Académique Documents
Professionnel Documents
Culture Documents
Multilin
EPM 5500P
Power Metering System
Instruction Manual
Manual P/N: 1601-0233-A3
Manual Order Code: GEK-113043B
Copyright © 2007 GE Multilin
T
GIS ERE
RE
GE Multilin ISO9001:2000
EM I
G
U LT I L
http://www.GEmultilin.com
GE Multilin's Quality Management
System is registered to ISO9001:2000
QMI # 005094
UL # A3775
GE Consumer & Industrial
Multilin
EPM 5500P
Power Metering System
Table of contents
Demand .....................................................................................................3–6
Crest factor...............................................................................................3–6
Harmonic distortion .............................................................................3–7
Telephone interference factor.........................................................3–8
K factor.......................................................................................................3–8
Unbalance factor...................................................................................3–9
Maximum/minimum statistics ........................................................3–9
Real time clock..................................................................................... 3–10
Phase angle difference .................................................................... 3–10
Overlimit alarming .....................................................3–10
Description............................................................................................. 3–10
Inequation enable register............................................................. 3–12
Limit setting register ......................................................................... 3–13
Time limit setting register ............................................................... 3–13
Inequation sign register .................................................................. 3–13
Digital output select registers....................................................... 3–14
Example .................................................................................................. 3–14
Alarm records....................................................................................... 3–15
Energy pulse output for IO models..........................3–16
Description............................................................................................. 3–16
Pulse output assignment register............................................... 3–16
Pulse ratio register............................................................................. 3–17
Pulse width setting register ........................................................... 3–17
Relay output.......................................................................................... 3–18
SETTINGS Overview......................................................................... 4–1
Description................................................................................................4–1
Access code entry .................................................................................4–2
Setting screens.............................................................. 4–3
Energy...................................................................................................... 5–12
Displaying statistical data ........................................5–18
Description............................................................................................. 5–18
Voltage statistics ................................................................................ 5–18
Current statistics................................................................................. 5–20
Power statistics ................................................................................... 5–21
Demand and frequency statistics .............................................. 5–22
COMMUNICA- Modbus Overview ......................................................... 6–1
TIONS Description................................................................................................6–1
Transmission mode ..............................................................................6–1
Data frame format ....................................................... 6–2
Description................................................................................................6–2
Address field ............................................................................................6–2
Function field ...........................................................................................6–3
Data field ...................................................................................................6–3
Error check field .....................................................................................6–4
Modbus functions ......................................................... 6–5
Frame formats ........................................................................................6–5
Function code 01: read relay output status..............................6–6
Function code 02: read digital input status ..............................6–7
Function code 03: read data............................................................6–9
Function code 05: control relay output.................................... 6–10
Function code 16: preset multiple registers........................... 6–11
Modbus memory map ................................................6–13
Data address table ............................................................................ 6–13
Format codes ....................................................................................... 6–43
WARRANTY GE Multilin warranty statement................................. 7–1
EPM 5500P
Power Metering System
Chapter 1: Introduction
Introduction
Safety Notes
DESCRIPTION Please read this manual carefully before conduct the
installation, operation, or maintenance on the EPM 5500P
Power Metering System.
The symbols listed below are used in this manual and labeled
on the meter to indicate danger (or potential dangers). When
these symbols appear, please follow the instructions strictly.
Danger symbol. Failure to observe this warning
may result in severe injury and even death.
DANGER
Introduction
OVERVIEW The EPM 5500P Power Metering System was designed with
the latest microprocessor and digital signal processing
technology. Electric power parameters, energy and demand
metering, power quality monitoring, remote control, over-
range alarming, statistics and records are available in one
pocket-sized unit. There are also basic alarms on over/under
current, voltage, power, power factor, frequency, unbalance
factors or demands and pulse output based on energy or
reactive energy in EPM 5500P. Status monitoring is possible
using the four digital inputs. The meter combines high
accuracy measurement with intelligent multifunction and a
simple user interface.
ENERGY The EPM 5500P can measure four quadrants of kWh and
MANAGEMENT kvarh in both directions, with an accuracy up to 0.5%.
Accuracy of active energy is as per IEC 62053-21 class 1. It
provided high standard energy data and energy demand
data. This data is important for line feeder statistics.
POWER QUALITY With its powerful digital signal processing ability, the EPM
ANALYSIS 5500P Power Metering System can be used as an online
power quality analysis instrument. It can simultaneously and
continuously analyze results such as voltage and current THD,
harmonics (up to the 31st - PL5500 B and PL5500 C up to 15th),
and voltage and current unbalance.
The main functions of EPM 5500P are listed below.
Metering
• Phase voltage: V1, V2, V3, Vavg (L-N)
Ordering
ORDER CODES The order codes for the EPM 5500P Power Metering System
are shown below.
Table 1–1: EPM 5500P order codes
PL5500 B - * - *
Base Unit Metering, time tag, energy, demand, THD, 20 to
PL5500 B
100 VAC (from PT), or 40 to 230 VAC (direct)
PL5500 C - * - *
Base Unit Metering, time tag, energy, demand, THD, 20 to
100 VAC (from PT), or 40 to 230 VAC (direct),
PL5500 C maximum/minimum, limit alarms, RS485,
harmonics (2 to 15th)
PL5500 – * – *
Base Unit Metering, time tag, energy, demand, THD, 20 to
100 VAC (from PT), or 40 to 230 VAC (direct),
PL5500 O D maximum/minimum, limit alarms, RS485,
harmonics (2 to 31st), CF, THFF, K factor, two (2)
digital inputs
Four (4) digital inputs (15 VDC provided by meter),
IO two (2) form-A outputs, 2 digital outputs for alarm
or pulse output.
Specifications
INPUTS POWER SUPPLY
Inputs: 100 to 240 V AC
100 to 300 V DC
Power consumption: 3 W maximum at 230 VAC
VOLTAGE INPUT
PT primary: 500 KV AC maximum
PT secondary: 230 V AC (L-N) or 400 V AC (L-L), with 20%
over-range
Frequency: 45 to 65Hz
Overload: 2 × rated voltage (continuous)
2500 V AC for 1 second (no cycling)
Burden: less than 0.2 VA
Measurement: true RMS AC
CURRENT INPUT
CT primary: 9999 A AC
CT secondary: 5 A AC, with 20% over-range
20 mA minimum initial current
Overload: 10 A (continuous)
100 A for 1 second (no cycling)
Burden: <0.1 VA
DIGITAL INPUTS
Optical isolated voltage:2500 V AC RMS
Type: wet contact
Resistance: 2 KΩ (typical)
Input voltage: 5 to 30 V DC
Close voltage: >10 V DC
Maximum input current:20 mA
Auxiliary power: 15 V DC / 100 mA
METERING VOLTAGE
Accuracy: ±0.2% of full-scale (measured)
±0.5% of full-scale (calculated)
Resolution 0.1%
Range: 40 to 276 V AC (VL-N, PT secondary)
Calculated parameters:VL-L for 3LN wiring
V2 and VL-L for 2LN wiring
V3-1 for 2LL wiring
CURRENT
Accuracy: ±0.2% of full-scale (directly measured)
±0.5% of full-scale (calculated)
Resolution 0.1%
Range: 1 to 120% of CT
Calculated parameters:In for 3CT wiring;
I2 for 2CT wiring;
I2 and I3 for 1CT wiring
NEUTRAL CURRENT
Accuracy: ±1.0% of full-scale
Resolution 0.1%
Range: 1 to 120% of CT
UNBALANCE
Measured types: voltage and current unbalance
Accuracy: ±1.0% of full-scale
Resolution 0.1%
Range: 0 to 200%
POWER
Measured types: real, reactive, and apparent power
Accuracy: ±0.5% of full-scale
Resolution 0.1%
Range: –9999 to 9999 MW/Mvar
0 to 9999 MVA
ENERGY
Measured types: real and reactive energy
Accuracy: ±0.5% of full-scale
Resolution 0.1 kWh/kvarh
Range: 0 to 999999999.9 kWh/kvarh
POWER FACTOR
Accuracy: ±1.0% of full-scale
Resolution 0.01
Range: –1.00 to –0.02; 0.02 to 1.00
FREQUENCY
Accuracy: ±0.2% of full-scale
Resolution 0.01 Hz
Range: 45 to 65 Hz
DEMAND
Measured types: real, reactive, and apparent demand
Accuracy: ±0.5% of full-scale
Resolution ±0.1%
Range: –9999 to 9999 MW/Mvar
0 to 9999 MVA
EPM 5500P
Power Metering System
Chapter 2: Installation
Installation
Overview
DESCRIPTION The chapter describes the installation of EPM 5500P. Please
read this chapter carefully before using the meter.
Mechanical installation
OVERVIEW The installation environment should fulfill the temperature
and humidity requirements of the EPM 5500P. Otherwise,
meter failure and damage may result.
PANEL INSTALLA- The following procedure describes how to install the EPM
TION 5500P as part of a switchgear panel.
1. Cut a square hole on the switchgear panel as indicated in
the figure below.
Re-insert the installation clips and push tightly to fix the meter
to the panel.
SPACE REQUIRED The space around the meter should sufficiently large to
FOR INSTALLA- ensure that the meter, terminal strip wiring, and wire
TION arrangement can be easily removed. The recommended
minimum space around the meter is show below.
Electrical installation
TERMINAL STRIPS There are up to three terminal strips on the back of EPM
5500P,: a voltage and current input terminal strip, an auxiliary
terminal strip, and an extend terminal strip. Only the EPM
5500P with the IO option has the extend terminal strip. The 1,
2, and 3 subscripts indicated on the terminal strip represent
each phase of three-phase system. They have the same
meaning as A, B and C or R, S and T in a three-phase system.
The NC label indicates no connection.
The PL5500 B model has no RS485 and DI.
NOTE
The PL5500 C model has no DI.
POWER Ensure the power supply voltage is the identical to what the
REQUIREMENTS meter requires for its auxiliary power.
The power supply of the EPM 5500P meter is rated for 100 to
240 V AC (50/60Hz) or 100 to 300 V DC. Typical power
consumption is less than 2 W. A regulator or UPS should be
used if there is significant power supply undulation. The power
supply terminals are 20, 22 and 24 (L, N, G).
VOLTAGE INPUT The nominal voltage input for the EPM 5500P is 230 V AC (L-N).
For the three-phase systems less than 500 V AC (L-L), the
voltage input can be directly connected to the meter. Refer to
the wiring diagram for detailed instructions. The maximum
line-to-neutral voltage for V1, V2, and V3 should be lower than
276 V AC. If the input voltage is higher than 276 V AC, then a
PT should be used.
Wiring schemes
THREE-PHASE The EPM 5500P can satisfy many types of three-phase wiring.
WIRING Please read this section carefully before you begin wiring and
select a configuration suitable to your power system.
The voltage and current input wiring modes can be
programmed in the meter settings. The voltage wiring mode
can be 3-phase 4-line wye (3LN), 3-phase 4-line 2PT wye mode
(2LN), and 3-phase 3-line open delta (2LL). The current input
wiring mode can be 3CT, 2CT, and 1CT. Any voltage wiring
mode can be grouped with any current wiring mode.
2CT wiring:
The difference between the two above wiring schemes is that
there is no current input in the I21 and I22 terminals. The I2
value is calculated from the following formula:
I1 + I2 + I3 = 0
Set the EPM 5500P current input mode to 2CT for this wiring
scheme.
1CT wiring:
The 1CT wiring scheme can be used for three-phase balanced
systems. The remaining two currents are calculated by the
EPM 5500P according to the supposed balance.
2LN, 2CT
2LN, 1CT
2LL, 3CT
2LL, 2CT
2LL, 1CT
SINGLE-PHASE.
2-LINE (WIRING
MODE 3LN, 3CT)
SINGLE-PHASE 3-
LINE (WIRING
MODE 3LN, 3CT)
Output wiring
RELAY OUTPUTS There are two additional relay outputs available as an option
in the PL5500 IO models. The terminals are R11, R12 (terminals
31, 32) and R21, R22 (terminals 33, 34). These two relay
outputs are used to provide remote control electric switches
in the power system.
The relay outputs are mechanical Form A contacts rated at
3 A/250 V AC or 3 A/30 V DC. An intermediate relay is
recommended as shown in the figure below.
DIGITAL There are two digital outputs available for the PL5500 IO
OUTPUTS models. The terminals of the digital outputs are DO1+, DO1–
(terminals 35, 36) and DO2+, DO2– (terminals 37, 38). The
digital outputs can be used as energy pulse outputs or
overlimit alarming outputs.
Communication wiring
DESCRIPTION The EPM 5500P has an RS485 communication port using the
Modbus RTU protocol. (PL5500 B has no communication
capability.) The communication terminals are A, B, and S
(terminals 11, 12, and 13). Terminal “A” is the positive
differential signal “+”, terminal “B” the negative differential
signal “–”, and terminal “S” is signal earth. In the case of
obvious earth potential differences, it is essential to join the
“S” terminal of every unit and ground it at the Master only.
Up to 32 devices can be connected on a RS485 bus. Use good
quality shielded twisted-pair cable, AWG22 (0.5mm2) or larger.
The overall length of the RS485 cable connecting all devices
cannot exceed 1200 m (4000 ft.). The EPM 5500P is used as a
slave device for master devices such as PCs, PLCs, data
collectors, or RTUs.
If the master does not have an RS485 communication port, a
converter must be used. Normally a RS232 to RS485 or USB to
RS485 device is used..
LINE MODE The connection from a master to the EPM 5500P meter in line
mode is made individually in the RS485 network as shown in
the following figure.
EPM 5500P
Power Metering System
Meter operation
CURRENT The true RMS value of three phase currents, neutral current,
and their average are measured and displayed in EPM 5500P.
Metered current values are indicated by the letter “I” in area 4
of the LCD (refer to EPM 5500P display segments on page 3–2
for details).
DEMAND The EPM 5500P measures real power demand, reactive power
demand, and apparent power demand. The sliding window
method is used to measure demand statistics in the EPM
5500P. The sliding window time can be from 1 to 30 minutes,
and the window slides in one minute increments.
For example, consider a sliding window time of 3 minutes. If
there is an average power of 12 Kw for the first Minute, 14 kW
for the second minute, and 10 Kw for the third minute, then
the total demand for the 3 minutes is:
12 kW + 14 kW + 10 kW
total demand = ------------------------------------------------------------- = 12 kW (EQ. 3–1)
3
If another minute has passed, and the average power of this
minute is 8 Kw, then the total power demand for the last three
minutes is:
total demand = 14 kW + 10 kW + 8 kW
---------------------------------------------------------- = 10 kW (EQ. 3–2)
3
CREST FACTOR The crest factor is used to express waveform distortion. This is
an important factor to scale the influence to the system
insulation. Crest factor is defined as follows:
50 Uh
CF = 1.414 ∑ -----
U1
- (EQ. 3–3)
h=1
50 Uh 2
THD = ∑ ⎛⎝ -----
U 1⎠
-⎞ × 100% (EQ. 3–4)
h=2
100 50 × h × P h × U h 2
THFF = ∑ ⎛⎝ ----------------------------------------
800 × 1000 × U 1⎠
-⎞ × 100% (EQ. 3–7)
h=1
K FACTOR The K factor is used to scale the power quality and is defined
as follows:
k
2
∑ ( n × Fn )
n=1
K = --------------------------------- (EQ. 3–8)
k
2
∑ Fn
n=1
REAL TIME The EPM 5500P contains a real time clock. The date, month,
CLOCK year, hour, minute and second can be read or set from front
panel or via communications.
PHASE ANGLE The phase angle difference indicates the phase angle
DIFFERENCE relationship between voltage and current, from 0 to 360°.
When the voltage input wiring is set to “2LL”, the EPM 5500P
indicates the phase difference of U23, I1, I2, and I3 relative to
U12. When the voltage input wiring is set to “2LN” or “3LN”, the
EPM 5500P indicates the phase difference of U2, U3, I1, I2, and
I3 relative to U1.
Overlimit alarming
DESCRIPTION When the metered data is greater the pre-set limit and over
the pre-set period of time, overlimit alarming will be picked up.
The overlimit value and time will be recorded for a maximum
of nine records. The digital output can be used as an indicator
or to as an alarm trigger.
A maximum 9 inequations related to the overlimit alarming
can be set. Any satisfaction of these inequations will trigger
the overlimit alarming. These equations can be assigned to a
digital output for PL5500 IO models. The example algorithm
below describes how to set the first inequation.
START:
Enable inequation1
var1 := Parameter
ref1 := Value
limit_t := time
Setting inequality_sign)
Setting associatedDO
If
Var1 inequality Ref1="True"
and
Last_time>Limit_t
then
{record event
output associatedDO}
END
In the above algorithm
• var1 := Parameter assigns Var1 to the alarming
paramter
• ref1 := Value sets the limit value to Ref1
• limit_t := time sets the time limit to the Limit_t
value
• associatedDO represents the related digital output
• If ... and ... determines if the parameter is over
the limit and over the time limit
• record event records the value, date, and time
LIMIT SETTING The limit setting register Ref (Ref1 to Ref9) should be set to the
REGISTER upper or lower limits of the parameter. The parameter limit is
related to the format of the register.
TIME LIMIT The time limit setting register Limit_t represents a time limit
SETTING and can be set from 0 to 255, with each increment of 1
REGISTER representing 300 ms. For example, if Limit_t = 20, the time
limit is 20 × 300 = 6000 ms.
The record and alarming output should be triggered
immediately on overlimit. All the inequations have the same
time limit.
ALARM RECORDS Only the most recent nine alarming records can be stored in
the EPM 5500P. The format of the record is shown below.
PULSE OUTPUT The pulse output assignment register can be any integer from
ASSIGNMENT 0 to 8 as indicated below:
REGISTER
Reg # Description Reg # Description
0 no assignment 5 Ep_total
1 Ep_imp 6 Ep_net
PULSE RATIO The pulse ratio register can be any integer from 1 to 6000,
REGISTER where each increment of 1 represents 0.1 kWh or 0.1 kvarh.
This value is the minimum resolution of energy pulse output.
PULSE WIDTH The pulse width setting register is any integer from 1 to 50,
SETTING where each increment of 1 represents 20 ms.
REGISTER The minimum time interval between two adjoining output
pulses is 20 ms. If the pulse width is 20 ms, then maximum
number of output pulses is 25 per second. If the pulse width is
80 ms, then the maximum number of output pulses is 10.
In practice, the pulse width and the pulse ratio are selected
according to system power. The relation of the two
parameters should satisfy the following equation:
( pulse_width + 1 ) × P max
pulse ratio > ---------------------------------------------------------------- (EQ. 3–13)
18000
In the above equation, Pmax is the maximum real or reactive
power, in units of KW or Kvar. The recommend pulse ratio is 3
to 5 times the value of the above expression.
RELAY OUTPUT The two relay outputs in the PL5500 IO models can be used to
control electric switchgear or equipment. There are two
output modes: latching or momentary. The momentary mode
is often used to control the electric switch. The closing time
interval for the momentary mode can be between 50 to
3000 ms.
EPM 5500P
Power Metering System
Chapter 4: Settings
Settings
Overview
DESCRIPTION Press the Harmonics and Volt/Amps key simultaneously while
in the data display mode to enter the parameter setting
mode.
Setting changes should be only performed by qualified
personnel after reading this manual.
ALERT
When in setting mode, press the Harmonics key to move the
cursor to the right, one digit at a time. Press the Power key to
increase values and the Energy key to decrease values. Press
To set the access code, see Access code setting on page 4–20.
Setting screens
METER ADDRESS The first setting screen displays the EPM 5500P
communications address. (PL5500 B does not have this page.)
The address can be any number from 1 to 247. The default
address is 17.
BAUD RATE Press the Volt/Amps key to display the second setting screen.
This screen is the baud rate setting. (PL5500 B does not have
this page.)
VOLTAGE INPUT Press the Volt/Amps key to display the third setting screen.
WIRING This screen displays the voltage input wiring settings as a
single line in area 2 of the LCD (refer to EPM 5500P display
segments on page 3–2 for details).
The voltage input can be one of three modes: 3LN, 2LN, and
2LL (refer to Voltage input on page 2–10 for details).
CURRENT INPUT Press the Volt/Amps key to display the fourth setting screen.
WIRING This screen displays the current input wiring settings as a
single line in area 2 of the LCD (refer to EPM 5500P display
segments on page 3–2 for details).
The current input can be one of three modes: 3CT, 2CT, and
1CT (refer to Current input on page 2–11 for details).
PT PRIMARY Press the Volt/Amps key to display the fifth setting screen.
VOLTAGE This screen displays the PT primary voltage PT1 as a single line
in area 2 of the LCD (refer to EPM 5500P display segments on
page 3–2 for details).
The PT1 value is an integer from 100 to 500000 V, in steps of
1 V.
PT SECONDARY Press the Volt/Amps key to display the sixth setting screen.
VOLTAGE This screen displays the PT secondary voltage PT2 as a single
line in area 2 of the LCD (refer to EPM 5500P display segments
on page 3–2 for details).
The PT2 value is an integer from 100 to 400 V, in steps of 1 V.
CT PRIMARY Press the Volt/Amps key to display the seventh setting screen.
CURRENT This screen displays the CT primary rated current CT1 as a
single line in area 2 of the LCD (refer to EPM 5500P display
segments on page 3–2 for details).
DIGITAL OUTPUT Press the Volt/Amps key to display the eighth setting screen.
MODE This screen displays the digital output mode (PL5500 IO) as a
single line in area 2 of the LCD (refer to EPM 5500P display
segments on page 3–2 for details).
DIGITAL OUTPUT Press the Volt/Amps key to display the ninth setting screen.
1 This screen displays the digital output 1 item as a single line in
area 2 of the LCD (refer to EPM 5500P display segments on
page 3–2 for details).
Digital output 1 can be selected from 0 to 8, where 0 to 8
represent the following nine energy items:
DIGITAL OUTPUT Press the Volt/Amps key to display the tenth setting screen.
2 This screen displays the digital output 2 item as a single line in
area 2 of the LCD (refer to EPM 5500P display segments on
page 3–2 for details).
Digital output 2 can be selected from 0 to 8, where 0 to 8
represent the energy items shown in Digital output values on
page 4–10.
DIGITAL OUTPUT Press the Volt/Amps key to display the eleventh setting
PULSE WIDTH screen. This screen displays the digital output pulse width as a
single line in area 2 of the LCD (refer to EPM 5500P display
segments on page 3–2 for details).
ENERGY PULSE Press the Volt/Amps key to display the twelfth setting screen.
RATE This screen displays the energy pulse rate as a single line in
area 2 of the LCD (refer to EPM 5500P display segments on
page 3–2 for details).
The energy pulse rate value is an integer from 1 to 6000,
where an increment of 1 represents 0.1 kWh or 0.1 kvarh.
In this example, the energy pulse rate value is set 10. As such,
the pulse rate is 10 × 0.1 kWh (or kvarh) = 1 kWh (or kvarh).
RELAY 1 MODE Press the Volt/Amps key to display the thirteenth setting
screen. This screen displays the relay 1 mode as a single line in
area 2 of the LCD (refer to EPM 5500P display segments on
page 3–2 for details).
There are two relay outputs in the PL5500 IO models. Each has
two output modes: latching and momentary. For the latching
mode, the relay output status is either on or off. For the
momentary mode, the relay output status changes from off to
on for a period of time Ton and then returns to off. Ton can be
setting from 50 to 300 ms.
The relay 1 mode value is either 0 or 1, where “0” represents
latching and “1” represents momentary.
RELAY 1 CLOSE Press the Volt/Amps key to display the fourteenth setting
TIME screen. This screen displays the relay 1 closing time as a single
line in area 2 of the LCD if the relay mode is set as momentary
(refer to EPM 5500P display segments on page 3–2 for details).
When the relay 1 mode is set as momentary, the closing time
Ton ranges from 50 to 3000 ms in steps of 1 ms.
RELAY 2 MODE Press the Volt/Amps key to display the fifteenth setting
screen. This screen displays the relay 2 mode as a single line in
area 2 of the LCD (refer to EPM 5500P display segments on
page 3–2 for details).
RELAY 2 CLOSE Press the Volt/Amps key to display the sixteenth setting
TIME screen. This screen displays the relay 2 close time as a single
line in area 2 of the LCD (refer to EPM 5500P display segments
on page 3–2 for details).
When the relay 2 mode is set as momentary, the closing time
Ton ranges from 50 to 3000 ms in steps of 1 ms.
SYSTEM DATE Press the Volt/Amps key to display the twentieth setting
screen. This screen sets the system date as a single line in
area 2 of the LCD (refer to EPM 5500P display segments on
page 3–2 for details).
The display format is MM:DD:YYYY, where MM is the month (1
to 12), DD is the day (1 to 31), and YYYY is the year (2000 to
2099).
SYSTEM TIME Press the Volt/Amps key to display the twenty-first setting
screen. This screen sets the system time as a single line in
area 2 of the LCD (refer to EPM 5500P display segments on
page 3–2 for details).
The display format is hh:mm:ss, where hh is the hours (1 to 24),
mm is the minutes (1 to 59), and ss is the seconds (1 to 59).
ACCESS CODE Press the Volt/Amps key to display the twenty-second setting
SETTING screen. This screen allows the user to program the access
code as a single line in area 2 of the LCD (refer to EPM 5500P
display segments on page 3–2 for details).
The access code is a four-digit decimal number, with a range
from 0000 to 9999. The factory default is 0000. Ensure that
any changes to the access code are recorded and kept in a
safe place.
EXITING SETTING Exit the setting by pressing the Harmonics and Volt/Amps
MODE keys simultaneously.
EPM 5500P
Power Metering System
Chapter 5: Metering
Metering
VOLTAGE AND There are four separate displays for voltage and current
CURRENT metering. Voltage and current data is displayed as four lines in
area 1 of the LCD (refer to EPM 5500P display segments on
page 3–2 for details).
In this example,
• U1 = 100.3 V, U2 = 100.1 V, U3 = 100.2 V, and
Ulnavg = 100.2 V.
• The load rating is 50% with an inductive load.
• The consumed energy is 8.8 kWh
• Communication state is normal
• Pulse output is on
• Digital inputs 1 through 3 are open, digital input 4 is
closed.
In this example,
• I1 = 2.498 A, I2 = 2.499 A, I3 = 2.491 A, and
In = 0.008 A.
When the meter is set to "2LL", the phase voltage and current
screens will not be displayed. The display will begin at the third
NOTE
screen shown below.
In this example,
• U12 = 173.2 V, U23 = 173.3 V, U31 = 173.1 V, and
Ullavg = 173.2 V.
Press Volt/Amps to display the fourth screen. This screen
display current for each phase and average current as shown
below.
In this example,
• I2 = 2.499 A, I3 = 2.491 A, and Iavg = 2.496 A.
Pressing Volt/Amps again returns the display to the first
screen.
POWER There are seven separate screens for power metering that
display power-related data. Power data is displayed as four
lines in area 1 of the LCD (refer to EPM 5500P display segments
on page 3–2 for details).
Press the Power key to display the first screen. This screen
displays power for each phase P1, P2, and P3, and the total
system power Psum.
In this example,
• P1 = 0.125 KW, P2 = 0.125 KW, P3 = 0.125 KW, and
Psum = 0.375 KW.
In this example,
• Q1 = 0.217 Kvar, Q2 = 0.216 Kvar, Q3 = 0.216 Kvar, and
Qsum = 0.649 Kvar.
Press Power again to display the third screen. This screen
displays the apparent power S1, S2, and S3 for each phase as
well as the total system apparent power Ssum as shown
below.
In this example,
• S1 = 0.250 KVA, S2 = 0.250 KVA, S3 = 0.249 KVA, and
Ssum = 0.749 KVA.
Press Power again to display the fourth power metering
screen. This screen displays the power factor PF1, PF2, and
PF3 for each phase, as well as the system average power
factor PF as shown below.
In this example,
• PF1 = 0.500, PF2 = 0.500, PF3 = 0. 500, and PF = 0.500.
In this example,
• Psum = 0.375 KW, Qsum = 0.649 Kvar,
Ssum = 0.749 KVA, and PF = 0.500.
Press Power again to display the sixth screen. This screen
displays the total system power Psum, the total system
reactive power Qsum, the total system apparent power Ssum,
and the system frequency F.
In this example,
• Psum = 0.375 KW, Qsum = 0. 649 Kvar,
Ssum = 0.749 KVA, and F = 50.00 Hz.
Press Power again to display the seventh screen. This screen
displays the three-phase system power demand Dmd_P, the
reactive power demand Dmd_Q, and the apparent Dmd_S.
In this example,
• Dmd_P = 0.375 KW, Dmd_Q = 0.649 Kvar, and
Dmd_S = 0.749 KVA.
Press Power once more to return to the first screen.
Phase power is not displayed when the voltage wiring setting
is “2LL”.
NOTE
HARMONICS There are three separate screens for harmonics metering that
display power quality data. Harmonics data is displayed as
four lines in area 1 of the LCD (refer to EPM 5500P display
segments on page 3–2 for details).
Press the Harmonics key to the first screen.
If the voltage input wiring is “2LL”, this screen displays the line-
to-line voltage THD values THD_U12, THD_U23, and THD_U31,
as well as the average line-to-line voltage THD_Ull.
In this example,
• THD_U12 = 0.68%, THD_U23 = 0. 68%,
THD_U31 = 0.68%, and THD_Ull = 0.68%.
In this example,
• THD_U1 = 0.68%, THD_U2 = 0.68%, THD_U3 = 0.68%,
and THD_Uln = 0.68%.
Press the Harmonics key again to display the second screen.
This screen displays the phase current THD values THD_I1,
THD_I2, and THD_I3, as well as the average current THD value
THD_Iavg.
In this example,
• THD_I1 = 0.68%, THD_I2 = 0.68%, THD_I3 = 0.68%,
and THD_Iavg = 0.68%.
Press the Harmonics key again to display the third screen.
This screen displays three-phase voltage unbalance factor
and three-phase current unbalance factor.
In this example,
• the voltage unbalance factor = 0.8% and the current
unbalance factor = 0.9%.
Press the Harmonics one more time to return to the first
screen.
ENERGY There are ten separate screens for energy metering that
display energy values and the real time clock. Energy data is
displayed as a single line in area 2 of the LCD (refer to EPM
5500P display segments on page 3–2 for details).
Press the Energy key to display the first screen. This screen
displays the consumption energy.
In this example,
• the consumption energy Ep_imp = 8.8 kWh
Press the Energy key again to display the second screen. This
screen displays the generation energy.
In this example,
• the generation energy Ep_exp = 0.0 kWh.
Press the Energy key again to display the third screen. This
screen displays the absolute sum of the consumption and
generated energy (the total energy).
In this example,
• the total energy Ep_total = 8.8 kWh.
Press the Energy key again to display the fourth screen. This
screen displays the algebraic sum of the consumption and
generated energy (the net energy).
In this example,
• the net energy Ep_net = 8.8 kWh.
5–14 EPM 5500P POWER METERING SYSTEM – USER GUIDE
METERING
Press the Energy key again to display the fifth screen. This
screen displays the inductive reactive energy Eq_imp.
In this example,
• the inductive reactive energy Eq_imp = 15.2 kvarh.
Press the Energy key again to display the sixth screen. This
screen displays the capacitive reactive energy Eq_exp.
In this example,
• the capacitive reactive energy Eq_exp = 0.0 kvarh.
Press the Energy key again to display the seventh screen. This
the absolute sum of the reactive energy Eq_total is displayed.
In this example,
• the absolute sum of the reactive energy
Eq_total = 15.2 kvarh.
Press the Energy key again to display the eighth screen. This
screen displays the algebraic sum of the reactive energy.
In this example,
• the algebraic sum of the reactive energy
Eq_net = 15.2 kvarh.
Press the Energy key again to display the ninth screen. This
screen displays the date portion of the real time clock in the
format mm:dd:yyyy.
In this example,
• U1_max = 100.3 V, U2_max = 100.1 V, and
U3_max = 100.2 V.
In this example,
• U1_min = 0.0 V, U2_min = 0.0 V, and U3_min = 0.0 V.
Press the Power key again to return to the maximum voltage
statistics screen. Press Volt/Amps key to display the second
statistics screen. This screen displays the maximum and
minimum value for line-to-line voltage.
In this example,
• U12_max = 173.2 V, U23_max = 173.3 V, and
V31_max = 173.1 V.
CURRENT Press Volt/Amps key to display the third statistics screen. This
STATISTICS screen displays maximum and minimum current values.
In this example,
• I1_max = 2.498A, I2_max = 2.499A, and
I3_max = 2.491A.
Press the Power key to change this display from maximum to
minimum and vice versa.
In this example,
• The total system maximum power, P_max =0.375 W,
the total system maximum reactive power
Q_max = 0.649 Kvar, and the total system maximum
apparent power S_max = 0.749 KVA
• The system average power factor maximum
PF_max = 1.000.
Press the Power key to change this display from maximum to
minimum and vice versa.
DEMAND AND Press Volt/Amps key to display the fifth statistics screen. This
FREQUENCY screen displays maximum and minimum values for demand
STATISTICS and frequency.
In this example,
• The maximum total power demand
Dmd_P_max = 0.375 KW, the maximum total reactive
power demand Dmd_P_max = 0.649 Kvar, and the
maximum total apparent power demand
Dmd_P_max = 0.749 KVA
• The maximum system frequency is 50.00 Hz.
Press the Power key to change this display from maximum to
minimum and vice versa.
Press Volt/Amps key once more to return to the first statistics
screen.
EPM 5500P
Power Metering System
Chapter 6: Communications
Communications
Modbus Overview
DESCRIPTION The Modbus RTU protocol is used for communication in the
EPM 5500P. The data format and error check method are
defined in the protocol, and the half-duplex query and
respond modes have been adopted in Modbus. There is only
one master device in the communication network. All other
devices are slaves waiting for the master query.
ADDRESS FIELD The address field of a message frame contains eight bits.
Valid slave device addresses are in the range of 0 to 247. A
master addresses a slave by placing the slave address in the
address field of the message. When the slave sends its
response, it places its own address in this address field of the
response to let the master know which slave is responding.
FUNCTION FIELD The function code field of a message frame contains eight
bits. Valid codes are in the range of 1 to 255. When a message
is sent from a master to a slave device, the function code field
tells the slave what action to perform.
The EPM 5500P supports the following function codes:
• Function code 01: Read relay output status. This
function obtains the current status of the relay output.
• Function code 02: Read digital input status. This
function obtains the current status of the digital input.
• Function code 03: Read data. This function obtains the
current binary value in one or more registers.
• Function code 05: Control relay output. This function
forces the relay state to on or off.
• Function code 16: Preset multiple registers. This
function places specific binary values into a series of
consecutive registers.
DATA FIELD The data field is constructed using sets of two hexadecimal
digits, in the range of 00h to FFh. The data field of messages
sent from a master to slave devices contains additional
information which the slave must use to take the action
defined by the function code. This can include items like
discrete and register addresses, the quantity of items to be
handled, and the count of actual data bytes in the field. For
example, if the master requests a slave to read a group of
ERROR CHECK All messages include an error check field based on the
FIELD cyclical redundancy check (CRC) method. The CRC field checks
the contents of the entire message. It is applied regardless of
any parity check method used for the individual characters of
the message. The CRC field is two bytes containing a 16-bit
binary value. The CRC value is calculated by the transmitting
device, which appends the CRC to the message.
The receiving device recalculates a CRC during receipt of the
message, and compares the calculated value to the actual
value it received in the CRC field. If the two values are not
equal, an error results. The CRC is started by first pre-loading
a 16-bit register to all 1s. Then a process begins of applying
successive 8-bit bytes of the message to the current contents
of the register. Only the eight bits of data in each character
are used for generating the CRC. Start bits, stop bits, and the
parity bit do not apply to the CRC. During generation of the
CRC, each 8-bit character is exclusive ORed with the register
contents and the result shifted in the direction of the least
significant bit (LSB), with a zero filled into the most significant
bit (MSB) position. The LSB is extracted and examined. If the
LSB was A1, the register is then exclusive ORed with a preset,
fixed value. If the LSB was a 0, no exclusive OR takes place.
This process is repeated until eight shifts have been
performed. After the last (eighth) shift, the next 8-bit byte is
exclusive ORed with the register current value, and the
process repeats for eight more shifts as described above. The
final contents of the register, after all the bytes of the
message have been applied, is the CRC value. When the CRC
is appended to the message, the low-order byte is appended
first, followed by the high-order byte.
Modbus functions
FRAME FORMATS The data frame format for Modbus functions is shown below.
The data frame consists of the following 16-bit (2-byte)
sections:
• ADDR: Address of slave device
• FN: Function code
• START_HI: Start register address high byte
FUNCTION CODE This function code is used to read the status of the EPM 5500P.
01: READ RELAY The status is reported as follows:
OUTPUT STATUS 1 = On, 0 = Off
There are 2 relay outputs in the PL5500 IO models. The
address for each relay is:
Relay1 = 0000H
Relay2 = 0001H
The following query/response reads the relay status of the
EPM 5500P with address 17 (11h). The response includes the
meter address, function code, quantity of data byte, the data,
and error checking. The status of Relay1 and Relay2 is
responding to the last 2 bits of the data word; that is,
Bit 0 = Relay1; Bit 1 = Relay2
Query Response
ADDR: 11h ADDR: 11h
FN: 01h FN: 01h
START_HI: 00h BYTE COUNT: 01h
START_LO: 00h DATA: 02h
NO_HI: 00h CRC16_HI: D4h
NO_LO: 02h CRC16_LO: 89h
CRC16_HI: BFh
CRC16_LO: 5Bh
FUNCTION CODE This function obtains the current status of the digital input,
02: READ DIGITAL where the status is reported as follows:
INPUT STATUS 1 = On, 0 = Off
There are four digital inputs in the EPM 5500P. The address of
each digital input is:
Query Response
ADDR: 11h ADDR: 11h
FN: 02h FN: 02h
START_HI: 00h BYTE COUNT: 01h
START_LO: 00h DATA: 03h
NO_HI: 00h CRC16_HI: E5h
NO_LO: 04h CRC16_LO: 49h
CRC16_HI: 7Bh
CRC16_LO: 59h
Therefore, we have:
Digital input 1 = On (bit 0 = 1)
Digital input 2 = On (bit 1 = 1)
Digital input 3 = Off (bit 1 = 0)
Digital input 4 = Off (bit 1 = 0)
FUNCTION CODE This function obtains the current binary value in one or more
03: READ DATA registers, allowing the master to obtain the measurement
results of the EPM 5500P.
The following query/response example reads three measured
data items (F, V1 and V2) from slave device 17 (11h), where the
data is in the following registers:
data for F is in 0130h
data for V1 is in 0131h
data for V2 is in 0132h
The EPM 5500P response includes the meter address, function
code, quantity of data byte, data, and error checking.
Query Response
ADDR: 11h ADDR: 11h
FN: 03h FN: 03h
START_HI: 01h BYTE COUNT: 06h
START_LO: 30h DATA 1 HIGH: 13h
NO_HI: 00h DATA 1 LOW: 88h
NO_LO: 03h DATA 2 HIGH: 03h
CRC16_HI: 06h DATA 2 LOW: E7h
CRC16_LO: A8h DATA 3 HIGH: 03h
DATA 3 LOW: E9h
CRC16_HI: 7Fh
CRC16_LO: 04h
FUNCTION CODE This function forces the relay state to on or off. The two relays
05: CONTROL in the EPM 5500P can be forced to be either status. The
RELAY OUTPUT address for each relay is:
Relay1 = 0000H
Relay2 = 0001H.
The value FF00h will set the relay on and the value 0000h will
turn it off; all other values are illegal and will have no effect.
The following query/response example requests the EPM
5500P with address 17 (11h) to turn on Relay1.
Query Response
ADDR: 11h ADDR: 11h
FN: 05h FN: 05h
START_HI: 00h START_HI: 00h
START_LO: 00h START_LO: 00h
VALUE_HI: FFh VALUE_HI: FFh
VALUE_LO: 00h VALUE_LO: 00h
CRC16_HI: 8Eh CRC16_HI: 8Eh
CRC16_LO: AAh CRC16_LO: AAh
FUNCTION CODE This function places specific binary values into a series of
16: PRESET consecutive registers. This allows the user to modify the
MULTIPLE contents of multiple registers. Any EPM 5500P register can
REGISTERS. have its contents changed by this message.
The following query/response example requests the EPM
5500P with address 17 (11h) to preset the following value:
Query Response
ADDR: 11h ADDR: 11h
FN: 10h FN: 10h
START_HI: 01h DATA START HI: 01h
START_LO: 56h DATA START LO: 56h
DATA_HI: 00h DATA HIGH: 00h
DATA_LO: 02h DATA LOW: 02h
BYTE_COUNT: 04h CRC16_HI: A2h
VALUE_HI: 0Ah CRC16_LO: B4h
VALUE_LO: 9Dh
VALUE_HI: 40h
VALUE_LO: 89h
CRC16_HI: 4Dh
CRC16_LO: B9h
FORMAT CODES The format described in the memory map are indicated below.
The term Rx indicates the numerical value in the EPM 5500P
register.
F0: Numeric value (unsigned 16-bit integer)
Register directly indicates a numeric value with no units.
F1: Voltage (unsigned 16-bit integer)
Represents the value of metered voltage in volts, where:
PT1 ⁄ PT2
V = Rx × ----------------------
10
K = Rx
------
10
Value Type
0 Pulse output
1 Alarm output
Value Mode
0 Latch
1 Momentary
Value Mode
0 do not clear values
1 clear values
Value State
0 Off
1 On
EPM 5500P
Power Metering System
Chapter 7: Warranty
Warranty
EPM 5500P
Power Metering System
Index
A
ACCESS CODE .................................................................4–2, 4–20, 6–13
ADDRESS .....................................................................................................4–3
ALARM RECORDS ...................................................................3–15, 6–39
ALARM REGISTERS ............................................................................. 6–37
APPLICATIONS .........................................................................................1–5
APPROVALS ............................................................................................ 1–17
B
BACKLIGHT ............................................................................................. 4–16
BAUD RATE ................................................................................... 4–3, 6–13
C
COMMUNICATIONS
baud rate............................................................................................4–4
memory map................................................................................. 6–13
Modbus protocol.............................................................................6–1
specifications................................................................................. 1–16
wiring................................................................................................. 2–34
CREST FACTOR ........................................................................... 3–6, 6–18
CT PRIMARY CURRENT .......................................................................4–7
CURRENT INPUT
Modbus registers ......................................................................... 6–13
settings................................................................................................4–5
specifications................................................................................. 1–12
wiring................................................................................................. 2–15
CURRENT METERING
Modbus registers ................................................6–15, 6–28, 6–33
overview..............................................................................................3–4
specifications................................................................................. 1–14
statistics........................................................................................... 5–20
values...................................................................................................5–3
D
DATE................................................................................................4–18, 6–37
DEMAND METERING
Modbus registers ................................................6–16, 6–30, 6–36
overview .............................................................................................3–6
settings............................................................................................. 4–17
specifications................................................................................. 1–15
statistics........................................................................................... 5–22
DIGITAL INPUTS
Modbus registers ......................................................................... 6–13
specifications................................................................................. 1–13
wiring................................................................................................. 2–28
DIGITAL OUTPUT
pulse width ..................................................................................... 4–12
DIGITAL OUTPUTS
energy pulse outputs................................................................. 3–16
settings......................................................................... 4–8, 4–9, 4–11
specifications................................................................................. 1–13
wiring................................................................................................. 2–31
E
ELECTRICAL INSTALLATION ............................................................2–7
ENERGY METERING
Modbus registers ......................................................................... 6–16
overview .............................................................................................3–5
screens ............................................................................................. 5–12
settings............................................................................................. 4–12
specifications................................................................................. 1–15
ENERGY PULSE OUTPUTS ............................................................. 3–16
ENERGY PULSE RATE ....................................................................... 4–12
F
FEATURES ...................................................................................................1–3
FREQUENCY METERING
Modbus registers ................................................6–14, 6–30, 6–35
overview..............................................................................................3–5
specifications................................................................................. 1–15
statistics........................................................................................... 5–22
FRONT PANEL ..........................................................................................3–1
FUNCTIONALITY .....................................................................................1–6
FUNCTIONS ...............................................................................................3–4
I
INEQUATION ENABLE REGISTER .............................................. 3–12
INSTALLATION .........................................................................................2–1
INTERFACE .................................................................................................3–1
K
K-FACTOR ...................................................................................................3–8
L
LCD DISPLAY.............................................................................................3–2
LIMIT SETTING REGISTER ............................................................... 3–13
M
MECHANICAL INSTALLATION ........................................................2–3
MODBUS
data formats.................................................................................. 6–43
data frame format .........................................................................6–2
functions.............................................................................................6–5
memory map................................................................................. 6–13
overview .............................................................................................6–1
O
ORDER CODES .........................................................................................1–7
OVERLIMIT ALARMING .................................................................... 3–10
OVERVIEW ..................................................................................................1–2
P
PASSCODE .................................................................................... 4–2, 4–20
PHASE ANGLES .................................................................................... 6–42
POWER FACTOR
Modbus registers ................................................6–15, 6–30, 6–35
specifications................................................................................. 1–15
POWER METERING
Modbus registers ................................................6–15, 6–29, 6–34
overview .............................................................................................3–4
specifications................................................................................. 1–15
statistics........................................................................................... 5–21
values...................................................................................................5–5
POWER SUPPLY ......................................................................... 2–9, 2–29
PT PRIMARY VOLTAGE ........................................................................4–6
PT SECONDARY VOLTAGE................................................................4–7
PULSE OUTPUTS ................................................................................. 3–16
R
REAL TIME CLOCK .............................................................................. 3–10
RELAY OUTPUTS
Modbus registers .............................................................6–13, 6–14
overview........................................................................................... 3–18
settings....................................................................4–13, 4–14, 4–15
wiring................................................................................................. 2–30
REMOTE CONTROL ...............................................................................1–3
S
SAFETY EARTH .........................................................................................2–8
SAFETY NOTES.........................................................................................1–1
SCADA ...........................................................................................................1–3
SPECIFICATIONS.................................................................................. 1–12
STATISTICS .............................................................................................. 5–18
overview..............................................................................................3–9
T
THD
Modbus registers ......................................................................... 6–16
overview .............................................................................................3–7
screens ............................................................................................. 5–10
specifications................................................................................. 1–16
THFF .................................................................................................. 3–8, 6–18
TIME.................................................................................................4–19, 6–37
TIME LIMIT SETTING REGISTER .................................................. 3–13
TYPICAL WIRING DIAGRAMS ....................................................... 2–18
U
UNBALANCE
Modbus registers ......................................................................... 6–16
overview .............................................................................................3–9
specifications................................................................................. 1–14
V
VOLTAGE INPUT
Modbus registers ......................................................................... 6–13
settings................................................................................................4–4
specifications................................................................................. 1–12
wiring.....................................................................................2–10, 2–12
VOLTAGE METERING
Modbus registers ................................................6–14, 6–26, 6–31
overview .............................................................................................3–4
specifications................................................................................. 1–14
statistics........................................................................................... 5–18
values...................................................................................................5–1
W
WARRANTY ................................................................................................7–1
WIRING DIAGRAMS ........................................................................... 2–18