1. TABLE OF CONTENTS
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 2 A4 E
Page 3/30
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 3 A4 E
2. DESCRIPTION OF THE CONTROL SYSTEM
24 V DC 230 V AC
2.4 Operation
The keypad is used to operate and also specify the settings of the control unit. The keypad is connected to the
Drive PLC.
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 4 A4 E
3. DESCRIPTION OF KEYPAD
The keypad (Schindler ID no. 53103838) is available for use in conjunction with the DO DSF 9 door control.
Functions:
• Display of operating states
• Setting of parameters
• Manual operation of doors in Service mode
VRET 1
Login: remote
Display -> par
Up
T
G
IF
Left Right
PR
SH
P
N
O
U
ST
Down
Additionally, in Display mode it is possible to toggle between the local and remote control mode.
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 5 A4 E
3.3.1 Display mode operation
Page1
After switching on the device, the following screen appears on the display.
DODSF9
3.3.1.1 Screen 1: Display of software version Version 2.00
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 6 A4 E
3.3.1.4 Screen 4: Login
The abbreviations have the following meaning:
• VRET Service operation (display only)
Indicates the position of the JREC switch
• Login: remote
Remote Local control mode changeover VRET 1
Local: Operation of the doors from the keypad Login:remote
Parameter settings enabled Display-> par
Remote: Signals from the lift control are evaluated
• Display par
Swap between Display mode and Parameter mode
Operation:
Press PRG key
The Local mode can be switched on and off with the UP key as long as the VRET signal is active
Press PRG key
The keypad can be switched to Parameter mode with the UP key as long as the VRET signal is active
3000 00
VRET 01 1
Login:remote
Display->par
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 7 A4 E
3.4.1.2 Interpreting the displays
Parameter 3000 Other parameters
Parameter number
Parameter number 3000 00 3140 00 Parameter value
Meaning of the
Current screen 1 1 parameter
( 0 = Display mode ) 0 open time
2.7 s
Press the SHIFT and PRG keys together to apply Closetime
the modification
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 8 A4 E
3.4.1.5 Switching back to Display mode
3000 00
STO0
0 STS0SKB0ETO0
ETS0VRET0MGH1
If the keypad is left in Parameter mode for 10 minutes, it will switch over to Display mode automatically.
Important note:
The modified parameters are automatically saved when the keypad is switched over to Display mode.
If the power is switched off without the keypad being switched to Display mode, the modifications will be lost.
Once the mains is switched on, the door control is in "Remote mode".
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 9 A4 E
4. COMMISSIONING
Checks:
• Inverter: The green LED must flash
• PLC: The green LED must light up
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 10 A4 E
• Screen 20 Analogue Pos
Setpoint doors closed 1000... 3000
Setpoint doors open 4000... 8000
• Screen 21 Left digit
Sensor on left
Setpoint 200 ... 350
• Screen 21 Right digit
Sensor on right
Setpoint 200 ... 350
Controller type
Name Code Default setting Min Max Unit Meaning
Control type 3301 0 0 1 0: All doors have same door weight
1: The door weight is determined
automatically each time the door
is opened
Door width
Name Code Default Min Max Unit Meaning
setting
Door width 3110 1133.0 600 2000 mm Is used to calculate the door position
4.5.1 Description
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 11 A4 E
Checks
• The doors must open to the open stop
• The doors must close to the closed stop and lock fully.
See section 4.8 Checking the closing force limiter for notes on setting the closing force limiter
π 3211 00 π 3221 00
23.2 mm 25.0 mm
Actual Pos Lockpoint
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 12 A4 E
4.8 Checking the closing force limiter
The software in the DO DSF 9 controller sets the limit values for the closing force limiter during the learning run.
However, there can be variations in the triggering behaviour, depending on the installation of the sensors and
the doors.
The commissioning engineer is responsible for the correct setting of the closing force limiter.
4.8.1 Procedure:
Parameters 3180 and 3190 can be used to adjust the individual closing force limiters to the desired setpoint.
The closing force limiter must be checked using a suitable measuring device – the force must not exceed
150 Newtons, in accordance with EN81/98.
Check:
The gap between the sensor values and the limit values can be checked on screens 21/22.
Opening: The values should be approximately 50..150 Newtons
Closing: The values should be approximately 30..70 Newtons
There is a risk of malfunction if the values are below 30 Newtons.
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 13 A4 E
5. OPTIMISATION
Average settings are used for the door opening and closing time parameters during the learning run. Different
times may be set retrospectively if necessary.
Key: 1) These values are adjusted automatically when the opening or closing times are modified, but
can also be readjusted afterwards.
The commissioning engineer is responsible for the correct maintenance of the kinetic energy.
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 14 A4 E
6. DESCRIPTION OF THE PARAMETERS
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 15 A4 E
6.2 Overview of parameters, screen 2
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 16 A4 E
3229 Deccel open "Deccel open" indicates the deceleration applied 35 2 800 %
to brake the doors when opening.
3230 Pos open Position of the doors when opened. This 30 0 300 mm
parameter may be used to set the position of the
doors when opened.
3231 Accel-close Acceleration of the doors on closing 50 2 800 %
3232 Speed close Speed of the doors on closing 50 2 200 %
3233 Deccel close “Deccel close” indicates the deceleration with 50 2 800 %
which the doors are braked on closing.
3234 Prestoppos “prestoppos” indicates the position from which 5 -50 500 mm
the doors begin to close at a reduced speed. The
reference point is the value specified in the
"Lockpoint" parameter
3235 lock speed “Lock speed” indicates the speed with which the 8 2 20 %
doors enter the locking position.
3241 Preclose- Range for precision adjustment of the closing 50 0 500 mm
range force limiter 3242 / 3243. The reference point is
the value specified in the "Lockpoint" parameter
3242 Close limit l Precision adjustment of the closing force limiter 100 0 150 %
to the left in the range according to 3241
3243 Close limit r Precision adjustment of the closing force limiter 100 0 150 %
to the right in the range according to 3241
3244 M_lim_open Limit value for open stop on learning run 13 -20 100 %
3245 M_lim_close “M_lim_close” specifies the stop limits for closing 16 -20 100 %
the doors.
3251 QSB Accel Quickstop run down ramp. This parameter can be 20 1 30
used to adjust the door behaviour when the light
curtain or closing force limiter responds.
3252 Quickstop Quickstop braking ramp 100 0 1000 %
3253 Add Torque Additional torque on closing 0 -50 100 %
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 17 A4 E
6.3 Overview of parameters, screen 3
Note:
All parameters with the suffix _h apply for a heavy door with automatic weight detection
(parameter type = 1)
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 19 A4 E
DESCRIPTION OF THE DISPLAY MODE SCREENS
After switching on the device, the following screen appears on the display.
The UP and DOWN keys are used to change to the next or previous screen.
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 20 A4 E
6.7 Screen 4: Login
The abbreviations have the following meaning:
• VRET Service operation (display only)
Indicates the position of the service operation switch VRET 1
Login:remote
• Login: remote Display->par
Remote Local control mode changeover
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 21 A4 E
- error opening Error on doors opening
- error closing Error on doors closing
Page7
All possible states of the frequency inverter are indicated. This also includes
all errors in the form of a number and a brief text. State
- Drive ready: Drive unit free from errors Drive ready
- Error number with corresponding text: See Errors section
Page8 Page9
Speed set Speed act
853 354
The current set point or the current value for the speed is indicated on these screens.
A minus sign indicates a reversal of rotation direction
Page10 Page11
Pos target Pos act
354 354
The current set point or the current value for the positioning is indicated on this screen.
Press the UP key to go to the next screen
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 22 A4 E
6.13 Screen 12: Number of cycles
This screen shows the number of cycles already completed.
One cycle consists of the doors closing and then opening again.
This value is provided for statistical purposes only and has no influence PPage12
on the controller.
Cycles
4967
Last Error
704: PowFU
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 23 A4 E
6.17 Screen 16 / 17: Motor temperature, motor current
The calculated temperature or the current motor current is indicated on these screens.
PPage16 Page17
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 24 A4 E
6.21 Screen 21: Closing force limiter sensor
Analogue signals 4 and 5 from the controller are displayed on this screen.
Analogue input 4 indicates the value from the closing force limiter for the
left-hand door. Analogue input 5 indicates the value from the closing force
Page21
limiter for the right-hand door. These are used in closing force calculation.
Digital switches may be connected instead of the analogue ones. Then the
Sensor L R
values for the analogue inputs are equal to zero, the controller detects this
300 310
and then works with the digital switches for closing force limitation.
The values on the analogue inputs when the doors are in the central position
should be between 200 and 350.
PPage22
Sensor limit
300 310
Reasonable values:
Sensor min min open
approx. 30 ... 70 for closing 50 55 136 121
approx. 50 ... 150 for opening
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 25 A4 E
6.25 Screen 26: Sensor distance during learning run
PScreen26
11111
Learning
0
PScreen27
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 26 A4 E
7. TROUBLESHOOTING
Belt slips at open stop Learning run force too high Check parameter 3202
Reduce parameter 3160 in 5% steps, as
necessary
Belt slips at closed stop Learning run force too high Check parameter 3202
Reduce parameter 3170 in 5% steps, as
necessary
The doors do not open to the Learning run force too low Set parameter 3202 to 1 on doors with
open stop toothed belt
Increase parameter 3160 in 5% steps, as
necessary
The doors do not close to the Learning run force too low Set parameter 3202 to 1 for doors with
closed stop toothed belt
Increase parameter 3170 in 5% steps, as
necessary
The doors remain at the open Limits for stopping torque Reduce parameter 3244 in 2% steps, as
stop for more than 6 seconds too high necessary
The doors remain at the open Limits for stopping torque Reduce parameter 3245 in 2% steps, as
stop for more than 3 seconds too high necessary
Door jerks and goes to KSKB not correctly Check wiring of KSKB. Measure signal
errorclosing connected or defective with multimeter
The door does not complete Absolute encoder not Turn the sensor cover through 90° and try
the learning run, outputs installed correctly. again
errorclosing and opens again
7.2 Keypad
Behaviour Possible cause Actions
Parameter mode cannot be - System not in Service mode Check signal VRET
selected - Keypad not logged in Setpoint: VRET 1
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 27 A4 E
parameter 3223, as necessary
Doors begin to open and Opening force limiter has - Reduce deceleration ramp on parameter
then stop in the second responded because deceleration 3229
half of the opening range was too high - Increase limit for closing force limiter with
parameter 3223, as necessary
Doors judder on Acceleration ramp set too high - Reduce acceleration ramp on parameter
acceleration 3227
Doors judder on braking Braking ramp too high - Reduce deceleration ramp on parameter
3229
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 28 A4 E
7.5 Error messages
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 29 A4 E
567 BusOff CAN controller reports “Warning” or - Check whether bus termination is fitted
“Bus off” state - Check the shielding on the lines
- Check PE connection
- Check bus load, reduce baud rate if necessary
591 ExtErr A digital signal that has been - Check external sensors
assigned the TRIP-Set function is
enabled
569 BusOff CAN controller reports “Warning” or - Check whether bus termination is fitted
“Bus off” state - Check the shielding on the lines
- Check PE connection
- Check bus load, reduce baud rate if necessary
605 IntErr - Consultation with manufacturer required
511 OverCurr1 Short circuit - Look for cause of short circuit, check motor
Capacitive charging current on motor cable
cable too high - Use shorter, lower capacitance motor cables
512 EartErr One motor phase has an earth - Check motor, check motor cables
contact - Use shorter, lower capacitance motor cables
Capacitive charging current on motor
cable too high
513 OverCurr3 Acceleration time set too short - Extend acceleration time
(C0012) - Check drive configuration
Faulty motor cable - Check wiring
Interturn fault in the motor - Check motor
514 OverCurr4 Deceleration time set too short - Extend deceleration time
(C0013) - Check rating of external brake resistance
515 ConstOC Frequent overlong overload - Check drive dimensioning
516 I2TOVL Motor thermally overloaded, e.g. as a - Check drive dimensioning
consequence of: - Check C0120
impermissible continuous current
frequent and overlong acceleration
processes
550 KK_OverT Ambient temperature too high - Allow drive controller to cool down and provide
Heat sink contaminated better ventilation
Impermissible high currents or - Clean heat sink
- Check drive dimensioning
acceleration processes too frequent
- Check load, replace any rough-running, faulty
and lasting too long bearings
553 MotorTemp Motor too hot because of - Check drive dimensioning
impermissible high currents or too
frequent long accelerations
554 FUTemp Interior of the drive controller too hot - Reduce load on drive controller
- Improve cooling
- Check fan in drive controller
579 IntErr - Consultation with manufacturer required
703 PTCErr Motor too hot because of - Check drive dimensioning
impermissible high currents or too
frequent long accelerations
704 PowerFU Frequency inverter reports no power - Check whether power supply is connected to
frequency inverter
705 FULiniErr Faulty loading of the frequency - Check wiring
inverter parameters - Switch power off and back on
1
Commissioning and diagnosis of Microfilm date KA No. Amd. Page Format Lang.
J264103
door drive DO DSF 9 30.11.06 801441 01 30 A4 E