Vous êtes sur la page 1sur 6

20kV transformer feeder cable

Typical calculations for a 20kV transformer feeder cable are presented below. After correct cable
voltage classification the following considerations apply:

Cable sizing for 20/3.3 kV, 12.5 MVA transformer feeder (photo credit: cabletecservices.co.uk)

1. Current carrying capacity

2. Short circuit rating

3. Voltage drop

4. Earth loop impedance

Consider a 20/3.3 kV, 12.5 MVA transformer to be fed by direct buried, 3 core XLPE, SWA, PVC, copper
conductor cable.

1. Cable current carrying capacity

Transformer full load current is calculated by:

Ifull-load = 12.5 × 106 / 1.73 × 20 × 103 = 361 A


Don’t forget derating factors… Manufacturers provide data sheets for cables including appropriate
derating factors based upon IEC 60287 (Table 1). For a ground temperature at depth of laying of 20°C,
the derating factor is 0.97.

The group derating factor based upon 3 cables laid in trench at 0.45 m centers is 0.84. Ground thermal
resistivity taken as the normal of 1.2°Cm/W for a UK installation and 1.00 rating factor. Cable
installation depth to be 0.8 m and 1.00 rating factor.

Therefore subsequent current rating of cable to be 361 / 0.97 × 0.84 = 443 A

From manufacturers tables selected cable size is 240 mm2.

Go back to contents ↑

2. Short circuit rating

The maximum system fault level in this application is 8.41 kA. From standard IEC 60364-5-54 (Electrical
Installations In Buildings – Earthing arrangements, protective conductors and protective bonding
conductors):

Isc = K × A / √t

Where:

 K – constant, 143 for XLPE cable

 A – cable cross-section, 240 mm2 based on current carrying capacity

 t – short circuit duration, for MV cables use 1 second

Isc = 240 × 143 / √1 = 34.4 kA

From manufacturer’s tables and/or Figures 1 (a–c) for working voltages up to and including 19000 /
33000 XLPE based insulated cable the selected 240 mm2 cable is just capable of this 1 second short
circuit rating.

Note tables are conservative and assume a fully loaded cable. At the initiation of the fault conductor
temperature is 90°C and at the end of the fault conductor temperature is 250°C.
Figure 1 – (a) Paper-, (b) PVC- and (c) XLPE-insulated copper conductor cable short circuit ratings

3. Voltage drop (Vd)


Consider a 100 m route length of cable with resistance, R = 0.0982 Ω/km and inductive reactance, XL =
0.097 Ω/km. At full load current, Ifl = 361 A at 0.85 power factor the cable voltage drop over a 100 m
cable length,

Vd = Ifl × XL × sinφ + Ifl × R × cosφ volts

Vd = (361 × 0.097 × 0.53 + 361 × 0.0982 × 0.85) × 100 / 1000


Vd = (18.56 + 30.13) ×100 / 1000
Vd = 4.87 V
Vd = 0.042%

Important Notes //

a. At 20 kV the voltage drop is negligible over such a short length of cable.

b. IEE Wiring Regulations require a voltage drop for any particular cable run to be such that the
total voltage drop in the circuit of which the cable forms part does not exceed 2½% of the
nominal supply voltage, i.e. 10.4 volts for a three phase 415 V supply and 6 volts for a single
phase 240 V supply.

c. Industrial plant users may use different specifications and apply 5% (or even 10%) under no load
to full load conditions and perhaps 20% at motor terminals under motor starting conditions.

d. Manufacturer’s data for building services installations is often expressed in terms of voltage
drop (volts) for a current of 1 ampere for a 1 meter run of a particular cable size.

Go back to contents ↑

4. Earth loop impedance

For building services work it is important with small cross-section wiring and low fault levels to
ensure that sufficient earth fault current flows to trip the MCB or fuse protection. For distribution
power networks with more sophisticated protection the check is still necessary and allows the
calculation of the likely touch voltages arising from the earth fault.

This in turn can then be checked against the allowable fault duration to avoid danger. See this article for
a consideration of the design criteria associated with touch and step potentials.

Criteria #1 – Consider the earthing resistance at the source substation 0.5.

Criteria #2 – The source substation 20 kV neutral is approximately 10 km from the 100 m cable under
consideration. In addition parallel copper conductor earth cable is run to supplement and improve
power cable amour resistance values from equipment back to the primary substation infeed neutral.

For this example assume power and supplementary earth copper cables and amour over the 10 km
distance have a combined effective resistance of 0.143.
Criteria #3 – The combined resistance of the 100 m, 240 mm2, cable armour (0.028 Ω / 100 m) and in
parallel 2 × 95 mm2 copper supplementary earth cables (0.00965 Ω /100 m) = 7.18 × 10-3 Ω.

Criteria #4 – Consider the earthing resistance at the cable fault to be 0.5.

Criteria #5 – The effective earth circuit is shown in Figure 2. The effective primary substation neutral-to-
fault cable resistance 0.15.

Figure 2 – Calculation example – earth loop impedance

Criteria #6 – The maximum earth fault current at 20 kV has to be determined. Sometimes this is limited
by a neutral earthing resistor and the maximum limited current may be taken for calculation. Maximum
earth fault current for this calculation is 1000 A.

For a fault to earth at the end of the 100 m cable, 10 km from the primary power infeed the fault
current,

If = (1000 × 0.15) / (1 + 0.15) = 131 A

Therefore touch voltage to earth at the cable fault 131 × 0.5 = 65.3 V

Go back to contents ↑

APPENDIX – Derating factors based on IEC 60287

Vous aimerez peut-être aussi