ATN Series Multi Function Timer

DIN W48×H48mm, Universal voltage multi-function timer (A)


Photo
electric

Features sensor

● Realization of wide range of power supply (B)


Fiber
optic
:100-240VAC 50/60Hz / 24-240VDC universal, sensor

24VAC 50/60Hz / 24VDC universal, 12VDC (C)


● Various output operation(6 kinds modes) Door/Area
sensor
● Multi time range(16 kinds of time range)
● Wide control time(0.05sec. to 100hour) (D)
Proximity
● Easy setting of time, time range, output operation mode sensor

● Easy to check output status by LED display (E)


Pressure
Please read “Caution for your safety” in operation sensor
manual before using.

Ordering information (F)


Rotary
encoder

AT 8 N AT 11 DN (G)
No mark 100-240VAC/24-240VDC Connector/
Power No mark 100-240VAC/24-240VDC Socket
1 12VDC supply
Power 1 12VDC
supply 2 24VAC/DC (H)
2 24VAC/DC Temp.
controller
Time Time limit contact 2c or time Time
operation limit contact 1c with operation DN Time limit 2c
N (I)
instantaneous contact 1c by Time limit 1c, SSR/
EN
selecting output operation mode Instantaneous contact 1c Power
controller
Number of plug pins Number of plug pins
8 8-pin plug type 11 11-pin plug type
Item Item (J)
AT Analog Timer AT Analog Timer Counter

※Sockets (PG-08, PS-08) are sold ※Sockets (PG-11, PS-11) are sold separately.
separately.
Specifications (K)
Timer

Model AT8N- AT11EN- AT11DN-


Function Multi function timer (L)
Panel
Control time setting range 0.05 sec. to 100 hour meter

Power supply • 100-240VAC 50/60Hz, 24-240VDC universal • 24VAC 50/60Hz, 24VDC universal • 12VDC
(M)
Allowable voltage range 90 to 110% of rated voltage Tacho/
Speed/ Pulse
• 100-240VAC : 4.3VA, 24-240VDC : 2W • 100-240VAC:3.5VA, 24-240VDC:1.5W meter
Power consumption
• 24VAC : 4.5VA, 24VDC : 2W • 12VDC : 1.5W • 24VAC:4VA, 24VDC:1.5 • 12VDC:1W
(N)
Reset time Max. 100ms Display
unit
Min. START
input INHIBIT - Min. 50ms (O)
signal Sensor
width RESET controller

START No-voltage input - Short-circuit impedance : Max. 1kΩ (P)


Input INHIBIT - Residual voltage : Max. 0.5V Switching
mode power
RESET Open-circuit impedance : Min. 100kΩ supply

Timing operation Power ON start type Signal ON Start type (Q)


Stepper
Time limit DPDT(2c), motor&
Time limit DPDT(1c)+ Time limit SPDT(1c), Driver&Controller
Control Contact type Instantaneous DPDT(1c) by Instantaneous SPDT(1c)
Time limit DPDT(2c)
output selecting output operation mode (R)
Graphic/
Contact capacity 250VAC 5A resistive load Logic
panel
Relay Mechanical Min. 10,000,000 operations
(S)
life cycle Electrical Min. 100,000 operations(250VAC 5A resistive load) Field
network
Repeat error Max. ±0.2% ±10ms device

SET error Max. ±5% ±50ms


(T)
Voltage error Max. ±0.5% Software

Temperature error Max. ±2%


Insulation resistance Min. 100MΩ(at 500VDC megger) (U)
Other
Dielectric strength 2000VAC 50/60Hz for 1 minute
Environ Ambient temperature -10 to 55℃, storage: -25 to 65℃
-ment Ambient humidity 35 to 85%RH
Approval
Accessory Bracket
Unit weight Approx. 90g
※Environment resistance is rated at no freezing or condensation.

K-59
ATN Series
Connections
AT8N
● [A], [F] mode ● [A1], [B], [F1], [I] mode
4 5 4 5
3 6 CONTACT: 3 6 CONTACT:
250VAC 5A 250VAC 5A
2 7 RESISTIVE LOAD 2 7 RESISTIVE LOAD
(Time limit 1c) (Time limit 1c) (Instantaneous 1c) (Time limit 1c)
1 8 1 8

- + - +
SOURCE: SOURCE:
• 100-240VAC 50/60㎐, 24-240VDC • 100-240VAC 50/60㎐, 24-240VDC
• 24VAC 50/60㎐, 24VDC • 24VAC 50/60㎐, 24VDC
• 12VDC • 12VDC
AT11DN AT11DEN
RESET RESET

START START

6 6
INHIBIT 5 7 INHIBIT 5 7
4 8 4 8
CONTACT : CONTACT :
3 9 3 9
250VAC 5A 250VAC 5A
2 10 RESISTIVE LOAD 2 10 RESISTIVE LOAD
1 11 1 11
(Time limit 1c) (Time limit 1c)
(Time limit 1c) (Instantaneous 1c)

- + - +
SOURCE: SOURCE:
• 100-240VAC 50/60㎐, 24-240VDC • 100-240VAC 50/60㎐, 24-240VDC
• 24VAC 50/60㎐, 24VDC • 24VAC 50/60㎐, 24VDC
• 12VDC • 12VDC
(unit: mm)
Dimensions
● Bracket ● Panel cut-out
15 64.5
Min. 65
□48 50
45 +0.6
0
Min. 65
44.8
56

45 +0.6
0

72
41

Panel 8-pin socket : PG-08 (Sold separately)


11-pin socket : PG-11 (Sold separately)
※Refer to the G-15 page.

K-60
Multi Function Timer
Parts description (A)
Photo
electric
sensor
Operation/Power LED
(Timer operation: Flashing Output LED (B)
Fiber

Timer stop:LED ON) [Time limit output operation(ON) : Light on] optic
sensor

(C)

Time range display Operation mode display Door/Area


sensor

AT8
Time range selector (A, A1, B, F, F1, I mode) (D)
Proximity
(Changing the time sensor
AT11DN/AT11EN
unit per 4 revolutions)
(A, F, F1, C, D, I mode) (E)
Pressure
sensor
Time unit
Operation mode selector
(sec, min, hour, 10h) (F)
Rotary
encoder

※Please rotate the time range switch and operation mode switch to CW(Clockwise) direction.
(G)
Connector/
Socket

Time specifications (H)


Temp.
controller
Time range Time unit Time setting range
(I)
0.5 0.05 to 0.5 sec. SSR/
Power
controller
1.0 0.1 to 1.0 sec.
sec
5 0.5 to 5 sec. (J)
Counter
10 1 to 10 sec.
0.5 0.05 to 0.5 min. (K)
Timer
1.0 0.1 to 1.0 min.
min
5 0.5 to 5 min. (L)
Panel
meter
10 1 to 10 min.
0.5 0.05 to 0.5 hour (M)
Tacho/
Speed/ Pulse
1.0 0.1 to 1.0 hour meter
hour
5 0.5 to 5 hour (N)
Display
10 1 to 10 hour unit

0.5 0.5 to 5 hour


(O)
Sensor
1.0 1 to 10 hour controller
10h
5 5 to 50 hour
(P)
Switching
10 10 to 100 hour mode power
supply

(Q)
Stepper
Output operation mode of each model motor&
Driver&Controller

(R)
● AT8N ● AT11DN/AT11EN Graphic/
Logic
panel
Display Output operation mode Display Output operation mode
(S)
Field
A Power ON Delay A Signal ON Delay network
device

A1 Power ON Delay 1 F Flicker (OFF Start) (T)


Software

B Power ON Delay 2 F1 Flicker 1 (ON Start)


(U)
F Flicker (OFF Start) C Signal OFF Delay Other

F1 Flicker 1 (ON Start) D Signal ON/OFF Delay

I Interval I Interval

K-61
ATN Series
AT8N Output operation mode [t:Setting time, t > t-a, Rt:Return time, Rt1>Rt]

Mode Time chart

A t Rt1 t Rt1 t-a


Power 2-7

Time limit contact N.C. 1-4(8-5)

Time limit contact N.O. 1-3(8-6)


Power ON Delay
Time limit output operation LED

Operation/Power LED

A1 t Rt1 t Rt1 t-a


Power 2-7
Time limit contact N.C. 8-5
Time limit contact N.O. 8-6 0.5 sec. 0.5 sec.

Instant limit contact N.C. 1-4


Power ON Delay 1
Instant limit contact N.O. 1-3
(One-shot output)
Time limit output operation LED

Operation/Power LED
※One- shot output is 0.5sec fixed.

B t Rt1 t Rt1 t-a


Power 2-7

Time limit contact N.C. 8-5


Time limit contact N.O. 8-6
Instant limit contact N.C. 1-4
Power ON Delay 2
Instant limit contact N.O. 1-3
Time limit output operation LED

Operation/Power LED

F t t t-a Rt1 t t t
Power 2-7

Time limit contact N.C. 1-4(8-5)


Time limit contact N.O. 1-3(8-6)
Flicker
Time limit output operation LED

Operation/Power LED

F1 t t t-a Rt1 t t t
Power 2-7
Time limit contact N.C. 8-5
Time limit contact N.O. 8-6
Instant limit contact N.C. 1-4
Flicker 1
Instant limit contact N.O. 1-3
Time limit output operation LED

Operation/Power LED

I t Rt1 t Rt1 t-a


Power 2-7

Time limit contact N.C. 8-5


Time limit contact N.O. 8-6

Instant limit contact N.C. 1-4


Interval
Instant limit contact N.O. 1-3
Time limit output operation LED

Operation/Power LED

※When using F, F1 output operation modes, if the time is set too short, the output may not work properly.
Please set the time at least over 100ms.

K-62
Multi Function Timer
AT11DN/AT11EN Output operation mode [t:Setting time, t=t1+t2, t>t-a]
(A)
Photo
electric
sensor
Mode Time chart
(B)
A t t1 t2 Fiber
optic
Power 2-10 sensor

START 2-6
(C)
INHIBIT 2-5 Door/Area
RESET 2-7 sensor

Signal ON Delay Time limit contact N.C.


Time limit contact N.O. (D)
Proximity
Time limit output operation LED sensor
Operation/Power LED
(E)
F t t t-a t t1 t2 Pressure
sensor
Power 2-10
START 2-6 (F)
Rotary
INHIBIT 2-5 encoder
RESET 2-7
Flicker Time limit contact N.C. (G)
Time limit contact N.O. Connector/
Socket
Time limit output operation LED
Operation/Power LED
(H)
Temp.

F1 t t t-a t t1 t2
controller

Power 2-10 (I)


START 2-6 SSR/
Power
INHIBIT 2-5 controller

RESET 2-7
Flicker 1 Time limit contact N.C. (J)
Counter
Time limit contact N.O.
Time limit output operation LED
Operation/Power LED (K)
Timer

C t t-a t-a t1 t2
(L)
Power 2-10 Panel
meter
START 2-6
INHIBIT 2-5
(M)
RESET 2-7 Tacho/
Speed/ Pulse
Signal OFF Delay Time limit contact N.C. meter
Time limit contact N.O.
Time limit output operation LED (N)
Display
unit
Operation/Power LED

D t t t-a t1 t2 t-a t t-a t-a (O)


Sensor
controller
Power 2-10
START 2-6 (P)
INHIBIT 2-5 Switching
mode power
RESET 2-7 supply

Signal ON-OFF Delay Time limit contact N.C. (Q)


Stepper
Time limit contact N.O. motor&
Time limit output operation LED Driver&Controller

Operation/Power LED (R)


Graphic/
Logic
I t t t t-a t-a t1 t2 panel

Power 2-10 (S)


Field
START 2-6 network
device
INHIBIT 2-5
RESET 2-7 (T)
Interval Time limit contact N.C. Software

Time limit contact N.O.


Time limit output operation LED
(U)
Operation/Power LED Other

※1: If power is removed or the RESET terminal is short-circuited, the timer will be reset.
2: If the INHIBIT terminal is short-circuited during a timing cycle, the time will stop.
3: When using F, F1 output operation modes, if the time is set too short, the output may not work properly.
Please set the time at least over 100ms.

K-63
ATN Series
Proper usage 2. Input with NPN open collector type
Characteristics of transistor should be Vceo = min. 25V,
Repeat function(Flicker) Ic = min. 10mA, Icbo = max. 0.2㎂, residual voltage =
● It enables to use one ATN timer for 3 sub relays and 2 max. 0.5V.
timers (Flicker function).
Simple to use flicker function with only one ATN timer. Reset Reset +
● Switch A : Start, Switch B : Reset. Start Start +
Inhibit Inhibit +
6 7 6 7
5 5
< Previous >
2 2
-
START R1 R1 R1 T1 R3

R3 3. NPN universal input


R2
RESET T2 It enables to use voltage output type as input signal source
instead of open collector output in solid-state circuit
R1 T1 Load R2 T2 R3 (proximity sensor, photo-electric sensor) which has range
of 10-30VDC output voltage.
When H signal change to L, timer will start.
< ATN Flicker mode >
When transistor(Q) is ON status, please make residual
voltage under 0.5V.

Time 10-30VDC
limit
+
RL
- START

START RESET 6
5 7
Load Q
Timer A B 0.4㎃

2
Interval mode
It enables to make instantaneous ON and time limit OFF
(remained circuit) with using Interval mode. Terminal connection
Please wire correctly with wiring instructions
T : Timer T : Timer(AT8) Power connection
Connect the power line without observing polarity for ATN
START Instan- START series AC power type, but please be careful of power
taneous
connection for DC power type.
Time
limit
Time Power supply 8-pin Type 11-pin Type
limit
AC Type Terminal ② - ⑦ Terminal ② - ⑩
T Load Terminal ② ← ⊖ Terminal ② ← ⊖
T Load
DC Type
Terminal ⑦ ← ⊕ Terminal ⑩ ← ⊕

< Previous > < Interval mode > When turning off the power, be careful of inductive
voltage.
Input signal condition(AT11DN, AT11EN) (If using power line with another high voltage line or
1. Relay contact input energy line near by, it may cause inductive voltage).
Please use gold-plated switches with good contact Power ripple should be under 10% and power supply
assurance and short bouncing time for contact input. should be within range of allowable voltage for DC power
(Open resistance : Over 100kΩ, Short-circuit resistance: type.
Under 1kΩ) Please supply the power quickly when using a switch or
※Please use a contact that can function reliably at 5VDC a relay contact. Otherwise, it may cause time error or
0.4mA. power reset failure.
The load of Control output should be under rated load
capacity.

K-64
Multi Function Timer
Setting time, time range, operation mode Common (A)
Photo
Do not change time range or operation mode while time For DC power supply type, be sure to check the polarity electric
sensor
operating. When changing it, please power off or apply of terminals.
reset signal. In case of 12VDC, 24VAC/DC model, isolated and limited (B)
Fiber
voltage/current or Class 2 source should be provided for optic
sensor
Input connection power supply.
AT11DN/AT11EN Timer is non-transformer type, therefore When supply the power to the timer, connection shown in (C)
Door/Area
please check following for connecting relay contact for (Fig. 6) might cause malfunction due to leakage current sensor

input signal and transistor. through R and C. Please connect R and C as shown in
(D)
(Fig. 7) to prevent malfunction. Proximity
(Fig. 1) ATS11DN/AT11EN sensor

START (Fig. 6) (Fig. 7) (E)


Pressure
RESET
Power sensor
INHIBIT
Leakage current
R

Power

Power
(F)

Timer

Timer
Rotary
R C T C encoder
T
+
Main circuit

(G)
+ Connector/
Socket
-
-
Rectification Transformer It might cause malfunction if changing the setting (H)
circuit with insulated
< Sensor > time, time range or operation mode during operating Temp.
< External sensor power supply > unit. Please change the the setting time, time range or
controller

operation mode after cut the power off. (I)


SSR/
When using the terminal ⑩ as a common terminal of Do not use this unit at below places. Power
controller
input signal as (Fig. 2), it may cause damage to the inner Place where there are severe vibration or impact.
circuit of AT11DN/AT11EN, please use the terminal ② for Place where strong alkalis or acids are used. (J)

common terminal as (Fig. 3). Place where there are direct rays of the sun Counter

Place where strong magnetic field or electric noise are


(Fig. 2) (Fig. 3) generated. (K)
Timer
INHIBIT RESET Installation environment
START START It shall be used indoor
RESET INHIBIT Altitude Max. 2000m (L)
Panel
Pollution Degree 2 meter

Installation Category II (M)


Tacho/
Speed/ Pulse
Power Power meter

(N)
Display
unit
When using more than one timer with one contact or
transistor input, the short current is flowed when it is (O)
connected as (Fig. 4). Please connect the power phase Sensor
controller
correctly as (Fig. 5) correctly.
(P)
(Fig. 4) (Fig. 5) Switching
mode power
supply
Short current

(Q)
Stepper
motor&
Driver&Controller

(R)
Power Power Graphic/
Logic
panel

(S)
INHIBIT, START, RESET signal applied by short input Field
network
terminal ②-⑤, ②-⑥ or ②-⑦. device
It may cause internal circuit damaged by wrong
connection. (T)
Software
If using power line with another high voltage line or
energy line at the same conduit, it may cause inductive
voltage. Therefore please use separated conduit for (U)
Other
power line.
When input(INHIBIT, START, RESET) wire is long, please
use shield wire and it should be short.

K-65