY BOARD Drawing for information only.
Manufacturer reserves the right to modify this drawing without notice.
* REMOVE JUMPER TO USE THIS FEATURE * Contact closed when Emergency Start is in ON position Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
5 Modified Tornatech & Seismic Logo 14/04/16
Approved
4 Added Seismic Logo 19/08/15 GPY-WS500 /E
3 General Revision 07/01/15 CDL
2016 All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Electric Fire Pump Controller Model: GPX
Terminals Diagram and Sizing Built to the latest edition of the NFPA 20 standard

3 Phases
Bonding Incoming Power
Ground

Power Terminals Notes:


1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC
L1 L2 L3
Models :GPA, GPR & GPS Gnd
IS
(Canada) or local code.
2 - Controller suitable for service entrance in USA.
3 - For more accurate motor connections refer to motor manufacturer or
motor nameplate.
1M 4 - Controller is phase sensitive. Incoming lines must be connected in ABC
Gnd
T1 T2 T3 sequence.
5 - Field wiring and lug sizes base on copper conductors only.
Do not use aluminium conductors.

Isolating Switch (IS) Field Wiring according to Bending Space (AWG or MCM). TERMINALS L1 - L2 - L3 (Use Copper Conductors Only)

Bending
Space 5 " (127 mm) 8 " (203 mm)

HP
5 7.5 10 15 20 25 30 40 50 60
Voltage

208 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (2 to 1/0) 1x (1/0 to 250) 1x (3/0 to 250) 1x (4/0 to 250)

220 to 240 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (1 to 250) 1x (2/0 to 250) 1x (3/0 to 250)

380 to 416 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (3 to 1/0)

440 to 480 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0)

600 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0)

Bending
Space 12 " (305 mm) 16 " (406 mm)

HP
75 100 125 150 200 250 300 350 400 450 500
Voltage

208 1x (300 to 500) 1x (500) 2x (4/0 to 500) 2x (250 to 500) 2x (400 to 600) -------- -------- -------- -------- -------- --------

220 to 240 1x (250 to 500) 1x (350 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (350 to 500) 2x (500 to 600) -------- -------- -------- -------- --------
2x (400 to 500)
380 to 416 1x (1/0 to 250) 1x (3/0 to 250) 1x (250) 1x (300 to 500) 2x (3/0 to 250) 2x (4/0 to 500) 2x (300 to 500) 2x (500 to 600) 2x (600) --------
2x (400 to 500)
440 to 480 1x (1 to 250) 1x (2/0 to 250) 1x (3/0 to 250) 1x (4/0 to 250) 1x (350 to 500) 2x (3/0 to 250) 2x (4/0 to 500) 2x (300 to 500) 2x (350 to 500) 2x (400 to 600) 2x (500 to 600)

600 1x (3 to 1/0) 1x (1 to 250) 1x (2/0 to 250) 1x (3/0 to 250) 1x (250 to 500) 1x (350 to 500) 2x (3/0 to 250) 2x (4/0 to 500) 2x (250 to 500) 2x (300 to 500) 2x (350 to 500)

Bending
Space 5 " (127 mm) 8 " (203 mm) 12 " (305 mm)

Wiring Size for motor connection for Models GPA, GPR & GPS (AWG or MCM). TERMINALS T1 - T2 - T3 (Use Copper Conductors Only)

HP
5 7.5 10 15 20 25 30 40 50 60
Voltage

208 1x (10) 1x (10) 1x (8 to 2) 1x (6 to 2) 1x (4 to 1/0) 1x (3 to 1/0) 1x (2 to 1/0) 1x (1/0 to 3/0) 1x (3/0) 1x (4/0 to 300)

220 to 240 1x (12 to 10) 1x (10) 1x (8 to 2) 1x (6 to 2) 1x (4 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (1 to 3/0) 1x (2/0 to 3/0) 1x (3/0)

380 to 416 1x (14 to 10) 1x (12 to 10) 1x (10) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (3 to 1/0)

440 to 480 1x (14 to 10) 1x (14 to 10) 1x (12 to 10) 1x (10) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (6 to 2) 1x (4 to 1/0) 1x (3 to 1/0)

600 1x (14 to 10) 1x (14 to 10) 1x (14 to 10) 1x ( 10) 1x (10) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (6 to 2) 1x (4 to 1/0)

HP
75 100 125 150 200 250 300 350 400 450 500
Voltage

208 1x (300) 2x (2/0 to 300) 2x (4/0 to 300) 2x (250 to 300) 2x (400 to 600) -------- -------- -------- -------- -------- --------

220 to 240 1x (250 to 300) 2x (2/0 to 300) 2x (3/0 to 300) 2x (4/0 to 300) 2x (350 to 500) 2x (500 to 600) -------- -------- -------- -------- --------

380 to 416 1x (1/0 to 3/0) 1x (3/0) 1x (250 to 300) 1x (300) 2x (3/0 to 300) 2x (4/0 to 300) 2x (300) 2x (400 to 500) 2x (500 to 600) 2x (600)

440 to 480 1x (1 to 2/0) 1x (2/0 to 3/0) 1x (3/0) 1x (4/0 to 300) 2x (1/0 to 300) 2x (3/0 to 300) 2x (4/0 to 300) 2x (300) 2x (350 to 500) 2x (400 to 600) 2x (500 to 600)

600 1x (3 to 1/0) 1x (1 to 2/0) 1x (2/0 to 3/0) 1x (3/0) 1x (250 to 300) 2x (2/0 to 300) 2x (3/0 to 300) 2x (4/0 to 300) 2x (250 to 300) 2x (300) 2x (350 to 500)

Drawing for information only.


Manufacturer reserves the right to modify this drawing without notice.
For drawing for approval or installation, please contact manufacturer.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
8 Modified Tornatech & Seismic Logo 14/04/16
Approved 7 Added Terminal Torque Ratings 14/09/15 GPX-TD500 1/3 /E
6 Added Seismic Logo 19/08/15
2016 All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Electric Fire Pump Controller Model: GPX
Terminals Diagram and Sizing Built to the latest edition of the NFPA 20 standard
Power Terminals
3 Phases 3 Phases
Bonding Incoming Power Bonding Incoming Power
Ground Ground

Notes:
1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC
Gnd L1 L2 L3 Gnd L1 L2 L3 (Canada) or local code.
IS IS 2 - Controller suitable for service entrance in USA.
3 - For more accurate motor connections refer to motor manufacturer or
motor nameplate.
2M 1M 2M 1M 4 - Controller is phase sensitive. Incoming lines must be connected in ABC
Gnd Gnd
T7 T8 T9 T1 T2 T3 T6 T4 T5 T1 T2 T3 sequence.
5 - Field wiring and lug sizes base on copper conductors only.
Do not use aluminium conductors.

M M

Models :GPP Models :GPW & GPY


Isolating Switch (IS) Field Wiring according to Bending Space (AWG or MCM). TERMINALS L1 - L2 - L3 (Use Copper Conductors Only)

Bending
Space 5 " (127 mm) 8 " (203 mm)

HP
5 7.5 10 15 20 25 30 40 50 60
Voltage

208 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (2 to 1/0) 1x (1/0 to 250) 1x (3/0 to 250) 1x (4/0 to 250)

220 to 240 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (1 to 250) 1x (2/0 to 250) 1x (3/0 to 250)

380 to 416 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (3 to 1/0)

440 to 480 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0)

600 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0)

Bending
Space 12 " (305 mm) 16 " (406 mm)

HP
75 100 125 150 200 250 300 350 400 450 500
Voltage

208 1x (300 to 500) 1x (500) 2x (4/0 to 500) 2x (250 to 500) 2x (400 to 600) -------- -------- -------- -------- -------- --------

220 to 240 1x (250 to 500) 1x (350 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (350 to 500) 2x (500 to 600) -------- -------- -------- -------- --------
2x (400 to 500)
380 to 416 1x (1/0 to 250) 1x (3/0 to 250) 1x (250) 1x (300 to 500) 2x (3/0 to 250) 2x (4/0 to 500) 2x (300 to 500) 2x (500 to 600) 2x (600) --------
2x (400 to 500)
440 to 480 1x (1 to 250) 1x (2/0 to 250) 1x (3/0 to 250) 1x (4/0 to 250) 1x (350 to 500) 2x (3/0 to 250) 2x (4/0 to 500) 2x (300 to 500) 2x (350 to 500) 2x (400 to 600) 2x (500 to 600)

600 1x (3 to 1/0) 1x (1 to 250) 1x (2/0 to 250) 1x (3/0 to 250) 1x (250 to 500) 1x (350 to 500) 2x (3/0 to 250) 2x (4/0 to 500) 2x (250 to 500) 2x (300 to 500) 2x (350 to 500)

Bending
Space 5 " (127 mm) 8 " (203 mm) 12 " (305 mm)

Wiring Size for motor connection for Models GPP, GPW & GPY (AWG or MCM). TERMINALS T1 - T2 - T3 - T4 - T5 - T6 - T7 - T8 - T9 (Use Copper Conductors Only)

HP
5 7.5 10 15 20 25 30 40 50 60
Voltage

208 1x (14 to 10) 1x (12 to 10) 1x (10) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (6 to 1/0) 1x (4 to 2/0) 1x (2 to 3/0) 1x (1 to 3/0)

220 to 240 1x (14 to 10) 1x (12 to 10) 1x (10) 1x (8 to 2) 1x (8 to 2) 1x (6 to 2) 1x (6 to 1/0) 1x (4 to 2/0) 1x (3 to 2/0) 1x (2 to 3/0)

380 to 416 1x (14 to 10) 1x (14 to 10) 1x (14 to 10) 1x (12 to 10) 1x (10) 1x (10) 1x (8 to 2) 1x (6 to 2) 1x (6 to 2) 1x (4 to 1/0)

440 to 480 1x (14 to 10) 1x (14 to 10) 1x (14 to 10) 1x (12 to 10) 1x (12 to 10) 1x (10) 1x (10 to 2) 1x (8 to 2) 1x (6 to 2) 1x (6 to 2)

600 1x (14 to 10) 1x (14 to 10) 1x (14 to 10) 1x (14 to 10) 1x (12 to 10) 1x (12 to 10) 1x (10) 1x (10 to 2) 1x (8 to 2) 1x (8 to 2)

HP
75 100 125 150 200 250 300 350 400 450 500
Voltage

208 1x (2/0 to 3/0) 1x (3/0) 1x (250 to 300) 2x (1/0 to 300) 2x (3/0 to 350) -------- -------- -------- -------- -------- --------

220 to 240 1x (1/0 to 3/0) 1x (3/0) 1x (4/0 to 300) 1x (300) 2x (2/0 to 300) 2x (4/0 to 350) -------- -------- -------- -------- --------

380 to 416 1x (4 to 2/0) 1x (2 to 2/0) 1x (1/0 to 3/0) 1x (2/0 to 3/0) 1x (4/0 to 300) 1x (300) 2x (2/0 to 300) 2x (3/0 to 300) 2x (4/0 to 350) 2x (4/0 to 350) --------

440 to 480 1x (4 to 2/0) 1x (3 to 2/0) 1x (2 to 3/0) 1x (1/0 to 3/0) 1x (2/0 to 3/0) 1x (4/0 to 300) 1x (300) 2x (1/0 to 300) 2x (2/0 to 300) 2x (3/0 to 350) 2x (4/0 to 350)

600 1x (6 to 2) 1x (4 to 2/0) 1x (3 to 2/0) 1x (2 to 3/0) 1x (1/0 to 3/0) 1x (2/0 to 3/0) 1x (4/0 to 300) 1x (250 to 300) 1x (300) 2x (1/0 to 300) 2x (2/0 to 300)

Drawing for information only.


Manufacturer reserves the right to modify this drawing without notice.
For drawing for approval or installation, please contact manufacturer.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
8 Modified Tornatech & Seismic Logo 14/04/16
Approved 7 Added Terminal Torque Ratings 14/09/15 GPX-TD500 2/3 /E
6 Added Seismic Logo 19/08/15
2016 All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Electric Fire Pump Controller Model: GPX
Terminals Diagram and Sizing Built to the latest edition of the NFPA 20 standard

Remote Alarm Terminals (I/O board) Control Terminals (I/O board)


Terminals Wire Size: Terminals Wire Size:
12 - 24 AWG 12 - 24 AWG
0.5 Nm 0.5 Nm

Remote Manual Start


Remote

MOTOR RUN
Normally open J19 - 14 23
Closes to alarm Manual Close to start pump
Motor J25
Running Normally closed J19 - 11 Start 24
Opens to alarm J19 - 12

Lockout
Normally closed J40 - 14 25
Lockout Close to block start
Power Opens to alarm J25

TB1
Available Normally open J40 - 11 Signal 26
(Fail Safe) Closes to alarm J40 - 12

Automatic Start
Remote
Normally open J42 - 14 Automatic Open to start pump 27
Phase Closes to alarm J1 J25
If used, remove jumper J1 28

TB2
Normally closed J42 - 11 Start
Reversal
Opens to alarm J42 - 12

(RE-ASSIGNABLE) Deluge Valve


Deluge
Normally open Open to start pump 29
J37 - 14 Valve J2
Pump Closes to alarm J25
Signal If used, remove jumper J2
TB3

Normally closed J37 - 11 30


Room
Alarm Opens to alarm J37 - 12

(RE-ASSIGNABLE)
Normally open
Motor Closes to alarm
J39 - 14
Field Connections for External Devices
TB4

Normally closed
Trouble
Opens to alarm
J39 - 11
J39 - 12
(I/O board)
Terminals Wire Size:
12 - 24 AWG
0.5 Nm

Water Reservoir Low


Normally open J41 - 14 Water Reservoir
(Field* Closes to alarm Low Close to signal alarm 31
TB5

Programmable) Normally closed J41 - 11 J25


Signal 32
Opens to alarm J41 - 12

Flow / Zone
Flow / Zone
Start / Stop Close to signal alarm 33
J25
Signal 34

Drawing for information only.


Manufacturer reserves the right to modify this drawing without notice.
For drawing for approval or installation, please contact manufacturer. *Not Available in GPS Models
REV. DESCRIPTION DD/MM/YY Drawing number
NYC
Dpt of Building
8 Modified Tornatech & Seismic Logo 14/04/16
Approved 7 Added Terminal Torque Ratings 14/09/15 GPX-TD500 3/3 /E
6 Added Seismic Logo 19/08/15
2016 All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.