Features sensor
AT 8 N AT 11 DN (G)
No mark 100-240VAC/24-240VDC Connector/
Power No mark 100-240VAC/24-240VDC Socket
1 12VDC supply
Power 1 12VDC
supply 2 24VAC/DC (H)
2 24VAC/DC Temp.
controller
Time Time limit contact 2c or time Time
operation limit contact 1c with operation DN Time limit 2c
N (I)
instantaneous contact 1c by Time limit 1c, SSR/
EN
selecting output operation mode Instantaneous contact 1c Power
controller
Number of plug pins Number of plug pins
8 8-pin plug type 11 11-pin plug type
Item Item (J)
AT Analog Timer AT Analog Timer Counter
※Sockets (PG-08, PS-08) are sold ※Sockets (PG-11, PS-11) are sold separately.
separately.
Specifications (K)
Timer
Power supply • 100-240VAC 50/60Hz, 24-240VDC universal • 24VAC 50/60Hz, 24VDC universal • 12VDC
(M)
Allowable voltage range 90 to 110% of rated voltage Tacho/
Speed/ Pulse
• 100-240VAC : 4.3VA, 24-240VDC : 2W • 100-240VAC:3.5VA, 24-240VDC:1.5W meter
Power consumption
• 24VAC : 4.5VA, 24VDC : 2W • 12VDC : 1.5W • 24VAC:4VA, 24VDC:1.5 • 12VDC:1W
(N)
Reset time Max. 100ms Display
unit
Min. START
input INHIBIT - Min. 50ms (O)
signal Sensor
width RESET controller
K-59
ATN Series
Connections
AT8N
● [A], [F] mode ● [A1], [B], [F1], [I] mode
4 5 4 5
3 6 CONTACT: 3 6 CONTACT:
250VAC 5A 250VAC 5A
2 7 RESISTIVE LOAD 2 7 RESISTIVE LOAD
(Time limit 1c) (Time limit 1c) (Instantaneous 1c) (Time limit 1c)
1 8 1 8
- + - +
SOURCE: SOURCE:
• 100-240VAC 50/60㎐, 24-240VDC • 100-240VAC 50/60㎐, 24-240VDC
• 24VAC 50/60㎐, 24VDC • 24VAC 50/60㎐, 24VDC
• 12VDC • 12VDC
AT11DN AT11DEN
RESET RESET
START START
6 6
INHIBIT 5 7 INHIBIT 5 7
4 8 4 8
CONTACT : CONTACT :
3 9 3 9
250VAC 5A 250VAC 5A
2 10 RESISTIVE LOAD 2 10 RESISTIVE LOAD
1 11 1 11
(Time limit 1c) (Time limit 1c)
(Time limit 1c) (Instantaneous 1c)
- + - +
SOURCE: SOURCE:
• 100-240VAC 50/60㎐, 24-240VDC • 100-240VAC 50/60㎐, 24-240VDC
• 24VAC 50/60㎐, 24VDC • 24VAC 50/60㎐, 24VDC
• 12VDC • 12VDC
(unit: mm)
Dimensions
● Bracket ● Panel cut-out
15 64.5
Min. 65
□48 50
45 +0.6
0
Min. 65
44.8
56
45 +0.6
0
72
41
K-60
Multi Function Timer
Parts description (A)
Photo
electric
sensor
Operation/Power LED
(Timer operation: Flashing Output LED (B)
Fiber
Timer stop:LED ON) [Time limit output operation(ON) : Light on] optic
sensor
(C)
AT8
Time range selector (A, A1, B, F, F1, I mode) (D)
Proximity
(Changing the time sensor
AT11DN/AT11EN
unit per 4 revolutions)
(A, F, F1, C, D, I mode) (E)
Pressure
sensor
Time unit
Operation mode selector
(sec, min, hour, 10h) (F)
Rotary
encoder
※Please rotate the time range switch and operation mode switch to CW(Clockwise) direction.
(G)
Connector/
Socket
(Q)
Stepper
Output operation mode of each model motor&
Driver&Controller
(R)
● AT8N ● AT11DN/AT11EN Graphic/
Logic
panel
Display Output operation mode Display Output operation mode
(S)
Field
A Power ON Delay A Signal ON Delay network
device
I Interval I Interval
K-61
ATN Series
AT8N Output operation mode [t:Setting time, t > t-a, Rt:Return time, Rt1>Rt]
Operation/Power LED
Operation/Power LED
※One- shot output is 0.5sec fixed.
Operation/Power LED
F t t t-a Rt1 t t t
Power 2-7
Operation/Power LED
F1 t t t-a Rt1 t t t
Power 2-7
Time limit contact N.C. 8-5
Time limit contact N.O. 8-6
Instant limit contact N.C. 1-4
Flicker 1
Instant limit contact N.O. 1-3
Time limit output operation LED
Operation/Power LED
Operation/Power LED
※When using F, F1 output operation modes, if the time is set too short, the output may not work properly.
Please set the time at least over 100ms.
K-62
Multi Function Timer
AT11DN/AT11EN Output operation mode [t:Setting time, t=t1+t2, t>t-a]
(A)
Photo
electric
sensor
Mode Time chart
(B)
A t t1 t2 Fiber
optic
Power 2-10 sensor
START 2-6
(C)
INHIBIT 2-5 Door/Area
RESET 2-7 sensor
F1 t t t-a t t1 t2
controller
RESET 2-7
Flicker 1 Time limit contact N.C. (J)
Counter
Time limit contact N.O.
Time limit output operation LED
Operation/Power LED (K)
Timer
C t t-a t-a t1 t2
(L)
Power 2-10 Panel
meter
START 2-6
INHIBIT 2-5
(M)
RESET 2-7 Tacho/
Speed/ Pulse
Signal OFF Delay Time limit contact N.C. meter
Time limit contact N.O.
Time limit output operation LED (N)
Display
unit
Operation/Power LED
※1: If power is removed or the RESET terminal is short-circuited, the timer will be reset.
2: If the INHIBIT terminal is short-circuited during a timing cycle, the time will stop.
3: When using F, F1 output operation modes, if the time is set too short, the output may not work properly.
Please set the time at least over 100ms.
K-63
ATN Series
Proper usage 2. Input with NPN open collector type
Characteristics of transistor should be Vceo = min. 25V,
Repeat function(Flicker) Ic = min. 10mA, Icbo = max. 0.2㎂, residual voltage =
● It enables to use one ATN timer for 3 sub relays and 2 max. 0.5V.
timers (Flicker function).
Simple to use flicker function with only one ATN timer. Reset Reset +
● Switch A : Start, Switch B : Reset. Start Start +
Inhibit Inhibit +
6 7 6 7
5 5
< Previous >
2 2
-
START R1 R1 R1 T1 R3
Time 10-30VDC
limit
+
RL
- START
START RESET 6
5 7
Load Q
Timer A B 0.4㎃
2
Interval mode
It enables to make instantaneous ON and time limit OFF
(remained circuit) with using Interval mode. Terminal connection
Please wire correctly with wiring instructions
T : Timer T : Timer(AT8) Power connection
Connect the power line without observing polarity for ATN
START Instan- START series AC power type, but please be careful of power
taneous
connection for DC power type.
Time
limit
Time Power supply 8-pin Type 11-pin Type
limit
AC Type Terminal ② - ⑦ Terminal ② - ⑩
T Load Terminal ② ← ⊖ Terminal ② ← ⊖
T Load
DC Type
Terminal ⑦ ← ⊕ Terminal ⑩ ← ⊕
< Previous > < Interval mode > When turning off the power, be careful of inductive
voltage.
Input signal condition(AT11DN, AT11EN) (If using power line with another high voltage line or
1. Relay contact input energy line near by, it may cause inductive voltage).
Please use gold-plated switches with good contact Power ripple should be under 10% and power supply
assurance and short bouncing time for contact input. should be within range of allowable voltage for DC power
(Open resistance : Over 100kΩ, Short-circuit resistance: type.
Under 1kΩ) Please supply the power quickly when using a switch or
※Please use a contact that can function reliably at 5VDC a relay contact. Otherwise, it may cause time error or
0.4mA. power reset failure.
The load of Control output should be under rated load
capacity.
K-64
Multi Function Timer
Setting time, time range, operation mode Common (A)
Photo
Do not change time range or operation mode while time For DC power supply type, be sure to check the polarity electric
sensor
operating. When changing it, please power off or apply of terminals.
reset signal. In case of 12VDC, 24VAC/DC model, isolated and limited (B)
Fiber
voltage/current or Class 2 source should be provided for optic
sensor
Input connection power supply.
AT11DN/AT11EN Timer is non-transformer type, therefore When supply the power to the timer, connection shown in (C)
Door/Area
please check following for connecting relay contact for (Fig. 6) might cause malfunction due to leakage current sensor
input signal and transistor. through R and C. Please connect R and C as shown in
(D)
(Fig. 7) to prevent malfunction. Proximity
(Fig. 1) ATS11DN/AT11EN sensor
Power
Power
(F)
Timer
Timer
Rotary
R C T C encoder
T
+
Main circuit
(G)
+ Connector/
Socket
-
-
Rectification Transformer It might cause malfunction if changing the setting (H)
circuit with insulated
< Sensor > time, time range or operation mode during operating Temp.
< External sensor power supply > unit. Please change the the setting time, time range or
controller
common terminal as (Fig. 3). Place where there are direct rays of the sun Counter
(N)
Display
unit
When using more than one timer with one contact or
transistor input, the short current is flowed when it is (O)
connected as (Fig. 4). Please connect the power phase Sensor
controller
correctly as (Fig. 5) correctly.
(P)
(Fig. 4) (Fig. 5) Switching
mode power
supply
Short current
(Q)
Stepper
motor&
Driver&Controller
(R)
Power Power Graphic/
Logic
panel
(S)
INHIBIT, START, RESET signal applied by short input Field
network
terminal ②-⑤, ②-⑥ or ②-⑦. device
It may cause internal circuit damaged by wrong
connection. (T)
Software
If using power line with another high voltage line or
energy line at the same conduit, it may cause inductive
voltage. Therefore please use separated conduit for (U)
Other
power line.
When input(INHIBIT, START, RESET) wire is long, please
use shield wire and it should be short.
K-65